Division 16 Sample

You might also like

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 170

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

DIVISION 16 ELECTRICAL SECTION 16010 BASIC ELECTRICAL REQUIREMENTS PART 1 - GENERAL 1.01 SCOPE OF WORK Work under this section shall include the supply, installation, testing and delivery in perfect running conditions of the electrical installations of the project : These installations comprise, but are not limited to, the following chapters : All switchboards & motor control panels. The UPS. The complete electrical installation in the buildings for connecting the lighting, sockets, power outlets and mechanical loads. The lighting fixtures. The telephone system. The fire alarm system. The matv and dish system. The public address system. The earthing system. The lightning system. The supply shall include all the equipment, accessories and other materials not enumerated in these specifications but found necessary for the completion and perfect functioning of the installations. Work shall be executed in a first-class work-manlike manner in accordance with these specifications, the drawings and notes indicated therein, the instructions of the Engineer, the provisions of the Bill of Quantities delivered in place and tested to the full satisfaction of the Engineer. 1.02 CONCEPT OF DESIGN The characteristics of the electric supply shall be as follows : _____________________________________________________________________________________ Division 16 Electrical Works Page 16-1

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr : 3 phase, 4 wire - 50Hz 380V between phases. 220V between phases and neutral with a solidly earthed neutral.

Low voltage network

The necessary electric power for the needs of the project shall be supplied at the main road and equipped by the local power authorities. All junction, derivation and outlet boxes shall be bakelite type or rigid PVC material. All outlet boxes for switches and sockets shall be bakelite type or rigid PVC material. All circuits (lighting + power ) running in perimetral of the offices shall be laid in floor screed. All feeder and derivation light points shall also run in floor screed or above false ceiling or in ceiling skirting (if existing). Separate circuits shall be provided for : a) Lighting and socket outlets. b) Air conditioning unit or exhaust fan. The lighting design shall have a cross-section of 2,5 mm2 and a circuit breaker of 1 x 15 A. The convenience socket outlet and exhaust fan shall have a cross section of 4mm2 and a circuit breaker 1 x 20 A. All work pertaining to the telephone system shall be in accordance with these specifications and shall meet all applicable rules and regulations of the local authorities. Earthing systems shall be in accordance with the requirements of the standards and codes mentioned in these specifications. The resistance of every earthing system shall be inferior to five (5) ohms. 1.03 GENERAL ELECTRICAL REQUIREMENTS ACTUAL ROUTE OF CABLES AND CONDUITS The location or conduits, cables, switchboards, cable trunking, etc...is shown on the drawings approximately, therefore the actual route of cables and conduits may differ from the plans according to the details or the building construction and the conditions of execution of the installation. The Contractor shall supply and install at his expense all secondary materials and special fittings found necessary to overcome the interference and to apply the modifications on the route of cables and conduits that are found necessary during the work to the complete satisfaction or the Engineer. DRILLING AND CUTTING The Contractor shall have to do all drillings and cutting of walls or other parts of the building for the complete proper installation of the conduits, cables, switchboards and other parts of equipment. Beams, girders and other principal structural members shall not be cut or drilled unless permission has been granted by the Engineer. If such drilling and cutting is made on finished surfaces, any marring of the surface shall be made _____________________________________________________________________________________ Division 16 Electrical Works Page 16-2

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

good by repair or replacement at the Contractor's expense. 1.04 EXTRA LOW VOLTAGE SYSTEM GENERAL REQUIREMENTS A. SCOPE OF WORK Work described here under shall apply to the supply and installation of all materials and execution of all works necessary for the extra low voltage systems in the project. The supply shall include all the equipment, accessories and other materials not enumerated in these Specifications but necessary for the completion and perfect functioning of the systems. All to be executed in accordance with these Specifications, the drawings and notes indicated therein and the instructions of the Engineer, delivered complete in place and tested to the full satisfaction of the Engineer. The Contractor shall coordinate the works of the extra low voltage system with the other installations to avoid any interference or damage to any of the systems or installations. The extra low voltage systems covered by these Specifications shall include : * * * * The telephone system, The fire alarm system. The MATV and Dish system. The public address system.

B. STUDIES TO BE PREPARED BY THE CONTRACTOR These Specifications indicate the operation requirements of all the extra low voltage systems as well as the various types of materials to be used and their characteristics. The Contractor shall prepare, according to the systems he is offering, all the wiring diagrams, the number and sizes of wires and cables necessary for the perfect functioning of each system. These distribution circuits shall have enough capacity to fulfill the operation requirements under the heaviest load conditions. No claim could be formulated by the Contractor under pretext of insufficiency of certain choices of Specifications indicated herein for the complete functioning of any of the systems required. The above mentioned layouts and wiring diagrams shall be presented to the Engineer for approval prior to the ordering of the materials.

1.05

SUMMARY A. This section specifies administrative and procedure requirements regarding electrical work. Additional requirements are specified in various sections of Division 16 and also may be required during the execution of work due to project conditions. Requirements of this section shall include, but not be limited to, the following:

B.

1. Submittals. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-3

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr 2. 3. 4. 5. 6. 7. Coordination drawings. Record documents. Maintenance manuals. Electrical installations. Cutting and patching. Temporary power and lighting.

C.

The requirements of this section do not supersede or take precedence over any provision of the General Conditions and Supplementary General Conditions, and should any discrepancy become apparent between these requirements and the General Conditions and Supplementary General Conditions, the Contractor shall notify the Engineer, in writing, and the Engineer shall interpret and decide such matters in accordance with the applicable provisions of the General Conditions and Supplementary General Conditions.

1.06

QUALITY ASSURANCE A. Materials and equipment shall conform to the latest edition of reference specifications specified herein and to applicable codes and requirements of local authorities having jurisdiction. 1. Locally manufactured products of foreign approved makes and of similar quality shall be approved by the Engineer. The Engineer shall be the sole judge to determine whether the product is of the same quality or not. Code Requirements: Comply with the latest applicable standards of the following unless specified otherwise under each section: The equipment, materials and installation shall satisfy the following: The specifications and technical conditions described in the present book of specifications. The General Specifications for Electrical Installations of the Local Authorities. The British Wiring Regulations IEE latedt edition. The recommendations of the "International Electro-Technical Commission (I.E.C.)".

2.

Tests after the completion of the installation shall satisfy the requirements of the standards mentioned above. 1.07 SUBMITTALS A. Definitions: The required submittals of this division, in addition to the definitions of the General Conditions, and elsewhere in the contract documents, are further categorized for convenience as follows:

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-4

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr 1. Product data shall include manufacturer's latest standard printed literature such as manufacturers installation instructions, catalog cuts, color charts, rough-in diagrams, wiring diagrams, and performance curves on materials, equipment and systems for this project. Product data shall include references to applicable specification section and item number. Product data shall be in addition to the required shop drawing submittals. Shop drawings shall include specially prepared technical data with diagrams, performance curves, data sheets, schedules, templates, patterns, reports, calculations, plans, sections, details, measurements, not in standard printed form. Shop drawings shall be in addition to the required product data and shall indicate applicable specification section and item numbers. Samples shall include physical examples of materials; in complete units for visual inspection. Samples shall indicate applicable specification section number and item numbers within that section. Certificates shall include statements of applicability, certifying reports from governing agencies, industry standards, and testing agencies and applicable certificates specified in each section of the specification. Test and Inspection reports shall include reports specified to be required in each section of the specifications. Coordination and Sequencing a. b. Coordinate preparation and processing of submittals with the construction schedule and progress so that the Work will not be delayed. Coordinate and sequence submittals for Work and Work interfaced with other Work so that the processing of submittals will not be delayed by the lack of required coordination between submittals. The obligation to coordinate the Work indicated on any submittal material with other trades and with field conditions is the responsibility of the Contractor. No claim will be allowed for Work that may have to be moved or replaced based on a claim that the work was placed in accordance with dimensions indicated on an approved submittal. No claim for an extension of Contract Time will be approved because of Contractor's failure to coordinate submissions.

2.

3.

4.

5. 2.

c.

d. 4.

Shop Drawings Before starting the work, the Contractor shall submit to the Engineer for his approval, the execution or shop drawings for the entire installation, especially the transfer stations, the main connections and junctions, the final route of cables and conduits and the details of the switchboards and any other part of the installation required by the Engineer. The Engineer reserves the right to alter of modify these plans if they are found to be insufficient or not complying with the established technical standards or if they do not afford the most satisfactory performance or accessibility for repairs.

Three sets of operating and maintenance instructions covering completely the operation and maintenance of electrical systems and automatic control equipment shall be furnished to the owner. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-5

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

Where necessary, one set of operating and maintenance instructions for each electrical equipment shall be framed behind glass and hung where directed. Where necessary, three sets of lubrication charts and manuals for each item of equipment shall be furnished to the owner. At the end of the work, the Contractor shall present three sets of as-built drawings of the whole installation, with all details required by the Engineer, and with the technical data of all installed equipment. 5. Product Data a. b. Submit product data as called for under "Submittals" in each individual specification section. Product data shall be submitted in sextuplicate for review. The Contractor shall indicate on copies of the literature the actual materials being submitted for review when literature contains selections.

6.

Samples a. b. Submit two (2) samples of each material (unless a different quantity is specified) as called for under "Submittals" in each individual section of the specifications. Samples shall be delivered where directed by the Engineer. Sidewalk delivery of samples will not be accepted.

1.08

COORDINATION DRAWINGS A. Prepare coordination drawings in accordance with provisions of the Contract Documents detailing major elements, components, and system of electrical equipment and materials in relationship with other systems, installations and building components. Indicate locations where space is limited for installation and access and where sequencing and coordination of installation are of importance to the efficient flow of the Work, including (but not necessarily limited to) the following: 1. Indicate the proposed locations of major raceway systems, equipment, and materials. Include the following: a. d. e. 2. 3. Clearances for servicing equipment, including space for equipment disassembly required for periodic maintenance. Equipment connections and support details. Sizes and location of required concrete pads and bases.

Indicate scheduling, sequencing, movement and positioning of large equipment into the building during construction. Prepare floor plans, elevations and details to indicate penetrations in floors, walls and ceilings and their relationship to other penetrations and installations.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-6

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

1.09

RECORD DOCUMENTS A. Prepare record documents in accordance with the provisions of the Contract Documents. In addition to the requirements specified in Division 1, indicate installed conditions for: 1. Major raceway systems, size and location, for both exterior and interior; locations of control devices; distribution and branch electrical circuitry; and fuse and circuit breaker size and arrangements. Equipment locations (exposed and concealed), dimensioned from prominent building lines. Approved substitutions, Contract Modifications and actual equipment and materials installed.

2. 3.

1.10

INSTRUCTION MANUALS The supplier shall prepare and produce instruction manuals in both Arabic and English languages for the use, operation and the maintenance of the supplied equipment and installations.

1.11

MATERIALS OF THE SAME KIND All materials of the same kind of service shall be identical and made by the same manufacturer. Any exception to this rule shall be approved by the Engineer.

1.12

TEST CERTIFICATE The supplier shall submit test certificates where required. These shall be issued by an internationally recognized inspection office certifying that all equipment materials, construction and functions are in agreement with the requirements of these Specifications and accepted Standards.

1.13

TEST AND ADJUSTING After the wiring systems are completed, it shall be tested for all controls and defects. Any defects appearing shall be remedied before any apparatus, is installed. Tests, both electrical and physical, shall be made of the various materials, equipment and installation comprising the electrical system. After the entire installation has been completed all necessary adjustments shall be made until all Performance requirements are met.

PART 3 - EXECUTION 3.01 EXAMINATION A. 3.02 Examine conditions at the job site where electrical work is to be performed to insure proper arrangement and fit of the work. Start of work implies acceptance of job site conditions.

PREPARATION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-7

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr The Engineer's drawings issued with these specifications show the approximate location of electrical apparatus; the exact locations are subject to the approval of the Engineer. The general run of feeders, branches and conduits are indicated on the drawings. It is not intended that the exact routing of circuits or locations of conduit be determined therefrom.

A.

3.03

INSTALLATION A. B. C. D. E. F. Sequence, coordinate and integrate the various elements of electrical systems, materials and equipment. Comply with the following requirements. Coordinate electrical systems, equipment and material installation with other building components. Verify dimensions by field measurements. Arrange for chases, slots and openings in other building components during progress of construction, to allow for electrical installations. Coordinate the installation of required supporting devices and sleeves to be set in poured-in-place concrete and other structural components, as they are constructed. Sequence, coordinate and integrate installations of electrical materials and equipment for efficient flow of the Work. Give particular attention to large equipment requiring positioning prior to closing in the building. Where mounting heights are not detailed or dimensioned, install systems, materials, and equipment to provide the maximum headroom possible. Coordinate connection of electrical systems with exterior underground and overhead utilities and services. Comply with requirements of governing regulations, franchised service companies and controlling agencies. Provide required connection for each service. Install systems, materials and equipment level and plumb, parallel and perpendicular to other building systems and components, where installed exposed in finished spaces. Install electrical equipment to facilitate servicing, maintenance and repair or replacement of equipment components. As much as practical, connect equipment for ease of disconnecting, with minimum of interference with other installations. Install access panels or doors where units are concealed behind finished surfaces. Access panels and doors are specified in Division 8 Section "Access Doors" and Section 16050 "Basic Electrical Materials and Methods." Employer Furnished Equipment 1. 2. N. Install and connect designated motor and control equipment furnished by the Employer. Connect designated equipment furnished by the Employer requiring an electric power supply.

G. H.

J. K.

L.

M.

Operation of Defective Equipment: The Employer reserves the right to operate operable defective equipment until it can be removed from service for correction by the Contractor.

END OF SECTION _____________________________________________________________________________________ Division 16 Electrical Works Page 16-8

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16050 BASIC ELECTRICAL MATERIALS AND METHODS

PART 1 - GENERAL 1.01 SUMMARY A. Provide labor, materials, equipment and services, and perform operations required for installation of basic electrical materials and methods and related work as indicated on the drawings and specified herein.

1.02

QUALITY ASSURANCE A. Materials and equipment shall conform to the latest edition of reference specifications specified herein and to applicable codes and requirements of local authorities having jurisdiction.

1.03

SUBMITTALS A. Submit the following submittals in accordance with Section 16010. 1. 2. 3. Shop drawings detailing fabrication and installation for metal fabrications, and supports and anchorage for electrical materials and equipment. Coordination drawings for access panel and door locations. Schedules indicating proposed methods and sequence of operations for selective demolition prior to commencement of Work. Include coordination for shutoff of electrical service, and details for dust and noise control. Coordinate sequencing with construction phasing and Employer occupancy.

1.04

DELIVERY, STORAGE AND HANDLING A. Deliver joint sealer materials in original unopened containers or bundles with labels informing about manufacturer, product name and designation, color, expiration period for use, pot life, curing time and mixing instructions for multi-component materials. Store and handle joint sealer materials in compliance with the manufacturer's recommendations to prevent their deterioration and damage.

B. 1.05

PROJECT CONDITIONS A. Conditions Affecting Selective Demolition: The following project conditions apply: 1. Protect adjacent materials indicated to remain. Install and maintain dust and noise barriers to keep dirt, dust and noise from being transmitted to adjacent areas. Remove protection and barriers after demolition operations are complete. Locate, identify and protect electrical services passing through demolition area and serving other areas outside the demolition limits. Maintain services to areas outside demolition limits. When services must be interrupted, install temporary services for affected areas.

2.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-9

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

3.

Provide temporary utility services to affected area. Provide minimum of 48-hour notice to Engineer prior to utility interruption.

PART 3 - EXECUTION 3.01 EXAMINATION A. 3.02 Examine conditions at the job site where work of this Section is to be performed to insure proper arrangement and fit of the work. Start of work implies acceptance of job site conditions. PREPARATION A. B. Examine the Contract Drawings and specifications in order to insure the completeness of the work required under this Section. Verify measurements and dimensions at the job site and cooperate in the coordination and scheduling of the work of this Section with the work of related trades, so as not to delay job progress. Provide templates as required to related trade for location of support and anchorage items.

C. 3.03

INSTALLATION, ERECTION AND APPLICATION A. Erection of Metal Supports and Anchorage 1. Cut, fit and place miscellaneous metal fabrications accurately in location, alignment and elevation to support and anchor electrical materials and equipment.

END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-10

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16110 RACEWAYS PART 1 - GENERAL 1.01 SUMMARY A. B. Provide labor, materials, equipment and services, and perform operations required for installation of Raceways and related work as indicated on the drawings or specified herein. Work Included: The work of this section shall include, but not be limited to, the following: 1. 2. 3. 4. C. Flexible metal conduit. Liquid-tight flexible metal conduit. Rigid metal conduit. Rigid PVC conduit.

Related Work Specified Elsewhere 1. 2. Basic Electrical Requirements - Section 16010. Basic Electrical Materials and Methods - Section 16050.

1.02

SUBMITTALS A. Submit the following in accordance with the requirements specified under "Submittals" of Section 16010. 1. Product Data: Submit manufacturer's technical product data, including specifications and installations, for each type of raceway system required. Include data substantiating that materials comply with requirements.

PART 2 - PRODUCTS 2.01 MANUFACTURES 2.02 Univolt Egatube Or any approved equal

MATERIALS A. Conduit and Tubing 1. 2. Provide metal conduit, tubing and fittings of types, grades, sizes and weights (wall thicknesses) for each service indicated. Rigid PVC: Conduit-heavy gauge normal impact unmodified rigid PVC and shall conform to BS 4607 Conduits shall be resistant to heat, suitable for a continuous service temperature of 70 degrees C., and shall be corrosion-proof, in combustible, gas and watertight, acid-proof. Thin wall rigid PVC conduit shall not be permitted.

3. Rigid Steel Conduit: Rigid steel, zinc-coated, threaded type conforming to BS _____________________________________________________________________________________ Division 16 Electrical Works Page 16-11

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr 4568 part 1. Provide zinc coating fused to inside and outside walls. 4. 5. Flexible Metal Conduit: Formed from continuous length of spirally wound, interlocked zinc-coated strip steel. Liquid-Tight Flexible Metal Conduit: Liquid-tight flexible metal conduit; constructed of single strip, flexible, continuous, interlocked, and double-wrapped steel; galvanized inside and outside; coat with liquid-tight jacket of flexible polyvinyl chloride (PVC). Conduit Straps and Supports: Hot dipped galvanized cast malleable iron or structural steel with hot dipped galvanized nuts and bolts. Conduit Bushings: Insulated bushings for conduits 3/4 and larger. Provide lay-in type lugs on grounding bushings. Expansion Fittings: Malleable iron-hot dipped galvanized end fittings with grounding strip and flexible tube and covered with neoprene tubing for rigid steel conduit in concrete. The use of aluminum material is prohibited. O-Z/Gedney Co. Type DX or DXX.

6. 7. 8.

PART 3 - EXECUTION 3.01 EXAMINATION A. Examine conditions at the job site where work of this section is to be performed to insure proper arrangement and fit of the work. Start of work implies acceptance of job site conditions.

3.02

PREPARATION A. B. Examine the Contract Drawings and specifications in order to insure the completeness of the work required under this section. Verify measurements and dimensions at the job site and cooperate in the coordination and scheduling of the work of this section with the work of related trades so as not to delay job progress. Provide templates as required to related trade for location of items.

C. 3.03

INSTALLATION A. Installation of Raceways 1. Install raceways as indicated; in accordance with manufacturer's written installation instructions, and in compliance with the applicable electrical code. Install units plumb and level, and maintain manufacturer's recommended clearances. Coordinate with other work including wires/cables, boxes, and panel work, as necessary to interface installation of electrical raceway and components with other work.

2.

B.

Installation of Conduits

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-12

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr 1. Install all conduits concealed or exposed as follows: a. Conduit sizes shall be in accordance with applicable electrical codes, minimum size 3/4". Mechanically fasten together metal conduits, enclosures, and raceways for conductors to form continuous electrical conductor. Connect to electrical boxes, fittings and cabinets to provide electrical continuity and firm mechanical assembly.

b.

Avoid use of dissimilar metals throughout system to eliminate possibility of electrolysis. Where dissimilar metals are in contact, coat surfaces with corrosion inhibiting compound before assembling, Burndy "Penetrox" or T&B Kopr-"Shield". Install miscellaneous fitting such as reducers, chase nipples, 3-piece unions, split couplings, and plugs that have been specifically designed and manufactured for their particular application. Install expansion fitting in raceways every 200 feet linear run or wherever structural expansion joints are crossed. Use roughing-in dimensions of electrically operated unit furnished by supplier. Set conduit and boxes for connection to units only after receiving review of dimensions and after checking location with other trades. Provide nylon pull cord in empty conduits, with ends secured to blocks to prevent accidental removal. Provide each end of the pulling cord with a linen tag identifying the termination. Test conduits required to be installed, but left empty, test with ball mandrel. Clear any conduit which rejects ball mandrel. Pay costs involved for restoration of conduit and surrounding surfaces to original condition.

c.

d.

e.

2.

Conduit Installation: Provide rigid PVC conduit where embedded in concrete, masonry, underfloor or earth. Follow requirements in other areas as follows: a. b. c. Use heavy gauge PVC above false ceiling. Use rigid steel conduit for exposed conduit installations other than above false ceiling, unless otherwise noted. Use flexible conduit in movable partitions and from outlet boxes to recessed lighting fixtures, and final 24 inches of connection to control items subject to movement or vibration, and in cells of precast concrete panels. Use liquid-tight flexible conduit for final 24 inches of connection to motors and in lieu of flexible conduit where subjected to one or more of the following conditions. 1) 2) 3) 4) e. f. Exterior location. Moist or humid atmosphere where condensate can be expected to accumulate. Corrosive atmosphere. Subjected to water spray or dripping oil, water or grease.

d.

Cut conduits straight, properly ream, and cut threads for heavy wall and intermediate steel conduit deep and clean.

Field-bend conduit with benders designed for purpose so as not to distort nor vary internal diameter. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-13

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

g. h. i. j. k. l. m. n. o. p. q.

