Lumen Method Summary

Project
Title Description Number Company Designer ILUMINACION ARTIFICIAL AMPLIACION PRODUCCION CAC-ILUML-01 BCO BCD

Room
Length [ X ] Width [ Y ] Height [ Z ] RCR Ceiling Walls Floor Workplane Height 185.5 m 36 m 8 m 1.04 50 % 30 % 10 % .75 m

Luminaire
Mounting Height Catalog Number Manufacturer IES File Name Lamp Description Number of Lamps Lamp Lumens Light Loss Factor Coefficient of Utilization 7 m TH 400M A16 (LEG 9, SC=1.3) Lithonia Lighting TH_400M_A16_(LEG_9,_SC=1.3).ies ONE 400-WATT CLEAR BT-37 METAL HALIDE, VERTICAL BASE-UP POSITION. 1 36000 0.72 0.78

Output
Illuminance Number of Luminaires Number of Columns [ X ] Number of Rows [Y] Column Spacing Row Spacing Column Start Row Start Power Density [X] [Y] [X] [Y] 333 lux 110 22 5 8.43 m 7.20 m 4.22 m 3.60 m 7.54 W/m
Y 4.22 X 8.43 3.60 7.20

Note: Calculations are based on procedures established by the Illuminating Engineering Society of North America, or standard industry practice. Visual computes output performance based on input data as provided by, and which is the sole responsibility of, the user. Acuity Brands Lighting, Inc. cannot be held responsible for the variations in actual situations which can effect calculated output.