Professional Documents
Culture Documents
1.1 Brief Description of The Excitation System
1.1 Brief Description of The Excitation System
To accomplish this, special field flashing equipment is needed. When the field flashing equipment is being supplied with power from a DC power source (power station battery), a resistor is used to limit the field flashing current. When it is being supplied from an AC power grid, a transformer serves as the adapter needed. Excitation of the generator is started by closing the field circuit-breaker Q1 and the field flashing breaker Q2. This supplies current to the field, which excites the generator up to 15 ....30% U. The generator then supplies voltage to the converter via the excitation transformer. Starting from approx.10% of the generator voltage, the firing electronics and the converter are able to continue the voltage build-up, so that the field flashing circuit is relieved of current. Once the voltage exceeds approx. 25% of U the field flashing breaker is finally opened, having no current. The diode bridge at the input to the field flashing breaker prevents a back-flow of current to the field flashing source. The converter TY has Final Pulse Stage, cooling and monitoring of the elements. Redundancy in the regulator section is ensured by means of two fully separate channels with independent measuring inputs and extensive monitoring (SUPERVISION) Channel 1 (AUTOMATIC channel) is built as voltage regulators and is ON during normal operation. In addition to the voltage regulator, which has a PID control algorithm,
the AUTOMATIC channel also contains various limiters and corrective control circuits to ensure the use and stable operation of the synchronous machine up to its operating limits. This channel possesses a Gate Control Unit with a subsequent Intermediate Pulse Stage to generate the firing pulses for the Thyristor converter. During normal operation, the Intermediate Pulse Stage of AUTOMATIC Channel, is active and transmits the firing pulses galvanically separated to the common pulse bus at the input to the Final Pulse Stage. Various monitoring functions of the AUTOMATIC channel and pulse monitoring on the common pulse bus initiate an automatic switch-over to stand by Channel (MANUAL)in case of a malfunction. Channel 2 (the MANUAL channel) is built as a simple field-current regulator with a PI control algorithm. It serves as a back-up channel in case of a malfunction on the AUTOMATIC channel. Manual channel performs valuable service for testing commissioning and preventive maintenance. The MANUAL channel has its own Gate Control Unit (the software for the If regulator is also implemented therein) and its own intermediate pulse Stage .During normal operation (AUTOMATIC), the output pulses from Intermediate Pulse Stage are blocked from reaching the pulse bus. Various monitoring on the MANUAL channel initiate an alarm in case of a malfunction while the MANUAL channel is on stand-by. If the MANUAL channel suffers a malfunction while it is in operation, the excitation is switched off (TRIP). Both channels are equipped with tracking equipment so that the inactive channel always generates the same control variable as the active channel during steady-state operation. This ensures smooth switch-over from Automatic to Manual channel and vice versa. To ensure that the MANUAL channel will, in a switch-over initiated by a malfunction, take over the operating point of the machine as it was prior to the problem, the response of the tracking for the MANUAL channel is set relatively slow. In addition to the pulse monitors (SUPERVISION) shown in the basic circuit diagram, the excitation system has an autonomous Excitation Monitoring. As one of its functions, this equipment monitors for field currents that exceed acceptable maximum limits. It initiates an emergency switch-over to the MANUAL channel whenever the field current exceeds the preset limit. If, even after such a switch-over, the field current does not drop back to
the permissible level, the excitation is switched off by Excitation Protection. The most important measuring inputs for the excitation system (If, Ug, Usyn) are redundant (2fold). The Excitation Monitoring checks these measuring inputs for discrepancy and plausibility. An alarm is always initiated in case of malfunction. In certain cases, a switch-over to MANUAL channel is also initiated. The excitation system contains an Excitation Protection to protect the excitation transformer, the converters, and the synchronous machine. The protection system can detect short-circuits in the excitation circuit and keep secondary damage within acceptable limits by a quick tripping of the excitation and an opening of the generator breaker. An overheating of the excitation transformer first sets off an alarm (at a given preset limit) and then likewise initiates a protective shut-down at an even higher limit . The over voltage protection in the deexcitation equipment provides an autonomous protective function for the rotor and the rectifier. This protection system monitors the field voltage in both polarities for over voltage and, if necessary, de-energizes the field via the de-excitation resistor.
them to issue the pulses at a given firing angle relative to the input voltage of the converter.