Make changes in direction of horizontal telephone conduit runs 1 inch or larger with minimum 36 inches radius long sweep elbow or bends. Not more than the equivalent of two (2) quarter bends (180 degrees total) are permitted for telephone, data and telecommunication conduit runs between terminations. Size conduit to meet applicable electrical codes. Fasten conduit terminations in sheet metal enclosures by 2 locknuts, and terminate with bushing. Install locknuts inside and outside enclosure. Conduits are not to cross pipe shafts, or ventilating duct openings. Keep conduits a minimum distance of 6 inches from parallel runs of flues, hot water pipes or other sources of heat. Support riser conduit at each floor level with clamp hangers. Use of running threads at conduit joints and terminations is prohibited. Where required, use 3-piece union or split coupling. Complete installation of electrical raceway before starting installation of cables/wires within raceways. Install conduit so as not to cut or run through structural members, cable holes or cable slots, except by special written permission of the Engineer. Concealed Conduits 1) 2) Encase conduits installed under floors on grade in minimum 2" concrete. Install underground conduits minimum of 24" below finished grade.

r.

Conduits in Concrete Slabs 1) 2) 3) 4) 5) Place conduits between bottom reinforcing steel and top reinforcing steel. Place conduits either parallel, or at 90 degrees, to main reinforcing steel. Separate conduits by not less than diameter of largest conduit to ensure proper concrete bond. Conduits crossing in slab must be reviewed for proper cover by the Engineer. Embedded conduit diameter is not to exceed 1/3 of slab thickness.

s. t.

Install conduits as not to damage or run through structural members. Avoid horizontal or cross runs in building partitions or side walls. Conduit Fittings 1)

Construct locknuts for securing conduit to metal enclosure with sharp edge for digging into metal, and ridged outside circumference for proper fastening. 2) Install insulated type bushings for terminating conduits 3/4" and larger. Bushings are to have flared bottom and ribbed sides. Upper edge to have phenolic insulating ring molded into bushing. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-14

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr 3) 4) Bushing of standard or insulated type to have screw type grounding terminal. Miscellaneous fittings such as reducers, chase nipples, 3-piece unions, split coupling, and plugs to be specifically designed for their particular application.

C.

Installation of Raceways and Wireways 1. Mechanically assemble metal enclosures, and raceways for conductors to form continuous electrical conductor, and connect to electrical boxes, fittings and cabinets as to provide effective electrical continuity and rigid mechanical assembly. a. Avoid use of dissimilar metals throughout system to eliminate possibility of electrolysis. Where dissimilar metals are in contact, coat surfaces with corrosion inhibiting compound before assembling. Install expansion fittings in raceways wherever structural expansion joints are crossed. Make changes in direction of raceway run with proper fittings, supplied by raceway manufacturer. No field bends of raceway sections will be permitted. Properly support and anchor raceways for their entire length by structural materials. Raceways are not to span any space unsupported. Do not support raceway from ductwork. Use boxes as supplied by raceway manufacturer wherever junction pull or devices boxes are required. Standard electrical "handy" boxes, etc. shall not be permitted for use with surface raceway installations.

b. c.

d.

e.

END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-15

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16111
CABLE TRAYS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. B. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. Requirements of the following Division 16 Sections apply to this section: 1. 2. 1.2 SUMMARY A. This section includes mettalic cable trays. Types of cable trays in this section include the following: 1. B. Ventilated (perforated) bottom. "Basic Electrical Requirements" "Basic Electrical Materials and Methods"

Related Sections: The following Division Section contains requirements that relate to this section. 1. Division 16 section "Supporting Devices".

1.3

SUBMITTALS General: Submit the following in accordance with Conditions of Contract and Division 1 Specification Sections: 1. 2. Product Data: Manufacturer' catalogues and data for cable tray products and accessories. Shop Drawings: Layout floor plans and elevations showing cable tray system. Designate components and accessories including clamps, brackets, hanger rods, splice plates connectors, expansion joint assemblies, straight lengths, and fittings. Show accurately scaled components and spatial relationships to adjacent equipment. Show tray types, dimensions, and finishes. Factory Test Reports: Certified copies of factory test reports performed in conformance with Standard approved on cable trays of types and size specified for this project. Field Test Reports: in compliance with "Field Quality Control" Article of this section. Maintenance data for inclusion in "Operating and maintenance Manual".

3. 4. 5.

1.04

QUALITY ASSURANCE

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-16

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Manufacturers: Firms regularly engaged in manufacture of cable trays and fittings of types and capacities required, whose products have been in satisfactory use in similar service for not less than 5 years. Electrical Component Standard: Components and installation shall comply with NFPA 70 "National Electrical Code", in the absence of over-ruling local regulations. Single-Source Responsibility: All cable tray components shall be the product of a single manufacturer. Coordination Drawings: Include cable tray systems in coordination drawings.

A.

B. C. D. 1.05

DELIVERY, STORAGE, AND HANDLING A. B. Deliver cable tray systems and accessories packaged in factory-fabricated fiberboard type containers. Handle cable tray systems and components carefully to avoid breakage, denting and scoring finishes. Do not install damaged equipment, replace and return damaged units to manufacturer. Store cable trays and accessories in original cartons and in clean dry space; protect from weather and construction traffic.

C.

PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated in the Work include but are not limited to the following: 1. 2. 3. 2.2 Thorsman. Swifts Wibe.

CABLE TRAYS, GENERAL REQUIREMENTS: A. Cable tray systems shall be of indicated types, sizes, and standard classes and shall be complete with manufacturer's recommended covers, barrier strips, dropouts, fittings, conduit adaptors, hold-down devices, grommets, and blind ends as required and indicated. Cable tray products shall have rounded edges and smooth surfaces. Except as otherwise indicated, provide metal cable trays, with splice plates, bolts, nuts and washers for connecting units; capable of supporting concentrated loads of 90kg at any point, over and above cable load. Provide cable tray covers, where indicated; construct of metal and finishes which mate and match cable trays. Provide cable tray supports and connectors, including bonding jumpers, as indicated and as recommended by cable tray manufacturer.

B. C.

D. E.

F. Galvanizing: is to be in accordance with ASTM B633, applied after fabrication. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-17

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

G.

Sizes: trays and ladders are to be standard metric sizes, 150, 300 and 600 mm wide, and at least 2,44 m 8ft. length of section. Size of tray or ladder is to be determined by number and sizes of cables in accordance with the Regulations and/or as shown on the Drawings. Tray or ladder is to have strength and rigidity to provide support for cables contained within. Deflection between supports is not to exceed 1/350 under full loading capacity. Earthing Connector: for plastic coated trays or ladders, provide earthing connector on each coupling between adjacent sections.

H. 2.3

MATERIALS AND FINISHES: A. Cable Trays, Fittings, and Accessories: Steel, hot-dipped galvanized after fabrication.

2.4

SIZES AND CONFIGURATIONS: A. Minimum Fitting Radius: 12 inches (300 mm).

2.5

CABLE TRAY ACCESSORIES: A. B. Covers: Solid type, of same materials and finished as cable trays. Barrier Strips: Same materials and finishes and finishes as cable trays.

2.6

SUPPORTS AND CONNECTOR: A. B. Cable tray supports and connectors, including bonding jumpers shall be as recommended by cable tray manufacturer. Bolts and screws shall be cadmium plated or electrolytically galvanized.

2.7

FASTENERS FOR SUPPORTS: A. B. C. D. Fasteners to connect cable tray supports to the building structure shall be as follows: Expansion Anchors: Carbon steel wedge or sleeve type. Toggle Bolts: All steel springhead type. Powder-Driven Threaded Studs: Heat-treated steel, designed specifically for the intended service.

2.8

FIRE STOPPING: A. B. C. General : Materials shall be approved for fire ratings consistent with penetrated barriers. Sleeves: Schedule 40, welded, black steel pipe sleeves. Sizes as indicated or minimum NEC size for cable or cable group to be installed. Sealing Fittings: Suitable for sealing cables in sleeves or core drilled holes.

D. Two-Part Sealant: Formed-in-place sealant as specified in paragraph "Fire-Resistant Joint _____________________________________________________________________________________ Division 16 Electrical Works Page 16-18

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Sealers" in Division 16 Section 16050, "Basic Electrical Materials and Methods".

2.9

WARNING SIGNS: A. Lettering: 37.5mm (1-1/2-inch) high, black on yellow background with legend "WARNING NOT TO BE USED AS WALKWAY, LADDER, OR SUPPORT FOR LADDERS OR PERSONNEL". Materials and Fastening: Conform to Section "Electrical Identification".

B.

PART 3 - EXECUTION 3.1 Installation of cable tray systems: A. B. C. D. Install cable trays in accordance with equipment manufacturer's written instruction. Remove burrs and sharp edges of cable trays. Conform to manufacturer's recommendations for selection and installation of supports. Strength of each support including fastenings to the structure shall be adequate to carry present and future load multiplied by a safety factor of at least four or the calculated load plus 90 kg (200 lbs), whichever is greater spacing of supports is not to exceed 1.5 m. Installation of supports shall be in accordance with cable tray manufacturer's written instruction and recommendations. Fastening Supports: Unless otherwise indicated, fasten cable tray supports securely to the building structure as specified in Division 16 Section "Supporting Devices". Support at Connections to Equipment: Where cable trays connect to equipment, provide flanged fittings fastened to the tray and to the equipment. Support the tray separately. Do not carry the weight of the tray on the equipment enclosure. Thermal Contraction and Expansion: Install expansion connectors in cable tray runs that exceed the following length: 1. 2. I. Steel Tray: 52.5 m (175 feet). Spacing and gap settings for expansion connectors shall not exceed recommendations of approved applicable standards.

E. F. G.

H.

Direction Changes : Make changes in direction of cable tray with standard cable tray fittings. J. Locate cable tray above piping except as required for tray accessibility and as otherwise indicated. K. Firestopping: Where cable trays penetrate fire and smoke barriers including walls, partitions, floors, and ceilings, install fire-stopping at penetrations after cables are installed. L. Sleeves For Future Cables: Install capped sleeves for future cables through firestopped cable tray penetrations of fire/smoke barriers. M. Working Space: Install cable trays with sufficient space to permit access for installing cables. N. Barriers: Where trays carry conductors of different systems, such as power, communications, and data processing, or different insulation levels, use separate cable trays. In case of absolute necessity, where an Engineer's approval is required install _____________________________________________________________________________________ Division 16 Electrical Works Page 16-19

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr barriers to separate the systems.

3.2

GROUNDING A. Electrically ground cable trays and ensure continuous electrical conductivity of cable tray system. Use tray as an equipment ground conductor for itself only, not for connected equipment.

3.3

WARNING SIGNS: A. After installation of cable trays is completed, install warning signs, on or in proximity to cable trays, where easily seen by occupants of space.

3.4

FIELD TESTING: A. 1. Earthing: Test cable trays to ensure electrical continuity of bonding and grounding connections. Furnish equipment, including jacks, jigs, fixtures, and calibrated indicating scales required for reliable testing. Obtain the Engineer's approval before transmitting loads to the structure. Test to 90 percent of rated proof-load for fastener. If fastening fails test, replace fastener and retest until satisfactory results are achieved.

3.5

CLEANING AND FINISH REPAIR: A. Upon completion of installation of cable trays, inspect trays, fittings, and accessories. Remove burrs, dirt, and construction debris and repair damaged finish including chips, scratches, and abrasions. Galvanized Finish: manufacturer. Repair damage with a zinc-rich paint recommended by the tray

B. C.

PVC or Paint Finish: Repair damage with matching touch-up coating recommended by the tray manufacturer. END OF SECTION

SECTION 16120 WIRES AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. B. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Section, apply to this Section. Requirements of the following Division 16 Sections apply to this section: 1. 2. 1.2 SUMMARY: "Basic Electrical Requirements." "Basic Electrical Materials and Methods"

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-20

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr This Section includes wires, cables, and connectors for power, lighting, signal, control and related systems rated 600 volts and less. Extent of electrical wire and cable work is indicated by drawings and schedules. Types of electrical wire, cable, and connectors specified in this section include the following: 1. 2. 3. 4. Single core copper conductor/cables Multicore copper conductor/cables Fixtures wires. Control and signal cables.

A. B. C.

D.

Applications of electrical wire, cable, and connectors required for project are as follows: 1. 2. 3. 4. 5. For power distribution circuits. For lighting circuits. For appliance and equipment circuits. For motor-branch circuits. For signal and control circuits where not specified required otherwise under other sections of the specification.

E.

Related Sections: The following Sections contain requirements that relate to this section: 1. Division 16 Section " Electrical Boxes and Fittings" for connectors for terminating cables in boxes and other electrical enclosures.

1.3

SUBMITTALS: A. B. Product Data: submit manufacturer's data on electrical wires, cables and connectors. Field Test Reports: indicating and interpreting test results relative to compliance with performance requirements of testing standards.

1.4

QUALITY ASSURANCE: A. B. C. Regulatory Requirements: Comply with provisions of the statutory laws having jurisdiction and local codes of practice applicable to the job site/host country. Conform to applicable codes and regulations regarding toxicity of combustion products of insulating materials. Manufacturers: Firms regularly engaged in manufacture of electrical wire and cable products of type and sizes required, whose products have been in satisfactory use in similar service for not less than 5 years. IEC Compliance: Comply with IEC requirements as applicable to construction, insulation and colour coding of electrical wires and cables.

D.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-21

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr NFPA Compliance: Comply with applicable NFPA requirements pertaining to cables and cable installations.

E. 1.5

DELIVERY, STORAGE AND HANDLING: A. B. C. Deliver wire and cable properly packaged in factory-fabricated type containers, wound on factory reels. Store wire and cable in clean dry space in original containers. Protect products from weather, damaging fumes, construction debris and traffic. Handle wire and cable carefully to avoid abrasing, puncturing and tearing wire and cable insulation and sheathing. Ensure that dielectric resistance integrity of wires/cables is maintained.

PART 2 - PRODUCTS 2.1 MANUFACTURERS: A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products which may be incorporated in the work include, but are not limited to , the following: Wire and Cable Pirelli- General Liban Cables. Or any approved equal 2.1 WIRES AND CABLES A. General: Unless otherwise specified or shown on the Drawings, cables and other feeders are to have copper conductors. Cable conductors are to be stranded for sections 4 mm 2 and above, based on IEC 228 Class 2. Signal and control cables are to have solid conductors unless otherwise specified. Flexible cords are to have finely stranded conductors. Conductors of single core cables 25 mm2 and above are to be compacted. Multi-core cables 35 mm2 and above are to be sectoral shape. 1. 2. Conductor Sizes: are to be metric and as shown on the Drawings. Conductors with cross-sectional area smaller than specified will not be accepted. Building Wiring Insulation: in the absence of a national code/regulation, insulation is to be colour coded or otherwise identified as follows: a. b. c. B. LV Wires: Neutral is to be light blue or white or black. Protective earth is to be green or green/yellow striped. Phase colours are suggested as red, yellow, dark blue for 380/220V systems.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-22

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr 1. Single Core PVC Insulated Wires: unless otherwise specified single conductor wires for wiring in conduit are to have annealed copper conductors, generally with concentric strands and insulated with flame retardant, moisture and heat resistant PVC/E to IEC 227 suitable for wet locations and for conductor temperature of 85 deg. C. Wires are to be 450/750 V grade.

C.

LV Cables: 1. Multi-Core PVC Insulated Cables (0.6/1 KV): to have annealed, copper conductors, insulated with PVC/E to IEC 227, flame retardant, moisture and heat resistant, suitable for wet locations and conductor temperatures of 85 deg. C, laid up, bedded with suitable filler and sheathed with PVC. Flexible Cable for Connection to appliances, window fans, pendants etc.: is to be 300/500 V grade , three or four core, with tinned finely stranded copper wires, EPR insulated, twisted and sheathed with chlorosulphonated polyethylene (CSP compound) and with strengthening cord. High Temperature Cable: solid or stranded plain annealed copper conductors to BS 6360 (in sizes up to 4 mm2), extruded silicon rubber insulation (0.6 mm radial thickness), aluminum/PVC laminate and PVC composite sheath with tinned earth continuity conductor/drain wire. Cable is to be rated 300/500V, capable of accepting voltage surges up to 5 KV, to operate continuously at 150 deg. C. and for short durations at 200 deg. C. It is to be certified to have passed IEC 331 and IEC 332 flame resistance and fire retardant tests.

2.

3.

D.

Control and Signal Cables 1. Multicore PVC Insulated Control Cables: 0.6/1 KV rating, solid 1.5 mm2, 2.5 mm2 or stranded 4 mm2 plain circular copper conductors, with heat resistive PVC/E to IEC 227, rated for 85 deg. C, of 7,12,19,24,30 or 37 cores. Cores are to be laid up together and filled with non-hygroscopic material, PVC over sheathed, to form compact and circular cable for use in switchgear, control gear and generally for control of power and lighting systems. PE Insulated Control and Signal Cables: for use on data systems, are to be generally 300 V rating, polyethylene insulated, colour coded, tinned copper conductors (0.6 mm diameter), twisted together into pairs. Multi-pair core assembly is to be covered with binder tape, spirally wound 0.075 mm bare copper shielding tape and provided with drain wire and overall PVC sheath.

2.

PART 3 - EXECUTION 3.1 INSTALLATION OF WIRES AND CABLES: A. General: Install electrical cables, wires and wiring connectors as indicated, in compliance with applicable requirements of the Regulations/codes applicable, and IEC, NFPA, and in accordance with recognized industry practices. Co-ordinate: wire/cable installation work including electrical raceway and equipment installation work, as necessary to properly interface installation of wires/cables with other work.

B.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-23

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Run d.c wiring in separate conduits than a.c. wiring. Use pulling compound or lubricant, where necessary; compound used must not deteriorate conductor or insulation. Use pulling means including, fish tape, cable, rope and basket weave wire/cable grips which will not damage cables or raceway. Install exposed cable, parallel and perpendicular to surfaces, or exposed structural members, and follow surface contours, where possible. Keep conductor splices to minimum. In case of splices, these are to be inside splice boxes, pull or junction boxes. Install splice and tap connectors which are compatible with conductor material. Tighten electrical connectors and terminals, including screws and bolts, in accordance with manufacturer's published torque tightening values. Where manufacturer's torquing requirements are not indicated, tighten connectors and terminals to comply with tightening torques specified in recognized standards. Pull cables simultaneously where more than one cable is being installed in the same raceway.

C. D. E. F. G. H. J.

K. 3.2

FIELD QUALITY CONTROL: A. B. C. Prior to energization of circuitry, check installed wires and cables with megohm meter to determine insulation resistance levels to ensure requirements are fulfilled. Prior to energization, test wires and cables for electrical continuity and for short-circuits. Subsequent to wire and cable hook-ups, energize circuitry and demonstrate functioning in accordance with requirements. Where necessary, correct malfunctioning units, and then retest to demonstrate compliance.

END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-24

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16135 ELECTRICAL BOXES AND FITTINGS PART 1 -GENERAL 1.01 SUMMARY A. Provide labor, materials, equipment and services, and perform operations required for installation of electrical boxes and fittings and related work as indicated work as indicated on the drawings and specified herein. Work Included: The work shall include, but not be limited to, the following: 1. 2. 3. 4. 5. 6. C. Outlet boxes Junction boxes Pull boxes Floor boxes Poke-throughs Knockout closures.

B.

Related Work Specified Elsewhere 1. 2. 3. Basic Electrical Requirements - Section 16010 Basic Electrical Materials and Methods - Section 16050 Grounding - Section 16450

1.02

QUALITY ASSURANCE A. Materials and equipment shall conform to the latest edition of reference specifications specified herein and to applicable codes and requirements of local authorities having jurisdiction. 1. 2. Code Compliance: Comply with electrical codes as applicable to construction and installation of electrical wiring boxes and fittings. UL Compliance: Comply with applicable requirements of UL 50, UL 514-Series, and UL 886 pertaining to electrical boxes and fittings. Provide electrical boxes and fittings which are UL-listed and labeled. NEMA Compliance: Comply with applicable requirements of NEMA Stds/Pub Nos. OS1, OS2 and Pub 250 pertaining to outlet and device boxes, covers and box supports.

3.

1.03

SUBMITTALS A. Submit the following in accordance with the requirements specified under "Submittals" in Section 16010. 1. Product Data : Submit manufacturer's data on electrical boxes and fittings.

PART 2 - PRODUCTS 2.01 MATERIALS _____________________________________________________________________________________ Division 16 Electrical Works Page 16-25

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

A.

Outlet Boxes: Provide galvanized coated flat rolled sheet-steel outlet wiring boxes, of shapes, cubic inch capacities and sizes, including box depths as required, suitable for installation at respective locations. Construct outlet boxes with mounting holes and with cable and conduit-size knockout openings in bottom and sides. Provide boxes with threaded screw holes, with corrosion-resistant cover and grounding screws for fastening surface and device type box covers, and for equipment type grounding. 1. Concrete box shall be 4 inches octagon with a removable backplate and 3/8 inch fixture stud, if required. Depth of box shall allow for a minimum of 1 inch of concrete to be poured above the backplate. Lighting fixture box shall be 4 inches octagon with 3/8 inch fixture stud. For suspended ceiling work, 4 inches octagon with removable backplate where required, and two parallel bars for securing to the cross-furring channels. Outlet Box Accessories: Provide outlet box accessories as required for each installation, including box supports, mounting ears and brackets, wallboard hangers, box extension rings, fixture studs, cable clamps and metal straps for supporting outlet boxes, which are compatible with outlet boxes being used to fulfill installation requirements for individual wiring situations. Device Boxes: Provide galvanized coated flat rolled sheet-steel device boxes of shapes, cubic inch capacities and sizes including box depths as required, nominal 4" square minimum 2-1/8" deep as required, suitable for installation at respective locations. Construct device boxes for flush mounting with mounting holes, and with cable-size knockout openings in bottom and ends, and with threaded screw holes in end plates for fastening devices. Provide cable clamps and corrosionresistant screws for fastening cable clamps, and for equipment type grounding. Multi-device boxes shall be of the multi-gang type, minimum 2-1/4" deep. Gangable "switch" boxes are not acceptable.

2.

3.

4.

5.

Device Box Accessories: Provide device box accessories as required for each installation, including mounting brackets, device box extensions, switch box supports, gang box covers, plaster ears, and plaster board expandable grip fasteners, which are compatible with device boxes being utilized to fulfill installation requirements for individual wiring situations.

B.

Raintight Outlet Boxes: Provide corrosion-resistant cast-aluminum, raintight outlet wiring boxes Type FS or FD and sizes, including depth of boxes, with threaded conduit holes for fastening electrical conduit, cast aluminum face plates with spring-hinged watertight caps suitably configured for each application, including face plate gaskets and corrosion-resistant plugs and fasteners, no overlapping edges. Junction Pull and Splice Boxes: Provide galvanized code-gauge sheet steel junction and pull boxes, with screw-on covers; of types, shapes and sizes to suit each respective location and installation; with welded seams and equipped with stainless steel nuts, bolts, screws and washers. Boxes installed outdoors to be fabricated of aluminum. Provide cover gaskets for boxes installed outdoors or in wet or damp locations. 1. 2. Where size of box is not indicated, size to permit pulling, racking and splicing of the cables. Braze a ground connector, suitable for copper cables to the inside of the box.

