การหาประสิทธิภาพเครื่องทำความเย็น
การหาประสิทธิภาพเครื่องทำความเย็น
Chiller
Compressor
Evaporator
Condenser
Cooling Water
Coolant
Cooling
coil
Chilled water
Condenser
Cooling water
Coolant
Compressor
Evaporative
condenser
water
Cooling water
Evaporator
Coolant
Cooling coil
Chilled water
Evaporator
Coolant
Air cool
Condenser
Evaporator
Cooling coil
Air
Coolant
Chilled water
Compressor
Air cool
Condenser
Evaporator
Air
Coolant
7 Absorption Chiller
Compressor
Condenser
Evaporator
Cooling
coil
B/D
Cooling Water
Coolant
Chilled water
Chilled Water
Coolant
Cooling Water
Evaporator Coolant
Cooling Tower
Compressor 264-277 Kw/hr ()
Chilled Water Pump 45.3 Kw/hr
Compressor
= Compressor
(Full load)
(Actual load) =
Kw/hr RT(/hr)
1,000 kg O C
1,000 kg 0 oC
79.68 kcal/kg
1 JRT = (1,000 x 79.68) / 24
= 3,320 kcal
o
Compressor
Chilled Water
Coolant
Q = R x 1,000 x T x C
Q
R
= , kcal/hr
= Evaporator, m3/hr
T = -
Evaporator , oC
C = , kcal/kgoC
(0.998 kcal/kgoC 40 oC)
~ 1 kcal/kg oC
Chiller 950
1.95 m/s
Evaporator 13.42
oC
Evaporator 8.58
Compressor 481 kw/hr
oC
T = 4.84 oC
R = /4 (10 in x 0.0254 m/in)2 x 1.95 m/s x 3,600 s/hr
= 355.71 m3/hr
Q = 355.71 x 1,000 x 4.84 x 1 kcal/hr
= 1,721,636.4 kcal/hr
(Actual load)
= 1,721,636.4 RT
3,024
= 569.32 RT
(Actual load)
= 481
569.32
= 0.845
kw/RT
kw/RT
Actual load
Chiller
- - Cooling tower
- - Evaporator
-
-
Actual load
Chiller 2
Actual load
Chiller 2
Standard Condition
o
Cooling tower = 32.2 C
Evaporator = 7.2 oC
T = 4.78 oC
R = 4,649 l/min = 278.94 m3/hr
1
Q = 278.94 x 1,000 x 4.78 x 1 kcal/hr
= 1,333,333.2 kcal/hr
(Actual load) = 1,333,333.2 = 440.9 RT
3,024
(Actual load)
= 270
= 0.61 kw/RT
440.9
Cooling tower 32.2 oC
Chiller 7.2 oC
RT
Cooling tower 38.05 oC
Chiller 9.11 oC
Correction Factor RT
35 oC , 9 oC = 0.98
40 oC , 9 oC
= 1.04
38 oC , 9 oC = {[(1.04-0.9)/5] x 3} + 0.98
= 1.016
= 440.9 x 1.016 = 447.95 RT
Correction Factor
35 oC , 9 oC = 0.94
40 oC , 9 oC = 0.88
38 oC , 9 oC = {[(0.94-0.88/5] x 2} + 0.88
= 0.904
= 270 x 0.904 = 244 RT
= 244 / 447.95
= 0.545 kw/RT
(Bench Mark) = ?
Building Chiller Replacement
World Bank .. 2543
CFC-Chiller < 0.8 1.0 kw/RT
Non CFC Chiller < 0.63 kw/RT
1.
2.
3.
( )
4.
()