The signal processors 25 analog input/output modules. Each of these processor systems has a common bus circuit and output, and the control lines. There is a specific range of addresses assigned to each assignment. Board including the power supply bus, the address lines, the two data lines to the input calculates the reactive current (I . sin ) and the active current ( I.cos ). With these two channel processor. Synchronized with these interrupts (i.e., with the phase positions of current Ig, the field current If, and the synchronous voltage Usyn. From the exchange data with the microprocessor card across the two data lines. generator voltage Ug) this processor measures the generator current Ig, and then hardwired connections or multi-conductor cables. Binary and analog input/output modules i.e., for galvanic isolation and adaptation to the electronics level. The most important input interrupts per period to trigger the cycles for processing actual values in the AUTOMATIC module on the processor bus) for filtering and further processing.
Monitoring each consist of the central microprocessor module and binary and parameters to the AUTOMATIC channel are the generator voltage Ug, the generator peripheral unit, Ug, Ig, and Usyn are sent to the Interrupt Generator (plug-in peripheral units (wall-mounted units). peripheral units are used for preprocessing signals from external measurement circuits, power supply units. Signals are exchanged among these processor systems via processed across separate peripheral units for each channel. These processor working on the bus (a house address that can be adjusted using a switch).
systems. The AUTOMATIC channel, the programmable controls and the Excitation The actual values measured from AUTOMATIC channel and MANUAL channel are The AUTOMATIC channel and the MANUAL channel, each have their own The digital voltage regulator is broken down into several autonomous microprocessor The inputs and outputs of the processor systems are directed across voltage-isolating The Interrupt Generator also uses the 3-phase Ug signal to generate the 12 themselves contain a limited number of hardware inputs and outputs with fixed equipment Whenever addresses from this range are called up, the signal processing module can results, the processor is then able to derive further operating parameters, such as the load angle, the active power, etc. The functions of all microprocessor systems other than the programmable controls have been accomplished in firmware. The non-varying standard function modules can be configured to the design desired, for plant-specific purposes, using software switches (KFlags). Thus, for example, the stored status of a K-Flag determines whether or not a Limiter is active, and whether the de-excitation or the excitation limiters take precedence. Because these K-flags determine the software Scope of Supply for the installation, they cannot be changed permanently via the Micro-Terminal. In this way, they differ from such setting data as the values of the parameters for the PID filter of the voltage regulator or the set-points for the limiters. These values can be permanently changed using the Micro-Terminal. Communication is possible with each of the processor systems via the Micro-Terminal by plugging on the connecting cable. In this way, signals within the processor and setting parameters can be viewed, analog signals can be issued, and the set parameters can be altered temporarily (F... range) or permanently (C... range). Unlike the other processor systems, the programmable controls do not include any firmware for realization of the functions. They have been designed so that the designer can adapt and change their functions easily using the Functional Block Programming Language P10. Digital and analog functions can be implemented in practically any degree of complexity desired using the P10 functional blocks. The control variable of the voltage regulator (AUTOMATIC channel) and the control variable of the field current regulator (MANUAL channel) are each processed in separate Gate Control Unit and formed into a chain of pulses at the appropriate firing angle. The pulses of the active channel are directed to the pulse bus via the associated Intermediate Pulse Stage. The pulses for each converter block are amplified sufficiently in Final Pulse Stage to fire the Thyristor.