C.

3. Junction Box - Sidewalk Type: Cast iron, hot dipped galvanized with threaded conduit _____________________________________________________________________________________ Division 16 Electrical Works Page 16-26

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr entrance hubs, flanged, reinforced checkered cover, gaskets, with pry bar slots and countersunk stainless steel screws.

4)

Nonmetallic Boxes: Nonmetallic boxes rigid PVC shall be used only with rigid PVC conduit. It shall be constructed so as to prevent contact between the conductors in the box and the supporting screws. It shall be made of high impact PVC and it shall be supplied as the same make of the rigid PVC conduit. Boxes shall conform to Federal Specifications W-J805.

D.

Knockout Closures: Provide corrosion-resistant box knockout closures, offset connectors, of types and sizes to suit respective installation requirements and applications.

PART 3 - EXECUTION 3.01 EXAMINATION A. Examine conditions at the job site where work of this Section is to be performed to insure proper arrangement and fit of the work. Start of work implies acceptance of job site conditions.

3.02

PREPARATION A. B. Examine the Contract Drawings and specifications in order to insure the completeness of the work required under this Section. Verify measurements and dimensions at the job site and cooperate in the coordination and scheduling of the work of this Section with the work of related trades, so as not to delay job progress. Provide templates as required to related trade for location of items.

C. 3.03

INSTALLATION A. Install electrical boxes and fittings as indicated; in accordance with manufacturer's written instructions, applicable requirements of the applicable electrical code and in accordance with recognized industry practices to fulfill project requirements. Obtain exact location of outlets from the drawings of interior details and finishes. Refer any condition that would place an outlet box in an unsuitable location to the Engineer. Mount outlet boxes for similar equipment in the same or similar areas at uniform heights. Where mounting heights are not indicated, locate outlet as required for the equipment connected thereto or as directed by the Engineer. Provide blank plates on outlet boxes in which no device is installed. Provide rain tight cast boxes for surface mounted weatherproof switches and receptacles. Provide pull and/or splice boxes where indicated on the drawings or required to facilitate pulling of wires and cables.

B. C.

D. E. F.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-27

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Support boxes located above hung ceilings independently of the ceiling. Fasten boxes to the structure by bar hangers or other supports as approved by the Engineer. Coordinate installation of electrical boxes and fittings with wire/cable, wiring devices, and raceway installation work. Provide weathertight outlets for interior and exterior locations exposed to weather or moisture. Provide knockout closures to cap unused knockout holes where blanks have been removed. Install electrical boxes in those locations which ensure ready accessibility to enclosed electrical wiring. Where mounted in removable partition panels, install outlets to permit removal of panels without removing the outlet box. Avoid installing boxes back-to-back in walls. Provide not less than 6 inches separation/ Do not install aluminum products in concrete. Position recessed outlet boxes accurately to allow for surface finish thickness. Set floor boxes level and flush with finish flooring material. Fasten electrical boxes firmly and rigidly to substrates, or structural surfaces to which attached, or solidly embed electrical boxes in concrete or masonry. Provide insulation at the rear of outlet boxes installed within exterior walls to prevent condensation within the boxes. Mounting Heights for Devices: The mounting heights for electrical outlets measured from the finished floor to the centerline of the outlet, shall be in accordance with the following, unless otherwise shown on the Engineerural, interior design or electrical drawings. Long dimensions of devices shall be vertical unless otherwise specified or shown on the drawings. 1. 2. 3. 4. 5. 6. 7. Wall Light Switches: 120 cm. Wall Receptacles: 30 cm. Wall Exit Fixtures: Bottom of fixture 5 cm. above door frame. Wall Mounted Telephone Outlets: 30 cm. Wall Telephones: 120 cm. Fire Alarm Pull Station: 140 cm. Fire Alarm Audio or Audio/Visual Alarms: Bottom 5cm. above door frame.

G. H. I. J. K.

L. M. N. O. P. Q. R.

S. T.

Provide electrical connections for installed boxes. Grounding: Upon completion of installation work, properly ground metallic electrical boxes and demonstrate compliance with requirements.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-28

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-29

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16140 WIRING DEVICES PART 1- GENERAL 1.01 SUMMARY A. Provide labor, materials, equipment and services, and perform operations required for installation of wiring devices and related work as indicated on the drawings and specified herein. Work Included: The work shall include, but not be limited to, the following: 1. 2. 3. C. Receptacles Wall lighting Switches Wall Plates

B.

Related Work Specified Elsewhere 1. 2. 3. Basic Electrical Requirements - Section 16010 Basic Electrical Materials and Methods - Section 16050 Electrical Identification - Section 16195.

1.02

QUALITY ASSURANCE A. Materials and equipment shall conform to the latest edition of reference specifications specified herein and to applicable codes and requirements of local authorities having jurisdiction. 1. Regulatory Requirements: Comply with provisions of the applicable electrical code.

1.03

SUBMITTALS A. Submit the following in accordance with the requirements specified under "Submittals" in Section 16010. 1. 2. Product Data for each type of product specified. Samples of those products indicated for sample submission in Engineer's comments on product data submittal. Include color and finish samples of device plates and other items per Engineer's request.

1.04

SEQUENCE AND SCHEDULING A. Schedule installation of finish plates after the surface upon which they are installed has received final finish.

PART 2 - PRODUCTS 2.01 MANUFACTURERS _____________________________________________________________________________________ Division 16 Electrical Works Page 16-30

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

2.02

Crabtree MK Legrand (Pass and Seymour) Ticcino Living Or approved equal. MATERIALS AND EQUIPMENT A. Provide wiring devices, in types, characteristics, grades, colors, and electrical ratings for applications indicated which are UL listed and which comply with NEMA WD1 and other applicable UL and NEMA standards. Provide brown color devices except as otherwise indicated. Verify color selections with Engineer. All switches and receptacles shall accomodate wire size 4 mm2. B. Receptacles 1. C. Receptacles shall be grounding type, with ratings and configurations shown on the drawings.

Wall Lighting Switches 1. Specification grade, 10 amperes, 250 volts AC, enclosed quiet operating mechanism.

D.

Wall Plates: Single and combination, of types, sizes and with ganging and cutouts as indicated. Provide plates which mate and math with wiring devices to which attached. Provide metal screws for securing plates to devices with screw heads colored to match finish of plates. Provide wall plates with engraved legend where indicated. Conform to requirements of Section 16195 "Electrical Identification." Provide plates possessing the following additional construction features: Lighting Switch Assemblies - (LS): Switches shall be similar to wall switches mounted but with common Face Plate. Switches shall be 250 volt ac 10 A rated with number of gangs as indicated on the Drawings. Switches shall be fully rated for tungesten filament and fluorescent lamp loads, and up to 80% of rated capacity for motor loads.

E.

PART 3 - EXECUTION 3.01 EXAMINATION A. Examine conditions at the job site where work of this Section is to be performed to insure proper arrangement and fit of the work. Start of work implies acceptance of job site

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-31

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr conditions.

3.02

PREPARATION A. B. Examine the Contract Drawings and specifications in order to insure the completeness of the work required under this Section. Verify measurements and dimensions at the job site and cooperate in the coordination and scheduling of the work of this Section with the work of related trades, so as not to delay job progress. Provide templates as required to related for location of items.

C. 3.02

INSTALLATION A. B. C. D. E. F. G. H. Install wiring devices and accessories as indicated, in accordance with manufacturer's written instructions, and requirements of applicable electrical code. Coordinate with other work, including painting, electrical boxes and wiring installations, as necessary to interface installation or wiring devices with other work. Install wiring devices only in electrical boxes which are clean; free from building materials, dirt, and debris. Install galvanized steel wall plates in unfinished spaces. Install wiring devices after wiring work is completed. Install wall plates after painting work is completed. Install telephone/power service poles in accordance with final furnishings arrangement plan, plumb, true, and secure. Tighten connectors and terminals, including screws and bolts, in accordance with equipment manufacturer's published torque tightening values for wiring devices. Where manufacturer's torquing requirements are not indicated, tighten connectors and terminals to comply with tightening torques specified in UL Standard 486A. Use properly scaled torque indicating hand tool. Wall Switches 1. 2. 3. J. Locate switches near doors at the strike side of doors. Switch the ungrounded wires of circuits. Mount switches with the long dimension vertical and the operating handle in upward position when in the "ON" position.

I.

Wall Mounted Receptacles: Unless otherwise indicated, mount wall mounted receptacles vertically, with "U" ground slot in the upper position . Where indicated to be mounted horizontally, mount receptacles with the neutral slot in the upper position.

3.04

PROTECTION

A. Protect installed components from damage. Replace damaged items prior to final _____________________________________________________________________________________ Division 16 Electrical Works Page 16-32

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr acceptance. END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-33

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16145 ELECTRICAL CONNECTIONS FOR EQUIPMENT PART 1 - GENERAL 1.01 SUMMARY A. Provide labor, materials, equipment and services, and perform operations required for installation of electrical connections for equipment and related work as indicated on the drawings and specified herein. Work Included: The work shall include, but not be limited to, the following: 1. 2. Electrical connections used for providing electrical power to equipment. Applications of electrical power connections specified in this Section include but are not limited to the following: a. b. c. d. e. f. C. To resistive heaters. From electrical source to motor starters. Frorm motor starters to motors. To lighting fixtures. To motor starters and controllers. To wiring devices.

B.

Related Work Specified Elsewhere 1. 2. 3. 4. 5. 6. 7. Basic Electrical Requirements - Section 16010 Basic Electrical Materials and Methods - Section 16050, Raceways - Section 16110. Wire and Cable (600 Volts and Below) - Section 16120. Electrical Identification - Section 16195. Electrical Tests - Section 16950. Refer to sections of other Divisions for specific individual equipment power requirements.

1.02

QUALITY ASSURANCE

A. Materials and equipment shall conform to the latest edition of reference specifications _____________________________________________________________________________________ Division 16 Electrical Works Page 16-34

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr specified herein and to applicable codes and requirements of local authorities having jurisdiction. 1. Code Compliance: Comply with applicable requirements of applicable electrical code as to type products used and installation of electrical power connections (terminals and splices), for junction boxes, motor starters, and disconnect switches.

B.

Manufacturers: Firms regularly engaged in manufacture of electrical connectors and terminals, of types and ratings required, and ancillary connection materials, including electrical insulating tape, soldering fluxes, and cable ties, whose products have been in satisfactory use in similar service for not less than 5 years.

1.03

SUBMITTALS A. Submit the following in accordance with the requirements specified under "Submittals" in Section 16010. 1. Product Data: Submit manufacturer's data on electrical connections for equipment products and materials.

PART 2 - PRODUCTS 2.01 MATERIALS AND COMPONENTS A. For each electrical connection indicated, provide assembly of materials, including but not necessarily limited to, pressure connectors, terminals (lugs), electrical insulating tape, electrical solder, electrical soldering flux, heat-shrinkable insulating tubing, cable ties, solderless wire-nuts and other items and accessories as needed to make splices and terminations of types indicated. Metal Conduit, Tubing and Fittings: Conform to Section 16110. Wires, Cables and Connectors 1. 2. Provide wires, cables, and connectors complying with Section 16050 "Basic heatshrinkable insulating and Methods", and Section 16120 "Wire and Cable". Electrical Connection Accessories: Provide electrical insulating tape, heatshrinkable insulating tubing and boots, electrical solder, electrical soldering flux, wirenuts and cable ties as recommended for use by accessories manufacturers for type services indicated.

B. C.

PART 3 - EXECUTION 3.01 EXAMINATION A.

Examine conditions at the job site where work of this Section is to be performed to insure proper arrangement and fit of the work. Start of work implies acceptance of job site conditions. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-35

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

3.02

PREPARATION A. B. Examine the Contract Drawings and specifications in order to insure the completeness of the work required under this Section. Verify measurements and dimensions at the job site and cooperate in the coordination and scheduling of the work of this Section with the work of related trades, so as not to delay job progress. Provide templates as required to related trade for location of items.

C. 3.03

INSTALLATION A. Install electrical connections as indicated; in accordance with equipment manufacturer's written instructions and with recognized industry practices, and complying with applicable requirements of UL and applicable electrical code, to ensure that products fulfill requirements. Coordinate with other work, including wires/cables, raceway and equipment installation, as necessary to properly interface installation of electrical connections for equipment with other work. Connect electrical power supply conductors to equipment conductors in accordance with equipment manufacturer's written instructions and wiring diagrams. Mate and match conductors of electrical connections for proper interface between electrical power supplies, and installed equipment. Cover splices with electrical insulating material equivalent to, or of greater insulation resistivity rating, than electrical insulation rating of those conductors being spliced. Prepare cables and wires, by cutting and stripping covering armor, jacket, and insulation properly to ensure uniform and neat appearance where cables and wires are terminated. Exercise care to avoid cutting through tapes which will remain on conductors. Also avoid "ringing' copper conductors while skinning wire. Trim cables and wires as short as practicable and arrange routing to facilitate inspection, testing and maintenance. Wiring to fire pump controllers and pumps, excluding the electrical switchgear and pump rooms, shall be enclosed in rigid steel conduit encased by 2 inches of concrete or shall utilize mineral insulated cable, type MI with a 2 hour fire resistive rating. Tighten connectors and terminals, including screws and bolts, in accordance with equipment manufacturers published torque tightening values for equipment connectors. Accomplish tightening by utilizing proper torquing tools, including torque screwdriver, beam-type torque wrench, and ratchet wrench with adjustable torque settings. Where manufacturer's torquing requirements are not available, tighten connectors and terminals to comply with torquing values contained in UL's 485A.

B.

C.

D. E.

F. G.

H.

3.04

FIELD QUALITY CONTROL A.

Upon completion of installation of electrical connections, and after circuitry has been energized with rated power source, test connections to demonstrate capability and _____________________________________________________________________________________ Division 16 Electrical Works Page 16-36

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr compliance with requirements. Ensure that direction of rotation of each motor fulfills requirement. Correct malfunctioning units at site, then retest to demonstrate compliance. END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-37

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16170 CIRCUIT AND MOTOR DISCONNECTS PART 1 - GENERAL 1.01 SUMMARY A. Provide labor, materials, equipment and services, and perform operations required for installation of circuit and motor disconnects and related work as indicated on the drawings and specified herein. Work Included: The work shall include, but not be limited to, the following: 1. C. Circuit and motor disconnects.

B.

Related Work Specified Elsewhere 1. 2. 3. 4. Basic Electrical Requirements - Section 16010 Basic Electrical Materials and Methods - section 16050 Electrical Identification - Section 16195 Electrical Tests - Section 16950.

1.02

QUALITY ASSURANCE A. Materials and equipment shall conform to the latest edition of reference specifications specified herein and to applicable codes and requirements of local authorities having jurisdiction. 1. Electrical Components Standards: Provide components complying with the applicable electrical code and which are listed and labeled by UL. Comply with UL Standard 98 and NEMA Standard KS 1.

1.03

SUBMITTALS A. Submit the following in accordance with the requirements specified under "Submittals" in Section 16010. 1. 2. Product data for each type of products specified. Maintenance data for circuit and motor disconnects, for inclusion Operation and Maintenance Manual specified in Section 16010 "Basic Electrical Requirements."

PART 2 - PRODUCTS 2.01 MATERIALS AND EQUIPMENT _____________________________________________________________________________________ Division 16 Electrical Works Page 16-38

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

A.

Provide circuit and motor disconnects in types, sizes, duties, features, ratings and enclosures as indicated. Provide NEMA 1 enclosure except for outdoor disconnects and other indicated locations provide NEMA 3R, enclosure with raintight hubs. For motor and motor starter disconnects, provide units with horsepower rating suitable to the loads. 1. Provide external operating handle with position indication, interlocked with enclosure cover to prevent opening cover unless disconnect is in the "OFF" position. Interlock to be defeatable for maintenance purposes. Provision for locking handle in the "OPEN" position only shall be made. Provide arc quenching devices on each pole for switches rated above 240 volts.

B. C. D.

Non-Fusible Disconnects: Heavy duty switches of classes and current ratings as indicated. Double-Throw Switches: Heavy duty switches of classes and current ratings as indicated. Circuit Breaker Disconnect: Thermal-magnetic, molded case type, trip-free, with each pole containing thermal inverse time delay and magnetic instantaneous overcurrent trip elements and interchangeable trip units for 225 ampere frame size and larger. Electrical Interlocks: Provide number and arrangement of interlock contacts in disconnects as indicated. Special Enclosure Material: Provide number and arrangement of interlock contacts in disconnects as indicated. 1. 2. 3. Stainless Steel Type 304. Molded fiberglass reinforced plastic. Heavy cast aluminum.

E. F.

PART 3 - EXECUTION 3.01 EXAMINATION A. Examine conditions at the job site where work of this Section is to be performed to insure proper arrangement and fit of the work. Start of work implies acceptance of job site conditions.

3.02

PREPARATION A. B. Examine the Contract Drawings and specifications in order to insure the completeness of the work required under this Section. Verify measurements and dimensions at the job site and cooperate in the coordination and scheduling of the work of this Section with the work of related trades, so as not to delay job progress. Provide templates as required to related trade for location of items.

C. 3.03

INSTALLATION A.

Provide circuit and motor disconnect switches as indicated and where required by the applicable electrical code. Comply with switch manufacturer's printed installation _____________________________________________________________________________________ Division 16 Electrical Works Page 16-39

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr instructions.

3.04

FIELD QUALITY CONTROL A. Prior to energizing disconnects perform tests as specified in Section 16950. END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-40

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16190 SUPPORTING DEVICES PART 1 - GENERAL 1.01 SUMMARY A. Provide labor, materials, equipment and services, and perform operations required for installation of supporting devices and related work as indicated on the drawings and specified herein. Work Included: The work shall include, but not be limited to, the following: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. C. Clevis hangers. Riser clamps. C-clamps. I-beam clamps. One-hole conduit straps. Two-hole conduit straps. Round steel rods. Lead expansion anchors. Toggle bolts. Wall and floor seals.

B.

Related Work Specified Elsewhere 1. 2. 3. Basic Electrical Requirements - Section 16010 Basic Electrical Materials and Methods - Section 16050 Supports, anchors, sleeves and seals furnished as part of factory-fabricated equipment, are specified as part of that equipment assembly in other Division 16 sections.

1.02

QUALITY ASSURANCE A. Materials and equipment shall conform to the latest edition of reference specifications specified herein and to applicable codes and requirements of local authorities having jurisdiction. 1. 2. Code Compliance: Comply with applicable electrical code requirements as applicable to construction and installation of electrical supporting devices. FS Compliance: Comply with Federal Specification FF-S-760 pertaining to retaining straps for conduit, pipe and cable.

1.03

SUBMITTALS

A. Submit the following in accordance with the requirements specified under "Submittals" in _____________________________________________________________________________________ Division 16 Electrical Works Page 16-41

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Section 16010. 1. Product Data: Submit manufacturer's data on supporting devices including catalog cuts, specifications, and installation instructions, for each type of support, anchor, sleeve and seal. Shop Drawings: Submit dimensioned drawings of fabricated products, indicating details of fabrication and materials.

2. PART 2 - PRODUCTS 2.01 MATERIALS A.

Manufactured Supporting Devices 1. Provide supporting devices which comply with manufacturer's standard materials, design and construction in accordance with published product information, as herein specified and as required for installation. Supports: Provide supporting devices of types, sizes and materials as required, and having the following construction features: a. Clevis Hangers: For supporting 2" rigid metal conduit; galvanized steel; with 1/2" diameter hole for round steel rod; approximately 54 pounds per 100 units. b. Riser Clamps: For supporting 5" rigid metal conduit; black steel; with 2 bolts and nuts, and 4" ears; approximately 510 pounds per 100 units. c. Reducing Couplings: Steel rod reducing coupling, 1/2" by 5/8"; black steel; approximately 16 pounds per 100 units. d. C-Clamps; Black malleable iron; 1/2" rod size; approximately 70 pounds per 100 units. e. I-Beam Clamps: Black steel, 1-1/4" by 3/16" stock; 3/8" cross bolt; flange width 2", approximately 52 pounds per 100 units. f. One-Hole Conduit Straps: For supporting 3/4" rigid metal conduit; galvanized steel; approximately 7 pounds per 100 units.

2.

g. Two-Hole Conduit Straps: For supporting 3/4" rigid metal conduit; galvanized steel; 3/4" strap width; and 2-1/8" between center of screw holes. h. Hexagon Nuts: per 100 units. i. j. 3. For 1/2" rod size; galvanized steel, approximately 4 pounds

Round Steel Rod: Black steel; 1/2" diameter; approximately 67 pounds per 100 feet. Offset Conduit Clamps: For supporting 2" rigid metal conduit; black steel; approximately 200 pounds per 100 units.

Anchors: Provide anchors of types, sizes and materials indicated, with the following construction features:

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-42

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr a. b. Lead Expansion Anchors: 1/2"; approximately 38 pounds per 100 units. Toggle Bolts: Springhead; 3/6" by 4"; approximately 5 pounds per 100 units.

4.

Sleeves and Seals: Provide sleeves and seals, of types, sizes and materials as required with the following construction features: a. Wall and Floor Seals: Provide factory-assembled watertight wall and floor seals, of types and sizes indicated; suitable for sealing around conduit, pipe or tubing passing through concrete floors and walls. Construct seals with steel sleeves, malleable iron body, neoprene sealing grommets and rings, metal pressure rings, pressure clamps and cap screws. Provide smoke and fire stop fittings to maintain five ratings as specified in Section 16050.

5.

Conduit Cable Supports: Provide cable supports with insulating wedging plug for nonarmored type electrical cables in risers; construct for 2" rigid metal conduit; 3-wires, type wire as indicated; construct body of malleable-iron casting with hot dip galvanized finish. U-Channel Strut Systems: Provide U-channel strut system for supporting electrical equipment, 12-gauge hot dip galvanized steel, of types and sizes indicated; construct with 9/16" diameter holes, 8" o.c. on top surface, with standard green finish. Provide the following fittings which mate and match with U-channel: a. b. c. d. e. f. g. h. i. Fixture hangers. Channel hangers. End caps. Beam clamps. Wiring studs. Thinwall conduit clamps. Rigid conduit clamps. Conduit hangers. U-bolts.

