Emerson Battery Selection Guidance
Emerson Battery Selection Guidance
Part 1:
Example :T12V100SE/A
T 12 V 100 SE / A
Identity number differences of batteries expressed by A,B,C....... no default)
Structure expressed by 1-3 bits capital letters, see the explanations below Capacity(rated capacity for Telion series, it is C10 for UPStar series, it is C20) Voltage rated voltage of battery, not default value Series number English capital letters T stands for Telion series U stands for UPStar series
Note The structure is expressed by 1-3 bits of capital letters and the definitions are given below: Fire retardant Front access Gas collection S F (Security); defined as default if the battery is not fire retardant (Front Access); Front access is defined as default E (Environmental); No gas collection is defined as default GFM-200
Part 2
Selection of batteries used for communication power supplies
1 Select the batteries with the reference to the tables in the rear part according to the following rules and the battery capacity calculated
through power supply selection (The Telion series batteries for selection include: 6V100Ah, 12V40Ah, 12V50Ah, 12V65Ah, 12V80Ah, 12V100Ah; 2V200Ah, 2V300Ah, 2V400Ah, 2V500Ah, 2V650Ah, 2V800Ah, 2V1000Ah, 2V1600Ah, 2V2000Ah, and 2V3000Ah). (1) Two 48V battery strings connected in parallel are the main configuration, other configurations are subordination selections; (2) Select 2V battery for the capacity above 48V400Ah (2 battery strings in parallel should be given the top priority, 1 string or less than 6 strings in parallel is the auxiliary configuration) ; (3) Select 12V battery for the capacity below 48V300Ah (2 battery strings in parallel is the main configuration, 1 string or 3 strings in parallel is the auxiliary configuration) ; 2V battery can also be selected (1 battery string of 48V200Ah or 48V300Ah) , among them, 2 battery strings in parallel is the preferable scheme. (4) Cautions for configuring battery capacity 1) Configuration of battery strings: For important telecom station, the batteries should be configured in 1+1 redundancy mode. Under other conditions, the designing capacity should be halved or only one battery string is selected. 2) Upper limit of battery capacity: Cmax 50Iload
Step
2 Determine the battery installation mode according to battery capacity and field reconnaissance data of battery room
(1) Field reconnaissance data of battery room include bearing capacity of floor (if the equipment is installed in 2nd floor or above), space of machine room, anti-shock requirements and so on; (2) User can also select the installation mode designed by ENP, which is much more widely applied; (3) Battery installation mode should be defined clearly if special design is required according to actual machine room layout.
Part 2
Selection of batteries used for communication power supplies
2. Installation illustrations and parameters of batteries used for communication power system
2.1. Installation illustrations and parameters of 48V100Ah battery
Single layer single row installation illustration of 48V100Ah battery
Quantity (PCS) 4
Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock Please refer to Appendix B if battery cabinet is used.
Quantity (PCS) 24
Note: Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock requirements and so on) Please refer to Appendix B if battery cabinet is used.
Part 2
Selection of batteries used for communication power supplies
Quantity (PCS) 24
Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock Please refer to Appendix B if battery cabinet is used.
Quantity (PCS) 24
Note: Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock requirements and so on) Please refer to Appendix B if battery cabinet is used.
Part 2
Selection of batteries used for communication power supplies
Quantity (PCS) 24
Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock Please refer to Appendix B if battery cabinet is used.
Quantity (PCS) 24
Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock Please refer to Appendix B if battery cabinet is used.
Part 2
Selection of batteries used for communication power supplies
Quantity (PCS) 24
Remark Single layer single row battery rack 4-layer flat-laying battery rack
Note: Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock requirements and so on) Please refer to Appendix B if battery cabinet is used.
Quantity (PCS) 24
Remark Single layer single row battery rack 4-layer flat-laying battery rack
Note: Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock requirements and so on) Please refer to Appendix B if battery cabinet is used.