intervened. The control deviation at the input to the PID filter is either the control deviation for voltage, the control deviation of a de-excitation limiter (the value determined by minimum value selection), or the control deviation of an excitation limiter (the value determined by maximum value selection). Flag F730 (PRIOR) is used to determine whether the exciting (Min. value) or the de-exciting signal takes precedence on the min/max value limiter (normally: F730 = 1111, i.e., the de-exciting signal takes precedence). With the exception of the Minimum Field Current Limiter, all other limiters have variable factoring multipliers of the signal outputs so that they can be adjusted individually together with the common PID filter, which has been optimized for voltage regulation. The setting parameters for this PID filter are as follows: Vo = KR Static amplification 1 Ta = ---- Integration time constant Tc1 Vp Proportional amplification 1 Tb = ---- Differential time constant Tc2 V Amplification of high frequencies
The BODE diagram below shows the assignment of settings in accordance with DIN/IEC standards based on a typical example:
The PID filter amplifications Vo, Vp, and V can be adjusted in p.u. values. But the ceiling factor pl+ must be adjusted correctly with parameter F310 if the total amplification (circuit amplification) of the control circuit is actually to conform to the p.u. settings. This factor must agree with the external amplification, i.e., with the ceiling value of the transformer-/ converter circuit: Ceiling factor(pl+) = Ufmax /Ufo in which Ufmax = ceiling field voltage Ufo = no-load field voltage To attain a suitable response of the AVR when starting excitation (EXCITATION ON), it may be necessary to change the proportional amplification of the regulator during this phase. Vp2 (transiently activated) and Vp1 (permanently activated) can be adjusted for this purpose. For example, the value of Vp2 takes effect immediately once the excitation is switched on and remains effective for a period as set at F30C. Once the period F30C (e.g., 5 sec) has expired, Vp shifts over to Vp1 (becomes the steady-state Vp) at the rate of change set. The standard operating mode for the PID filter is voltage regulation, for which the discrepancy between the voltage set-point and the current value for generator voltage Ug (the control deviation) is supplied at the input. To compensate for the voltage drop in the block transformer, or whenever several generators are operating to the same distributing bus, the generator voltage must be varied in proportion to the measured generator current (droop influence). To accomplish this, the voltage set-point is varied as a function of the measured reactive current IX and/or active current IR. Flag F712 enables the IX droop, Flag F710 the IR droop. The desired compensation is set in F282 and F286 respectively. Flags F284 and F288 are used
to select whether this droop influence is to increase the voltage or to reduce it (compensation). Combined influence of the active and reactive currents is attained by enabling both droops, IX and IR. Flag F716 activates a so-called Soft-Start at the starting of excitation. This Soft-Start ensures that the voltage set-point integrates from 0% to 100% within the time set on F290 when the excitation is switched on (EXCITATION ON). A smooth excitation of the generator can be achieved in this way whenever there is no demand for a quick excitation.
Example: The setting of =idt equivalent to Version a (F416) at a constant 1.6 times the nominal field current for 10 seconds (with TH1/2 = 105%) is:
loading of the generator is low. In this case, if the stator current limiter is not kept from influencing the field current, the control circuit will oscillate back and forth between the Inductive Stator Current Limiter (deexciting) and the Capacitive Stator Current Limiter (exciting).The output signal of that function then dominates the control variable of the Ig-dependent limiter via a maximum value selection.
The purpose of a Power System Stabilizer is to use the generator excitation to damp electromechanical oscillations between the network and the generator. Depending on the design of the generator and the requirements imposed for network stability, its main function will be either to damp the oscillations originating in the machine or those from the network. A synchronous generator working in a combined power network is, in principle, an oscillating structure. In order to produce a torque, the magnetic field of the rotor and the stator must form a given angle (referred to as the rotor displacement or load angle ). The electrical torque ME increases as the angle increases, just as with a torsion spring. Because the ME of the generator and the mechanical driving torque MA from the turbine are in equilibrium during steady-state operation, the angle remains in a given position. Whenever this state of equilibrium between MA and ME is disturbed, the load angle slips of this rest position, and change thereby the electrical torque ME. The torque attempts to restore the load angle to a stationary position. Due to the mass inertia of the turbine/generator rotor, however, this can only take place aperiodically. It does so in the form of more or less effectively damped oscillations (again similar to the effect of mass inertia on a torsion spring). In order to damp the oscillations, there must be a damping torque produced depending not on the electrical torque ME associated with the angle, but on the difference in frequency (Df) between the rotor and the stator rotating field, i.e., on the slippage. This torque is produced mainly by the so-called damper winding in the rotor, but the dimensioning of this is subject to limits imposed by considerations of design and economy. Some further action is therefore needed to increase the damping effect. The following drastically simplified formula shows the parameters upon which the amount of active power PE supplied by the generator depends: PE = active power
It can be seen from the above relationship that the active power that the generator transfers depends not only on the load angle , but also on the field current If. That means