6.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-43

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

2.02

FABRICATION A. Fabricated Supporting Devices 1. Pipe Sleeves: Provide pipe sleeves of one of the following: a. Sheet Metal: Fabricate from galvanized sheet metal; round tube closed with snaplock joint, welded spiral seams, or welded longitudinal joint. Fabricate sleeves from the following gauge metal: 3" and smaller, 2--gauge; 4 to 16gauge; over 6", 14-gauge. b. Steel Pipe: Fabricate from Schedule 40 galvanized steel pipe; remove burrs. c. Iron Pipe: Fabricate from cast-iron or ductile-iron pipe; remove burrs. d. Plastic Pipe: Fabricate from Schedule 80 PVC plastic pipe; remove burrs. 2. Sleeve Seals: Provide sleeves for piping which penetrates foundation walls below grade, or exterior walls as specified in Section 16050.

PART 3 - EXECUTION 3.01 EXAMINATION A. Examine conditions at the job site where work of this Section is to be performed to insure proper arrangement and fit of the work. Start of work implies acceptance of job site conditions. Provide templates as required to related for location of items.

C. 3.02

PREPARATION A. B. Examine the Contract Drawings and specifications in order to insure the completeness of the work required under this Section. Verify measurements and dimensions at the job site and cooperate in the coordination and scheduling of the work of this Section with the work of related trades, so as not to delay job progress.

3.03

INSTALLATION A. Install hangers, anchors, sleeves and seals as indicated; in accordance with manufacture's written instructions and with recognized industry practices to ensure supporting devices comply with requirements. Coordinate with other electrical work, including raceway and wiring work, as necessary to interface installation of supporting devices with other work. Install hangers, support, clamps and attachments to support raceway and electrical equipment properly from building structure. Arrange for grouping of parallel runs of horizontal conduits to be supported together on trapeze type hangers where possible. Install supports with spacing indicated and in compliance with applicable electrical code requirements.

B. C.

Torque sleeve seal nuts, complying with manufacturer's recommended values. Ensure that sealing grommets expand to form watertight seal. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-44

D.

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-45

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16195 ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.01 SUMMARY A. Provide labor, materials, equipment and services, and perform operations required for installation of electrical identification and related work as indicated on the drawings and specified herein. Work Included: The work shall include, but not be limited to, the following: 1. 2. 3. 4. 5. C. Electrical power, control and communication conductors. Operational instruction and warnings. Danger signs. Equipment/system identification signs and painting. Manhole covers.

B.

Related Work Specified Elsewhere 1. 2. Basic Electrical Requirements - Section 16010 Basic Electrical Materials and Methods - Section 16050.

1.02

QUALITY ASSURANCE A. Materials and equipment shall conform to the latest edition of reference specifications specified herein and to applicable codes and requirements of local authorities having jurisdiction. 1. Code Compliance: Comply with applicable electrical code requirements to installation of identifying labels and markers for wiring and equipment.

1.03

SUBMITTALS A. Submit the following in accordance with the requirements specified under "Submittals" in Section 16010. 1. 2. Product Data: Submit manufacturer's data on electrical identification materials and products. Samples: Submit samples of each color, lettering style and other graphic representation required for each identification material or system.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-46

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

PART 2 - PRODUCTS 2.01 MATERIALS A. Except as otherwise indicated, provide manufacturer's standard products of categories and types required for each application. Where more than single type is specified for an application, provide single selection for each application. Color-Coded Conduit Markers 1. Provide manufacturer's standard pre-printed, flexible or semi-rigid, permanent, plastic-sheet conduit markers, extending 360 degrees around conduits; designed for attachment to conduit by adhesive, adhesive lap joint of marker, matching adhesive plastic tape at each end of marker, or pretensioned snap-on. Colors: Unless otherwise specified or required by governing regulations, provide white markers with red letters.

B.

2. C.

Cable Conductor Identification Bands: Provide manufacturer's standard vinyl-cloth selfadhesive cable/conductor markers of wrap-around type, either prenumbered plastic coated type, or write-on type with clear plastic self-adhesive cover flap; numbered to show circuit identification. Engraved Plastic-Laminate Signs: Provide engraving stock melamine plastic laminate, complying with FS L-P-387, in size and thicknesses indicated, engraved with engraver's standard letter style of sizes and wording indicated, black face and white core plies (letter color) except as otherwise indicated, punched for mechanical fastening except where adhesive mounting is necessary because of substrate. 1. 2. Thickness: 1/6 inch, except as otherwise indicated. Fasteners: Self-tapping stainless steel screws, except contact-type permanent adhesive where screws cannot or should not penetrate substrate.

D.

PART 3 - EXECUTION E. Lettering and Graphics: Coordinate names, abbreviations and other designations used in electrical identification work, with corresponding designations shown, specified or scheduled. Provide numbers, lettering and wording as indicated or, if not otherwise indicated, as recommended by manufacturer or as required for proper identification and operation/maintenance of electrical systems and equipment. Comply with ANSI A13.1 pertaining to minimum sizes for letters and numbers.

3.01

EXAMINATION A. Examine conditions at the job site where work of this Section is to be performed to insure proper arrangement and fit of the work. Start of work implies acceptance of job site conditions.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-47

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

3.02

PREPARATION A. B. Examine the Contract Drawings and specifications in order to insure the completeness of the work required under this Section. Verify measurements and dimensions at the job site and cooperate in the coordination and scheduling of the work of this Section with the work of related trades, so as not to delay job progress.

3.03

APPLICATION AND INSTALLATION A. General Installation Requirements 1. Install electrical identification products as indicated, in accordance with manufacturer's written instruction, and requirements of the applicable electrical code. Coordination: Where identification is to be applied to surfaces which require finish, install identification after completion of painting. Regulations: Comply with governing regulations and requests of governing authorities for identification of electrical work.

2. 3. B.

Conduit Identification: Where electrical conduit is installed in spaces with mechanical piping which is identified by color-coded method, apply color-coded identification on electrical conduit in manner similar to piping identification. Except as otherwise specified, use white as coded color for conduit. Equipment/System Identification 1. Install engraved plastic-laminate signs on each major unit of electrical equipment in building; including central or master unit of each electrical system including communication/control/signal system, unless unit is specified with its own selfexplanatory identification or signal system. Except as otherwise indicated, provide single line of text, 1/2" high lettering on 1-1/2" high sign (2" high where 2 lines are required), white lettering in black field. Provide text matching terminology and numbering of the contract documents and shop drawings. Provide signs for each unit of the following categories of electrical work. a. b. 2. Panelboards, electrical cabinets and enclosures Access panel/doors to electrical facilities.

C.

Install signs at locations indicated or specified. Where not otherwise indicated at location for convenience of viewing without interference with operation and maintenance of equipment. Secure to substrate with fasteners, except use adhesive where fasteners should not or cannot penetrate substrate. Plates for receptacles on emergency circuits shall be painted red. Receptacles on emergency circuits shall have nameplates with white letters on red background giving the panelboard and circuit number to which it is connected..

3. 4.

5. Provide a nameplate with 1/4 inch white letters on black background, mounted on _____________________________________________________________________________________ Division 16 Electrical Works Page 16-48

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr outside of panelboard trims with nomenclature as indicated on drawings. 6. Provide a nameplate with 1/4 inch white letters on black background, mounted on the outside of local disconnects, starters, control devices, pushbuttons, selector switches and pilot lights identifying the equipment served and/or their function. Provide a red dot self-adhesive identification affixed to the visible trim of lighting fixtures connected to emergency circuits. Provide a typed directory card inserted behind a clear plastic covering within a frame on the inside face of panelboard door identifying circuit utilizations and locations and wire and cable color coding for each voltage system. END OF SECTION

7. 8.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-49

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16425 LOW VOLTAGE SWITCHBOARD PART 1 - GENERAL 1.01 SUMMARY A. Provide labor, materials, equipment and services, and perform operations required for installation of low voltage switchboards and related work as indicated on the drawings and specified herein. Work Included: The work shall include, but not be limited to, the following: 1. 2. Indoor low voltage switchboards. Switchboard components shall be coordinated and include, but not be limited to, the following: a. b. c. C. Transition sections as required. Secondary switchboard section. Accessories.

B.

Related Work Specified Elsewhere 1. 2. 3. 4. Basic Electrical Requirements - Section 16010. Basic Electrical Materials and Methods - Section 16050. Electrical Identification - Section 16195. Electrical Testing - Section 16950.

1.02

QUALITY ASSURANCE A. Materials and equipment shall conform to the latest edition of reference specifications specified herein and to applicable codes and requirements of local authorities having jurisdiction. 1. Codes and Standards a. B. Code Compliance: Comply with requirements of the applicable electrical code.

Factory Testing and Inspection: The manufacturer shall thoroughly test the assembled switchboard for proper functioning and compliance with the specifications. Submit certification to the Engineer that this testing has been completed and that the function and compliance conform to the specifications.

1.03

SUBMITTALS

A. Submit the following in accordance with submittal requirements specified in Section _____________________________________________________________________________________ Division 16 Electrical Works Page 16-50

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr 16010. 1. Product Data: Submit manufacturer's technical product data on low voltage switchboards. Application data to include, but not be limited to, the following: a. b. c. d. e. f. g. h. i. j. k. 2. Voltage. Phase. Frequency. Horizontal bus capacity. Vertical bus capacity. Short-circuit ratings. Main and branch circuit rating and types. Metering. Types of wiring. Enclosures. Sections. Submit layout drawings including, but not limited to, the

Shop Drawings: following: a.

Outline and arrangement drawings showing overall dimensions of the switchboard assembly, front views, floor plan, side views, shipping sections, weights of each shipping section, recommended clearances to the front, rear, sides and top. Certified dimensional drawings of the switchboard showing mounting or anchor bolts required, space available at top and bottom of the switchboard for feeder conduit and cable. A single line diagram showing main bus, disconnect circuit breakers and/or switches, current and potential transformers, meters, instruments, relays, control and selector switches, pilot lights, etc. Connection and elementary diagrams for switchboard components. Differentiate between portions of wiring that are manufacturer installed and portions that are field installed. Bill of Material.

b.

c.

d.

e. 3.

Maintenance Data: Submit maintenance data and parts list for each switchboard including a "troubleshooting" maintenance guide. Include that data, product data, and shop drawings in a maintenance manual. Instruction manuals with equipment data having sufficient detail for setting relays, timers, and breakers and time-current curves for breaker and fuses.

4.

1.04

DELIVERY, STORAGE AND HANDLING A. B. Handle switchboard equipment carefully to prevent damage, breaking, and scoring. Do not install damaged sections or components; replace with new.

Store switchboard equipment in a clean, dry place. Protect from weather, dirt, fumes, water, construction debris, and physical damage. Assume responsibility and security for materials and equipment. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-51

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

C. D. E. 1.05

Comply with manufacturer's rigging and moving instructions for unloading switchboard components and transporting them to final location for installation. Coordinate and schedule delivery of equipment which permits, ready building ingress for large equipment components to their designated installation spaces. Each packing crate and carton shall be visibly marked to identify contents.

SHORT CIRCUIT AND COORDINATION STUDY A. The low voltage switchboard manufacturer shall submit a fault current and coordination study encompassing but not limited to the following: 1. Short circuit study to determine the duties on the systems. The study shall tabulate the duties at ratings of distribution and protective devices down to the branch circuit level. System protective device coordination study starting with the electric service company protective devices and downstream including feeders, mains and branch circuit protective devices. Submit a set of coordination curves. Motor starting voltage profiles for large motors.

2.

3. PART 2 - PRODUCTS 2.01

MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide switchboard of one of the following: 1. 2. 3. 4. 5. 6. ABB General Electric Merlin Gerin Square D Company Westinghouse Local Firms having an experience of twenty years minimum in manufacturing and assembling of switchboards shall be accepted if approved by the Engineer.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-52

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

2.02

MATERIALS AND EQUIPMENT A. Low Voltage Switchboard and Components 1. a. General Provide low voltage switchboard, disconnects and ancillary components of sizes, ratings, classes, types, and characteristics indicated; which comply with manufacturer's standard design, materials, components, and construction in accordance with published product information, as required for installation and as specified herein. Dimensions shall not exceed those shown on drawings. Switchboards and buswork shall be constructed to permit future expansion. Where spaces for future disconnects are indicated, compartments shall be equipped with current carrying parts and covers ready to receive future disconnects. Provide pulling eyes, jacking facilities and lifting lugs on each to facilitate setting, lifting and skidding into place. Nameplates: Provide in accordance with Section 16195. Where switchboards are utilized for service entrance equipment, construction shall comply with service entrance requirements including but not limited to. 1. 2. 3. 4. Provide bonding jumpers between the enclosure, ground and neutral busses. Neutral disconnect link. Isolating barries between service entrance main disconnect, buswork, terminals and compartments from the remainder of the switchboard. Comply with the requirements of the Electric Service Company.Provide buswork and metering instrumentation (provisions) as required by the Electric Service Company. shipping section

b. c. d. e. f. g.

2.

Enclosure a. b. Switchboards shall be dead front, totally metal enclosed, of indoor construction. Enclosure shall be fabricated of minimum 12 gauge steel, formed and framed for rigidity, self-supporting with the required number of vertical sections bolted together. Sides, top and rear covers shall be fabricated of code gauge steel, bolted to the framework. Vertical wiring gutters shall have hinged or removable bolted covers. Housing shall be throughly cleaned and degreased after fabrication, bonderized and primed with zinc chromate. Finish shall be two coats of grey enamel, for indoor units.

c.

3. Buswork _____________________________________________________________________________________ Division 16 Electrical Works Page 16-53

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

a. b.

Buswork shall be 3-phase, 4-wire fabricated of copper plated at joints and connection points. Bolted connections shall be provided with Belleville Washers. Main buswork shall have full capacity throughout the entire length of the switchboard. Vertical buswork shall be equal in size to the sum of the frame sizes in the vertical section including spares and spaces with a maximum size equal to that of the main bus. Bus extensions to feeder disconnects and from the load side of the disconnect to the cable compartment shall be equal to the frame size of the disconnect. Provide an A-B-C type of bus arrangement, left to right, top to bottom, front to back, throughout as viewed from the front of the switchboard. Minimum rating shall equal the frame or switch size of the main disconnect. Buswork shall be braced and supported to safely withstand short circuit stresses equal to the full available fault currents at the switchboard. Provide two-hole long barrel compression cable connectors for cables as indicated per phase, neutral and ground. In addition, provide two hole long barrel mechanical clamp type cable connectors, adjustable between 95 mm2 - 240 mm2 at each end of the ground bus. Neutral bus shall be rated 100 percent of the phase busses and be continuous for the entire length of the switchboard. Ground bus shall be continuous for the entire length of the switchboard.

c. d. e. f.

g. h. 4.

Instrumentation a. b. An isolated metering compartment shall be located above the main disconnect. Provide within the meetering compartment or an auxiliary compartment, three volt metering potential transformers, one single phase control power transformer, connected on the line side of the main breaker, protected by current limiting fuses. Provide on the main bus three metering window type current transformers. Mounted on the hinged door of the metering compartment shall be the following instrumentation. 1) 2) 3) e. Indicating ammeter and ammeter switch. Indicating voltmeter and voltmeter switch. Kilowatt hour demand meter with built-in test switch assembly.

c. d.

Indicating ammeters and voltmeters shall be of the switchboard type for semi-flush mounting, approximately 4-1/2 inches square with 250 degree scale. Instruments shall be accurate to within 1 percent and shall be magnetically shielded. Ammeter and voltmeter selector switches shall be of the rotary type. Ammeter switches shall permit reading three line currents and include an "off" position. Voltmeter selector switches shall permit reading line-to-line and line-to-neutral voltages and include an "off" position.

f.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-54

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr g. Kilowatt-hour demand meter shall be of the semi-flush mounting, with a 15 minute maximum demand register. Meters shall be of the two-element type and shall display C/T and P/T ratios, and the meter constant. Furnish test plug (s) as required for testing kilowatt hour meter.

B.

Switchboard shall be of front accessible construction with main and branch feeder disconnects and spaces for future disconnect group mounted and with instrumentation as shown on the drawings and as specified. 1. 2. 3. Vertical sections shall be rear aligned. Disconnects shall be as shown on the drawings and specified with necessary interconnections, and control wiring terminated at terminal blocks. Disconnects shall be as follows: a. b. 4. Main Disconnect : Power Insulated case circuit breaker. Molded case circuit breaker

Branch Feeder Disconnects:

Switchboard and disconnects shall be selected on a fully rated basis. Short circuit rating shall be determined.

C.

Insulated Case Circuit Breaker Disconnect: Factory assembled insulated case circuit breaker, fixed mounted, electrically operated, stored energy operating mechanism, position indicator, of frame sizes, characteristics and rating including RMS symmetrical interrupting ratings shown on drawings and as specified. 1. Circuit breaker shall have integral solid state self powered overcurrent trip devices and current sensors providing adjustable long time pickup and delay, short time pickup and delay, adjustable instantaneous, and integral zone selective coordinated ground fault protection. Target indicators shall indicate overload, short circuit and ground fault modes General Electric "Power Break" with "Microversatrip 9" or approved equal.

2. D.

Molded-Case Circuit-Breaker Disconnects 1. Factory-assembled, molded-case circuit-breakers of frame sizes, characteristics, and ratings including RMS symmetrical interrupting ratings indicated. Select breakers with permanent thermal and instantaneous magnetic trip, ampere ratings as indicated. Construct with overcenter, trip-free, toggle-type operating mechanisms with quick-make, quick-break action and positive handle trip indication. Construct breakers for mounting and operating in any physical position, and operating in an ambient temperature of 40 C. Provide breakers with mechanical screw type removable connector lugs, AL/CU rated. Circuit-breakers shall have interchangeable trip units for sizes 225 ampere frame and larger. Circuit-breakers shall be individually bolt mounted. Multi-pole circuit-breakers shall be of the common trip type and not be single pole units with handle ties. Cable lugs shall be suitable for 70 C wire.

2.

E.

Circuit-Breaker-Current Limiting Disconnect: Thermal magnetic molded case type, noninterchangeable trip, unfused with interrupting rating of 200,000 amperes RMS symmetrical at 240 volts and 150,000 amperes at 480 volts. General Electric THL series or TEL/TFL current limiting

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-55

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

or approved equal. Cable lugs shall be suitable for 70 C wire. F. Accessories: The following accessories shall be furnished with each switchboard: 1. 2. 3. 4. 5. Two (2) sets of spare indicating lamps. One (1) quart of touchup paint. Portable test kit for testing and calibration of the static logic circuits and the current sensing circuits. One set of special wrenches, removable hand cranks, tools as required to maintain and disassemble parts of the switchgear for field maintenance. Three (3) sets of spare control or instrumentation circuit fuses of each type and size.

PART 3 - EXECUTION 3.01 EXAMINATION A. Examine conditions at the job site where work of this Section is to be performed to insure proper arrangement and fit of the work. Start of work implies acceptance of job site conditions.

3.02

PREPARATION A. B. Examine the Contract Drawings and specifications in order to insure the completeness of the work required under this Section. Verify measurements and dimensions at the job site and cooperate in the coordination and scheduling of the work of this Section with the work of related trades, so as not to delay job progress. Provide templates as required to related trade for location of items.

C.

3.03

INSTALLATION A. Install switchboard as indicated, in accordance with equipment manufacturer's written instructions, and with recognized industry practices. Bolt the switchboard to a steel channel frame set flush with the finished floor or housekeeping pad. Design and placement of the frame shall be in accordance with the approved manufacturer's drawing and instructions. Set, adjust and calibrate protective devices in accordance with the approved coordinated study. Tighten connectors and terminals, including screws and bolts, in accordance with equipment manufacturer's published torque tightening values for equipment connectors. Where manufacturer's torquing requirements are not indicated, tighten connectors and terminals to comply with tightening torques specified in UL Std. 486A and B.

B. C.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-56

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Grounding: Provide equipment grounding connections for the switchboard as indicated and as specified in Section 16450 "Grounding." Tighten connections to comply with tightening torques specified in UL Std 486A to assure permanent and effective grounds.

D.

3.04

FIELD QUALITY CONTROL A. Prior to energization of switchboards and circuitry, perform tests as specified in Section 1690 "Electrical Tests." If the testing should indicate failure to meet to the requirements of the specifications, the manufacturer shall provide additions, modifications or replacements necessary to provide the Employer with a unit which fully conforms to the specifications. Repair work shall be scheduled at a time convenient to the facility being served.

3.05

ADJUSTING AND CLEANING A. Adjust operating mechanisms for free mechanical movement. Touchup scratched or marred surfaces to match original finishes. END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-57

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16450 GROUNDING PART 1 - GENERAL 1.01 SUMMARY A. Provide labor, materials, equipment and services, and perform operations required for installation of grounding and related work as indicated on the drawings and specified herein. Work Included: The work shall include, but not be limited to, the following: 1. Grounding and bonding to encompass systems, circuits and equipment Applications of electrical grounding and bonding work includes: a. b. c. C. Ground sources. Systems grounds Equipment grounds.

B.

Related Work Specified Elsewhere 1. 2. 3. Basic Electrical Requirements - Section 16010. Basic Electrical Materials and Methods - Section 16050. Electrical Tests - Section 16950.

1.02

DESCRIPTION A. Ground Source - Building Electrical System 1. The ground source for the building electrical system shall include the following: a. b. c. 2. Ground metal member of a metal structure. Incoming water service piping. Utility company ground conductors.

The building electrical system ground source shall have a maximum resistance to ground of 5 ohms. Provide additional ground conductors and/or ground rods if required to limit the ground source resistance.

B. C.

Systems Grounds: A system ground shall be provided for each separately derived system including service entrance, each voltage level, and generators. Equipment Grounds 1. 2. Non-current carrying components of the electrical system shall be grounded. The continuity of the grounding system shall be maintained throughout the electrical incoming, distribution and utilization systems.

1.03

QUALITY ASSURANCE

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-58

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Materials and equipment shall conform to the latest edition of reference specifications specified herein and to applicable codes and requirements of local authorities having jurisdiction. 1. Electrical Code Compliance: Comply with applicable electrical code requirements of the authority having jurisdiction, as applicable to electrical grounding and bonding, pertaining to systems, circuits and equipment. UL Compliance: Comply with applicable requirements of UL Standards No. 467, "Electrical Grounding and Bonding Equipment", and 869, "Electric Service Equipment", pertaining to grounding and bonding of systems, circuits and equipment. In addition, comply with UL Std 486A, "Wire Connectors and Soldering Lugs for Use With Copper Conductors". Provide grounding and bonding products which are UL-listed and labeled for their intended usage.

