** For Temp Setting:- (Setting to be done in Group:30(Faults) ) To view the value of the Temp.

the AO1 and the AI1 is to be Short(Refer RDCU details) 1) Check the connection whether it is PTC (Thermistor) or PT 100(RTD). 2) If PTC then Alarm:- 939 ohm Fault: - 1036 ohm 3) 3) If PT100 then 4) Check Parameter:01.19: AI1 [V] 01.23: AO1 [mA] 01.16: MOTOR 1 TEMP [C] 30.01: MOT THERM P MODE 30.02: MOTOR THERM PROT 30.03: MOT1 TEMP AI1 SEL 30.04: MOT 1 TEMP ALM L 30.05: MOT 1 TEMP FLT L **For Master Slave:Master should be in SPEED mode and follower Torque Selector should be in ADD mode. 70.08(CH2 M/F Mode) - Master in Master drive /Follower in Follower drive. 70.11 (Master Signal 3) - 210(Torque ref 3) only in Master drive. 70.18(Follower Torque Ref.)- Master (only in Follower drive) 70.17(Follower Torque Ref.)- Follower(only in Folower drive) In case of Master (70.17 & 17.18) doesnt matter 26.01: TORQUE SELECTOR {0} {29} Par.26.1 SPEED in Master. ADD in Follower. 25.03: LOAD SHARE [%] {0} {29} Par.25.3 100. (It should be 100%) only in Follower. Other wise increase the value of Window width through Automation to match the speed of Master and Follower. 23.07: WINDOW INTG ON {0} {29} Par.23.7 ON (By Automation) 23.08: WINDOW WIDTH POS [rpm] {0} {29} Par.23.8 0-25 (By Automation) 23.09: WINDOW WIDTH NEG [rpm] {0} {29} Par.23.9 0-25 (By Automation) For Monitoring:02.10: TORQUE REF 3 [%] {0} {29} Par.2.10 XXX (In Master) 02.20: DS TORQ REF A [%] {0} {29} Par.2.20 XXX (In Slave) 2.10 Of Master and 2.20 of Slave should be same. 01.07: MOTOR TORQ FILT2 [%]{0} {29} Par.1.7 Value of Master and Slave should be same. {0} {29} Par.1.19 {0} {29} Par.1.23 {0} {29} Par.1.16 {0} {29} Par.30.1 {0} {29} Par.30.2 {0} {29} Par.30.3 {0} {29} Par.30.4 {0} {29} Par.30.5 3.1 9.1 38.2 USER MODE/DTC FAULT 3xPT100 ST/PTC. 90/939 110/1036. Alarm:- 90 degree Fault: - 110 degree

You might also like