that a transient change can be made in the active power PE and with that in the effective electrical torque ME by varying the field current. The principle of operation of the DVR Power System Stabilizer becomes clear from a consideration of the oscillations in power output and frequency (PE, f) and the vector diagram: If it is assumed, that oscillations in the network frequency generates load oscillations with the mass inertia of the rotor, then the active load of the generator (e.g. MW-measured) is influenced with a sinusoidal value -PE (ME-MA = -PE). By inversion of -PE, one obtains the fluctuation in power provided by the rotor, +PE. As is known, the slip signal f follows +PE with a phase delayed by 90. The +ME produced by the periodic changes in the load angle is in phase with +PE. A good damping is attained if ME is varied in phase with the slip f. However, this signal must also be advanced somewhat to compensate for the time constants in the excitation circuit and the generator. As mentioned above, the electrical torque ME can be influenced by varying the field current. To accomplish this, a suitable control signal, referred to as variable disturbance compensation, must be imposed upon the voltage set-point or the converter control variable Ucontr. As can be seen from the vector diagram, by applying proper weighting factors (K1, K2), and then adding together the signals -PE and f, an overall stabilization signal can be produced that rotates in advance of the Df signal by any angle desired between 0 and 90. Because the amplitude of -DPE remains proportional to the amplitude of f, a constant angle in advance of f results for the compensation of the time constants referred to above. The optimum weighting factors K1 and K2 for a synchronous generator working to a power network depend on its operating point at any moment and the external reactance of the network. Normally, the selection of a compromise setting is good enough to attain stability in all operating points and for all external reactance. For special demands, these settings must be parameterized as a function of the external reactance (which means, optional equipment: Xe-Identification). The Power System Stabilizer PSS is a section of the AVR computer program and is processed once per network cycle. The voltage at the generator terminals and the generator current are measured in order to define the signals PE and f. The calculated signals for _P_ (=PE) and f are then sent across DC filters D (real differentiators) that transmit only the dynamic portion of the signals. The PE and f signals obtained in this
way are then weighted (multiplied by) with the factors K1 and K2 and sent to the summing point of the voltage regulator.
The PSS stabilization signal is imposed on the automatic voltage regulator only if the following prerequisites are met: Generator on line Generator power output > the value F338 Generator voltage in a range between F33C and F33A The stabilization signal is limited at the output from the PSS to the lower and upper limits. Flag defines whether the stabilization signal is introduced before or after the PID filter (usually before the filter). Because the PID filter, as noted above already takes the ceiling factor Vp1 into account, the PSS signal needs to be multiplied by Vp1 if it is added to the voltage regulator following the PID filter (divider at the input to the min/max limiter). This precaution prevents the DC filter D in the P-channel from producing an unnecessary stabilization effect in the case of rapid changes in turbine load. As an alternative for the AVRs Power System Stabilizer, a stabilization signal from an outside system can be imposed by activating the binary input PSS-SIGN.EXT. Flag F340 can be used to select between an analog and a 12-bit signal, and F33E to select the polarity desired for that signal.
without additional limiters. Its main function is to maintain the excitation of the generator even if the AUTOMATIC channel becomes non-operational. The MANUAL channel also performs valuable service for purposes of testing, commissioning, and preventive maintenance. Its measurements, regulator, generation of firing pulses, and power supply are physically separate from those on the AUTOMATIC channel. 2.4.2 Principle of Operation All the functions of the MANUAL channel including the generation of firing pulses, have been implemented in a single electronic module, the Gate Control Unit. The control variable Ucontr of voltage regulator is used as the reference value for generating firing pulses on the principle, known as ramp control (Comparison of Ucontr with Usynsynchronous sawtooth signal). For further processing in the UN 0096 Intermediate Pulse Stage, the Gate Control Unit supplies six firing pulses at its output whose phase position with respect to the synchronous voltage Usyn is in accordance with control variable Ucontr. An internal linearization ensures that the field voltage produced via the firing pulses remains proportional to the control variable Ucontr throughout the entire range. As a result, the circuit amplification of the control remains constant over the entire range. Whenever excitation is switched ON the set-point for Generator Voltage is set automatically at the preset - ref. Value. This provision ensures that the generator voltage always attains approximately its nominal value after the field flashing. The Gate Control Unit can be refunctioned ( by pre-selection with a switch ) for purposes of testing to act as a purely firing pulse control. In this case, the control variable Ucontr is adjusted directly using the RAISE/LOWER push buttons on the front of the module. In this way, for example, the relationship between the phase position of the firing pulses and the control variable Ucontr can be checked easily.
from the Intermediate Pulse Stage (with pulse transmitters) and are then directed to the common pulse bus. This transmission of the pulse signals to the pulse bus via passive transmitters ensures a high degree of active channel autonomy. Practically no possible malfunctions on the inactive channel (including, for example, sustained pulses) affect the active channel.