A.

2.

1.04

SUBMITTALS A. Submit the following in accordance with the requirements specified under "Submittals" in Section 16010. 1. Product Data: Submit manufacturer's data on grounding and bonding products and associated accessories.

PART 2 - PRODUCTS 2.01 MATERIALS AND COMPONENTS A. Except as otherwise indicated, provide electrical grounding and bonding system indicated; with assembly of materials, including, but not limited to, cables/wires, connectors, solderless lug terminals, grounding electrodes and plate electrodes, bonding jumper braid, surge arrested and additional accessories needed for installation. Where materials or components are not indicated, provide products which comply with the applicable electric code and UL requirements and with established industry standards for those applications indicated. Conductors: Unless otherwise indicate, provide electrical grounding conductors for grounding system connections that match power supply wiring materials and are sized according to the applicable electrical code, with minimum size 4 mm2. Ground conductors shall be insulated unless otherwise specified or shown on the drawings. Ground Connector - Type A: High copper alloy or bonze fitting with bolted pressure connector and silicone bronze U-bolt and nuts for connecting cable to pipe O-Z/Gedney Co. Cat. No. G-100B through G1200B with accessories. Ground Connector - Type B: High copper alloy or bronze bolted pressure connector brazed to offset steel tongue for connecting cable to steel surface. O-Z/Gedney Co. Type QGL. Ground Connector - Type C: High copper alloy or bonze bolted pressure connector with drilled tongue for connecting cable to copper bar. Burndy Copr. Type VVA. Bonding Jumper Braid: Copper braided tape, constructed of 30-gauge bare copper wires and properly sized for indicated applications.

B.

C.

D. E. F. G.

Flexible Jumper Strap: Flexible flat conductor, 480 strands of 30-gauge bare copper wire; 3/4 inch wide, 9-1/2 inches long, 48,250 CM. Select braid with holes sized for 3/8 inch _____________________________________________________________________________________ Division 16 Electrical Works Page 16-59

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr diameter bolts and protect braid with copper bolt hole ends.

H.

Bonding Plates, Connectors, Terminals and Clamps: Provide electrical bonding plates, connectors, terminals, lugs and clamps as recommended by bonding plate, connector, terminal and clamp manufacturers for indicated applications. Electrical Grounding Connection Accessories: Provide electrical insulating tape, heatshrinkable insulating tubing, welding materials, bonding straps, as recommended by accessories manufacturers for type service indicated. Field Welding: Provide welded connections where grounding conductors connect to underground grounding and plate electrodes, or where otherwise inaccessible. Welding shall utilize the exothermic process. Provide required molds, tools and cartridges and use in strict accordance with manufacturer's instructions.

I.

J.

PART 3 - EXECUTION 3.01 EXAMINATION A. Examine conditions at the job site where work of this Section is to be performed to insure proper arrangement and fit of the work. Start of work implies acceptance of job site conditions.

3.02

PREPARATION A. B. Examine the Contract Drawings and specifications in order to insure the completeness of the work required under this Section. Verify measurements and dimensions at the job site and cooperate in the coordination and scheduling of the work of this Section with the work of related trades, so ass not to delay job progress. Provide templates as required to related trade for location of items.

C.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-60

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

3.03

INSTALLATION A. General 1. Install electrical grounding and bonding systems as indicated on drawings and specified herein, in accordance with manufacturer's instructions and applicable portions of the electrical code, and in accordance with recognized industry practices to ensure that products comply with requirements. Coordinate with other wok as necessary to interface installation of electrical grounding and bonding system work with other work. Exothermic weld grounding conductors to underground grounding electrodes or where otherwise inaccessible. Repaint impaired surfaces. Apply corrosion-resistant finish to field-connections, buried metallic grounding and bonding products, and places where factory applied protective coating have been destroyed, which are subjected to corrosive action. Install clamp-on connectors on clean metal contact surfaces, to ensure electrical conductivity and circuit integrity. Silver plate copper contact surfaces joined together by bolting. Tighten grounding and bonding connectors and terminals, including screws and bolts, in accordance with manufacturer's published torque tightening values for connectors and bolts. Where manufacturer's torquing requirements are not indicated, tighten connections to comply with tightening torque values specified in UL 486A to assure permanent and effective grounding. Route grounding connections and conductors to ground and protective devices in shortest and straightest paths as possible to minimize transient voltage rises. Install exposed ground conductors to provide maximum mechanical protection utilizing ceiling corners, hung ceilings and webs of beams.

2. 3. 4.

5.

6.

7.

B.

Ground Source 1. 2. Install braided type bonding jumper with code-sized ground clamps on water meter piping to electrically bypass water meters. Connect grounding electrode conductors to 1-inch diameter, or greater, metallic cold water pipe using a suitable sized ground clamp. Provide connections to flanged piping at street side of flange. Install counterpoises which encircle the building and are connected to (each structural column) (1/2 of the structural columns) (1/3 of the structural columns) to each driven electrode and to the reinforcing bars encased in concrete. Conductors shall be bare, stranded, soft drawn copper, sized as shown on drawings.

3.

C.

Systems Grounds 1.

Ground electrical service system neutral at service entrance equipment to grounding electrodes. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-61

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

2.

Ground each separately-derived system neutral to: a. b. Effectively grounding metallic water pipe. Ground dry type transformers, in addition, to the ground conductor installed with the incoming primary conductors.

D.

Equipment Grounds 1. General a. Provide a ground conductor in conduits and other raceways. Connect the conductor from the ground bus or connector at the source to each piece of raceway and to items to which the conduits or raceways connect. Terminate feeder and branch circuit insulated equipment grounding conductors with grounding lug, bus or bushing. Provide conduit grounding bushing, bonded together and connected to the grounding electrode on incoming and outgoing conduits to distribution equipment. Use multiple bolt type connectors for bolted connections with bolts, washers an top nuts made of high copper or silicone bronze. Bond ground wires run in conduit at point where wire enters and emerges from conduit. Connect metal piping systems to the service equipment ground bus or connector with a ground conductor.

b. c.

d. e. f. 2.

Grounding of Motors a. Connect a ground conductor from the ground bus in the panel board or motor control center to a ground lug in the motor terminal box. Install the ground conductor with the motor branch circuit conductors. The rigid conduit may be used as the grounding conductor for small motors connected to lighting panels if a ground conductor is connected from a lug in he motor terminal box to the lug of a grounding type bushing installed on the rigid conduit ahead of the flexible conduit a the motor.

b.

3. 4.

Grounding of Receptacles: Connect a ground conductor from the receptacle grounding terminal too the panelboard grounds bus. Grounding of Pull Boxes: Braze a ground connector Type B in pull boxes and connect to grounding bushing on incoming and outgoing conduits with a copper conductor. Grounding of Panelboards With Ground Bus: Connect a ground conductor from grounding bushings on the incoming and outgoing feeder conduits to terminals on the conduit to terminals on the ground bus. Where a feeder ground conductor is installed, this conductor shall be connected to the ground bus.

5.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-62

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr 6. Grounding of Lighting Fixtures: Provide ground wire to fixtures fed with flexible conduit or hung from swivel hangers, concealed within the conduit or suspension hangers. Alterations (Ground System Extension): Extend existing system to include electrical work in the scope of this alteration.

7. 3.04

FIELD QUALITY CONTROL A. Upon completion of installation of electrical grounding and bonding systems, test ground resistance with ground resistance tester. Where tester. Where tests show resistant-toground is over 5 ohms, take appropriate action to reduce resistance to 5 ohms or less by driving additional ground rods; then retest to demonstrate compliance. Test the grounding systems as specified in Section 16950. END OF SECTION

B.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-63

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.01 SUMMARY A. Provide labor, materials, equipment and services, and perform operations required for installation of panelboards and related work as indicated on the drawings and specified herein. Work Included: The work shall include, but not be limited to, the following: 1. C. Lighting and appliance panelboard.

B.

Related Work Specified Elsewhere 1. 2. 3. 4. Basic Electrical Requirements - Section 16010 Basic Electrical Materials and Methods - Section 16050 Electrical Identification - Section 16195 Electrical Tests - Section 16950.

D. 1.02

Allowances: Refer to Section 01020 "Allowances" for allowances regarding the work of this Section.

QUALITY ASSURANCE A. Materials and equipment shall conform to the latest edition of reference specifications specified herein and to applicable codes and requirements of local authorities having jurisdiction. 1. Electrical Code Compliance: Comply with applicable local code requirements of the authority having jurisdiction as applicable to installation, and construction of electrical panelboards and enclosures. IEC Compliance: Comply with applicable requirements of IEC.

2. 1.03 SUBMITTALS A.

Submit the following in accordance with the requirements specified under "Submittals" in Section 16010. 1. Product Data: Submit manufacturer's data on panelboards and enclosures, including dimensions, interiors, certifications, etc.

1.04

SEQUENCING AND SCHEDULING

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-64

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Coordinate installation of panelboards and enclosures with installation of wires/cables, electrical boxes and fittings, and raceway work.

A.

PART 2 - PRODUCTS 2.01 MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide panelboard products of one of the following (for each type and rating of panelboard and enclosure): 1. 2. 3. 4. 5. 6. 2.02 ABB General Electric Company Merlin Gerin Square D Company Westinghouse Electric Corp. Local Firms having an experience of twenty years minimum in manufacturing and assembling of Panelboard shall be accepted if approved by the Engineer.

MATERIALS AND EQUIPMENT A. Except as otherwise indicated, provide panelboards, enclosures and ancillary components, of types, sizes and ratings indicated, which comply with manufacturer's standard materials; with the design and construction in accordance with published product information; equip with proper number of unit panelboard devices as required for installation. Where types, sizes, or rating are not indicated, comply with applicable electrical code, UL and established industry standards for those applications indicated. 1. 2. Panelboard shall be the product of one manufacturer, unless otherwise noted on drawings. Where interrupting ratings of circuit breakers are specified, or shown on drawings to be based on integrated series short circuit ratings, the series combination shall have been tested in accordance with UL 67 standards. Manufacturer shall certify that equipment furnished is adequately rated in the selected configuration. Where current limiting fuses are utilized on the line side in the series configuration, the circuit breaker manufacturer shall select and certified in Section 16195, shall be provided on the outside face of the panelboard trim reading "Caution-Series Rated System". Where main bus rating is not shown on the drawings, it shall be rated not less than the setting of the feeder overcurrent device.

3.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-65

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

B. 1.

Lighting and Appliance panelboards 380/220 Volt Class a. Dead-front safety type lighting and appliance panelboard as indicated, with switching and protective devices in quantities, ratings, types and arrangements shown; with anti-burn solderless pressure type lug connectors approved for use with copper conductors; equip-break circuit-breakers, with toggle handles that indicate when tripped. Provide suitable lugs on neutral bus for each outgoing circuit required; and provide bare uninslated grounding bars suitable for bolting to enclosures where indicated. Panelboard shall be Westinghouse Load centers or GE Power Mark Plus load center, or approved equal. Panelboard and circuit-breakers shall be selected on a fully rated basis.

b. C.

Panelboard Enclosures: Hot galvinzed sheet steel cabinet type enclosures, NEMA Type 1 general purpose type unless otherwise noted, code-gauge, minimu 14-gauge thickness. Door and trim to have minimum 12 gauge thickness. Construct with multiple knockouts and minimu (4") (6") wiring gutters on sides. Provide fronts with adjustable trim clamps, and doors with flush locks and keys, panelboard enclosures keyed alike, with concealed piano door hinges and door swings as indicated . Equip with interior circuit-directory frame for wire and cable color code identification for each voltage system with clear plastic covering. Provide baked gray enamel finish over a rust inhibitor coating. Design enclosures for recessed or surface mounting as indicated. Provide enclosures which are fabricated by same manufacturer as panelboards, which mate and match properly with panelboards to be enclosed. Provide multiple point catch and vault type handle for doors over 47" high. Panelboard Interiors 1. Assembly of branch circuit units and electro-plated buses on a rigid back pan arranged to permit removal of any unit without disturbing adjacent units. Bus work shall be fabricated of 98% pure electrolytic copper, silver plated. Provide full-size neutral bus and 50% sized bare uninsulated ground buses where indicated or specified. Provide suitable lugs for full circuit capacity on neutral and ground buses. Main terminals shall be equipped with solderless pressure indent type connector with means to prevent swiveling. Arrange buses so that any three adjacent branches, (1,3,5) are connected to Phases A, B and C respectively with the same phase sequence maintained throughout. Provide appropriate bus work and hardware ready to receive future switch and fuse or circuit breaker with blank plates for circuits marked "FUTURE" or "SPACE". Nameplates for Panelboards: Provide in accordance with Section 16195.

D.

2.

3. 4. 5. 6. E.

Molded-Case Circuit-Breakers 1.

Factory-assembled, molded-case circuit-breakers of frame sizes, characteristics, and ratings including RMS symmetrical interrupting ratings indicated. Select breakers with permanent thermal and instantaneous magnetic trip, ampere ratings as indicated. Construct with overcenter, trip-free, toggle-type operating _____________________________________________________________________________________ Division 16 Electrical Works Page 16-66

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr mechanisms with quick-make, quick-break action and positive handle trip indication. Construct breakers for mounting and operating in any physical position, and operating in an ambient temperature of 40C. Provide breakers with mechanical screw type removable connector lugs, AL/CU rated. 2. Circuit-breakers shall have interchangeable trip units for sizes 225 ampere frame and larger. Circuit-breakers shall be individually bolt mounted in the panelboard. Multi-pole circuit-breakers shall be of the common trip type and not be single pole units with handle ties. Cable lugs shall be suitable for 75 degrees C wire.

F.

Circuit-Breaker-Current Limiting: Thermal magnetic molded case type, noninterchangeable trip, unfused with interrupting rating of 200,000 amperes RMS symmetrical at 240 volts and 150,000 amperes at 480 volts. General Electric THL series or TEL/TFL current limiting or approved equal. Cable lugs shall be suitable for 75 C wire. Plug-On Circuit Breakers 1. All plug-on circuit breakers shall have trip settings and number of poles as indicated on the drawings. All circuit breakers shall have their ampere trip rating clearly marked and visible. Breakers shall have quick-make, quick-break, toggle mechanisms, and shall provide positive trip-free operation on abnormal overloads. Stationary and movable contacts shall be adequately protected with effective and rapid arc interruption. Each pole of the breaker shall be equipped with an inverse time delay thermal overcurrent trip element and magnetic instantaneous overcurrent trip elements for common tripping of all poles for multiple breakers. Multiple pole breakers shall have a single handle mechanism. Automatic tripping shall be indicated by the break handle assuming a clearly distinctive position from the manual ON and OFF position. Circuit breakers shall have minimum RMS symmetrical interrupting capacities equal to 10,000 A at 190 V, and 6,000A at 380V. Each circuit breaker assembly shall have undergone and passed heat tests according to UL test procedures and shall be UL listed.

G.

2.

3. 4. L.

Accessories: Provide panelboard accessories and devices including, but not necessarily limited to, cartridge time-delay type fuses, ground-fault protection units, etc., as for rating and application indicated.

PART 3 - EXECUTION 3.01 EXAMINATION A. Examine conditions at the job site where work of this Section is to be performed to insure proper arrangement and fit of the work. Start of work implies acceptance of job site conditions.

3.02

PREPARATION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-67

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Examine the Contract Drawings and specifications in order to insure the completeness of the work required under this Section. Verify measurements and dimensions at the job site and cooperate in the coordination and scheduling of the work of this Section with the work of related trades so as not to delay job progress. Provide templates as required to related trade for location of items.

A. B.

C. 3.03

INSTALLATION A. Install panelboard and enclosure as indicated, in accordance with manufacturer's written instructions, applicable requirements of the applicable electrical code and in compliance with recognized industry practices to ensure that products fulfill requirements. Mount surface units on exterior foundation walls at least 1 inch from wall and do not block vertical flow of air behind cabinets. Close unused cabinet openings. Install cabinet interiors after conduit connections are completed. Install trims in final position prior to finish painting. Mount top of panelboard 6 feet-6 inches above finished floor. Tighten connectors and terminals, including screws and bolts, in accordance with equipment manufacturer's published torque tightening values for equipment connectors. Where manufacturer's torquing requirements are not indicated, tighten connectors and terminals to comply with tightening torques specified in UL Standards 486 A and B. Fasten enclosures firmly to walls and structural surfaces, ensuring that they are permanently and mechanically anchored. Provide properly wired electrical connections for panelboards within enclosures. Type panelboard's circuit directory card upon completion of installation work. Insert fuses of rating indicated, within installed panelboards. Grounding: Provide equipment grounding connection as specified in Section 16450 for panelboard enclosures.

B. C. D. E. F. G.

H. I. J. K. L. 3.04

FIELD QUALITY CONTROL A. Prior to energization of electrical circuitry, check accessible connections to manufacturer's tightening torque specifications.

3.05

DEMONSTRATION A. Subsequent to wire and cable hookups, energize panelboards and demonstrate functioning in accordance with requirements. Where necessary, correct malfunctioning units, and then retest to demonstrate compliance.

3.06 ADJUSTING AND CLEANING _____________________________________________________________________________________ Division 16 Electrical Works Page 16-68

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

A. B.

Adjust operating mechanisms for free mechanical movement. Tourchup scrateched or marred surfaces to match original finishes. END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-69

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16476 LV CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to the work of this section. B. Requirements of the following Division 16 apply to this section:1. 1.2 "Basic Electrical Requirements"

SUMMARY: A. Extent of Low Voltage (LV) circuit-breaker (CB) work is indicated by drawings and schedules. B. Types of circuit breakers in this section include the following: 1. 2. C. Molded-case circuit breakers (MCCB's). Miniature Circuit Breakers (MCB's)

Related Sections: the following divisions sections contain requirements that relate to this section: 1. 2. Division-16 "Switchboards" and "Panelboards" sections. Division-16 "Wires and Cables" Section, work required in conjunction with CB protective devices; not work of this section.

1.3

SUBMITTALS: A. Product Data: Submit manufacturer's product data including frame size (continuous current rating), short circuit interrupting ratings, special and regular features of mounting , trip rating and illustrated relay features etc. as required by the Engineer and installation instructions for each type of circuit breakers. B. Wiring Diagrams: Submit wiring diagrams for circuit breakers and accessories showing connections to electrical power feeders and associated equipment. Differentiate between portions of wiring which are manufacturer-installed and portions which are field-installed. Certification: Submit certified type test and routine factory test data which indicates currentinterrupting ratings for each circuit breaker.

C.

D. Protection coordination: submit complete network study showing proper selection of circuit breakers characteristic time-current curves that will achieve descrimination under fault conditions between down stream and up-stream circuit breakers to and including power company's source protection at the substations. 1.4 QUALITY ASSURANCE: _____________________________________________________________________________________ Division 16 Electrical Works Page 16-70

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

A. Manufacturer's Qualifications: Firms regularly engaged in manufacture of circuit breakers of types, ratings, and capacities required, whose products have been in satisfactory use in similar service for not less than 5 years. B. C. Installer's Qualifications: Firm with at least 3 years of successful installation experience on projects utilizing circuit-breaker devices similar to those required for this project. Codes and Standards: 1. Electrical Code Compliance: Comply with applicable local electrical code requirements of the authority having jurisdiction, as applicable to construction and installation of circuit breakers. IEC Compliance: Comply with IEC 947-2 for power and molded-case circuit breakers, and IEC 898 for miniature circuit breakers.

2. 1.5

DELIVERY, STORAGE AND HANDLING: A. Deliver circuit breakers and components in factory-fabricated type containers or wrappings, which properly protect devices from damage. B. Store circuit breakers in original packaging and protect from weather and construction traffic. Wherever possible, store indoors; where necessary to store outdoors, store above grade and enclose with watertight wrapping. Handle circuit breakers carefully to prevent physical damage to CBs and components. Do not install damaged CBs; remove from site and replace damaged devices with new.

C.

PART 2 - PRODUCTS 2.1 MANUFACTURERS: A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering circuit-breaker products which may be incorporated in the work include, but are not limited to, the following: G.E.C. General Electric Co. Merlin Gerin Square D Company. Westinghouse Electric Corp. Siemens Or approved equal (UK). (USA) (France) (USA) (USA) (Germany)

2.2

CIRCUIT BREAKERS: A. General: Except as otherwise indicated, provide circuit breakers and ancillary components, of types, sizes, ratings and electrical characteristics indicated, which comply with manufacturer's standard design, materials, components, and construction in accordance with published product information, and as required for a complete installation which shall be subject to approval or rejection of the Engineer.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-71

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

D. Moulded Case Circuit Breakers (MCCBs) 1. Type: totally enclosed, moulded case, constructed from high quality, high temperature resistant, tropicalized, moulded insulating materials, for normal operation at 70 deg. C within enclosures, and provided with front operated single toggle type handle mechanism for manual operation of main contacts in addition to automatic operation under overcurrent conditions. Tripping to be indicated by handle automatically assuming a middle position between manual on and off positions. Multi-pole breakers are to have common integral trip bar for simultaneous operation of all poles. Ampere rating is to be clearly visible. All terminals are to be box lug or clamp type with set screws, suitable for copper or Aluminium conductors. Circuit Breaker Trip Units: unless otherwise specified or shown on the Drawings, circuit breakers up to and including 600/630 A frame size, are to be thermal-magnetic type, having bi-metallic inverse time delay overcurrent element for small overloads and instantaneous magnetic overcurrent trip element for operation under short-circuit conditions on each pole. Circuit breakers 250 A and larger are to have adjustable instantaneous trips. Where solid state electronic trip circuit breakers are required these are indicated in the Schedules suffixed with the letter "e". Switching Mechanism: quick-make, quick-break type, with positive trip-free operation so that contacts cannot be held closed against excess currents under manual or automatic operation. Contacts are to be non-welding silver alloy with approved arc-quenching devices of metallic grid construction. Thermal Overcurrent Trips are to be compensated to allow for ambient temperature higher at breaker than at protected circuit or device. Compensation is to be applicable between 25 and 50 deg. C. In case of adjustable thermal settings, range of adjustment is not to exceed maximum trip rating shown on the Drawings. Trip Current Rating (Amps) indicates nominal maximum rating at which overload element is set to operate. MCCBS For MDP's fully rated (100%) for maximum voltage of 600 V a.c. and 250 V d.c., with interrupting capacities at rated system voltages and frequency in accordance with preferred ratings shown in the tables at end of this section, complying with interrupting capacity to IEC 947-2 Sequence II (service short-circuit rating as shown on drawings, and tested to IEC 947-2 test sequence I, II, III and IV for circuit breakers of utilization category B). MCCBs Application For LPs, and DPs to IEC 947-2, with Sequence III (ultimate) shortcircuit capacity in accordance with preferred ratings shown in the tables at end of this section. Tripped Position: when tripped automatically by overcurrent condition, operating mechanism of circuit breaker is to assume an intermediate position clearly indicated by the handle between on and off positions. Interchangeable Trips: thermal-magnetic trip circuit breakers 250 A frame size to 600/630 A frame size are to have interchangeable trip units.

