250kVA Unified Power Quality Controller

250kVA Unified Power Quality Controller


P. Ganesan, R. Sudeep Kumar Power Electronics Group Centre for Development of Advanced Computing (CDAC), Trivandrum, India
ganesh@cdactvm.in , sudeep@cdactvm.in

250kVA Unified Power Quality Controller

Overview of the Presentation


Introduction to Power Quality Problems and Solutions Overview of Unified Power Quality Controller Specification of 250kVA Unified Power Quality Controller Power circuit configuration of 250kVA UPQC Converter topology of Shunt Compensator Converter topology of Series Compensator Power circuit Test results and field trial of the UPQC Conclusion

1/26

250kVA Unified Power Quality Controller

Power Quality Affected by Polluting Load


PCC

A
Pure Sinusoidal Distorted voltage

L O A D

Polluting Load

2/26

250kVA Unified Power Quality Controller

Two Main Power Quality Problems

Harmonics and Reactive current drawn by the loads. Voltage Sag,Swell,Unbalance etc.

3/26

250kVA Unified Power Quality Controller

Modern Power Quality Solutions


Shunt Active Filter (STATCOM) Series Active Filter (Dynamic Voltage Restorer)

4/26

250kVA Unified Power Quality Controller

STATCOM
Vpcc Isat Ls Vdc Vsat Compensates Reactive Current Harmonic Current
5/26

250kVA Unified Power Quality Controller

Dynamic Voltage Restorer(DVR)


Vgrid Vdvr Vload

Vdc Corrects Voltage sag and Swell Voltage unbalance Voltage flicker
6/26

250kVA Unified Power Quality Controller

Single Line diagram of Unified Power Quality Controller (UPQC)


VGRID GRID I FILTER Vdvr Idvr Vdc IGRID LOAD

Series Active Filter

Shunt Active Filter

7/26

250kVA Unified Power Quality Controller

Power Flow Control of UPQC Under Nominal Voltage Condition


VOLTAGE CURRENT POWER 100% 100% 100% 100% 100% 100% 100% 100% 100%

3 Phase grid Supply

CONTACTOR

TRANSFORMER

LOAD

0%

0%

SERIES AF

SHUNT AF

8/26

250kVA Unified Power Quality Controller

Power Flow Control of UPQC Under Low Voltage Condition


VOLTAGE CURRENT POWER 90% 110% 100% 100% 110% 110% 100% 100% 100%

3 Phase grid Supply

CONTACTOR

TRANSFORMER

LOAD

10%

10% SERIES AF SHUNT AF

10%

9/26

250kVA Unified Power Quality Controller

Power Flow Control of UPQC Under High Voltage Condition


VOLTAGE CURRENT POWER 110% 90% 100% 100% 90% 90% 100% 100% 100%

3 Phase grid Supply

CONTACTOR

TRANSFORMER

LOAD

10% 10% SERIES AF SHUNT AF

10%

10/26

250kVA Unified Power Quality Controller

UPQC System Specification


Input Voltage Output Voltage Rating Power Factor Configuration Cooling Enclosure Digital Controller :415V, 3 Phase, +10%, -15%, 50 Hz :415V, 3 Phase, +/- 1%, 50 Hz (phase voltages will be balanced) :250kVA(output load) :Will be maintained at near Unity at the grid side :IGBT Inverter :Forced Air 1x3 bridge for shunt 3x1 bridge for series

Ambient temperature :45o C :Suitable for indoor application :DSP based controller 11/26