Part 2
Selection of batteries used for communication power supplies
Quantity (PCS) 24
Remark Single layer single row battery rack single laying 2-row battery rack
Note: Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock requirements and so on)
Quantity (PCS) 24
Remark Single layer single row battery rack single laying 2-row battery rack
Note: Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock requirements and so on)
Part 2
Selection of batteries used for communication power supplies
Quantity (PCS) 24
Remark Single layer single row battery rack single laying 2-row battery rack
Battery installation mode can be designed according to reconnaissance data (space of machine room, bearing capacity of floor and anti-shock
Part 3
Selection of batteries used for UPS
1 Select the batteries with the reference to the tables in the rear part according to the following rules and the battery capacity calculated through
power supply selection. 1 Telion 2V series battery 400Ah 3000Ah should be used when the capacity of battery strings exceeds 400Ah; 2 3 4 5 Generally, the number of battery strings in parallel is 2 or 3; One battery string is the main configuration mode if the required voltage is high 240V or above , others are subordinate configuration; Telion series battery should be preferably selected if the backup time is required to be longer than 8h; UPStar series battery(low price) should be preferably selected if the cost is the main considerations.
Two battery series can be selected Telion series 6V100Ah 12V40Ah, 12V50Ah, 12V65Ah, 12V80Ah, 12V100Ah 2V200Ah, 12V24Ah, 12V38Ah, 2V300Ah, 2V400Ah, 2V500Ah, 2V650Ah, 2V800Ah, 2V1000Ah, 2V1600Ah, 2V2000Ah, and 2V3000Ah; UPStar series 12V65Ah, 12V100Ah, and 6V200Ah .
Step
2 Determine the battery installation mode according to battery capacity and field reconnaissance data of battery room
1 2 3 above , space of machine room, anti-shock requirements and so on; User can also select the installation mode designed by ENP, which is much more widely applied;
Field reconnaissance data of battery room include bearing capacity of floor if the equipment is installed in 2nd floor or
Battery installation mode should be defined clearly if special design is required according to actual machine room layout.
Part 3
Selection of batteries used for UPS
Quantity (PCS) 3 3 6 6
Remark
suitable for 1KVA UPS with backup time of 1h suitable for 1KVA UPS with backup time of 2h suitable for 1KVA UPS with backup time of 4h suitable for 1KVA UPS with backup time of 8h
Part 3
Selection of batteries used for UPS
2.2 Installation illustrations and parameters of batteries with 96V rated voltage
battery model
U12V38/A U12V65/A U12V100/A U12V100/A
Quantity (PCS)
8 8 8 16
Total weight K g
132 207 327.2 654.4
Remark
suitable for 2KVA UPS with backup time of 1h suitable for 2KVA UPS with backup time of 2h suitable for 2KVA UPS with backup time of 4h suitable for 2KVA UPS with backup time of 8h
Part 3
Selection of batteries used for UPS
2.3 Installation illustrations and parameters of batteries with 120V rated voltage
battery model
U12V38/A U12V65/A U12V100/A U12V100/A
Quantity (PCS)
10 10 10 20
Battery installation sizes L W H mm 450 450 450 900 530 900 900 900 battery cabinet: 620 battery cabinet 800 battery cabinet 800
Total weight K g
158.2 261 411.3 822.6
Remark
suitable for 3KVA UPS with backup time of 1h suitable for 3KVA UPS with backup time of 2h suitable for 3KVA UPS with backup time of 4h suitable for 3KVA UPS with backup time of 8h
Part 3
Selection of batteries used for UPS