2.

3.

4.

5. 6.

7.

8.

9.

10. Sealing: circuit breakers with non-interchangeable trip units are to be sealed. Circuit breakers with interchangeable trip units are to have trip unit covers sealed to prevent tampering. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-72

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr 11. Compensation: thermal overcurrent trips are to be ambient temperature compensating between 25 and 50 deg. C. 12. Electronic Trips Units, applicable to circuit breakers 400 A frame size and larger, are to be solid state with long time delay settings between 0.5 and 1.0 times maximum trip rating, short time delay range of 3 to 10 times maximum trip rating with a maximum clearing time of 0.2 seconds, and instantaneous protection adjustable from 5 to 10 times continuous rating. Solid state trip units are to be insensitive to changes in ambient temperature between -20 and +55 deg. C. Earth fault protection is to be built into trip unit where specified, and is to be suitable for connection to external current sensor. Push-totrip button is to be provided on cover for testing the trip unit. 13. Accessories: circuit breakers are to be designed to accommodate standard attachments including shunt-trip, under- voltage release, combined auxiliary and alarm switches, and electrical operator to any circuit breaker of rating (frame size) 100 A and over. Padlocking devices are to be provided, where shown on the Drawings. 14. Residual Current Operated Earth Leakage Trip Devices (RCDs) are provided as add-on or built-in earth leakage accessories, where required. Protection against earth fault current, in addition to overcurrent and short-circuit protection, is to be in accordance with the Regulations. Trip current sensitivity on breakers for branch circuits is to be 30 mA maximum, and for main breakers ratings are to be 300 mA. Circuit breakers are to include current transformer with tripping coil assembly, test button and trip free mechanism to ensure circuit breaker cannot be held closed against earth faults. 15. Current Limiting Circuit Breakers: moulded case type without fusible elements. When operating within current limiting range, the I2t of let-through current is to be less than 1/2 cycle wave of symmetrical protective short-circuit current as compatible with breaker construction. 16. Current Limiting Circuit Breakers are to have, on each pole, adjustable inverse time-delay over-current characteristics for overload protection and instantaneous trip for short-circuit protection. Operation of main contacts is to be based on electro-magnetic repulsion forces between contacts created by fault current. Ratings are specified at rated voltage for an rms value of prospective short-circuit current.

E.

Miniature Circuit Breakers (MCBs) 1. 2. Type: thermal magnetic non-adjustable type, tested in accordance with IEC 898 or BS 3871, Part 1. Minimum Short-Circuit Breaking Capacities are to be as follows: 6 - 100 A MCB : 3. 6, 10, 16 kA or 25 kA at 240/415 V a.c.

Construction: MCBs are to be tropicalized for operation at ambient temperatures up to 70 deg. C within panelboard enclosure and humidities up to 95%, and are to be constructed from high quality, high temperature, moulded insulating materials. Guaranteed duties and characteristics are to be submitted for temperatures above 40 deg. C. MCBs and combinational devices are to be modular, of unified profile and mounted to a standard DIN rail.

Operation: under overload conditions, thermal tripping is to provide close protection of insulated conductors. Under short-circuit conditions, magnetic trip is to operate at 7 - 10 times normal rated current (type 3 characteristic). Magnetic operation is to be in the _____________________________________________________________________________________ Division 16 Electrical Works Page 16-73

4.

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr current limiting region and opening time is not to exceed 5 milli-seconds. 5. Ratings: preferred rated currents are to be 6, 10, 15, 20, 25, 30, 40, 50, 60, 80 and 100 A, calibrated at 40 deg. C, available as 1, 2, 3 and 4-pole circuit breakers. Derating above 40 deg. C is not to exceed 1% per deg. C, and loading is not to exceed 70% of circuit breaker rating. Residual Current Devices for earth leakage protective circuit breakers may be add-on devices, or built-in and integral with the standard miniature circuit breaker. Nonadjustable sensitivities of 10 mA, 30 mA, 100 mA and 300 mA are to be available for all ratings of 2-pole and 4-pole circuit breakers. Auxiliaries, where required or shown on the Drawings, are to include alarm switch, auxiliary switch, shunt trip, under voltage trip and similar units which are to be modular additions to the circuit breakers.

6.

7.

PART 3 - EXECUTION 3.1 EXAMINATION: A. Examine areas and conditions under which circuit breakers are to be installed and evaluate conditions detrimental to proper completion of the Work. Do not proceed with the Work until unsatisfactory conditions have been corrected in an acceptable manner.

3.2

INSTALLATION OF CIRCUIT BREAKERS: A. Install circuit breakers and accessories as indicated, in accordance with manufacturer's written instructions and with recognized industry practices to ensure that protective devices comply with requirements. Comply with requirements of Local Regulations and Standards, and applicable approved or recommended "Standard of Installation" pertaining to installation of circuit breakers and general wiring practices. B. C. Coordinate with other work, including electrical wiring work, switchboards, panelboards as necessary to interface installation of circuit breaker work with other work. Tighten electrical connectors and terminals, including screws and bolts, in accordance with equipment manufacturer's published torque tightening values for equipment connectors. Where manufacturer's torquing requirements are not indicated, tighten connectors and terminals to comply with tightening torques of compatible standards.

3.3

ADJUST AND CLEAN: A. Inspect circuit-breaker operating mechanisms for malfunctioning and, where necessary, clean and adjust units for free mechanical movement.

3.4

GROUNDING: A. Provide equipment grounding connections for circuit breakers as indicated. Tighten connectors to comply with tightening torques specified in manufacturers standards or compatible international standards to assure permanent and effective grounding.

3.5

FIELD QUALITY CONTROL:

A. Upon completion of installation and after circuitry has been energized, demonstrate capability _____________________________________________________________________________________ Division 16 Electrical Works Page 16-74

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr and compliance of system with requirements. Where possible, correct malfunctioning units on site, then retest to demonstrate compliance; otherwise, remove and replace with new units, and proceed with retesting. Testing and retesting at no cost to Owner. END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-75

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16480 MOTOR CONTROLLERS PART 1 - GENERAL 1.01 SUMMARY A. Provide labor, materials, equipment and services, and perform operations required for installation of motor controllers and related work as indicated on the drawings and specified herein. Work Included: The work shall include, but not be limited to, the following: 1. 2. C. Combination motor controllers. Fractional HP manual motor controllers.

B.

Related Work Specified Elsewhere 1. 2. 3. 4. 5. Basic Electrical Requirements - Section 16010 Basic Electrical Materials and Methods - Section 16050. Circuit and Motor Disconnects - Section 16170. Electrical Identification - Section 16195. Motor Control Panels - Section 16482.

1.02

QUALITY ASSURANCE A. Materials and equipment shall conform to the latest edition of reference specifications specified herein and to applicable codes and requirements of local authorities having jurisdiction. 1. 2. 3. 4. Electrical Code Compliance: Comply with applicable electrical code requirements of the authority having jurisdiction. NFPA Compliance: Comply with applicable requirements of NFPA 70E, "Standard for Electrical Safety Requirements for Employee Workplaces." IEC Compliance: Comply with applicable requirements of IEC. NEMA Compliance: Comply with applicable requirements of NEMA Standard ICS 2, "Industrial Control Devices, Controllers and Assemblies", and Publ. No.250, "Enclosures for Electrical Equipment (1000 Volts Maximum)", pertaining to motor controllers and enclosures.

1.03

SUBMITTALS

A. Submit the following in accordance with the requirements specified under "Submittals" in _____________________________________________________________________________________ Division 16 Electrical Works Page 16-76

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr section 16010. 1. 2. 3. Product Data: Submit manufacturer's and installation instructions on motor controllers. Shop Drawings: Submit shop drawings of motor controllers. Wiring Diagrams: Submit power and control wiring diagrams for motor controllers. Differentiate between portions of wiring which are manufacturerinstalled and portions which are field-installed.

1.04

DELIVERY, STORAGE AND HANDLING A. B . C. Deliver materials and equipment specified herein in manufacturer's unopened containers, with manufacturer's name and point of origin on each container. Deliver materials and equipment and handle as to prevent the inclusion of foreign materials and the damage of materials by water or breakage. Store materials and equipment in clean dry place and assume responsibility and security for materials and equipment. Take precautions for protection from detrimental conditions.

1.05

SEQUENCING AND SCHEDULING A. Sequence motor controller installation work with other work to minimize possibility of damage and soiling during remainder of construction period.

1.06

MAINTENANCE A. Maintenance Data: Submit maintenance data and parts list for each motor controller and component; including "troubleshooting" maintenance guide. Include that data, product data and shop drawings is a maintenance manual; in accordance with requirements of Section 16010.

PART 2 - PRODUCTS 2.01 MANUFACTURERS A. Subject to compliance with requirements, provide motor controllers of one of the following (for each type and rating of motor controller): 1. 2. 3. 4. 5. 6. 7. 8. 9. 2.02 Course-Hinds Co. Cutler-Hammer Products, Eaton Corp. Furnas Electric Co. General Electric Co. Teleme conique. Siemens Energy & Automation, Inc. Square D Co. Westinghouse Electric Corp. Or approved equal

MATERIALS AND EQUIPMENT

A. Disconnect Type _____________________________________________________________________________________ Division 16 Electrical Works Page 16-77

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

1. B.

Disconnects shall be of the moulded case circuit breaker, bolt-on type, and shall conform to requirements of Section 16425.

Motor Controllers 1. Except as otherwise indicated, provide motor controllers and ancillary components which comply with manufacturer's standard materials, design and construction in accordance with published product information and as required for installation. Equipment shall be the product of one manufacturer, unless located in a hazardous location, to insure standardization of spare parts, operation and maintenance. Where motors furnished by the Contractor (subject to Engineer's approval) differ from the ratings indicated, the Contractor shall provide the required adjustments to wiring, conduit, disconnects, controllers and protection as required. Provide externally manually reset type thermal overload protection in each phase, located within the controller, and selected on the basis of the actual full load nameplate current rating of the motor, taking into account the reduction in current if capacitors are installed downstream of the overload protection. Provide an individual control power transformer within each motor controller for motors, operating at voltages above 120 volts. Secondary voltage of the control power transformer shall be 120 volts, fused on one side and grounded on the other side. Do not connect switching contacts in the grounded side of the control circuits. Rating of the control transformers shall be adequate for imposed control devices 120 volts operating coils, pilot lamps, relays, etc. Provide primary fuse protection where required by the applicable electrical code. Provide a minimum of two normally open and two normally closed auxiliary contacts (two convertible contacts are acceptable)in addition to a normally open "seal-in" contact. Where the required number of auxiliary contacts (spare plus active) cannot be mounted on the controller contractor, provide control relays within the controller enclosure. Starters shall be enclosed. Enclosures shall be NEMA Type 1 general purpose type where installed indoors in dry locations and NEMA Type 3R where installed outdoors, unless otherwise noted. Where installed in hazardous location, enclosures shall be suitable and as approved for the class, division and group in the classified area. Minimum size of controller shall be NEMA size (1). Controller contacts shall be NEMA rated. Where controllers are utilized with high efficiency, high power factor motors, contacts shall be suitable for the higher than usual inrush currents associated with these motors. Provide combination magnetic full voltage (across-the-line) single speed nonreversing controllers for motors operating at other than 120 volts unless otherwise indicated. Provide manual motor controllers for motors operating at 120 volts unless otherwise indicated.

2. 3.

4.

5.

6.

7.

8. 9.

10.

11.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-78

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Combination Magnetic Full Voltage (Across-the-Line) Single Speed Non-Reversing Controllers: Combination unit consisting of a disconnect, and a full voltage magnetic across-the-line magnetic controller mounted in a common enclosure, with NEMA sizes and ratings as indicated. Fractional HP Manual Controllers: Single-phase fractional HP manual motor controllers, of sizes and rating indicated. Equip with manually operated quick-make, quick-break toggle mechanism; and with one-piece melting alloy type thermal units. Controller to become inoperative when thermal unit is removed. Provide controllers with double break silver alloy contacts, visible from both sides of controller; green pilot lights, and switch capable of being padlocked-OFF. Enclose controller unit in NEMA Type 1 general purpose enclosure suitable for flush mounting in finished areas and surface mounting in nonfinished areas. Where installed in hazardous locations, enclosure shall be suitable and approved for the class, division and group in the classified area. Coat with manufacturer's standard color finish.

C.

D.

PART 3 - EXECUTION 3.01 EXAMINATION A. Examine conditions at the job site where work of this Section is to be performed to insure proper arrangement and fit of the work. Start of work implies acceptance of job site conditions.

3.02

PREPARATION A. B. Examine the Contract Drawings and specifications in order to insure the completeness of the work required under this Section. Verify measurements and dimension at the job site and cooperate in the coordination and scheduling of the work of this Section with the work of related trades, so as not to delay job progress. Provide templates as required to related trade for location of items.

C.

3.03

INSTALLATION A. Install motor controllers as indicated, in accordance with equipment manufacturer's written instructions and with recognized industry practices; comply with applicable requirements of the applicable Electrical Code, UL and NEMA standards, to insure that products fulfill requirements. Provide disconnect switches at motors where shown on the drawings or where required by the applicable electrical code. Install equipment at uniform heights with operating means at convenient heights above the floor. Wire motors, starters and controls in accordance with approved wiring diagrams. Do not use freehand field wiring diagrams or sketches.

B. C. D.

E. Examine motors for presence of moisture prior to installation. Refer any doubtful _____________________________________________________________________________________ Division 16 Electrical Works Page 16-79

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr condition to Engineer for decision.

F. G. H. I.

Support controller enclosures independent of the connecting conduits. Do not use connecting conduits to support controller and/or control enclosures. Check control wiring for proper connection before energizing by "ringing" or "taking" out circuits. Refer to the Heating, Ventilating and Air Conditioning and Plumbing drawings and specifications for the manner of control, operation and monitoring of motors and other electrically operated equipment. Provide a motor controller for each motor and each electrically operated piece of equipment except where motor controllers and controls are furnished by the manufacturer of the motor or piece of equipment. Motor controllers shall be internally wired and connected to other motor controllers and to controls to provide the required control operation and monitoring. Connect motor controllers and controls furnished by the manufacturers of motors and other electrically operated equipment. Tighten connectors and terminals, including screws and bolts, in accordance with equipment manufacturer's published torque tightening values for equipment connectors. Where manufacturer's torquing requirements are not indicated, tighten connectors and terminals to comply with tightening torques specified in UL Standards 486 A and B, and the applicable Electrical Code. Grounding: Provide equipment grounding connections for motor controller equipment as specified in Section 16450. Tighten connections to comply with tightening torques specified in UL Standard 486A to assure permanent and effective grounding.

J.

K.

3.04

FIELD QUALITY CONTROL A. B. Prior to energizing motor controllers, perform tests as specified in Section 16950 "Electrical Tests". Touchup scratched or marred enclosure surfaces to match original finishes.

3.05

ADJUSTING AND CLEANING A. B. Adjust operating mechanism, where necessary, for free mechanical movement. Touch up scratched or marred enclosure surfaces to match original finishes. END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-80

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16482 MOTOR-CONTROL PANELS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. B. 1.2 Drawings and general provisions of Contract, including General and Supplementary Conditions and Division I Specification Sections, apply to this Section. Requirements of the following Division 16 Sections apply to this Section:

SUMMARY A. B. This Section includes motor-control panels (MCPs) for use on a.c. circuits rated 600 V or less. Related Sections: The following Division 16 Sections contain requirements that related to this Section: 1. 2. 3. 4. "Circuit Breakers" and "Circuit and Motor Disconnects" for circuit breakers, fusible switches, fuses, and other similar devices used in MCPs. "Motor Controllers" for motor-control devices installed in MCPs. "Electrical Identification" for identification labels and warning signs for MCPs and their components. "Wires and Cables", for insulated cables used in switchgear.

1.3

SUBMITTALS A. B. C. General: Submit the following in accordance with Conditions of Contact and Division 1 Specification Sections. Product data for each product and component specified. Shop drawings for each MCP including dimensioned plans and elevations and component lists. Show ratings, including short-time and short-circuit ratings, and horizontal and vertical bus ampacities. Shop drawing of spare fuse cabinet showing material, dimensions, and features including storage provisions for fuse cartons. Schedule of features, characteristics, ratings, and factory settings of individual MCP units. Wiring Diagrams: Interconnecting wiring diagrams pertinent to the class and type specified for the MCP. Schematic diagram of each type of controller unit indicated.

D. E. F. G.

Qualification data for field-testing organization certificates, signed by the Contractor, certifying that the organization complies with the requirements specified in Quality Assurance below. Include list of completed projects with project names, addresses, names of Engineers and Owners, plus other information specified. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-81

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

H. I. 1.4

Certified reports of field tests and observations specified in the article "Field Quality Control" in this Section. Maintenance data for MCPs, for inclusion in "Operating and Maintenance Manuals" specified in Division 1 and in Division 16 Section "Basic Electrical Requirements."

QUALITY ASSURANCE A. Compliance with IEC: comply with the requirements of the following standards, as applicable: IEC269.1, IEC255,IEC50 IEC 185 IEC 337-2 IEC 51 and IEC 512 IEC 521 IEC 144 IEC 158-1A IEC 947 IEC 439 IEC 292-1, 1A, 1B, BS 4941 PTI B. C. D. E. Cartridge fuses Electrical Protective Relays Current Transformer Control Devices Direct acting Indicating analogue Electrical measuring Instruments. Electrical Meters Degree of protection of enclosures Contactors Low Voltage Switch gear & Control gear LV Switchgear and Control Gear Assemblies. Motor starters D.O.L.

NEMA Standards: NEMA ICS 2, "Standards for Industrial Control Devices, Controllers and Assemblies", Where not in contradiction with above standards. IEC Standard: standards. "Motor Control Panels", Where not in contradictions with above

Electrical Component Standard: NFPA 70, "National Electrical Code," for components and installation, where not in contraction with above standards. Field-Testing Organization Qualifications: To qualify for acceptance, the testing organization must demonstrate, that it has the experience and capability to conduct satisfactorily the testing indicated.

Product Selection for Restricted Space: The Drawings indicate maximum dimensions for MCPs including clearances between MCPs and adjacent surfaces and items and are based on common types and models of major manufacturers. MCPs of other manufacturers having equal characteristics and complying with indicated maximum dimensions may be _____________________________________________________________________________________ Division 16 Electrical Works Page 16-82

F.

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr considered. Refer to Division I Section "Product Substitutions."

1.5

DELIVERY, STORAGE, AND HANDLING A. B. Deliver in shipping splits of lengths that can be moved past obstruction in delivery path as indicated. Store so condensation will not occur on or in MCPs. Provide temporary heaters as required to prevent condensation. Store MCP's in clean dry spaces. Protect from weather, dirt, fumes, water, construction debris and physical damage. Handle MCPs in accordance with manufacturer's rigging and moving instructions, and where applicable with NEMA ICS 2.3, "Instructions for Handling Installation, Operation, and Maintenance of Motor Control Panels." Use factory-installed lifting provisions.

C.

1.6

EXTRA MATERIALS A. Spare Fuses: Furnish six spares of each type and rating of fuse and fusible devices required. Include spares for: 1. 2. 3. B. C. Control Power fuses. Fuses and fusible devices for fused circuit breakers or motor circuit protectors. Fuses for fusible switches.

Spare Indicating Lights: Furnish 6 of each type required. Touch-Up Paint: Furnish 3 half-pint containers.

PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated in the Work include, but are not limited to, the following: Cutler Hammer Products, Eaton Corp. GEC Klockner Moeller Mitsubishi Siemens Or any approved equal 2.2 BUSES A. B. C. D. E. Material: Plated copper. Material: Plated aluminum Ampacity Ratings: As indicated for horizontal and vertical main buses. Neutral Buses: Full size Neutral Buses: Half size (USA) (England) (Germany) (Japan) (Germany)

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-83

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Equipment Ground Bus: Noninsulated, horizontal copper bus 50mm (2-inches) by 6mm (1/4-inch), minimum, and in accordance with the standards. Horizontal Bus Arrangement: Extend main phase, neutral and ground buses with same capacity the entire length of the MCP, with provision for future extension at both ends by means of bolt holes and captive bus splice sections or approved equivalent. Short-Circuit Withstand Rating: Same as short-circuit current rating of section.

F. G.

H. 2.3

FUNCTIONAL FEATURES A. General: Provide a modular arrangement of motor controllers, control devices, overcurrent protective devices, transformers, panelboards, instruments, indicating panels, blank panels, and other items mounted in the compartments of the motor-control panel as indicated. Overcurrent Protective Devices: Provide types of devices with features, ratings, and circuit assignments indicated. Individual feeder tap units acceptable through 250 ampere rating only, shall be installed on drawout mountings with connectors that automatically line up and connect with vertical section buses while being racked into their normal energized positions. Spaces and Blank Units: Compartments fully bussed and equipped with guide rails or equivalent, ready for insertion of drawout units. Space Units: Type, sizes, and ratings as indicated, and installed in compartments indicated "spare." Automated Control and Monitoring: Provide necessary interface equipment and devices to permit connection and interfacing with central control and monitoring system field processing units.

B.

C. D. E.

2.4

SPARE FUSE CABINET A. Steel Box or identifying devices as specified, wall mounted, lockable, and compartment.

2.5

IDENTIFICATION PRODUCTS A. Provide identifying devices as specified in Division 16 Section "Electrical Identification."

2.6

FINISHES A. Manufacturer's standard finish suitable for the environment in which installed. Colour to be approved by the Engineer.

PART 3 - EXECUTION 3.1 INSTALLATION A.

General: Install MCPs in accordance with the manufacturer's written installation instructions and regulations/codes applicable. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-84

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

B.

Anchor each motor-control panel assembly to steel-channel sills arranged and sized in accordance with manufacturer's recommendations. Attach by tack welding or bolting. Level and grout sills flush with motor-control panel mounting surface.