CHAPTER 4 CONVERTER
Thyristor:
The term thyristor usually refers to a family of four layer solid state device having turn on characteristics that can be externally controlled by either current or voltage. They are also referred to as breakdown device because their working depends on avalanche breakdown. Thyristors have only two stages: OFF and ON. Thyristors have a similar function to Uni-junctions they act as switches. Thyristors use current flow as a switch.
Thyristors have three states: 1. Reverse blocking mode Voltage is applied in the direction that would be blocked by a diode 2. Forward blocking mode Voltage is applied in the direction that would cause a diode to conduct, but the thyristor has not yet been triggered into conduction 3. Forward conducting mode The thyristor has been triggered into conduction and will remain conducting until the forward current drops below a threshold value known as the "holding current". Converter is a semiconductor device which converts ac input voltage into a constant dc output voltage. In present excitation system three phase fully controlled thyristor converter is used.
Because of the following advantages thyristor converters are used. a) Thyristors are used for high power applications .i.e., up to 10Kv,3500A,1KHz. b) Having high reliability and low losses. c) Uni-directional device like diode. d) Its operation as a rectifier which are low resistance in forward conduction mode and high resistance in reverse conduction mode.
PROTECTION OF THYRISTORS:
For reliable operation of a thyristor demands that its specified ratings are not exceeded. When Subjected to or over voltages. During the turn - on of SCR di/dt prohibitively large. False triggering of SCR by high value of dv/dt andSpurious signals between gate and cathode may leads to unwanted turn on.
destroys the thyristor. Thyristor thermal time is constant. The causes due to faults and short circuits or surge currents. Electronic crowbar protection is used against the over voltages. The rate rise of anode current must be kept at the time of turn on below the rated or specified limiting value. The di/dt value maintained below limited value by using a inductor also called di/dt inductor in series with anode circuit. The locality of heating is avoided by applying gate current but not greater the maximum gate current.
produced. This voltage several times the break over voltage of the device, then thyristor destroys permanently.
Gate protection:
Gate circuit should also be protected against the over voltages and surges. Over voltage at gate circuit can cause false triggering of the SCR may rises the junction temperature behind specified limit leading to its damage. Protection against over voltage can be achieved by connecting a ZD across the gate circuit, and a resister is connected in series with gate circuit to protect against the s. A capacitor and resister are connected across gate to cathode to by pass the noise.
Fig: Field Flashing Because the field flashing contactor is not able to switch off the energy stored in the field, the control ensures that the contactor can only reopen if the field circuit breaker has already been opened (generating the TRIP order) or, in a normal field flashing sequence, when the converter has taken over the field current. Field flashing occurs in the following stages: The excitation is switched on, closing the field flashing contactor ( Field Circuit Breaker is already closed ). The start-up excitation current flows through the rotor, driving the generator voltage up to approx. 15% U After about 10% U, the firing pulses to the converter are released and it begins to excite the generator to its rated voltage. After about 30% U, the field flashing contactor opens (with no current, since the converter is now supplying the current). The diode bridge at the input to the field flashing contactor prevents a feed-back from the converter to the source of field flashing while the contactor is still closed.
5.3 De-excitation
When malfunctions occur, the stored field energy must be dissipated as quickly and safely as possible to protect the generator. This is done by the converter, the field circuit-breaker, and the de-excitation (discharge) resistor. De-excitation (with opening of the field circuit-breaker) takes place in the following stages:
The converter, drives to its inverter limit position (negative ceiling voltage), recovers a portion of the field energy into the network. A trip command is given to the field circuit breaker. The de-excitation contact closes, diverting the field voltage to the de-excitation resistor. Then, immediately, the main contacts open, building voltage. The field voltage commutates to the de-excitation resistor. The current diminishes at a given time constant TE: (With linear resistance: TE = Lf/ (Rf + Re)) Due to the reversal of the field voltage by the converter, the field current commutates from the main contacts of the field circuit-breaker to the de-excitation resistor in a very early phase. This reversal of the field voltage prevents burn-off on the main contacts and provides effective protection for the field circuit-breaker. Depending on the operating policy, an operational shut-down of the excitation can also be effected with the field circuit-breaker closed. This method is useful mainly when the excitation is switched on and off frequently. In this case, the converter is merely driven into the inverter limit position so that the field energy is recovered into the network. The converter then blocks since it is supplying positive current only.