2.4 Installation illustrations and parameters of batteries with 240V rated voltage
battery model
U12V38/A U12V65/A U12V100/A U12V100/A U12V100/A
Quantity (PCS)
20 20 20 40 80
Total weight K g
301.3 502 802 1604 3208
Remark
suitable for 6KVA UPS with backup time of 1h suitable for 6KVA UPS with backup time of 2h or 10KVA UPS with backup time of 1h suitable for 6KVA UPS with backup time of 4h or 10KVA UPS with backup time of 2h suitable for 6KVA UPS with backup time of 8h or 10KVA UPS with backup time of 4h suitable for 10KVA UPS with backup time of 8h
Part 3
Selection of batteries used for UPS
2.5 Installation illustrations and parameters of batteries with 480V rated voltage
single battery string(480V) installation illustration Capacity of battery strings 480V24Ah 480V38Ah 480V65Ah 480V100Ah 480V130Ah 480V200Ah 480V300Ah battery model U12V24/A U12V38/A U12V65/A U12V100/A U12V65/A U12V100/A U12V100/A Quantity (PCS) 40 40 40 40 80 80 120 Number of battery strings 1-string 1-string 1-string 1-string 2-string of 480V65Ah in parallel 2-string of 480V100Ah in parallel 3-string of 480V100Ah in parallel 980 980 980
2 battery strings(480V) in parallel Battery installation sizes L 800 800 980 980 W 450 450 450 450 450 450 450 H mm battery cabinet 900 total 2PCS 900 total 2PCS 1245 total 2PCS 1245 total 2PCS 1245 total 4PCS 1245 total 4PCS 1245 total 6PCS battery cabinet battery cabinet battery cabinet battery cabinet battery cabinet battery cabinet Total weight Kg 430.6 602.6 1004 1604 2008 3208 4812
3 battery strings(480V) in parallel Remark suitable for 10KVA UPS with backup time of 1h or 15KVA UPS with backup time of 30min suitable for 15KVA UPS with backup time of 1h or 20KVA UPS with backup time of 30min suitable for 10KVA UPS with backup time of 2h or 20KVA UPS with backup time of 1h suitable for 10KVA UPS with backup time of 4h or 15KVA/20KVA UPS with backup time of 2h suitable for 15KVA UPS with backup time of 4h suitable for 10KVA/15KVA UPS with backup time of 8h or 20KVA UPS with backup time of 4h suitable for 20KVA UPS with backup time of 8h
Part 3
Selection of batteries used for UPS
2.6 Installation illustrations and parameters of batteries with 360V rated voltage
650Ah cell)
1000Ah cell)
Part 3
Selection of batteries used for UPS
Quantity (PCS) 30
Battery installation sizes L W H mm One 20PCS-battery cabinet (800 900) and one 10PCS-battery 620 450 530 800
Remark suitable for 20KVA UPS with backup time of 10min suitable for 20KVA UPS with backup time of 15min; or 30KVA UPS with backup time of 10min suitable for 30KVA UPS with backup time of 15min suitable for 20KVA/30KVA UPS with backup time
cabinet 360V38Ah U12V38/A 30 1-string 2-string of 360V24Ah in parallel 1-string 800 450 900
460
646
360V65Ah
U12V65/A
30
815
of 30min or 40KVA UPS with backup time of 10min/15min or 60KVA with backup time of 10min suitable for 20KVA UPS with backup time of 1h; or 40KVA UPS with backup time of 30min or 60KVA UPS with backup time of 15min; suitable for 20KVA UPS with backup time of 2h or 30KVA UPS with backup time of 1h suitable for 20KVA UPS with backup time of 3h or 30KVA UPS with backup time of 2h; or 40KVA UPS with backup time of 1h or 60KVA UPS with backup time of 30min suitable for 20KVA UPS with backup time of 4h/5h;
360V100Ah
U12V100/A
30
1325
360V130Ah
U12V65/A
60
1630
360V200Ah
U12V100/A
60
2650
360V300Ah
U12V100/A
90
3975
or 30KVA UPS with backup time of 3h/4h; or 40KVA UPS with backup time of 2h; or 60KVA UPS with backup time of 1h
Part 3
Selection of batteries used for UPS
battery model
Quantity (PCS)
Total weight Kg
360V400Ah
T2V400E/A
180
1-string
400
1010
