RELAY SETTING CALCULATION FOR OVERCURRENT AND VOLTAGE OPERATED RELAYS OF LBDS-9
Subject. Project
Relay Setting Calculation Doc. No. ISP/AREVA-EMC-A/IX/22/16/29/DE/1007J LBDS Package 22 - New Stream 2.5 MT Expansions at IISCO Steel Plant Page- 1
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J
2.2 Proposed Is (DT) setting for O/C (I>>) (50-1/DT) a. b. c. Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = 1.75 1400 1.55
2.3 Proposed Is (DT) setting for S/C (I>>>) (50-2/DT) a. b. c. Minimum Isc setting proposed in multiples (M) of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = 4.5 3600 0.65
0.65 0.65
1.55
1.55
Consultant : SATCON
Page 2 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 1400 1400 11650 8000 4800 3200 1600 1520 1440 1400 1360 1280 1200 1120 1040 960 880 1.75 1.75 14.5625 10 6 4 2 1.9 1.8 1.75 1.7 1.6 1.5 1.4 1.3 1.2 1.1 80.02 80.02 665.89 457.26 274.36 182.90 91.45 86.88 82.31 80.02 77.73 73.16 68.59 64.02 59.44 54.87 50.30 1.55 6.84 1.40 1.63 2.11 2.74 5.52 5.96 6.51 6.84 7.22 8.15 9.46 11.40 14.64 21.08 40.36 IDMT zone I> I>>
2.5 Undervoltage protection (27) a. b. c. d. V< in volts = 0.4*Vn (I/C brkr trip) DT setting in sec = V<< in volts = 0.8*Vn (Annunciation, I/C brkr closing circuit interlock) DT setting in sec = 44 2.5 88 2
2.6 Overvoltage protection (59) a. b. V> in volts = 1.1*Vn (For annunciation) DT setting in sec = 121 1
1.1 Rated PT secondary voltage (Vn) 1.2 Undervoltage protection (27) a. b. c. d. V< in volts = 0.4*Vn (I/C and B/C brkr closing circuit interlock) DT setting in sec = V<< in volts = 0.8*Vn (I/C and B/C brkr closing circuit interlock) DT setting in sec =
44 2.5 88 2
1.3 Overvoltage protection (59) a. b. V>> in volts = 1.1*Vn (For annunciation) DT setting in sec = 121 1
Consultant : SATCON
Page 3 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J
1.4 Residual overvoltage/neutral displacement protection (60) a. b. c. d. V0> in volts = 0.06*Vn (For Alarm) DT setting in sec = V0>> in volts = 0.2*Vn (for tripping of respective I/C) DT setting in sec = 6.6 0.05 20 0.1
2.2 Proposed I> (DT) setting for O/C (50-1) a. b. c. Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = 3 1200 1.25
2.3 Proposed I>> (DT) setting for O/C (50-2) a. b. c. Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = 8.25 3300 0.35 Not used
2.4 Proposed I>>> (DT) setting for O/C (50-3) a. Minimum Isc setting proposed in multiples (M) of In
Consultant : SATCON
Page 4 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J b. c. Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =
8000 3300 3300 1200 1200 11650 6000 3000 1800 1200 1140 1080 1020 960 900 840 780 720 660
20 8.25 8.25 3 3 19.417 10 5 3 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1
457.26 188.62 188.62 68.59 68.59 665.88 342.95 171.47 102.88 68.59 65.16 61.73 58.30 54.87 51.44 48.01 44.58 41.15 37.72
0.35 0.35 1.25 1.25 4.76 1.09 1.41 2.03 2.99 4.76 5.15 5.62 6.23 7.04 8.17 9.85 12.64 18.20 34.85
IDMT zone
2.6 25 Check Synchronisation a. b. c. d. e. Phase angle setting Vdiff setting in volts Slip frequency setting in Hz Dead Bus Charging Voltage setting in volts Live Bus Voltage setting in volts 15 5.5 0.1 20 32 > 20% > 30%
o
5%
Consultant : SATCON
Page 5 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J
g. h.