3.2

IDENTIFICATION A. B. Identify field-installed wiring and component and provide warning signs as specified in Division 16 Section "Electrical Identification." Operating Instructions: Frame printed operating instructions for MCPs, including control sequences, and emergency procedures. Fabricate frame of finished wood or metal and cover instructions with clear acrylic plastic. Mount on front of MCPs.

3.3

CONNECTIONS A. Tighten MCP bus joint bolts and electrical connector and terminal bolts in accordance with manufacturer's installation instructions and torque-tightening values. Where manufacturer's torque values are not stated, use those specified in applicable standards.

3.4

FIELD QUALITY CONTROL A. General: Comply with applicable requirements of the International Electrical Testing Association (INETA) Standard ATS, "Acceptance Testing Specifications for Electrical Power Distribution Equipment and Systems." Independent Testing Organization: Arrange and pay for the services of an independent electrical testing organization to perform quality control electrical testing and calibration, visual and mechanical inspections, and tests of MCPs. Testing Preparation and Pretesting: Perform the following preparations for tests: 1. Test insulation resistance of MCP buses; components; and of connecting supply, feeder, and control circuits. For components with solid-state devices or other sensitive components, perform tests in accordance with manufacturer's instructions. Make continuity tests of circuits. Provide set of Contract Documents to test organization. Include full updating on final system configuration and parameters where they supplement or differ from those indicated in original Contract Documents. Provide manufacturer's instructions for installation and testing of MDD to test connections, and nameplate compliance with up-to-date system drawings. Inspect MCPs for defects and physical damage, testing laboratory labels, circuit connections, and nameplate compliance with up-to-date system drawings. Perform operational test and exercise of mechanical components and other operable devices in accordance with manufacturer's instruction manual.

B.

C.

2. 3.

4. 5. 6. 7.

Check MCP anchorage, external clearances, and alignment and fit of components including internal elements. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-85

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

8. 9.

Check tightness of bolted electrical connections with calibrated torque wrench. Refer to manufacturer's instructions for proper torque values. Perform visual and mechanical inspection and related work for motor control and protective devices as specified in Division 16 Sections "Overcurrent Protective Devices and "Motor Controllers." Device Ratings and Settings: Verify ratings and settings of overload relays, motor circuit protectors, and overcurrent protective devices. Make final adjustments of devices in accordance with Division 16 Sections "Overcurrent Protection Devices" and "Motor Controllers."

10.

D.

Quality Control Testing Program: Assure MCP installation meets specified requirements, is operational within specified tolerances, and provides appropriate protection for systems and equipment. 1. 2. 3. Test and inspect MCPs in accordance with manufacturer's recommendations and these specifications. Schedule tests and provide notification at least 1 week in advance of test commencement. Reports: Prepare written reports of test results and observations. Report defective materials and workmanship. Include complete records of adjustments and corrective action taken. Labeling: On satisfactory completion of tests and related effort, apply a label to tested components indicating results, person responsible, and date. Test insulation resistance of buses and portions of control wiring that disconnect from solid-state devices through normal disconnecting features. Insulation resistance less than 100 megohms is not acceptable. Verify appropriate capacity, overcurrent protection, and operating voltage of control power elements including control power transformers and control power wiring. Check phasing of supply source to the bus. Test motor-control devices as specified in Division 16 Section "Motor Controllers." Test overcurrent protective devices as specified in Division 16 Section "Overcurrent Protective Devices."

4. 5.

6.

7. 8. 9. E. 3.5

Retesting: Correct deficiencies and retest. Verify by the retests that specified requirements are met.

CLEANING A. Inspect interior and exterior of MCPs. Remove paint splatters and other sports, dirt, and debris. Touch up scratches and mars of finish to match original finish.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-86

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-87

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16500 LIGHTING FIXTURES PART 1 - GENERAL 1.01 SUMMARY A. Provide labor, materials, equipment, and services, and perform operations required for installation of lighting fixtures and related work as indicated on the drawings and specified herein. Work Included: The work shall include, but not be limited to, the following: 1. 2. 3. C. Fluorescent lighting fixtures. compact fluorescent lighting fixtures. Incandescent Lighting fixtures.

B.

Related Work Specified Elsewhere 1. 2. 3. Basic Electrical Requirements - Section 16010 Basic Electrical Materials and Methods - Section 16050. Electrical Tests - Section 16950.

1.02

QUALITY ASSURANCE A. Materials and equipment shall conform to the latest edition of reference specifications specified herein and to applicable codes and requirements of local authorities having jurisdiction. 1. Code Compliance: Comply with IEC Publication 162.

1.03

SUBMITTALS A. Submit the following in accordance with the requirements specified under "Submittals" in Section 16010. 1. 2. Product Data: Submit manufacturers' product data and installation instructions on each type of lighting fixture and component. Shop Drawings: Submit shop drawings for each lighting fixture and accessory on separate sheets, clearly showing dimensions, mounting details, light control assemblies, conduit entrances, photometric information and test reports (prepared by an independent testing laboratory) for luminance, efficiency, and comfort levels. Submit details indicating compability with ceiling grid system. a. Samples: Submit one operating unit for each type of lighting fixture specified to the Engineer upon request at no cost to the Engineer or Employer.

1.04

DELIVERY, STORAGE AND HANDLING

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-88

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Deliver lighting fixtures, accessories, poles and standards, in factory-fabricated containers or wrappings, which properly protect fixtures from damage. Store lighting fixtures, accessories, poles and standards in original packaging. Store inside well-ventilated area protected from weather, moisture, soiling, extreme temperatures, humidity, laid flat and blocked off ground. Handle lighting fixtures, accessories, poles and standards carefully to prevent damage, breaking, and scoring of finishes. Do not install damaged units or components; replace with new.

A. B.

C.

PART 2 - PRODUCTS 2.01 MANUFACTURERS A. Manufacturers: Factory of lamps and Ballasts should be the product from the original country of the manufacturer. Subject to compliance with requirements, provide products of one of the following: 1. 2. Ballasts Lamps a. b. c. d. e. 3. 2.02 Thorn Sylvania Electric Products, Inc. Philips Lighting Co. Osram Or any approved equal

Lighting Fixtures: Manufacturer shall be as specified under each fixture type or approved equal.

MATERIALS AND EQUIPMENT A. Provide lighting fixtures, of sizes, types and rating indicated; including, but not limited to, housings, lamps, lampholders, reflectors, energy efficient ballasts, starters and wiring. Ship fixtures factory-assembled, with those components required for installation. Design fixtures with concealed hinges and catches, with metal parts grounded as common unit, and so constructed as to dampen ballast generated noise. Pendant fixtures shall be furnished with ball or swivel type aligners unless otherwise noted per fixture type. Where fluorescent fixtures are mounted in continuous rows, the wires through the channels shall be 2.5 mm2 minimum, 90C, 600 V or approved equal. Wire rated 300 volts will not be permitted with 220 volt fluorescent. Enclosures: Fabricate fixture enclosures with a minimum of 0.5 mm thick cold rolled sheet steel. Enclosures may be constructed of other metals, provided they are equivalent in mechanical strength and acceptable for the purpose. Sheet Metal Work: Sheet metal work shall be free from tool marks and dents, and shall have accurate angles bent as sharp as compatible with the gauges of the required metal.

B. C.

D.

E.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-89

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Intersections and joints shall be formed true of adequate strength and structural rigidity to prevent any distortion after assembly.

F.

Housings shall be so constructed that electrical components are easily accessible and replaceable without removing fixtures from their mountings, or disassembly of adjacent construction. Castings: Castings shall be exact replicas of the approved patterns and shall be free of sand pits, blemishes, scales and rust, and shall be smoothly finished. Tolerance shall be provided for any shrinkage of the metal castings in order that the finished casting will accurately fit in their designated locations. Lamp sockets in lighting fixtures shall be suitable for the indicated lamps and shall be set so that lamps are positioned in optically correct relation to lighting fixture components. If adjustable socket positions are are provided, socket should be preset in factory for lamp specified. If different socket positions are specified for same fixtures, sockets shall be preset for each type, and cartons marked accordingly. Lampholders for fluorescent fixtures shall be white and where installed in industrial fixtures, they shall be of the turret type. Lamp sockets for incandescent fixtures shall be of the medium base type for lamps 300 watts and smaller and of the mogul type for lamps 500 watts and larger. Hardware for steel and aluminum fixtures, screws, bolts, nuts, and other fastening and latching hardware shall be cadmium or equivalent plated. For stainless steel fixtures, hardware shall be stainless steel. For bronze fixtures, hardware shall be stainless steel or bonze. Temperatures: Fixtures and ballasts shall operate within the temperature limits of their design in the applications and mounting conditions herein specified or shown on drawings. Wiring: Provide electrical wiring within fixture suitable for connecting to branch circuit wiring as follows: 1.5 mm2 of silicon rubber insulation with glass braid finish. Fluorescent Lamp Ballasts: High power factor, complying with IEC requirements, two lamp type wherever feasible (3 lamp types are not acceptable), lowest sound level and lowest case temperature rise rating. 1. 2. Switch Start: Energy saving type. Starters : Electronic, instant type

G.

H.

I.

J. K. L. M.

N. O.

Lamps: Provide fluorescent lamps of energy saving types as indicate. Lighting Fixture Types: Various fixture types required are indicated on Engineer's lighting plan fixture schedule. Fixtures must comply with minimum requirements as stated. Review Engineerural drawings and specifications to verify ceiling types, modules, suspension systems appropriate to installation.

PART 3 - EXECUTION 3.01 EXAMINATION A.

Examine conditions at the job site where work of this Section is to be performed to insure proper arrangement and fit of the work. Start of work implies acceptance of job site _____________________________________________________________________________________ Division 16 Electrical Works Page 16-90

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr conditions.

3.02

PREPARATION A. B. Examine the Contract Drawings and specifications in order to insure the completeness of the work required under this Section. Verify measurements and dimensions at the job site and cooperate in the coordination and scheduling of the work of this Section with the work of related trades, so as not to delay job progress.

3.03

INSTALLATION A. Install lighting fixtures and accessories at locations and heights as indicated, in accordance with fixture manufacturer's written instruction, requirements of the applicable electrical code, to ensure that lighting fixtures fulfill requirements. Provide fixtures and/or fixture outlet boxes with hangers to properly support fixture weight, Submit design of hangers, method of fastening, other than indicated or specified herein, for review by Engineer. Install flush mounted fixtures properly to eliminate light leakage between fixture frame and finished surface, and between fixture frame and fixture. Where fixtures are of the air handling type or installed in partially-transparent ceilings, construct fixtures to eliminate light leaks above the ceiling line. Provide plaster frames for recessed fixtures installed in other than suspended grid type acoustical ceiling systems. Brace frames temporarily to prevent distortion during handling. If ceiling system requires, each recessed and semi-recessed fixture shall be furnished with a mounting frame or ring compatible with the ceiling in which they are to be installed. The frames and rings shall be one piece or constructed with electrically-welded butt joints, and of sufficient size and strength to sustain the weight of the fixture. Fasten fixtures securely to indicated structural supports and ensure that pendant fixtures are plumb and level. Provide individually mounted pendant fixtures longer than 2 feet with twin stem hangers. Provide stem hanger with ball aligners and provisions for minimum one inch vertical adjustment. Mount continuous rows of fixtures with an additional stem hanger greater than number of fixtures in the row. Tighten connectors and terminals, including screws and bolts, in accordance with equipment manufacturer's published torque tightening values for equipment connectors. Where manufacturer's torquing requirements are not indicated, tighten connectors and terminals to comply with tightening torques specified in UL Stds 486A and B, and the applicable electrical code. Support surface mounted fixtures greater than 2 feet in length at a point in addition to the outlet box fixture stud. Provide yokes, brackets, and supplementary supporting members needed to mount lighting fixtures to carrier channels or other suitable ceiling members.

B.

C.

D. I.

F.

G.

H. I. J.

Reflectors, reflector cones and visible trim of lighting fixtures shall not be installed until completion of plastering, ceiling tile work, painting and general cleanup. They shall be carefully handled to avoid scratching or fingerprinting and shall be, at the time of _____________________________________________________________________________________ Division 16 Electrical Works Page 16-91

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr acceptance by the Employer, clean.

K. L.

Lenses shall be clean and free of dust. Lighting fixture locations in mechanical equipment rooms and/or fan lofts are approximate. Coordinate installation of fixture with installation of mechanical equipment and mount fixtures at uniform heights to properly illuminate equipment including gauges and meter. Run exposed conduit to these fixtures.

3.04

ADJUSTING AND CLEANING A B. Clean lighting fixtures of dirt and construction debris upon completion of installation. Clean fingerprints and smudges from lenses. Protect installed fixtures form damage during remainder of construction period. END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-92

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16610 UNINTERRUPTIBLE POWER SUPPLY SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes a 3-phase, on-line, static-type, non-redundant, uninterruptible power supply system (UPS), including the following principal component parts: 1. 2. 3. 4. 5. B. Rectifier/Battery Charger Battery Inverter Static Bypass Transfer Switch Maintenance Bypass Isolation Switch Related sections: the following sections contain requirements that relate to this section: 1. Division 16 " Wires and cables " 2. Division 16 " LV circuit Breakers " 1.3 DEFINITIONS A. Rated Full-Load: Load corresponding to full-rated kVA at 80 percent power factor. B. C. Static: Containing no moving electrical parts and using solid-state components for switching and control. Transient: That part of the change in a variable such as voltage or current that disappears during transition from one steady-state operating condition to another.

D. Uninterruptible Power Supply (UPS): A system that automatically provides power, without delay or transients, during any period when the normal power supply is incapable of performing acceptably. 1.4 SUBMITTALS A. General: Submit the following according to Conditions of Contract and Division 1 Specification Sections. B. Product data for products specified in this Section. Include data on features, components, ratings, and performance.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-93

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Maintenance data for system and products for inclusion in Operating and Maintenance Manual specified in Division 1. Include the following: 1. Detailed operating instructions covering operation under both normal and abnormal conditions.

C.

D. Shop drawings detailing fabrication, internal and interconnecting wiring, and installation of UPS system. Include dimensioned plan, elevation views, and details of control panels. Show access and clearance requirements. Differentiate between field-installed and factory-installed wiring and components. Indicate weight and loading points E. F. Product certificates signed by manufacturer of UPS system certifying the product complies with specified requirements. Qualification data for manufacturer specified in Quality Assurance Article to demonstrate their capabilities and experience. Include list of completed projects with project names, addresses, and names of Engineers and Owners, plus other information specified.

G. Independent field-testing organization certificates, signed by Contractor, certifying that the organization complies with the requirements specified in Quality Assurance below. H. Factory Test Plan: Detailed list, schedule, or tabulation of events for each factory test requirement. Include the following: 1. 2. 3. I. J. 1.5 Description of input source and output loads to be used. Describe actions required to simulate source load variation and simulation of various operating conditions and malfunctions. List of indications, parameter values, and system responses considered satisfactory for each test action. Provide space for tabulation of actual observations during test. Description of Instruments and Test Equipment Required: Provide adequate detail to make test plan reusable in the field for those tests required to be repeated there. Factory test reports evidencing compliance with specified requirements. Field test reports for tests specified in Part 3.

QUALITY ASSURANCE A. Manufacturer Qualifications: Firms experienced in manufacturing equipment of the types and capacities indicated with a record of successful in-service performance. 1. Service Center: UPS system manufacturer maintains a service center capable of providing training, parts, and emergency maintenance and repairs at the Project site with 4 hours maximum response time. Local Representative: provide evidence that proposed equipment manufacturer has a locally established and authorized organization which can be called upon for professional advice and maintenance as may be required, and which can immediately supply spare parts to support day to day and emergency maintenance requirements. Failure to satisfy the Engineer may disqualify a manufacturer.

2.

Independent Field-Testing Organization Qualifications: Demonstrate, based on evaluation of organization-submitted criteria conforming to ASTM E 699, that the organization has the _____________________________________________________________________________________ Division 16 Electrical Works Page 16-94

B.

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr experience and capability to satisfactorily conduct the testing indicated.

C. Single-Source Responsibility: Obtain UPS system components from a single manufacturer with responsibility for entire system. D. Maintenance Contract: obtain an undertaking by the equipment manufacturer and his authorized local representative to provide an annual maintenance contract, available after substantial completion of the work, covering routine service and emergency service by trained employees, and to ensure supply of necessary standard spare parts. WARRANTY A. Special Project Warranty for Batteries: Submit a written warranty, mutually executed by manufacturer and the principal Installer, agreeing to replace UPS system storage batteries that fail in materials or workmanship within the special project warranty period specified below. This warranty will be in addition to, and not a limitation of, other rights and remedies the Employer may have against the Contractor under the Contract Documents. 1. Special Project Warranty Period for Batteries: 10 years beginning on the date of Substantial Completion. A full warranty applies to the first year of the period, and a pro rata warranty for the last 9 years. 1.7 DELIVERY, STORAGE, AND HANDLING A. Deliver equipment in fully enclosed vans after specified environmental conditions have been permanently established in spaces where equipment is to be placed. B. Store equipment in spaces with noncondensing environments that are controlled within manufacturer's ambient tolerances for nonoperating equipment. 1.8 EXTRA MATERIALS A. Furnish extra materials matching products installed as described below, packaged with protective covering for storage, and identified with labels describing contents. Deliver extra materials to the Employer. B. C. Fuses: 1 for every 10 of each type and rating, but not less than 1 of each. Spare Parts: Employer. as recommended by Manufacturer upon certification by Engineer and

1.6

PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated in the Work include, but are not limited to, the following: B. Manufacturers: following: Subject to compliance with requirements, provide products by the

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-95

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

1. Uninterruptible Power Supply Systems: A. B. Emerson (UK) MGE Merlin Gerin (France)

2. Batteries, Storage: A. B. 2.2 Oldham Chloride Systems.

SYSTEM SERVICE CONDITIONS A. Environmental Conditions Capabilities: Operate in the following environmental conditions without mechanical or electrical damage or degradation of operating capability. 1. Ambient Temperature: 0 deg C to 35 deg C. 2. Relative Humidity: 3. Altitude: 0 to 95 percent, noncondensing. Sea level.

2.3

SYSTEM DESCRIPTION A. General: system is to be interposed between normal a.c. power supply and critical load, to secure a minimum period of continuity of no-break battery back-up for 20 minutes at full load in case of failure of normal a.c. supply and maintain output voltage, frequency and phase deviation within specified tolerances. B. System is to be non-redundant, maintained (continuously supplying load through the inverter), with automatic no- break transfer to or retransfer from alternate source (bypass) in case of failure or overload on rectifier- battery-inverter system. Normal A.C. Power Supply will be available from one protected source fed from either normal a.c. network or from alternate a.c. normal supply and in-house stand-by diesel generator set as shown on the Drawings. Characteristics of output of generator set (when provided) and UPS system are to be coordinated for best results. Study and advise on special requirements of generator characteristic output and stability. SYSTEM OPERATION A. Static transfer switch is to automatically transfer critical (100%) load from inverter to by-pass source (which is normal a.c. supply) if: 1. inverter output voltage characteristics fall outside specified limits 2. critical load exceeds overload rating of UPS 3. over temperature is sensed 4. manual (push button) command is given.

C.

2.4

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-96

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

5. Transfer to by pass mode is to be inhibited, and an alarm initiated if voltage, frequency and/or phase shift of by pass power are outside acceptable tolerances. B. Re-transfer of critical load from auto by-pass source to inverter (UPS mode) is only to be possible under the following conditions: inverter output voltage characteristics return to within specified tolerances original load current reduces to within rated full load capacity of UPS re-transfer selector switch is in automatic position. C. Lock-out feature is to inhibit re-transfer if by-pass source conditions are outside preset tolerances or if UPS output and by-pass are not synchronized and phase locked or if UPS output is not restored to normal conditions. D. When normal power is restored following an outage, rectifier / charger is to initially draw no power except for transformer in-rush current. After approximately 15 seconds (walk-in time ), input power requirements are to rise to power level to drive critical load and recharge battery. 2.5 A. SYSTEM CHARACTERISTICS Rectifier/ charger input: nominal input voltage voltage input variation frequency transformer exciting current in rush power factor total harmonic feedback current limiting : : : : : : : 380 V, three phase, four wire, 50 Hz +10%, -15% from nominal +/-5% from nominal less than 600% nominal current 0.8 lagging at full load and nominal input voltage maximum 10% (total) 115% max. of that required to operate inverters and charge battery at full rated load, adjustment possible between 100% and 125% walk-in current in rush B. Rectifier/ charger output: float and equalize operation regulation 0-100% load adjustable, automatic , compatible : with battery : +/-1% max. from : 25% to 100% FLC in 15 seconds.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-97

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr : +/-2% rms. (0 to 100% resistive load) .

ripple C. Static inverters: nominal output output voltage regulation Single or 3-phase balanced load system load) unbalanced load (3-phase system output only) phase displacement (for 3-phase output system only unbalance output voltage harmonic waveform harmonic frequency stability :

: : :

380 V, three phase, four wire, 50 Hz

+/-2% (0 - 100%

+/-3% (at 100% unbalance)

120 deg. (+/-5 deg.) : at 100% 5% : 3% max. max.

load total single

normally synchornized to input line frequency over +/-2% adjustable range; free running at +/- 0.5% over full battery voltage variation, load and p.f. range; slew rate not to exceed 0.1 Hz/sec +/-10% max.

dynamic output voltage tolerance recovering sudden full load than application or removal over-load rating minutes

to within 1% in less : 100 milliseconds : 125% for 10

150% for 60 seconds 1000% for 5 cycles 105% continuous. D. Automatic static transfer switch: transfer time second (overlapping) maximum : 150 micro-

total (sensing and transfer/ retransfer time : 2 milliseconds, _____________________________________________________________________________________ Division 16 Electrical Works Page 16-98

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

maximum retransfer mode (selectable) retransfer delay automode transfer point output voltage (adjustable) retransfer point output (adjustable) transfer inhibit output point (adjustable) : +/-20% of nominal voltage : +/-5% of nominal voltage : : automatic / inhibit 2 - 32 secs. in (selectable) : +/-10% of nominal

2.6

SYSTEM PERFORMANCE A. Maximum Acoustical Noise: 58 dB, "A" weighting, emanating from the system under any condition of normal operation, measured 4 feet (1.2 m) from the nearest surface of the enclosure for UPS ratings under 20 kVA; 60 dB(A) for ratings of 20 kVA to 125 kVA. B. Maximum Energizing Inrush: 6 times full-load current.