5610
or 30KVA UPS with backup time of 5h; or 40KVA UPS with backup time of 3h; or 60KVA UPS with backup time of 2h suitable for 30KVA UPS with backup time of 6h; or 40KVA UPS with backup time of 4h suitable for 30KVA UPS with backup time of 8h; or 40KVA UPS with backup time of 5h/6h or 60KVA UPS with backup time of 3h/4h suitable for 40KVA UPS with backup time of 8h; or 60KVA UPS with backup time of 5h Used for 60KVA UPS with backup time of 6h Used for 60KVA UPS with backup time of 8h
360V500Ah
T2V500E/A
180
1-string
400
1010
7762
360V650Ah
T2V650/A
180
1-string
400
1022
9157
360V800Ah
T2V800/A
2.7 Installation illustrations and parameters of batteries with 384V rated voltage
Part 3
Selection of batteries used for UPS
1 battery string(384V) installation illustration(2V400Ah Capacity of battery strings 384V100Ah battery model U12V100/A Quantity (PCS) 32
600Ah cell)
2 battery strings(384V) installation illustration(2V800Ah Battery installation sizes L W H 480 mm 1190 415 975 battery rack 1500
1000Ah cell)
Number of battery strings 1-string 2-string of 384V65Ah in parallel 2-string of 384V100Ah in parallel 3-string of 384V100Ah in parallel
Remark suitable for 80KVA UPS with backup time of 15min or 120KVA UPS with backup time of 10min suitable for 80KVA UPS with backup time of 30min or 160KVA UPS with backup time of 15min or 200KVA UPS with backup time of 10min suitable for 160/200KVA UPS with backup time of 15min; or 300KVA UPS with backup time of 10min suitable for 120KVA UPS with backup time of 30min or 300KVA UPS with backup time of 15min or 400KVA UPS with backup time of 10min suitable for 80KVA UPS with backup time of 1h or 160/200KVA UPS with backup time of 30min or 400KVA UPS with backup time of 15min or 600KVA UPS with backup time of 10min
384V130Ah
U12V65/A
64
battery rack 1485 total 2PCS battery rack 1500 total 2PCS battery rack 1500 total 3PCS
1500
384V200Ah
U12V100/A
64
480
1190
2464
384V300Ah
U12V100/A
96
480
1190
3696
384V400Ah
T2V400E/A
192
1-string
5984
Part 3
Selection of batteries used for UPS
or 600KVA UPS with backup time of 15min; or 800KVA UPS with backup time of 10min suitable for 80KVA UPS with backup time of 2h;
384V800Ah
T2V800/A
192
1-string
493
1450
12192
or 160KVA UPS with backup time of 1h; or 300KVA UPS with backup time of 30min suitable for 80KVA UPS with backup time of 3h/4h; or 120/160KVA UPS with backup time of 2h;
384V1000Ah T2V1000/A
192
1-string
14688
or 200KVA UPS with backup time of 1h; or 400KVA UPS with backup time of 30min; or 800KVA UPS with backup time of 15min suitable for 300KVA UPS with backup time of 1h or 600KVA UPS with backup time of 30min suitable for 200KVA UPS with backup time of 2h suitable for 120/160KVA UPS with backup time of 3h/4h; or 400KVA UPS with backup time of 1h; or 800KVA UPS with backup time of 30min suitable for 200KVA UPS with backup time of 3h;
384V1300Ah 384V1600Ah
T2V650/A T2V800/A
battery rack 14720 800 1022 986 1450 battery rack 12640 battery rack 12640 986 1450
384V2000Ah T2V1000/A
384V3000Ah T2V3000/A
192
44480
or 300KVA UPS with backup time of 2h; or 600KVA UPS with backup time of 1h
384V4000Ah T2V2000/A
384
59200
Appendix A
1. Telion series
SN Product Photo Product Model Specification Outline Dimensions L W H(mm) Weight (Kg) Remark
T6V100/A (3-GFM-100)
6V100Ah
205
177
300
27.0
T12V50/A (6-GFM-50)
12V50Ah
357
178
221
28.0
T12V65SE/A (6-GFM-65N)
12V65Ah
356
178
230
33.0
Appendix A
SN
Product Photo
Product Model
Specification
Weight (Kg)
Remark
T12V80/A (6-GFM-80)
12V80Ah
400
177
300
46.0
T12V100/A (6-GFM-100)
12V100Ah
400
177
300
54.0
T12V100SE/A (6-GFM-100N)