Relay used Setting ranges : I> I>> I>>> TMS = Definite time setting =
MICOM P122 steps 0.1-25In 0.5-40In 0.5-40In 0.025-1.5 0-150 sec @ 0.01 In @ 0.01 In @ 0.01 In @ 0.025 @ 0.01 sec
2.0 SETTING VALUES 2.1 Proposed Is (IDMT) setting for O/C (51), I> a. b. c. d. Curve used for Is (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Is = Current in amps corresponding to PS = PS*In Proposed TMS setting = IEC SI 1 600 0.325 Standard inverse
2.2 Proposed Is (DT) setting for O/C (I>>) (50-1/DT) a. b. c. Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = 1.5 900 0.95
2.3 Proposed Is (DT) setting for S/C (I>>>) (50-2/DT) a. b. c. Minimum Isc setting proposed in multiples (M) of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = 5 3000 0.05
12000 3000 3000 3000 900 900 11650 6000 4200 3000 2256
685.89 171.47 171.47 171.47 51.44 51.44 665.89 342.95 240.06 171.47 128.95
0.05 0.05 0.95 0.95 0.95 5.59 0.74 0.97 1.15 1.39 1.70
DT Zone (I>>)
Consultant : SATCON
Page 6 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 1200 1140 1080 1020 960 900 840 780 720 660 2.00 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1 68.59 65.16 61.73 58.30 54.87 51.44 48.01 44.58 41.15 37.72 3.26 3.52 3.85 4.26 4.82 5.59 6.74 8.65 12.46 23.85 IDMT zone I>
2.2 Proposed I> (DT) setting for O/C (50-1) a. b. c. Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = 1.5 4500 0.65 Not used
2.3 Proposed I>> (DT) setting for O/C (50-2) a. Minimum Isc setting proposed in multiples M of In b. Isc Current in amps corresponding to Isc setting = M*In
Consultant : SATCON
Page 7 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J c. Proposed DT time in sec =
60000 4500 4500 27000 24300 18900 10800 11280 8100 5400 5130 4860 4590 4500 4320 4050 3780 3510 3240 2970
20 1.5 1.5 10 9 7 4 4.1777 3 2 1.9 1.8 1.7 1.6666 1.6 1.5 1.4 1.3 1.2 1.1
685.89 51.44 51.44 308.65 277.79 216.06 123.46 128.95 92.60 61.73 58.64 55.56 52.47 51.44 49.38 46.30 43.21 40.12 37.04 33.95
0.65 0.65 3.75 0.82 0.86 0.97 1.37 1.33 1.73 2.76 2.98 3.26 3.61 3.75 4.08 4.73 5.70 7.32 10.54 20.18
2.5 Undervoltage protection (27) a. b. c. d. V< in volts = 0.4*Vn (I/C brkr trip) DT setting in sec = V<< in volts = 0.8*Vn (Annunciation, I/C brkr closing circuit interlock) DT setting in sec = 44 2.5 88 2
2.6 Overvoltage protection (59) a. b. V> in volts = 1.1*Vn (For annunciation) DT setting in sec = 121 1 Available range 0.3 0.8 2756 551 27556 55112 0.1-2.5 x I ref 5-30 x I ref 5-30 x I ref 0.2-0.5 0.4-1.5
2.7 Transformer Differential Protection (87T) a. b. c. d. e. f. m1 m2 I ref = Trafo full load current in amps on 31.5 MVA base (FLC) Idiff> in amps = 0.2 x I ref Idiff>> in amps = 10 x I ref Idiff>>> in amps = 20 x I ref
Consultant : SATCON
Page 8 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J g. h. IRm2 in amps = 4 x I ref Rush I in amps = 0.2 x I ref 11022 551 1.5-10 x I ref 0.1-0.5 x I ref
Standard inverse
2.2 Proposed I> (DT) setting for O/C (50-1) a. Minimum Isc setting proposed in multiples M of In b. c. Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =
2.3 Proposed I>> (DT) setting for O/C (50-2) a. Minimum Isc setting proposed in multiples M of In b. c. Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =
2.4 Proposed I>>> (DT) setting for O/C (50-3) a. Minimum Isc setting proposed in multiples (M) of In b. c. Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =
20
342.95
0.35
