Professional Documents
Culture Documents
Summary Slide: Capacitor Protection
Summary Slide: Capacitor Protection
Capacitor Protection
Capacitor Protection
Capacitor protection
Capacitor banks- General
Capacitor protection
Shunt Reactors-General
400 kV
130 kV
60 Mvar XX Mvar
Capacitor protection
Shunt Reactors-General
Capacitor protection
Shunt Capacitor Configurations
D-connected
Single Y-connected
Double Y-connected Earthed or unearthed
Capacitor protection
Earthing of Shunt Capacitors
Safety Regulation may prescribe unearthed shunt capacitors Sensitive earth fault protection may be easy to arrange
Capacitor protection
Bank Connections and Grounding
Lower cost (insulation of neutral) switch duty not as severe (recovery voltages are reduced) mechanically, structure is simpler High inrush currents may occur in station grounds which may and cause instrumentation problems (protection relay performance) An open phase produces zero-sequence harmonic currents and cause telephone interference Need for current limiting fuses if only one series group
Capacitor protection
DOUBLE Y-CONNECTED UNEARTHED CAPACITOR
Capacitor protection
Shunt Capacitor Faults
Capacitor protection
Abnormal Conditions
Inrush currents
Capacitor protection
General conditions as per IEC 60871-1 (1997)
Capacitors should be able to withstand 10% over voltage The capacitors should tolerate 30% overcurrent (r.m.s. value) arising from overvoltage and harmonics. Depending on the capacitance deviations, which may be not more than 1.15 Cn, the maximum current may be up to 1.15 x 1.3 = 1.5 In Capacitors may not be reconnected until they have discharged to 10% of their rated voltage.
Capacitor protection
CAPACITOR UNITS AND FUSES
P
Capacitor protection
Unit Overcurrent Protection
External or internal fuses Risk for damage: P < Pmax Fusing: P > Pmin Often done by manufacturer
Capacitor protection
Capacitor Bank Protections
(3I >>)
Ground-fault protection
(I )
Unbalance protection
(IN-N)
Capacitor protection
Short- circuit protection
Provides protection against short circuits and earth faults Two or three phase over current along with earth fault relay used
This should be set to as short a time as possible without causing spurious tripping due to switching transients.
Capacitor protection
PHASE-TO-PHASE RACK FAULT
Capacitor protection
Ground- fault protection
Protection settings have to be coordinated with the existing ground-fault protection of the network and carried out individually in each case without any general guidelines.
Capacitor protection
BANK OVERCURRENT PROTECTION Using
I> I>
I> I>
ABB Group - 19 2-May-12
Capacitor protection
Capacitor bank overload relay
This protection prevents capacitor overload due to overvoltage and/or harmonic currents. The overload protection is measuring in three phases for banks with grounded neutral. For banks with insulated neutral it is usually measuring in two phases. The SPAJ 160C is actually a maximum-valuedetecting voltage protection whereby the relay converts measured capacitor currents, including harmonics up to the 13th, to a maximum voltage value. Its characteristic corresponds to the voltage tolerance levels according to ANSI/IEE std. 18 and IEC 60871-1.
Capacitor protection
Under current relay
This protection disconnects the bank from the busbar upon voltage failure, to prevent reconnection of a charged capacitor. The relay can inhibit reclosing of the capacitor bank circuit breaker for a preset discharge time, trec by means of an auxiliary contact connected in the closing circuit.
Capacitor protection
Unbalance relay
Blown internal fuses Short circuits across bushings Short circuits between capacitor units /racks
If capacitor value decrease below 5/6 of nominal value bank must be taken out of service
Faulty elements taken out by fuses cause increase in voltage level Capacitors can withstand 110% of rated voltage
Capacitor protection
Unbalance Protection Schemes
Provide early unbalance alarm signal to indicate the operation of fuses (internally or externally fused capacitors) or failure of capacitor elements (fuseless capacitors) Trip the bank for unbalances that are large enough to indicate that continuing operation may result in damage to remaining good capacitors or elements from overvoltage Many schemes available for detecting unbalances
Most installations will require an individual engineering analysis to determine the most appropriate detection scheme
Capacitor protection
UNBALANCE PROTECTION Double Y-connected unearthed Capacitor Neutral Unbalance Overcurrent Relay
I>
Capacitor protection
SPAJ 160 C : Unbalance , Overload and Under current functions
Capacitor protection
Capacitor protection
Questions to be answered
What is the % of allowable unbalance current in a healthy bank. Is there any standard IS or IEC for this? Capacitor failure rates is very high compared to other devices (e.g: NDPL). Why? With internal fuses replacement not possible. Why not provide them external to capacitor. Often clearance between terminal of capacitor and other live parts is not enough.