250kVA Unified Power Quality Controller

Converter Topology
Shunt Compensator
+ve Bus

Series Compensator
+ve Bus

+
Capacitor Bank

+
Capacitor Bank

-ve Bus
R Y B

-ve Bus
P N

No of Switches : 6

No of Switches : 12 ( 4 *3 )
12/26

250kVA Unified Power Quality Controller


Vgr Vgy Vgb

PT Igr

415V AC Contactor CR1

Power Circuit
TRX 1

R Igy Y
TRX 2
C11 C12

L O

Igb B
TRX 3
C13 C14

A D

C15 C16
PT4 PT5 PT6

DB2 MAIN SMPS & GATE DRIVER SMPS C10 DB1 SSR 3 R7
C9 R5 R6

TRX 4

F1 F2 F3
415 V Ishr Ishy

Vdb

Vdy

Vdr

415V AC Contactor

CR2
L1 Id1 L2 Id2 L3 Id3 Vdc DC F/B Ckt

L4

R8

C1

C3

C5 R1 R3

C7

S4-S9
R2 R4 C2 C4 C6 C8

13/26

SERIES ACTVE FILTER

SHUNT ACTIVE FILTER

250kVA Unified Power Quality Controller

Shunt compensator control Block Diagram


* Vdc

Vdc

Load Current Unit Vector

a, b, c ,

I lq

d, q

LPF
I iq
+

L
++

Viq

STATCOM Current

a, b, c ,

, d, q
I id
+ + ++

Vid

L
Grid Voltage magnitude

14/26

250kVA Unified Power Quality Controller

Control Scheme for Series Active Filter


Grid Iinv SA Vdc SA SB VLoad 1: N Load SB Lf IP IL Cf

Vc

Iinv(ref) = Ip +

f Vload(ref) Vload N Tvc L f (Iinv(ref) Iinv ) Vinv(ref) = Vc + N TiL


15/26

250kVA Unified Power Quality Controller

Control Hardware
18 Analog Input channels ADC interface (on-chip + external)

6 PWM For Shunt Compensator 12 PWM For 3x1 Series Compensator Fault Signal from IPM

PWM Interface

6 PWM

I/O Interfaces

3PWM

DSP TMS 320F240


DAC Interface
Monitoring

FPGA
3 PWM

Fault Interface

RS 232 Driver

32K word of RAM CY7C1020

16/26

250kVA Unified Power Quality Controller

Digital Controller

FPGA

TMS 320F240 DSP

17/26

250kVA Unified Power Quality Controller

Performance Evaluation of 250kVA UPQC


Readings at different load
Grid Voltage (V) Vgrn 239 237 240 Vgyn 238 236 240 Vgbn 240 238 240 Grid Current (A) Igr 56 53 43 Igy 77 73 66 Igb 63 59 53 Load Voltage (V) Vlrn 221 220 221 Vlyn 219 219 220 Vlbn 220 220 219 Load Current (A) Ilr 70 63 55 Ily 88 82 76 Ilb 75 64 58

Grid and Load Power Factor


Grid Power Factor Load Power Factor

R 0.97 0.97 0.98

0.98 0.97 0.98 0.98 0.97 0.98

0.78 0.82 0.85 0.78 0.81 0.85 0.80 0.82 0.85

18/26

250kVA Unified Power Quality Controller

Performance Evaluation of Shunt Active Filter


3 Phase AC Supply

120kVA UPS with front end 6 pulse Thyristor rectifier 3x1 Series Active Filter 1x3 Shunt Active Filter Harmonics THD 3 5 7 9 11 13 15 17 Before Harmonic After Harmonic Compensation (%) Compensation (%) 9.4 4.5 0.7 2.1 8.2 0.3 1.9 2.6 0.1 0.4 0.4 0.4 1.9 0.2 1.7 2.3 0.3 0.3

Grid current before Compensation

Grid current after Compensation

19/26

250kVA Unified Power Quality Controller

Performance Evaluation of Shunt Active Filter


Grid Current before compensation

Grid Current after compensation

Harmonic Spectrum before compensation

Harmonic Spectrum after compensation

20/26

250kVA Unified Power Quality Controller

Performance Evaluation of Series Active Filter


Buck Mode Boost Mode

Vset = 210V
Channel1-R phase Grid Voltage Channel2-R phase Load Voltage

Vset = 270V
Channel1- Y phase Grid Voltage Channel2- Y phase Load Voltage

21/26

250kVA Unified Power Quality Controller

Transient Response of Series Active Filter


Vset = 210V (r.m.s) to 270V (r.m.s) Channel1 R-phase Grid Voltage Channel2 R phase Load voltage

Step input

22/26

250kVA Unified Power Quality Controller

250kVA UPQC at C-DAC Lab in India

23/26

250kVA Unified Power Quality Controller

250kVA UPQC at C-DAC Lab in India


Cooling Fan Shunt AF Power stack

Series AF Power stack Shunt AF Coupling Inductor Sensors

Series AF Coupling Transformers

Series AF LC Filter

24/26

250kVA Unified Power Quality Controller

250kVA UPQC at C-DAC Lab in India

Shunt AF Power stack

Series AF Power stack

25/26

250kVA Unified Power Quality Controller

Conclusions on UPQC
UPQC can mitigate Voltage sag,swell and Unbalance UPQC can supply VAR to load It isolates the load current harmonics from flowing to the utility It maintains unity input power factor at all conditions Dynamic response is fast

26/26

250kVA Unified Power Quality Controller

Thank you