Professional Documents
Culture Documents
Lwvolt h49 t41 Nycy 1core
Lwvolt h49 t41 Nycy 1core
NYCY 0.6/1 kV
Copper Conductor, PVC Insulated, Copper tape Screening, PVC Sheated
1. Conductor
2. Insulation
3. Filler
4/5. Screen
6. Sheath
:
:
:
:
:
APL
Used for street and outdoor lighting, house services in urban network indoor
Cu
DCV
DIMENSIONAL DATA
SIZE
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
No.of wire
and Shaped
Of Conductor
pcs
shape
7
7
19
19
19
37
37
37
61
61
61
61
91
rm
rm
rm
rm
rm
rm
rm
rm
rm
rm
rm
rm
rm
Nominal Thickness
Approximately
Overall
Net.
Insulation Outer Sheath
Diameter Weight
mm
mm
1.2
1.4
1.8
1.6
1.8
2
2.2
2.4
2.6
2.8
2
2
2.1
2.3
2.3
CORE
Min.
Bending
Diameter
Std.
Length
per reel
m
mm
kg/km
mm
15.8
15.9
17.5
19.6
21.9
23.7
25.7
28.5
31.7
35.6
39.3
43.9
48.7
594
705
928
1253
1692
2128
2432
2102
3937
4940
6178
7842
9918
284
286
315
353
394
427
463
513
571
641
707
790
877
1000
500
300
ELECTRICAL DATA
SIZE
mm2
DC Resistance
at 20C
Conductor Insulation
(Max)
(Min)
Ohm/km
M.ohm.km
Current Carrying
Capacity at 30C
In Ground
In Air
kA
kA
DC
Voltage
Test
25
35
50
70
95
120
150
185
240
300
400
500
630
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
40
30
20
169
210
250
310
375
425
480
550
640
730
855
990
1126
140
175
215
270
335
390
445
510
620
710
850
1000
1195
11.23
15.72
22.45
31.43
42.66
53.89
67.36
83.07
107.77
134.71
179.62
224.52
282.90
5.02
7.03
10.04
14.06
19.08
24.10
30.12
37.15
48.20
60.25
80.33
100.41
126.52
3.55
4.97
7.10
9.94
13.49
17.04
21.30
26.27
34.08
42.60
56.80
71.00
89.46
8.5 kV
for
5 minutes