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 4500 4500 2250 2250 11280 4500 3750 3000 2850 2700 2550 2400 2250 2100 1950 1800 1650 3 3 1.5 1.5 7.520 3 2.5 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1 51.44 51.44 25.72 25.72 128.95 51.44 42.87 34.29 32.58 30.87 29.15 27.44 25.72 24.01 22.29 20.58 18.86 0.35 1.30 1.30 4.73 0.93 1.73 2.08 2.76 2.98 3.26 3.61 4.08 4.73 5.70 7.32 10.54 20.18 IDMT zone I>> DT zone I>
2.6 25 Check Synchronisation a. b. c. d. e. Phase angle setting Vdiff setting in volts Slip frequency setting in Hz Dead Bus Charging Voltage setting in volts Live Bus Voltage setting in volts 15o 5.5 0.1 20 32 > 20% > 30% 5%
Consultant : SATCON
Page 10 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 2.1 Proposed Is (IDMT) setting for O/C (51) a. Curve used for Is (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] b. c. d. Plug setting (PS) proposed = Is = Current in amps corresponding to PS = PS*In Proposed TMS setting =
Standard Inverse
2.2 Proposed Is (DT) setting for O/C (I>>) (50-1/DT) a. Minimum Isc setting proposed in multiples M of In b. c. Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =
2.3 Proposed Is (DT) setting for S/C (I>>>) (50-2/DT) a. Minimum Isc setting proposed in multiples (M) of In b. c. Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =
20 4 4 17.7777 10 6 4 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1
28.58 5.72 5.72 5.72 3.22 1.93 1.29 0.64 0.61 0.58 0.55 0.51 0.48 0.45 0.42 0.39 0.35
0.05 0.05 0.47 0.47 0.59 0.77 1.00 2.01 2.17 2.37 2.62 2.96 3.44 4.15 5.32 7.66 14.67
2.5 Undervoltage protection (27) a. U< in volts = 0.8*Vn (For tripping) b. DT setting in sec =
88 1.00
2.6 Residual overvoltage/neutral displacement protection (60) a. Ue> in volts = 0.06*Vn (For Alarm) b. DT setting in sec =
6.6 0.05
Consultant : SATCON
Page 11 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J c. d. Ue>> in volts = 0.2*Vn (For tripping) DT setting in sec = 22 0.1
Standard inverse
2.2 Proposed Is (DT) setting for O/C (I>>) (50-1/DT) a. Minimum Isc setting proposed in multiples M of In b. c. Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =
0.9 225 1
2.3 Proposed Is (DT) setting for S/C (I>>>) (50-2/DT) a. Minimum Isc setting proposed in multiples (M) of In b. c. Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =
20 11.5 11.5
Consultant : SATCON
Page 12 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 2875 225 225 11280 2165 1688 938 375 356 338 319 300 281 263 244 225 206 11.5 0.9 0.9 60.16 11.55 9.00 5.00 2.00 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1 32.87 2.57 2.57 128.95 24.75 19.29 10.72 4.29 4.07 3.86 3.64 3.43 3.22 3.00 2.79 2.57 2.36 1.00 1.00 14.37 0.61 1.05 1.17 1.60 3.76 4.06 4.44 4.92 5.56 6.45 7.78 9.98 14.37 27.52 IDMT zone I> DT Zone (I>>)
1.1 Rated PT secondary voltage (Vn) 1.2 Undervoltage protection (27) a. b. c. d. V< in volts = 0.4*Vn (I/C and B/C brkr closing circuit interlock) DT setting in sec = V<< in volts = 0.8*Vn (I/C and B/C brkr closing circuit interlock, u/v trip of motor feeders) DT setting in sec =
44 2.5 88 2
1.3 Overvoltage protection (59) a. b. V> in volts = 1.1*Vn (For annunciation and tripping of capacitor feeders) DT setting in sec = 121 1
1.4 Residual overvoltage/neutral displacement protection (60) a. b. c. d. V0> in volts = 0.06*Vn (For Alarm) DT setting in sec = V0>> in volts = 0.2*Vn (for tripping of respective I/C) DT setting in sec = 6.6 0.05 20 0.1
