Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 3

InfoMile Solutions

Client: S.V.POWER PVT LTD Project: 500 TPH CFBC BOILER Job Title: Design of Footing Building: COMPRESSOR BUILDING Date: Done by: Checked by: 15.09.2008 AKV Rev: M25 Fe500 fck fy 0

Reference

Description of Problem
Grade of Concrete Grade of Steel Unit Weight of Soil Safe Bearing Capacity of soil, SBC Depth of Pedestal Width of Pedestal Length of Pedestal above footing Length of Footing Width of Footing Area of Footing Depth of Footing Effective Cover to Steel Effective depth Moment of inertia about x, Moment of inertia about z, Weight of soil above footing Weight of Footing GOVERNING LOAD CASES NORMAL LOADS(DL+IL) Pi Mxi Mzi DL+IL+EQX Pii Mxii Mzii DL+IL+EQZ Piii Mxiii Mziii NORMAL LOADS(DL+IL) Pi/A Mxi/Zxx Mzi/Zzz Pmaxi Pmini SINCE Pmaxi<SBC, SIZE PROVIDED IS SAFE DL+IL+EQX Pii/A Mxii/Zxx Mzii/Zzz Pmaxii Pminii SINCE Pmaxii<1.25SBC, SIZE PROVIDED IS SAFE DL+IL+EQZ Piii/A Mxiii/Zxx Mziii/Zzz Pmaxiii Pminiii SINCE Pmaxiii<1.25SBC, SIZE PROVIDED IS SAFE

Values Units
25.00 MPa 500.00 MPa 18.00 kN 600.00 kN/m2 0.60 m 0.30 m 2.70 m 1.50 m 1.20 m 1.80 m2 0.40 m 0.06 m 0.34 m 0.45 m3 0.36 m3 78.73 kN 18.00 kN

X Z

lpz bpx hp Lz Bx A D cc d Zxx Zzz Ws Wf

369.82 kN 8.53 kNm 5.88 kNm 392.16 kN 7.94 kNm 36.04 kNm 388.82 kN 8.02 kNm 30.50 kNm

259.20 kN/m2 18.96 kN/m2 16.33 kN/m2 294.49 kN/m2 223.91 kN/m2

271.61 kN/m2 17.64 kN/m2 100.10 kN/m2 389.35 kN/m2 153.86 kN/m2

269.75 kN/m2 17.82 kN/m2 84.73 kN/m2 372.30 kN/m2 167.20 kN/m2

file:///opt/scribd/conversion/tmp/scratch29580/65552165.xls

InfoMile Solutions
Client: S.V.POWER PVT LTD Project: 500 TPH CFBC BOILER Job Title: Design of Footing Building: COMPRESSOR BUILDING Date: Done by: Checked by: 15.09.2008 AKV Rev: 0

Reference

Description of Problem

Values Units
371.71

Mx X Mz Z 1.50 0.30 0.6 311.65

1.20 171.50

251.93

287.57

274.21

SP16, Design aids to IS:456-2000

cl. 26.3.3.b.1 & 2 of IS:456-2000

Moments at the face of Pedestal: Moment about X-direction Mxu/bd2 (Mxu = 1.5*Mx) Percent of Steel required Area of steel required/m Provided Diameter of bar # 12 Spacing required Check for max. spacing Provide #12mm bars @ 200mm Moment about Z-direction (Mzu = 1.5*Mz) Mzu/bd2 Percent of Steelrequired Area of steel required/m Provided Diameter of bar # 12 Spacing required Check for max. spacing Provide #12mm bars @ 200mm Check for Shear: Pr. at d diatance from face 284.30 Shear For both directions 29.49 Maximum Shear Force v = Vu/bd (Vu = 1.5*V) Available steel Area Percent of steel provided For the above % of steel Design Shear strength

Mx pt Ast

35.61 kNm 0.46 MPa 0.12 % 408.00 mm2 4.00 250.00 mm 250.00 mm

Mz pt Ast

SP16, Design aids to IS:456-2000

Cl. 26.3.3.b.1 & 2 of IS:456-2000

28.67 kNm 0.37 MPa 0.12 % 408.00 mm2 4.00 250.00 mm 250.00 mm

kN/m2 kN V v

357.03 kN/m2 33.07 kN 33.07 kN 0.15 MPa 565.49 mm2 0.17 % 0.35 MPa

Table 19 of IS:456-2000

Since c > v, Safe One Way Shear

file:///opt/scribd/conversion/tmp/scratch29580/65552165.xls

InfoMile Solutions
Client: S.V.POWER PVT LTD Project: 500 TPH CFBC BOILER Job Title: Design of Footing Building: COMPRESSOR BUILDING Date: Done by: Checked by: 15.09.2008 AKV Rev: 0

Reference

Description of Problem
Punching Shear Punching Resistance Punching resistance is >

Values Units
895.33 kN 392.16 kN

Hence Safe in Punching Shear


Cl. 26.5.2.1 of IS:456-2000 Shrinkage reinforcement at top: Minimum Area of steel Provided Diameter of bar # 10 Spacing required Provide #10mm bars @ 250mm Final Results: Provide Size of the Footing: 1200 x 1500 x 400mm Bottom Main reinforcement about X-Direction: Provide #12mm bars @ 200 c/c Bottom Main reinforcementabout Z-Direction: Provide #12mm bars @ 200 c/c Shrinkage reinforcement at top: Provide #10mm bars @ 250 c/c 408.00 mm2 78.54 mm2 192.50 mm

file:///opt/scribd/conversion/tmp/scratch29580/65552165.xls