1. Over Mvar Incomer or Bus bar Mvar reading increase more than 9 mvar Capacitor Bank will close after waiting 5 minutes. 2. Under Mvar Incomer or Bus bar Mvar reading decrease less than 01 mvar Capacitor Bank will open after waiting 5 minutes. 3. Under voltage
Stage#1
Incomer or Bus bar voltage reading decrease less than 12.7 Kv Capacitor Bank will close after waiting 01minute .
Stage#2
Incomer or Bus bar voltage reading decrease less than 5 Kv Capacitor bank will open after 10 sec. 4. Over voltage
Stage#1
Incomer or Bus bar voltage reading increase more than 14.4 Kv If capacitor bank was closed before it will not open only ACCS will give over Voltage alarm.
Stage#2
Incomer or Bus bar voltage reading increase more than 14.7 Kv Capacitor bank will open after waiting 01 minute. 5. CCWC (CONTINOUS CURRENT WITHSTANDS CAPABILITY) : When capacitor bank feeder current exceed more than 390 A. Capacitor bank will trip after waiting 01 minute and reclose block need to manual reset.
14.2kV 14.6kV
V2-1
(Under voltage stage-1)
12.7kV 5.0kV
V2-2
(Under voltage stage-2)