RAW WATER SYSTEM

           

SOURCE: MAHI RIVER QUALITY PARAMETERS: PH: 7.8 TSS :10 mg/l(TOTAL SUSPENDED SOLIDS ) TDS 398mg/l (TOTAL DISSOLVED SOLID) TOTAL HARDNESS:AS CaCO3 :148 ppm Ca HARDNESS ::68ppm Mg HADRNESS: NIL SILICA as SiO2:23 ppm : SULPHATE as CaSO4:31.2 ppm : P-ALKALINITY :NIL M-ALKALINITY,CaCO3 :206 ppm

RAW WATER SYSTEM


1.0 RAW WATER RESERVOIR
RAW WATER PONDS TAG :T-1804/T-1805  CAPACITY OF POND(EACH) 20,000 cuM  LEVEL MAX : 3.60 M  LEVEL MIN RAW WATER :1.13M FIRE WATER :0 .16M MAINTAINED LEVEL :2.80M


2.0 RAW WATER PUMPS :P-1807A,B


CAPACITY : 180 cuM/Hr FOR P 1807A : 100 cuM/Hr FOR P 1807B DAILY AVG CONSUMPTION: 4165 cuM SUPPLIER OF PUMPS: :M/S WORTHINGTON PUMPS (I) LTD

FIRE WATER SYSTEM (PUMP HOUSE )




JOCKEY PUMPS (P1803A,B)

CAPACITY : 40 cu M/HR


HIGH TENSION(H.T) MOTOR PUMPS (P1802A,B)

CAPACITY::410 cu M/HR


DIESEL ENG. DRIV EN PUMPS:(P-1801A,B,C)

CAPACITY: 410 cu M/HR(EACH)




DEWATERING PUMP (P-1827) CAPACITY:10 cu M/HR

MAKE : M/S KIRLOSKAR BROTHERS PVT.LTD.

FIRE WATER SYSTEM (OPERATING SEQUENCE)


FIRE WATER HEADER PRESSURE;:10.5 KSCG AUTO AUTO PUMP NO CUT IN CUT-OFF P1803A 8.55 10.5 P1803B 8.50 10.5 P1802A 8.0 -- P1802B 7.2 -- P1801A 6.6 __ P1801B 6.0 -- P1801C 5.6 ---

FIRE WATER SYSTEM AUTO CUT IN SEQUENCE




   

IN-CASE OF FALL IN HEADER PRESSURE FOLLOWING AUTO CUT-IN SEQUENCE IS PROVIDED:FIRST: JOCKEYS WILL START, SECOND : H.T. PUMP A THIRD :H.T. PUMP B FOURTH : DIESEL PUMP A
IN- CASE H.T.PUMP DO NOT START WITH-IN 10 SECONDS,THEN DIESEL PUMP-A SHALL START ON AUTO.

TANK FARM

BENZENE TANK FARM  FURNACE OIL ( F.O.) TANK FARM (Normal Paraffin, Off-Spec,Slop)  LAB / HAB TANK FARM.


BENZENE TANK FARM T-1903A,B


CONICAL-FLOATING (INTERNAL) ROOF STORAGES: 2 NOS  VOLUMETRIC CAPACITY :1480 cuM(EACH)  NITROGEN BLANKETTED TANKS (MAINTAINED PRESSURE) :25 MM WG  MOC OF TANK : C.S.  NITROGEN BLANKETTING OF THE TANKS reduces LOSSES.& ENVIRONMENTAL POLLUTION AS V.P. OF BENZENE IS QUITE SUBSTANTIAL AT AMBIENT TEMPERATURE...  DAILY CONSUMPTION : 100 cuM  HAZARD CLASS : A.


F.O. TANK FARM (T-1908A,B),


(T-1906A,B) (T-1918) (T-1913)



ATMOSPHERIC CONICAL ROOF TANKS: : (GOOSE NECK): 2nos


VOLUMETRIC CAPACITY(EACH):1680 cuM

     

INTERNALLY fitted WITH STEAM HEATING COILS.(L.P.STEAM) TANK TEMP MAINTAINED: : 100 DEG C DAILY AVG REQUIREMENT: 165 cu M F.O. USED FOR NHOH ,OHOH,PACOL &UF charge HEATERS,,BOILERS ETC. HAZARD CLASS :C MOC OF TANK : C.S.

NORMAL PARAFFIN TANK (T-1906A,B)





CONICAL FIXED ROOF TANK:2 Nos


VOLUMETRIC CAPACITY(EACH)4030 Cum

NITROGEN BLANKETTED TANK  MAINTAINED PRESS : 25mm WC  MATERIAL OF CONSTRUCTION :C.S.  HAZARD CLASS: C  DAILY CONS :260 cuM


OFF-SPEC TANK T-1918


CONICAL FLOATING ROOF TANK  NITROGEN BLANKETTING PROVISION EXIT,HOWEVER NOT IN USE.  CAPACITY : 1050 cu M  MOC OF TANK: C.S.  HAZARD CLASS: C


SLOP TANK
T-1913
CONICAL FIXED ROOF TANK.  CAPACITY : 280 cu M  MOC OF TANK :C.S.  ELABORATE WATER DRAINING FACILITY AVAILABLE.


LAB/HAB TANK FARM


T-1932A,B T-1910,T-1911
T-1933,1934,1935.
 

 

CONICAL FIXED ROOF TANKS VOLUMETRIC CAPACITY,cu M T-1932A,B:1089? T-1910:365 T-1911:7685 T-1933,1934,19352345 HAZARD CLASS : C HAB TANKS: 987 ,CFR 879cu M ALL DITTO FOR LAB

DATA

SHEET FOR PUMPS ENTIRE TANK FARM

Tank Farm Data Sheet for Pumps


SN 1 2 3 4 5 6 Tag P 1904 AB P 1932 AB P 1912 AB P 1913 ABC P 1913 D,E P 1933 AB Service Benz LAB LAB LAB LAB LAB Type/Make Centi./KSB Centi./Khimline Centi/KSB Ceti/KSB Ceti/KSB Ceti/KSB Cap. (M3/hr) 12.0 95.0 25.0 38.0 65.0 75.0 Press. (kg/cm2) 6.0 2.0 2.5 4.0 4.0 4.0

Tank Farm Data Sheet for Pumps


SN 7 8 9 10 Tag P 1911 ABC P 1909 AB P 1917 P 1925 AB Service F.O. N.P. Off spec. Slop Type/Make Screw/Tush aco Centi/ Centi/ Centi/ Cap. Press. (M3/hr) (kg/cm2) 65.0 12.0 38.0 30.0 15.0 4.0 6.0 4.0

PRESSURE VACCUM RELIEVE VALVE (PVRV)

PRESSURE SAFETY VALVE(PSV)




HGGF

SELF-ACTUATED PRESSURE CONTROLLED VALVE (PCV)

PILOT OPERATED PRESSURE CONTROL VALVE (POPCV)

KEROSENE (S.K.&R.K) STORAGE TANKS

LPG STORAGE BULLETS.


Pressure vessel (UNDER SMPV REGULATION)  Design pressure:  Operating pressure:  Design temperature;  Operating temperture;  ROAD TANKERS UNLOADING OPERATION: SPECIFIC.


NORMAL PENTANE STORAGE TANK.


DOM ROOF STORAGE TANK  UNLOADING PROCEDURE: SPECIFIC