SRI LATHA TRANSFORMERS

S.No.42, Industrial Estate Anakapalli TEST CERTIFICATE


Name of the Customer :- Sri Konatala Subramanyam Kalyana Mandapam, Anakapalli

Capacity of the Transformer :- 160 KVA Manufacturers serial No. :- 01/2010 BC 1000 BC 11000 bc 433 bc 250 Bph. 2.5 CA 1000 CA 11000 ca 433 ca 250 Cph 2.5

I.R.Values (M.Ohms) :- AB 1000 Ratio Test (Volts) :- AB 11000 Ab 433 An 250

No Load Current (Amps) :- Aph. 2.5 Transformer Losses :a) b)

No Load Losses (Watts) 180 Full Load Losses (Watts) 450

Short Circuit Test :- (Amps) :- Aph. 210 Bph. 210 Cph 210 Induced Over Voltage with stand Test :- OK (2 X 11 KV for Minute) High pressure test :HT to LT HT to Earth Transformer Oil test :a) Dielectric Strength 40 KV/60Sec. Sig. of Testing Engineer : 28 KV for Minute OK : 3 KV for Minute OK