12V100Ah
360
177
265
43.5
T12V100SE/B (6-GFM-10019N)
12V100Ah
407
173
225
42.0
Appendix A
SN
Product Photo
Product Model
Specification
Weight (Kg)
Remark
T12V100SEF/A (6-GFM-100PS)
12V100Ah
520
105
253
42.0
10
T2V200E/A (GFM-200
2V200Ah
98
178
385
16.0
11
T2V300E/A (GFM-300
2V300Ah
143
178
385
24.5
12
T2V400E/A (GFM-400
2V400Ah
164
178
385
27.0
Appendix A
SN
Product Photo
Product Model
Specification
Weight (Kg)
Remark
13
T2V500E/A (GFM-500
2V500Ah
214
180
385
38.0
14
T2V650/A (GFM-650)
2V650Ah
261
180
385
46.0
15
T2V800/A (GFM-800
2V800Ah
254
210
512
61.0
16
T2V1000/A (GFM-1000
2V1000Ah
254
210
521
74.0
Appendix A
SN
Product Photo
Product Model
Specification
Weight (Kg)
Remark
17
T2V1600/A (GFM-1600)
2V1600Ah
355
332
387
130.0
18
T2V2000/A (GFM-2000)
2V2000Ah
425
357
387
155.0
19
T2V3000/A (GFM-3000)
2V3000Ah
616
358
388
243.0
Main features
1 2 Long life in telecom level Designing according to special telecom requirements with 15-year designing life. New generation grid alloy: The battery has strong anti-corrosion and anti-distortion capabilities because its grid uses special alloy made of Pb-Ca-Sn-Al low percent of Ca, high percent of Sn , which ensures the long life of the battery. Besides, the level of negative pole is improved, which can suppress the generation of hydrogen to prevent the water in the electrolyte from decomposing. High reliable sealing The terminals are sealed reliably. They are coated with a layer of heat-shrinking tube that can act as a protection coat after being heated. An O shape sealing ring is installed around the tube and the ring is the second sealing protection layer. The upper part of the terminal is sealed with imported resin that can act as a third sealing protection coat. Thus these three protection coat guarantee the battery have no leakage, so the leakage problem is solved completely. Excellent deep-discharging recovery function: Perform short circuit test on the batteries. The battery capacity can maintain at 95% or above after 5 times of cycle discharge test. Anti heat-failure function If the battery is charged with constant voltage at 75 ambient temperature, the charging current will not increase abnormally, which indicates that the battery has a strong temperature adaptability. Patented gas collection device The device collects the gas(mainly hydrogen) generated in charging process(such as high temperature and sealing environment) and the possible acid fog, process them and then expel the waste gases, thus gas accumulation is avoided and the adaptability of the battery to environment is improved. Suitable for: Mobile station outdoor, network access(integrated cabinet) and other precise equipment. UL and CE safety certification: Product using safety is fully guaranteed.
4 5 6
Appendix A
U12V24/A
12V24Ah
165
125
181
8.7
U12V38/A
12V38Ah
196
165
176
13
U12V65/A
12V65Ah
322
167
175
22
U12V100/A
12V100Ah
407
173
220
37
Appendix A
SN
Product Photo
Product Model
Specification
Weight (Kg)
Remark Launch to
UH12V370/A
370W/cell @ 15min
341
172
240
36
Launch to 6 UH6V740/A 740W/cell @ 15min 341 172 240 36 market in Dec, 2002 Main features
1 2 3 4 5 6 Simple maintenance: Sealing technology is used, so there is no necessity of adding water or acid periodically in the whole life of the battery. Safe & Reliable Reliable sealing No abundant electrolyte, anti-explosion design Multi-sealing technology is used to guarantee no leakage of the battery Small self-discharging: Self discharging each day is below 0.1% Small internal resistance: Good discharging performance at big current Long life: 10-year designing float-charging life