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J a. b. c. d. e. f. System voltage in kV Selected CT Ratio = Symmetrical S/C current in amps at 415V bus during 3phase fault = In = Rated primary current in amps corresponding to selected CT ratio Relay used Setting ranges : I> inverse I> definite time I>> definite time TMS = Definite time setting for I> = Definite time setting for I>> = g. h. i. j. k. l. n. Transformer rating = Voltage ratio = Transformer full load current, HV = Transformer full load current, LV = Transformer vector group = Transformer % impedance = Through fault current at HV side = 0.5 - 2.5 In 0.5 - 5.0 In 0.5 - 40.0 In and infinity 0.05 - 1.0 0.05 - 300s 0.04 - 300s 1600 6600/433 140 2133 Dyn11 6.25% 33007 2165.46 A (From ETAP output) A kVA V A A 0.415 3000/5 33007 3000 SPAJ 140C kV A A A (ABB)
2.0 SETTING VALUES 2.1 Proposed I> (IDMT) setting for O/C (51), a. b. c. d. Curve used for I> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = I> = Current in amps corresponding to PS = PS*In Proposed TMS setting = IEC SI 0.85 2550 0.275 1.1 3300 0.7 (Assumed) Standard inverse
2.2 Proposed I> (DT) setting for O/C (50) a. b. c. Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =
2.3 Proposed I>> (DT) setting for O/C (50) a. b. c. Minimum Isc setting proposed in multiples (M) of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =
Not used
Consultant : SATCON
Page 14 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J
CURRENT IN AMPS (I) I = MxIs MULTIPLES OF SET CURRENT (M) M EQUIVALENT TIME OF OPERATIOM MVA (sec) MVA sec
ZONE OF OPERATION
60000 3300 3300 33007 25500 22950 20400 17850 15300 12750 10200 7650 5100 4845 4590 4335 4080 3825 3570 3315 3300 3060 2805
20 1.1 1.1 12.9439 10 9 8 7 6 5 4 3 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.29411 1.2 1.1
43.13 2.37 2.37 23.73 18.33 16.50 14.66 12.83 11.00 9.16 7.33 5.50 3.67 3.48 3.30 3.12 2.93 2.75 2.57 2.38 2.37 2.20 2.02
0.7 0.7 7.45 0.73 0.82 0.86 0.91 0.97 1.06 1.18 1.37 1.73 2.76 2.98 3.26 3.61 4.08 4.73 5.70 7.32 7.45 10.54 20.18
DT Zone (I>>)
2.6 Overvoltage protection (59) at incomer a. b. c. d. e. Relay used Available setting = Time = Selected setting = Purpose VAGM22 110-140 Inst. 110 Tripping % %
Consultant : SATCON
Page 15 of 15
10
TIME IN SECONDS
0.1
0.01 1.00 33kV INCOMER 6.6KV BUS COUPLER 10.00 33KV BUS COUPLER 6.6KV TRAFO FDR LTPCC
MVA
33KV TRAFO FDR
1000.00
CONSORTIUM
Subject. Project
Relay Setting Calculation Doc. No. ISP/AREVA-EMC-A/IX/22/16/29/DE/1007J LBDS Package 22 - New Stream 2.5 MT Expansions at IISCO Steel Plant Page- 1
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J A. 1.0 a. b. c. d. e. f. 33kV INCOMER BASIC DATA System voltage in kV Selected CT Ratio = Symmetrical S/C current in amps at 6.6kV bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> Ie>> TMS = Definite time setting = 2.0 2.1 a. b. c. d. 2.2 a. b. c. 2.3 SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51N), Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Proposed Ie>> (DT) setting for E/F (50N) Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = Time of Operation for Different Fault Current
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M EQUIVALENT MVA MVA TIME OF OPERATIOM (sec) sec
33 800/1 400 800 MICOM P127 0.1 - 1.0 In 0.1 - 8 In 0.025 - 1.5 0 - 150 sec
kV A A A
Standard inverse
ZONE OF OPERATION
16000 200 200 2400 1800 1200 1080 960 840 720 600 480 400 360 240
914.52 11.43 11.43 137.18 102.88 68.59 61.73 54.87 48.01 41.15 34.29 27.44 22.86 20.58 13.72
0.7 0.7 2.05 0.34 0.38 0.45 0.47 0.49 0.53 0.58 0.64 0.75 0.86 0.95 1.50
DT Zone (Ie>>)
Consultant : SATCON
Page 2 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 228 216 204 200 192 180 168 156 144 132 1.9 1.8 1.7 1.6666 1.6 1.5 1.4 1.3 1.2 1.1 13.03 12.35 11.66 11.43 10.97 10.29 9.60 8.92 8.23 7.54 1.63 1.78 1.97 2.05 2.22 2.58 3.11 3.99 5.75 11.01
