Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

7/19/11

Page 1

Schneider Electric - Curve Direct V3.4 - Tripping curves


t(s)

NW20H1-Micrologic 6.0 A-2000A


NS1000N-Micrologic 2.0 A-1000A

1000

100

10

0.1

0.01
1

10

100

1000

10000

I(A)

7/19/11

Page 2

Settings
Range

Masterpact

Compact

Circuit-breaker

NW20H1

NS1000N

Trip unit/curve

Micrologic 6.0 A

Micrologic 2.0 A

Rating

2000.00

1000.00

Long-time
Io
Ir

1.00

2000.0A

1.00

1000.0A

tr

2.0

2.0s

2.0

2.0s

Im/Isd

1.50

3000.0A

5.00

5000.0A

It (delay)

OFF

tm/tsd

0.20

Short-time

0.20s

Instantaneous
Ii

OFF

Discrimination
Limit

Upstream device

You might also like