2006 0906 Uninterruptible Power Supplies
2006 0906 Uninterruptible Power Supplies
2006 0906 Uninterruptible Power Supplies
JOHN LIGUORI
CONSULTING ENGINEER MSEE, PE
INTRODUCTION
PURPOSE WHAT IS AN UNINTERRUPTIBLE POWER SUPPLY? WHY USE A UPS?
PURPOSE
THE PURPOSE OF THIS PRESENTATION IS TO DISCUSS THE DIFFERENT TYPES OF UNINTERRUPTIBLE POWER SUPPLIES AVAILABLE, WHAT THE UPS PROTECTS AGAINST, THE COMPONENTS OF A UPS, AND ISSUES REGARDING SELECTION AND SIZING. THE DIFFERENT TYPES AND CAUSES OF POWER DISTURBANCES ARE DISCUSSED, AS WELL AS WHAT THE POWER UTILITY, THE ORIGINAL EQUIPMENT MANUFACTURER, AND YOU, CAN DO TO MINIMIZE THEIR EFFECT.
POWER DISTURBANCES
CAUSES TYPES DURATION RESULTING PROBLEMS COMMENTS WHAT THE POWER UTILITY CAN DO WHAT THE ORIGINAL EQUIPMENT MANUFACTURER (OEM) CAN DO WHAT YOU CAN DO PROTECTIVE DEVICES
WAVEFORM DISTORTION
DC OFFSET HARMONICS INTERHARMONICS NOTCHING NOISE
VOLTAGE IMBALANCE
10
11
DISSIPATIVE
EQUIPMENT EXPERIENCES REPEATED STRESSES THAT LEAD TO FAILURE LATER FOR NO APPARENT REASON
DESTRUCTIVE
EQUIPMENT FAILS AT THE INSTANT THE DISTURBANCE OCCURS
12
TRANSFORMERS
HEATING AUDIBLE NOISE VIBRATION
13
14
WHAT THE POWER UTILITY CAN DO TO MINIMIZE THE EFFECT OF POWER DISTURBANCES
INSTALL STORM RESISTANT WIRING USE INFRA RED SCANNING TO DETECT WEAK SPOTS IN POWER LINES INSTALL REMOTE CONTROLLED RADIO SWITCHES TO RESTORE POWER QUICKLY CLEAR TREE LIMBS AWAY FROM POWER LINES
15
16
17
LINE FILTERS
FILTERS OUT HARMONICS, TRANSIENTS AND NOISE
ISOLATION TRANSFORMER
ELIMINATES DC OFFSET AND NOISE
PROTECTIVE DEVICE OFFER PROTECTION? LINE FILTER ISOLATION VOLTAGE TRANSFORMER REGULATING LINE CONDITIONER YES YES YES
ON-LINE UPS
INTERRUPTION SAG, UNDER VOLTAGE SURGE, OVER VOLTAGE VOLTAGE FLUCTUATION FREQUENCY VARIATION SPIKES / TRANSIENTS IMPULSIVE OSCILLATORY DC OFFSET HARMONICS INTERHARMONICS NOTCHING NOISE YES YES YES YES YES YES YES YES
WAVEFORM DISTORTION
YES
VOLTAGE IMBALANCE
YES YES YES YES YES YES YES YES YES YES YES YES YES
19
UPS
ARCHITECTURES WAVEFORMS INVERTER TECHNOLOGY COMPONENTS SWITCHOVER TIME ADVANTAGES / DIS-ADVANTAGES SIZING BATTERY SAFETY
20
UPS ARCHITECTURES
LINE INTERACTIVE ON-LINE
21
AUTOMATIC SWITCH
BATTERY
AC FAIL
22
AUTOMATIC SWITCH
BATTERY
INVERTER FAIL
23
BATTERY
24
UPS WAVEFORMS
TRUE SINEWAVE MODIFIED SINEWAVE SQUARE WAVE
25
UPS WAVEFORMS
170
VOLTAGE
0 0 4 8 12 16 20
TIME (ms)
-170
26
27
TRANSISTOR BRIDGE
TRANSFORMER
FILTER
28
SINEWAVE OSCILLATOR
COMPARISON AMPLIFIER
POWER AMPLIFIER
29
SWITCH DRIVE
TRANSISTOR SWITCHES
TRANSFORMER
30
UPS COMPONENTS
CONVERTER - AC TO DC
SPD - PROTECTS AGAINST SPIKES AND TRANSIENTS
BATTERY
STORED ENERGY DEVICE - PROTECTS AGAINST INTERRUPTIONS
INVERTER DC TO AC
WAVEFORM SYNTHESIS PROTECTS AGAINST DC OFFSET AND INTERHARMONICS FILTER PROTECTS AGAINST HARMONICS, NOTCHING AND NOISE VOLTAGE REGULATOR PROTECTS AGAINST SAGS, SURGES AND FLUCTUATIONS
31
SWITCHOVER TIME
A TYPICAL SWITCHOVER TIME
ONE QUARTER CYCLE OR LESS FOR SOME EQUIPMENT THIS IS NOT TOLERABLE
2 4 ms
32
ON-LINE ADVANTAGES
ZERO SWITCHOVER TIME FROM MAIN LINE TO BATTERY POWER ALWAYS ISOLATED FROM POWER DISTURBANCES ON THE MAIN LINE
33
TOTAL UPS LOAD MUST NOT EXCEED THE UPS VOLT AMP (VA) RATING TOTAL UPS LOAD MUST NOT EXCEED THE UPS WATT (W) RATING
35
BATTERY SAFETY
MAINTENANCE
INSPECT PERIODICALLY REPLACE AS NEEDED
RISKS
ACID ELECTRIC SHOCK BURN FLYING, MOLTEN METAL (EYES) INJURIES RESULTING FROM CARRYING HEAVY BATTERY PACKS
DISPOSAL
DISPOSE OF PROPERLY RECYCLE WHENEVER POSSIBLE
36
GENERAL DISCUSSION
DOES A UPS OFFER COMPLETE PROTECTION? DO YOU THINK POWER DISTURBANCES WONT HAPPEN TO YOU ? MISCELLANEOUS
37
38
39
MISCELLANEOUS
MANY RETAIL UPS FOR COMPUTER APPLICATIONS ARE LINE INTERACTIVE MANUFACTURERS AND BUILDING CODES DO NOT ALLOW EXTENSION CORDS OR SURGE SUPPRESSORS TO BE USED WITH A UPS
40
RUN TIME WITH AN OUTAGE RELIABILITY AUDIBLE NOISE MONITOR AND CONTROL HARDWARE / SOFTWARE
LOCAL / REMOTE CONTROL
41
REFERENCES
IEEE STANDARD 1100-2005
RECOMMENDED PRACTICE FOR POWERING AND GROUNDING SENSITIVE ELECTRONIC EQUIPMENT
42
QUESTIONS