B. 1.0 a. b. c. d.
33kV BUS COUPLER BASIC DATA System voltage in kV Selected CT Ratio = Symmetrical S/C current in amps at 6.6kV bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> Ie>> TMS = Definite time setting = 0.01 - 4.0 In 0.002 - 8.0 In 0.05 - 10 0 - 100 sec (Inverse time) (Definite time) 33 400/1 400 400 kV A A A
e. f.
MICOM P132
SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51N), Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Proposed Ie>> (DT) setting for E/F (50N) Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = Time of Operation for Different Fault Current
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M EQUIVALENT MVA MVA TIME OF OPERATIOM (sec) sec
Standard inverse
ZONE OF OPERATION
20 0.4 0.4
DT Zone (Ie>>)
Consultant : SATCON
Page 3 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J
800 720 640 560 480 400 240 160 152 144 136 128 120 112 104 96 88
45.73 41.15 36.58 32.01 27.44 22.86 13.72 9.15 8.69 8.23 7.77 7.32 6.86 6.40 5.94 5.49 5.03
0.37 0.39 0.41 0.44 0.48 0.53 0.79 1.25 1.35 1.48 1.64 1.85 2.15 2.59 3.33 4.79 9.17 IDMT Zone (Ie>)
C. 1.0 a. b. c. d.
33kV TRANSFORMER FEEDER FOR 25/31.5 MVA TRAFO BASIC DATA System voltage in kV Selected CT Ratio = Symmetrical S/C current in amps at 6.6kV bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> Ie>> TMS = Definite time setting = 0.1 - 1.0 In 0.1 - 8 In 0.025 - 1.5 0 - 150 sec @ 0.005 In (Inverse time) @ 0.005 In (Definite time) @ 0.025 @ 0.01 sec 33 600/1 400 600 kV A A A
e. f.
MICOM P122
SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51N), Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Proposed Ie>> (DT) setting for E/F (50N) Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = Time of Operation for Different Fault Current 0.2 120 0.1 IEC SI 0.1 60 0.05 Standard inverse
Consultant : SATCON
Page 4 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J
ZONE OF OPERATION
12000 120 120 1200 900 600 540 480 420 400 360 300 240 180 120 114 108 102 96 90 84 78 72 66 D. 1.0 a. b. c. d.
20 0.2 0.2 20 15 10 9 8 7 6.6666 6 5 4 3 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1
685.89 6.86 6.86 68.59 51.44 34.29 30.87 27.44 24.01 22.86 20.58 17.15 13.72 10.29 6.86 6.52 6.17 5.83 5.49 5.14 4.80 4.46 4.12 3.77
0.1 0.1 0.50 0.11 0.13 0.15 0.16 0.16 0.18 0.18 0.19 0.21 0.25 0.32 0.50 0.54 0.59 0.66 0.74 0.86 1.04 1.33 1.92 3.67
DT Zone (Ie>>)
6.6KV INCOMER FROM 25/31.5 MVA TRAFO BASIC DATA System voltage in kV Selected CT Ratio = Symmetrical S/C current in amps at 415V bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> Ie>> TMS = Definite time setting = 0.1 - 0.8 In 0.1 - 8 In 0.05 - 10 0 - 100 sec (Inverse time) (Definite time) 6.6 3000/1 600 3000 kV A A A
e. f.
MICOM P632
2.0 2.1
Consultant : SATCON
Page 5 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J a. b. c. d. 2.2 a. b. c. 2.3 Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Proposed Ie>> (DT) setting for E/F (50N) Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = Time of Operation for Different Fault Current
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M EQUIVALENT MVA MVA TIME OF OPERATIOM (sec) sec
Standard inverse
ZONE OF OPERATION
60000 360 360 3000 2700 2400 2100 1800 1500 1200 900 600 570 540 510 480 450 420 390 375 360 330 2.4 a. b.