Appendix B
Query table of battery model used for telecom power system, installation rack/cabinet and the total weight
battery model
T12V50SE/A(6-GFM-50) T12V65SE/A(6-GFM-65N) T12V65SE/A(6-GFM-65N) T12V100SE/A(6-GFM-100N)
installation mode
Remark
Code of single battery Code of single battery 8PCS can be placed in ONUF01B Used for microwave base station Code of single battery 4PCS can be placed in ONU512A, 8PCS can be placed in ONU512C 2PCS can be placed in BTS30A Code of single battery ONUF01A, 4PCS can be placed in
5 6 7 8 9 10 11 12
T12V100SE/B(6-GFM-10019N) T12V100/A(6-GFM-100) T12V100/A(6-GFM-100) T12V100/A(6-GFM-100) T12V100/A(6-GFM-100) T12V100/A(6-GFM-100) T12V100/A(6-GFM-100) cabinet for 2-layer 1 row cabinet for 3-layer 1 row Rack for single layer single row rack for 2-layer 1-row rack for 2-layer flat-laying rack for 2-layer 3-row Cabinet for single layer single row
F02A Under condition that 12V cell is selected Under condition that 12V cell is selected Under condition that 12V cell is selected Under condition that 12V cell is selected
48V100Ah 48V100Ah
48V100Ah 48V100Ah
Appendix B
Query table of battery model used for telecom power system, installation rack/cabinet and the total weight
battery model
T2V200E/A (GFM-200 T2V300E/A (GFM-300 T2V400E/A (GFM-400 T2V500E/A (GFM-500 T2V650/A (GFM-650) T2V800/A (GFM-800 T2V1000/A (GFM-1000 T2V1600/A (GFM-1600) T2V2000/A (GFM-2000) T2V3000/A (GFM-3000) T2V200E/A (GFM-200 T2V300E/A (GFM-300 T2V400E/A (GFM-400 T2V500E/A (GFM-500 T2V650/A (GFM-650) T2V800/A (GFM-800 T2V1000/A (GFM-1000 ) ) ) ) ) ) ) ) ) ) ) )
installation mode
rack for 6-layer flat-laying rack for 2-layer 2-row rack for 6-layer flat-laying rack for 2-layer 2-row rack for 4-layer flat-laying rack for 2-layer 2-row rack for 4-layer flat-laying rack for 2-layer 2-row rack for 4-layer flat-laying rack for 2-layer 2-row rack for 4-layer flat-laying rack for 4-layer flat-laying rack for single layer 2-row rack for single layer 2-row rack for single layer 2-row cabinet for 6-layer flat-laying cabinet for 8-layer flat-laying cabinet for 8-layer flat-laying cabinet for 8-layer flat-laying cabinet for 8-layer flat-laying cabinet for 4-layer flat-laying cabinet for 4-layer flat-laying
Width mm 874 752 874 1022 1290 1058 1550 1148 1800 1148 1580 1580 4432 4432 4432 600 600 600 800 1000 1600 1600
Depth mm 400 459 400 459 400 446 400 518 400 640 493 493 784 968 1348 550 550 550 550 550 600 600
Height mm 1006 1200 1276 1200 1006 1116 1014 1125 1018 1126 1450 1450 540 540 540 2000 2000 2000 2000 2000 1500 1500
Total Weight Kg 422 410 643 630 748 733 1035 1015 1221 1200 1524 1836 3000 3700 5560 564 768 852 1092 1284 1764 2076
Remark flat-laying vertical laying flat-laying vertical laying flat-laying vertical laying flat-laying vertical laying flat-laying vertical laying
48V1000Ah, 24PCS 48V1600Ah, 24PCS 48V2000Ah, 24PCS 48V3000Ah, 24PCS 48V200Ah, 48V300Ah, 48V400Ah, 48V500Ah, 48V650Ah, 48V800Ah, 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS
48V1000Ah, 24PCS
Appendix C
Close Circuit Voltage Open Circuit Voltage Unit of battery capacity Float Charging Voltage 10h rate rated capacity 3h rate rated capacity 1h rate rated capacity Ah Ah Ah the value is 1.00 C10 the value is 0.75 C10 the value is 0.55 C10 which is the value obtained at 25 basic temperature Ah
by multiplying the discharging current I(A) with the discharging time t(h) 10h rate discharging current, the value is 1.00I10(A) 3h rate discharging current, the value is 2.50I10(A) 1h rate discharging current, the value is 5.50I10(A)