AMBALICA SUGAR PVT LTD 31.08.2011 Sr. No.

2 3 8&9 10 11 12 13 15 Clarification For 690V drive and motor, there will be higher efficiency, lower current rating, lower size cable, switchgear and fuses. Unordered motor should be EFF-1 Busbars should be interleaved with RYBRYBN configuration Microprocessor based relay should be provided for all motors Convertor transformer is must for VFD loads Configuration of DG should be 2X750KVA with Grid sync. And AMF (No momentary sync. It should be permanently) Charger should be FCBC a. For boiler feed pump there should be changeover switch for starting any pump from any VFD b. There will be battery of 2 VFD panels devided logicallyand connected both secondary of converter trafo. c. For above 2 batteries of VFD panel there will be 1 VFD of highest rating VFD in that battery as a stand by. d. There will be standby bus network for all VFDs in that battery. First choice for LT switchgear will be L&T as per as possible Siemens should not accepted. GPR should be Siemens make 7UM63 or ABB REM543 AVR should be ABB unitrol make only. No SFU acceptable, only 800A ACB should be given There should be 4 GPRs for two turbines with dedicated sensing equipment. VFD panel should be designed as per requirement of PV system i.e. flange at top for heat evacuation MCW pump and CT fan if provided with VFD will give its payback in less than 6 months