250kVA Unified Power Quality Controller
250kVA Unified Power Quality Controller
1/26
A
Pure Sinusoidal Distorted voltage
L O A D
Polluting Load
2/26
Harmonics and Reactive current drawn by the loads. Voltage Sag,Swell,Unbalance etc.
3/26
4/26
STATCOM
Vpcc Isat Ls Vdc Vsat Compensates Reactive Current Harmonic Current
5/26
Vdc Corrects Voltage sag and Swell Voltage unbalance Voltage flicker
6/26
7/26
CONTACTOR
TRANSFORMER
LOAD
0%
0%
SERIES AF
SHUNT AF
8/26
CONTACTOR
TRANSFORMER
LOAD
10%
10%
9/26
CONTACTOR
TRANSFORMER
LOAD
10%
10/26
Ambient temperature :45o C :Suitable for indoor application :DSP based controller 11/26
Converter Topology
Shunt Compensator
+ve Bus
Series Compensator
+ve Bus
+
Capacitor Bank
+
Capacitor Bank
-ve Bus
R Y B
-ve Bus
P N
No of Switches : 6
No of Switches : 12 ( 4 *3 )
12/26
PT Igr
Power Circuit
TRX 1
R Igy Y
TRX 2
C11 C12
L O
Igb B
TRX 3
C13 C14
A D
C15 C16
PT4 PT5 PT6
DB2 MAIN SMPS & GATE DRIVER SMPS C10 DB1 SSR 3 R7
C9 R5 R6
TRX 4
F1 F2 F3
415 V Ishr Ishy
Vdb
Vdy
Vdr
415V AC Contactor
CR2
L1 Id1 L2 Id2 L3 Id3 Vdc DC F/B Ckt
L4
R8
C1
C3
C5 R1 R3
C7
S4-S9
R2 R4 C2 C4 C6 C8
13/26
Vdc
a, b, c ,
I lq
d, q
LPF
I iq
+
L
++
Viq
STATCOM Current
a, b, c ,
, d, q
I id
+ + ++
Vid
L
Grid Voltage magnitude
14/26
Vc
Iinv(ref) = Ip +
Control Hardware
18 Analog Input channels ADC interface (on-chip + external)
6 PWM For Shunt Compensator 12 PWM For 3x1 Series Compensator Fault Signal from IPM
PWM Interface
6 PWM
I/O Interfaces
3PWM
FPGA
3 PWM
Fault Interface
RS 232 Driver
16/26
Digital Controller
FPGA
17/26
18/26
120kVA UPS with front end 6 pulse Thyristor rectifier 3x1 Series Active Filter 1x3 Shunt Active Filter Harmonics THD 3 5 7 9 11 13 15 17 Before Harmonic After Harmonic Compensation (%) Compensation (%) 9.4 4.5 0.7 2.1 8.2 0.3 1.9 2.6 0.1 0.4 0.4 0.4 1.9 0.2 1.7 2.3 0.3 0.3
19/26
20/26
Vset = 210V
Channel1-R phase Grid Voltage Channel2-R phase Load Voltage
Vset = 270V
Channel1- Y phase Grid Voltage Channel2- Y phase Load Voltage
21/26
Step input
22/26
23/26
Series AF LC Filter
24/26
25/26
Conclusions on UPQC
UPQC can mitigate Voltage sag,swell and Unbalance UPQC can supply VAR to load It isolates the load current harmonics from flowing to the utility It maintains unity input power factor at all conditions Dynamic response is fast