20 0.12 0.12 10 9 8 7 6 5 4 3 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.25 1.2 1.1
685.89 4.12 4.12 34.29 30.87 27.44 24.01 20.58 17.15 13.72 10.29 6.86 6.52 6.17 5.83 5.49 5.14 4.80 4.46 4.29 4.12 3.77
0.7 0.7 2.87 0.22 0.23 0.25 0.26 0.29 0.32 0.37 0.47 0.75 0.81 0.89 0.98 1.11 1.29 1.56 2.00 2.35 2.87 5.50
DT Zone (Ie>>)
REF (64R) [Biasing by residual current] Instantaneous Idiff> in amps = 0.1*FLC m= 300 1.005 (fixed slope)
E. 1.0 a. b.
Consultant : SATCON
Page 6 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J c. d. Symmetrical S/C current in amps at 415V bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> TMS = 2.0 2.1 a b c d 2.2 SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51G), Curve used for Ie>1 (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Time of Operation for Different Fault Current
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M EQUIVALENT MVA MVA TIME OF OPERATIOM (sec) sec
36950 600
e. f.
(Inverse time)
Standard inverse
ZONE OF OPERATION
6600 4950 3300 2970 2640 2310 1980 1650 1320 990 660 627 600 594 561 528 495 462 429 396 363
20 15 10 9 8 7 6 5 4 3 2 1.9 1.8181 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1
75.45 56.59 37.72 33.95 30.18 26.41 22.63 18.86 15.09 11.32 7.54 7.17 6.86 6.79 6.41 6.04 5.66 5.28 4.90 4.53 4.15
0.23 0.25 0.30 0.31 0.33 0.35 0.38 0.43 0.50 0.63 1.00 1.08 1.16 1.18 1.31 1.48 1.72 2.07 2.66 3.83 7.34 IDMT Zone (Ie>)
F. 1.0 a.
Consultant : SATCON
Page 7 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J b. c. d. Selected CT Ratio = Symmetrical S/C current in amps at 6.6kV bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> Ie>> TMS = Definite time setting = 2.0 2.1 a. b. c. d. 2.2 a. b. c. 2.3 SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51N), Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Proposed Ie>> (DT) setting for E/F (50N) Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = Time of Operation for Different Fault Current
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M EQUIVALENT MVA MVA TIME OF OPERATIOM (sec) sec
A A A
e. f.
Standard inverse
ZONE OF OPERATION
30000 225 225 1350 1215 1080 945 810 675 600 405 270 257 243 225 216 203 189
342.95 2.57 2.57 15.43 13.89 12.35 10.80 9.26 7.72 6.86 4.63 3.09 2.93 2.78 2.57 2.47 2.31 2.16
0.4 0.4 1.36 0.30 0.31 0.33 0.35 0.38 0.43 0.46 0.63 1.00 1.08 1.18 1.36 1.48 1.72 2.07
DT Zone (Ie>>)
Consultant : SATCON
Page 8 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 176 162 149 1.3 1.2 1.1 2.01 1.85 1.70 2.66 3.83 7.34
G. 1.0 a. b. c. d.
6.6kV TRANSFORMER FEEDER FOR LTPCC BASIC DATA System voltage in kV Selected CT Ratio = Symmetrical S/C current in amps at 6.6kV bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> Ie>> TMS = Definite time setting = 0.1 - 1.0 In 0.1 - 8 In 0.025 - 1.5 0 - 150 sec @ 0.005 In (Inverse time) @ 0.005 In (Definite time) @ 0.025 @ 0.01 sec 6.6 250/1 600 250 kV A A A
e. f.
MICOM P122
SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51N), Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Proposed Ie>> (DT) setting for E/F (50N) Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = Time of Operation for Different Fault Current
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M EQUIVALENT MVA MVA TIME OF OPERATIOM (sec) sec
Standard inverse
0.2 50 0.1
ZONE OF OPERATION
20 0.2 0.2 24 15 10 9 8 7 6
57.16 0.57 0.57 6.86 4.29 2.86 2.57 2.29 2.00 1.71
0.1 0.1 0.75 0.16 0.19 0.22 0.23 0.25 0.26 0.29
DT Zone (Ie>>)
IDMT Zone
Consultant : SATCON
Page 9 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 125 100 75 50 48 45 43 40 38 35 33 30 28 H. 1.0 a. b. c. d. 5 4 3 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1 1.43 1.14 0.86 0.57 0.54 0.51 0.49 0.46 0.43 0.40 0.37 0.34 0.31 0.32 0.37 0.47 0.75 0.81 0.89 0.98 1.11 1.29 1.56 2.00 2.87 5.50 (Ie>)
415V INCOMER AND BUS COUPLER BASIC DATA System voltage in kV Selected CT Ratio = Symmetrical S/C current in amps at 415V bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> Ie>> TMS = Definite time setting = 0.1 - 0.8 In 0.1 - 10 In 0.05 - 1.0 0.05 - 300 sec (Inverse time) (Definite time) 0.415 3000/5 36950 3000 kV A A (Based on ETAP fault calculation) A
e. f.