CHAPTER 6
The Excitation Monitoring supplies the criterion for switching off the field flashing Whether this criterion is activated based on the actual value for generator voltage Ug or for field current If, or both, depends on the settings of the two threshold values F200/F202 (0% setting means that the output is always logical 1). The measurements Ug1/2 and If1/2 are switched over depending on the present status of the channels (Channel 1 or Channel 2 ON). Whenever Flag F750 is not activated, the binary output is fixed at logical 1.
In that case, Flag F75A can be used to deactivate comparative measurements Ug1/ Usyn1 and Ug2 / Usyn2. The primary monitoring compares Ug1 with Ug2 and generates the messages that Channel 1 or Channel 2 has suffered a malfunction. Whenever Ug1 < Ug2 and the binary message from CH1 reports no malfunction, a malfunction on Measurement Channel 1 is reported (Ug1/Usyn1 FAILURE). A similar malfunction is also present whenever the binary message CH1 DISTURBANCE is reported and a discrepancy is detected between Ug1&Ug2. The generation of the alarm Ug2 / Usyn2 FAILURE is analogous to that for Channel 1. The secondary monitoring compares Ug1 with Usyn1 & Ug2 with Usyn2. This is enabled whenever the binary message of the comparison channel reports a malfunction, or whenever both binary messages report no malfunction - but both secondary monitors report a malfunction. As long as the secondary monitoring is blocked, the differences Ug1Usyn1 or Ug2Usyn2 trigger malfunction signals for the measurement channel involved (suspicion that there is a corresponding error in Usyn). The measurement channel malfunctions are enabled operationally, whenever, after excitation has been switched on, generator voltage Ug exceeds the value set on F204. The voltages Ug1 and Ug2 are checked 16 seconds after the excitation is switched off to see that they do not exceed the limit value F210 that applies to both of them . At the same time, g1/Ug2/Usyn1/Usyn2 are checked for extreme values (> or < the operating range). Monitoring for extreme values is likewise enabled during normal operation ( Excitation ON and Ug > F204 ). Flag F754 is used to enable or block the malfunction signals to the binary outputs. Basically, the monitoring of the actual values for If1/If2 functions like that of the Ug1/Ug2 monitoring.
S.NO 1 2 3 4 5 6 7 8 9 10 11
PARTICULARS VREF VACT IFACT IGACT ACTIVE POWER REACTIVE POWER POWER FACTOR ACTIVE CURRENT(IR) REACTIVE CURRENT(IX) POWER ANGLE FIRING ANGLE
ACTUAL VALUE 99.6% 99.7% 73.5% 70.3% 70.3% 10.1% 0.99 IND 70.5% 10.2% 56.6% 64.0%
OBTAINED VALUE 100% 100.3% 76.5% 70.7% 70.5% 14.2% 0.98 IND 70.3% 13.8% 54.6% 63.2%
TEST
VALUES OBTAINED WHEN EXCITATION IS LOWERED S.NO 1 2 3 4 5 6 7 8 9 10 11 PARTICULARS ACTUAL VREF VACT IFACT IGACT ACTIVE POWER REACTIVE POWER POWER FACTOR ACTIVE CURRENT(IR) REACTIVE CURRENT(IX) POWER ANGLE FIRING VALUE 100% 100% 78.7% 83.9% 83.9% 15.5% 0.98 IND 83.5% 14.0% 61.3 DEG 60.1 DEG OBTAINED VALUE 99.7% 99.7% 76.1% 83.7% 83.0% 11.0% 0.99 IND 83.0% 9.4% 63.1 DEG 59.9 DEG
ANGLE
CONCLUSION
For generating the EMF in stator winding, excitation is required to the rotor of a generator. There are two types of excitation 1. Static excitation system. 2. Brushless excitation system. A certain disadvantage in brushless excitation system is the slow response time of the field in case of fast load changes specified. No slip-rings and brushes, direct measurements of the field parameters not possible. To avoid all loses, static excitation is used. Since it does not have any rotating parts, mechanical loses and windage loses. This system has fast response and speed control. While preferring this excitation system, there are no limitations for the redundancy of Thyristor bridge circuits. Static excitation has fast field discharge by resistor and inverter operation, direct measurement of field quantity is possible. The meaning of excitation is nothing but continuous supply of DC current (i.e., field current) to the rotor to buildup required output voltage in the stator. Field current is changed with respect to the change of load, so the digital automatic voltage regulator (DAVR) is used to regulate the output voltage according to the load variations.
So we conclude that static excitation system with DAVR is preferred since it is having excellent dynamic performance and better options for R & M.