SPAJ 140C
SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51N), Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Proposed Ie>> (DT) setting for E/F (50N) Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = Time of Operation for Different Fault Current
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M EQUIVALENT MVA MVA TIME OF OPERATIOM (sec) sec
Standard inverse
60000
20
43.13
0.7
Consultant : SATCON
Page 10 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 360 360 36950 4500 3000 2700 2400 2100 1800 1500 1200 900 600 570 540 510 480 450 420 390 375 360 330 0.12 0.12 123.1666 15 10 9 8 7 6 5 4 3 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.25 1.2 1.1 0.26 0.26 26.56 3.23 2.16 1.94 1.73 1.51 1.29 1.08 0.86 0.65 0.43 0.41 0.39 0.37 0.35 0.32 0.30 0.28 0.27 0.26 0.24 0.7 20.12 0.73 1.32 1.56 1.64 1.73 1.85 2.01 2.25 2.61 3.31 5.27 5.69 6.22 6.89 7.78 9.03 10.89 13.97 16.43 20.12 38.52 IDMT Zone (Ie>) (Ie>>)
J. 1.0 a. b. c. d.
e. f.
CDG 11
(3 sec version)
SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51G), Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Time of Operation for Different Fault Current IEC SI 0.6 300 0.75 Standard inverse
Consultant : SATCON
Page 11 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M EQUIVALENT MVA MVA TIME OF OPERATIOM (sec) sec
ZONE OF OPERATION
36950 4500 3000 2700 2400 2100 1800 1500 1200 900 600 570 540 510 480 450 420 390 360 330
123.1666 15 10 9 8 7 6 5 4 3 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1
26.56 3.23 2.16 1.94 1.73 1.51 1.29 1.08 0.86 0.65 0.43 0.41 0.39 0.37 0.35 0.32 0.30 0.28 0.26 0.24
1.04 1.89 2.23 2.34 2.47 2.65 2.88 3.21 3.73 4.73 7.52 8.13 8.88 9.84 11.12 12.90 15.55 19.96 28.74 55.03 IDMT Zone (Ie>)
Consultant : SATCON
Page 12 of 12
100
10
TIME IN SEC
MVA
Back Up 51G
100.00
Consultant : SATCON
10
TIME IN SEC
0.1 0.10 6.6kV TRAFO FDR 1.00 6.6KV BUS COUPLER 10.00 6.6KV INCOMER
600A SLG
MVA
1000.00
Consultant : SATCON
100
10
TIME IN SEC
MVA
33KV BUS COUPLER
1000.00
Consultant : SATCON
ETAP
7.0.0C
Study Case: SC
Revision: Config.:
3-Phase Fault
ip 79.775 Ik 33.007 I"k
Line-to-Ground Fault
ip 89.314 Ib 36.954 Ik 36.954 I"k 28.585
Line-to-Line Fault
ip 69.087 Ib 28.585 Ik 28.585 I"k
*Line-to-Line-to-Ground
ip 86.248 Ib 35.685 Ik 35.685
36.954
35.685
All fault currents are in rms kA. Current ip is calculated using Method C. * LLG fault current is the larger of the two faulted line currents.
ETAP
7.0.0C
Study Case: SC
Revision: Config.:
Fault Zf (ohm)
Resistance 0.00000 Reactance 0.00000 Impedance 0.00000
MV SWBD 6.6 kV
2.17
V 28 k 5.
DS
LV SWBD 0.433 kV
33.01
33.0 kA
MV SWBD 6.6 kV
V 81 k 3.
DS
LV SWBD 0.433 kV
36.95
36.9 5 kA