C. Maximum Output Voltage Transient Excursions from Rated Value: Not to exceed 5% upon loss or restoration of a.c. input power. 2.7 SYSTEM COMPONENTS, GENERAL A. Components: Solid-state devices using semiconductor elements of the hermetically sealed type. Devices include rectifier/battery charger, inverter, static bypass switch, and system controls. B. Enclosure: Major components such as static bypass switch, rectifier, battery, inverter, and maintenance bypass in separate compartments of enclosures or in separate cabinets, depending on system size, as generally laid-out on drawings.. C. Control Assemblies: Mount on modular plug-ins, arranged for easy maintenance. D. Surge Suppression: Protect UPS system input elements, rectifier/charger, inverter, controls, and output components against voltage transients with surge suppressors conforming to UL 1449, "Transient Voltage Surge Suppressors." _____________________________________________________________________________________ Division 16 Electrical Works Page 16-99

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

E. Power Assemblies: Mount rectifier and inverter sections and static bypass switch on modular plug-ins, arranged for easy maintenance. F. Design and fabricate internal supports for assemblies, subassemblies, components, supports, and fastenings for batteries, to withstand static, anticipated seismic forces, or both in any direction, with the minimum force value used being equal to the equipment weight. G. Sub-assemblies and components are to be mounted on pull-out and/or swing-out trays where possible. Cables connecting to trays are to be sufficiently long and flexible to allow easy access to all components. Where it is not possible to mount components in pull-out or swingout trays, they are to be easily accessible inside the enclosure. H. Materials and parts: indicator lights are to be twin LED type, those denoting blown fuse conditions are to be seen by operator without removing panels or opening cabinet doors. Power connections and remote alarm and control wiring are to be accessible at terminal boards. Power semi-conductors are to be fused. Metal surfaces including copper and aluminium heat sinks and busbars are to be treated with permanent protective coating. Electro-mechanical power devices and relays are to be vacuum impregnated, insulated for maximum operating voltage conditions, and enclosed in dust-tight enclosures. Cables are to be fire resistant high temperature grade.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-100

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

2.8

RECTIFIER / CHARGER UNIT: A. Rectifier charger unit is to have mainline circuit breaker , automatic with soft start-up (walk-in) feature, using silicon controlled rectifiers (thyristors) with control logic circuitry to control firing angles to thyristors to suit power output requirements and protect against primary power surges, lightning transients, under-voltage and over-voltage conditions. Output is to be passed through LC filters to d.c. bus. Charger current is to be voltage regulated and current limited. Where three-phase supply is involved, rectifier is to be at least six-pulse type. B. Capacity: Adequate to supply the inverter during full output load conditions and simultaneously recharge the battery from fully discharged condition to 95 percent of full charge within 10 times the rated discharge time for duration of supply under battery power at full load, and maintain full charge at floating voltage until next-operation. C. Harmonic suppression inherent in the rectifier/battery charger design reduces total harmonic content of the current drawn from the input power source by the system to less than 10 percent for sources with X/R ratios from 2 to 30. This applies for all load currents from 0 to 100 percent of full load. D. Battery float charging conditions, in terms of voltage and charging current under normal operating conditions, are within battery manufacturer's recommendations for maximum battery life. E. Input Isolation Transformer: A 3-phase, self-cooled, 2-winding, class H, dry type with a grounded, insulated, metallic electrostatic shield installed between primary and secondary windings. F. Input Power Factor: At least 0.85 lagging when supply voltage and current are at nominal rated values and UPS is supplying rated full load.

2.9

BATTERY A. Battery: high rate discharge, heavy duty, industrial , high impact resistant , clear plastic encased, sealed lead-acid (gas recombination) type cells with automatically reclosing explosion proof safety vents. Electrolyte specific gravity is not to exceed 1.25 when fully charged at 25 deg. C. Ampere-hour rating is to be sufficient for emergency period specified with all inverters operating at full rated output, to a discharge limit of not less than 1.65 V per cell. Cells are to be normally maintained at 2.25 V per cell. Guaranteed life is not to be less than 10 years, with a capacity drop down to not less than 80% under normal expected service. B. Battery Racks: steel construction, with plastic insulating rails at points of contact with battery cases. Racks are to be painted with electrolyte resistant paint, are to be of appropriate design for space in which installed, and directly accessible for maintenance. Cables are to be rubber insulated electrolyte resistant type.

2.10

INVERTER

A. Type: Inverter is to employ single-phase bridge circuit for single-phase output or single -phase units connected on 3-phase bridges, using transistor or thyristor circuits, fourth-generation technology (logic controlled pulse-width modulation), and complete with output transformer and filters. Inverter start-up is to be automatic, to reach full voltage within milliseconds and deliver power to the load within 2 seconds. Inverter is to start at any load including shortcircuit. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-101

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

B. Oscillator: is to operate and maintain output frequency of inverter within specified tolerances, and be capable of synchronization and phase-locking to normal power supply frequency. When inverter is phase-locked to normal power supply, and latter fails, oscillator is to automatically revert to free running state (quartz oscillator) and maintain specified limits. C. Protection: UPS modules are to have built- in or inherent electronic current -limiting protection against permanent self damage effective down to short-circuits. Fast acting, current limiting devices are to protect against failure of any solid state component. Internal failure in any UPS module is to cause immediate isolation from input and output by operation of static interrupters or causing shut down of faulty module . Protection is to be provided against, but is not limited to, the following: input over and under voltage and power line surges output over voltage and voltage surges sudden abnormal changes in output load conditions short-circuits at output terminals inverter and rectifier overcurrent auxiliary control circuit overcurrent 2.11 STATIC BYPASS SWITCH A. Static Switch Type: Hybrid type, make-before-break transfer, solid state device with logic thyristor assembly, isolatable or completely withdrawable for maintenance. When signal to close switch is initiated, thyristors are to instataneously conduct power to prevent deviations and breaks in load voltage outside specified tolerances. B. Switch Rating: Continuous-duty at rated full load. 2.12 MAINTENANCE BYPASS ISOLATION SWITCH A. Comply with Division 16 Sections relevant to circuit disconnects and enclosures. B. Manual Switch Rating and Type: Continuous-duty at rated full load of system, (make - before - break) type manually operated. Switch is to allow load to be transfered to by-pass source without interruption of output, and provide an isolation of UPS and static switch during maintenance. C. Mounting Provisions: Locate inside one of the modular system cabinets, behind a lockable door. D. Key interlock requires unlocking maintenance bypass isolation switch before switching from normal position with key that is released only when UPS is bypassed by static bypass switch. Lock is type designed specifically for electrical component interlocking. E. Test position is to permit testing of static switch while load is being fed from bypass power circuit. F. Transfer inhibited warning circuit is to be provided to give an alarm indication in case by-pass supply is beyond acceptable tolerances. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-102

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

2.13

INDICATION AND CONTROL A. General: Group displays, indications, and basic system controls on a common control panel on the front of the UPS enclosure. B. Minimum displays, indicating devices, and controls include those in the lists below. Provide sensors, transducers, terminals, relays, and wiring required to support listed items. An audible signal sounds for all alarms in addition to the visual indication. C. D. Indications: Labeled LED display. Indications: Plain-language messages on a liquid crystal or digital LED display. 1. Quantitative Indications: Include the following: a. b. c. d. e. f. g. h. i. j. Input voltage, each phase, line-to-line. Input current, each phase, line-to-line. Bypass input voltage, each phase, line-to-line. Bypass input frequency. System output voltage, each phase, line-to-line. System output current, each phase. System output frequency. D.C. bus voltage. Battery current and direction (charge/discharge). Elapsed time-discharging battery.

2. Status Indications: Include the following: a. b. c. d. e. Normal operation. Load on bypass. Load on battery. Inverter off. Alarm condition exists.

3. Alarm Indications: Include the following: a. b. c. d. e. f. Bypass a.c. input overvoltage or undervoltage. Bypass a.c. input overfrequency or underfrequency. Bypass a.c. input and inverter out of synchronization. Bypass a.c. input has wrong-phase rotation. Bypass a.c. input has single-phase condition. Bypass a.c. input filter fuse blown.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-103

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

g. h. i. j. k. l. m. n. o. p. q. r. s. t. u. v. w. x. y. z.

Internal frequency standard in use. Battery system alarm. Control power failure. Fan failure. UPS overload. Battery charging control faulty. Input overvoltage or undervoltage. Input transformer overtemperature. Input circuit breaker tripped. Input has wrong-phase rotation. Input has single-phase condition. Approaching end of battery operation. Battery undervoltage shutdown. Maximum battery voltage. Inverter fuse blown. Inverter transformer overtemperature. Inverter overtemperature. Static bypass switch overtemperature. Inverter power supply fault. Inverter transistors out of saturation.

aa. Identification of faulty inverter section/leg. bb. Inverter output overvoltage or undervoltage. cc. UPS overload shutdown. dd. Inverter current sensor fault. ee. Inverter output contactor open. ff. Inverter current limit. 4. Controls: Include the following: a. b. c. d. e. f. g. Inverter on-off. UPS start. Battery test. Battery input circuit breaker Auto/ manual reset-test switch Manual reset switch Hybrid switch transfer test push-button inverter after timed inverter of normal operation and inhibit re-transfer of load to _____________________________________________________________________________________ Division 16 Electrical Works Page 16-104

h. Re-transfer auto/ inhibit selector switch to allow automatic re-transfer of load to

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

inverter until hybrid switch is in auto-mode i. Battery automatiuc/equalize recharge timer, 0 - 30 hours adjustable, with automatic / boost/ equalize switch (accessible to maintenance personnel only and to be used only with manufacturer's recommendation for type of battery specified) j. k. l. m. E. 2.14 Output voltage and frequency adjustment controls with locking devices (accessible to maintenance personnel only) Indicator test / reset switch Control power supply isolator (accessible to maintenance personnel only) Alarm test-silence-reset.

Analog Meters: Accuracy within 2 percent.

REMOTE UPS CONTROL AND MONITORING SYSTEM A. Description: Make available the indication and control functions specified above for the unit control panel at a remote microcomputer. Record power-line transients and provides analytical capability. Include the items described below, but do not include the remote computer or the connecting signal wiring. System includes: 1. Modem and connectors for data transmission via RS-232 link and external signal wiring to a computer. 2. Software that permits secure monitoring and controlling of UPS functions; and provides on-screen explanations, interpretations, and action guidance for monitoring indications. Include on-screen descriptions of control functions and guidance for their use. Permit storage and analysis of power-line transient records. Design for IBM-compatible microcomputer systems.

2.15

MECHANICAL FEATURES A. Enclosures: equipment is to be housed in a free-standing, well ventilated, totally enclosed modular assembly with front accessible lockable doors, giving easy access for maintenance, inspection and adjustments, and with provisions for handling and lifting during and after installation. Enclosures are to be suitable for industrial, tropical environments, protection IP &deg-prot& to IEC 144, of galvanized sheet steel construction treated against corrosion and with light grey RAL7032 baked paint or epoxy finish to approved standard. B. Ventilation: for units rated over 5 kVA, an integral, forced-air, cooling system is to be provided in each UPS module to remove dissipated heat efficiently, and ensure components operate within environmental ratings. Air is to enter bottom of cabinet through replaceable filters, and exhaust through the top. At least two fans are to be provided for ventilating each enclosure. No degradation of performance is to occur in the event of a single fan failure. Temperature sensors, mounted on semi-conductor heat sinks, are to initiate alarm if maximum working temperature is exceeded.

2.16

SOURCE QUALITY CONTROL A. Factory test complete UPS system, including battery, prior to shipment. Include the following

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-105

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

tests: 1. Functional test and demonstration of all functions, controls, indicators, sensors, and protective devices. 2. Full-load test. 3. Transient load response test. 4. Overload test. 5. Power failure test. 6. Efficiency test at 50-percent, 75-percent, and 100-percent load. B. Observation of Test: Provide a 2-week advance notice of tests and opportunity for observation of test by Owner's representative. C. Report test results on "Factory Test Plan" specified in Part 1 of this Section.

PART 3 - EXECUTION 3.1 INSTALLATION A. Install system components on 4-inch-high (100-mm-high) concrete housekeeping bases. Castin-place concrete, reinforcing, and formwork are specified in Division 3. Install systems according to manufacturer's printed instructions. B. Maintain minimum working space at equipment according to manufacturer's shop drawings. C. Connections: Interconnect system components. Make connections to supply and load circuits according to manufacturer's wiring diagrams and as indicated. D. Manufacturer's Field Services: Arrange and pay for the services of a factory-authorized service representative to supervise the installation, connection, tests, and adjustment of the unit.

3.2

IDENTIFICATION A. Identify components according to Division 16 Section "Electrical Identification." B. Identify each battery cell individually.

3.3

FIELD QUALITY CONTROL A. Supervised Adjustment and Pretesting: Under supervision of factory-authorized service representative, pretest system functions, operations, and protective features. Adjust to ensure operation complies with specifications. Load the system using a variable load bank simulating kVA, kW, and power factor of loads for which unit is rated. B. Tests: Provide the services of a qualified testing agency to perform the tests listed below according to manufacturer's recommendations upon completion of installation of system. Load the system using a variable load bank simulating kVA, kW, and power factor of load for which unit is rated. Use instruments that have been recently calibrated according to approved standards. 1. Simulation of malfunctions to verify protective device operation.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-106

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

2. Tests of duration of supply on emergency, demonstrations of low-battery voltage shutdown, and transfers due to normal source failure and restoration. 3. Tests of harmonic content of input and output current under 25 percent, 50 percent, and 100 percent of rated load. 4. Tests of voltage output under specified transient-load conditions. 5. Tests of efficiency at 50-percent, 75-percent, and 100-percent rated load. 6. Functional Tests of Remote Status and Alarm Panel. 7. Functional Tests of Battery-Monitoring System. C. 3.4 Retest: Correct deficiencies and retest until specified requirements are met.

CLEANING A. Upon completion of installation, inspect system components. Remove paint splatters and other spots, dirt, and debris. Repair scratches and mars of finish to match original finish. Clean components internally using methods and materials recommended by manufacturer.

3.5

DEMONSTRATION A. Training: Arrange and pay for the services of a factory-authorized service representative to demonstrate adjustment, operation, and maintenance of the system and to train Owner's personnel. B. Conduct a minimum of 8 hours of training as specified under Instructions to Owner's Employees in the Project Closeout Section of these Specifications. C. Schedule training with at least a 7-day advance notification.

3.6

COMMISSIONING A. Battery Equalization: Equalize charging of battery cells according to manufacturer's instructions. Record individual cell voltages. END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-107

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16670 LIGHTNING PROTECTION SYSTEMS PART 1 - GENERAL 1.01 SUMMARY A. Submit labor, materials, equipment and services, and perform operations required for installation of Lighting Protection Systems and related work as indicated on the drawings or specified herein. Work Included: The work of this section shall include, but not be limited to, the following: a. b. c. d. e. f. g. C. Conductors. Connectors. Fasteners Grounding plates Grounding rods. Rod clamps Splicers.

B.

Related Work Specified Elsewhere 1. 2. 3. Basic Electrical Requirements - Section 16010. Basic Electrical Materials and Methods - Section 16050. Grounding - Section 16450.

1.02

QUALITY ASSURANCE A. Materials and equipment shall conform to the latest edition of reference specifications specified herein and to applicable codes and requirements of local authorities having jurisdiction. 1. B. Electrical Component Standard: Provide work complying with applicable requirements of the applicable electrical code.

Installer Qualifications: Engage an experienced installer to install lightning protection system. Installer shall be an authorized agent of the manufacturer of the equipment and have a minimum of five (5) years of continuous experience in this area. Submit evidence of such qualifications to the Engineer.

1.03

SUBMITTALS A. Submit the following in accordance with Submittal Requirements specified in Section 16010. 1. Product Data: Submit manufacturer's technical product data, including specifications and installations, for each type of detailing, product specified, including roof adhesive where used.

Shop Drawings: Shop Drawings shall detail a layout of the lightning protection system including, but not limited to, air terminal locations, conductor routing, _____________________________________________________________________________________ Division 16 Electrical Works Page 16-108

2.

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr connections and grounding.

1.04

SEQUENCING AND SCHEDULING A. Coordinate installation of lightning protection system with the installation of other building systems and components, including electrical wiring, supporting structures and building materials, and metal components requiring interface with lightning protection systems.

PART 2 - PRODUCTS 2.01 MANUFACTURERS A. Manufacturers: Submit to compliance with requirements, provide products by one of the following: 1. 2. Furse Wallis

Or approved equal 2.02 MATERIALS AND EQUIPMENT A. Provide lightning protection system materials and components, that comply with manufacturer's standard design, in accordance with published product information. Provide air terminals, bonding plates, conductors, connectors, conductor straps, fasteners, grounding plates, grounding rods clamps, splicers and other components required for a system that meets NFPA 78 Standards. Type of metal for air terminals, bases and cables: Copper with solid air terminals. Air terminals for Single-Ply Roof Mounting: If required, provide units with bases especially designed for single-ply roof materials. Ground Rods: 3/4 inch minimum diameter by 10-feet long, copper clad steel with minimum 27 percent of the rod weight in the copper cladding.

B. C. D.

PART 3 - EXECUTION 3.01 EXAMINATION A. Examine conditions at the job site where work of this Section is to be performed to insure proper arrangement and fit of the work. Start of work implies acceptance of job site conditions.

3.02

PREPARATION A. B. Examine the Contract Drawings and specifications in order to insure the completeness of the work required under this Section. Verify measurements and dimensions at the job site and cooperate in the coordination and scheduling of the work of this Section with the work of related trades so as not to delay job progress.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-109

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Provide templates as required to related trade for location of items.

C. 3.03

INSTALLATION A. B. Install lightning protection system in accordance with equipment manufacturer's written instructions, and in compliance with applicable installation standards specified above. Install conductors with direct paths from air terminals to ground connections avoiding sharp bends and narrow loops. Run conductors in non-metallic raceway Schedule 40 minimum. Conceal system wiring. Splices and Clamps: Use approved exothermic welded connections for conductor splices and connections between conductors and other components. Provide required molds, tools and cartridges and use in strict accordance with manufacturer's instructions. Corrosion Protection 1. Use no combination of materials that may form an electrolytic couple of such nature that corrosion is accelerate in the presence of moisture, unless moisture is permanently excluded form the junction of such metals. Where unusual conditions exist that would cause deterioration or corrosion of conductors, use conductors with suitable protective coating. When connecting copper materials to aluminum material UL approved bimetallic type fittings or connectors specially designed for making connections between the two metals shall be used.

C. D.

E.

2.

F. G.

Grounding and Bonding: Provide equipment grounding and bonding connections sufficiently tight to assure permanent and effective grounds and bonds. Where conductors or raceway pass though roofing, provide proper flashing to conform with roofing requirements. Downlead cables from the cable roof system shall not be brought directly through the roof. Thru-roof connectors with solid rods or conduit through pitch pockets shall be utilized for this purpose. Conductors shall be secured 3 feet on center. Conducators shall maintain a horizontal or downward course. No bend of a conductor shall form an angle less than 90 degrees nor shall have a radius of bend less than 8 inches. Metal bodies on the roof, including but not limited to exhaust fans, roof vents, HVAC units, roof drains, plumbing vents, ladders, railing, antennas, louvers, roof hatches, metal stacks, smoke vents shall be bonded to the system. Refer to Engineer, HVAC and Plumbing drawings for the location of these items. Metal, such as roof drains, metal copings, metal flashings, gutters, downspouts, metal wall vents, door and window frames, metal balcony railings, structural steel and reinforcing rods, interior metal piping, ductwork and machinery and in general any isolated metal object at or below roof level which is within a distance as defined in the specified standards of a system element, shall be bonded to the system using proper, approved splicers, fittings and conductors.

H.

J.

K.

The lightning protection system shall be bonded to the main water service and the building grounding system. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-110

L.

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-111

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16721 FIRE ALARM SYSTEM ANALOGUE ADDRESSABLE TYPE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. B. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. Requirements of the following Division 16 section apply to this section 1. " Basic Electrical Requirements ". 1.2 SUMMARY A. This Section includes fire alarm systems, including the following: 1. Main fire alarm control panel (MFAC) 2. Analogue automatic detectors 3. Alarm and sundry devices 4. Complete wiring system, and any related accessories. B. Related Sections: The following Sections contain requirements that relate to this Section: 1. 2. 1.3 DEFINITIONS A. B. C. Alarm-Initiating Device: A smoke detector, heat detector or flame detector. Alarm Signal: Signifies a state of emergency requiring immediate action. Pertains to signals such as the operation of any other alarm initiating device. Class A Wiring: Circuits arranged and electrically supervised so a single break or single earth fault condition will be indicated by a trouble signal at the main fire alarm control panels (MFAC) and the circuit will continue to be capable of operation for its intended service in the faulted condition no matter where the break or earth fault condition occurs. Hard-Wired System: Alarm, supervisory, and initiating devices directly connected, through individual dedicated conductors, to a central control panel without the use of multiplexing circuits or devices. Supervisory Signal:Indicates abnormal status or need for action regarding fire suppression or other protective system. Trouble Signal: Indicates that a fault, such as an open circuit or earth, has occurred in the system. Division 16 Section " Wires and cables ". Division 16 Section " Raceways ".

D.

E. F.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-112

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

G. 1.4

Zone: Initiating device or combination of alarm-Initiating devices connected to alarminitiating device circuits.

SYSTEM DESCRIPTION A. System: is to be of modular design and consist of standardized hardware and software packages only. It is to be possible to expand and modify the system with minimum changes in such a way that already existing system modules are not affected.

BType: fire alarm system is to be Class A for alarm initiation and alarm indicating devices, analogue addressable, pre-signal zoned, non-coded system. Automatic fire detector and sensor circuits are to be grouped in loops. C. D. E. Signal Transmission: Hard-wired, using separate or multiple individual circuits for zone (s) of alarm initiation and alarm device operation. Audible Alarm Indication: By bells for alarm Addressable devices: such as automatic fire detectors are to be individually-addressed in connecting fault-tolerant loops and grouped in software-assignable zones as shown on the Drawings. Compatibility: all basic equipment used, except standard peripheral units, shall be designed and manufactured by the same manufacturer to ensure system uniformity of standards, compatibility in operation, parts availability, trained support and maintenance. Data transmission: data network is to connect MFAC with the main control unit in the central security room. Standard half or full duplex, digital, serial data transmission techniques are to be used. Every path of the data transmission network must be monitored for open and short circuit. Communication faults are to be announced both at the. A parity bit per byte is to be employed to detect any transmission errors.Manufacturer is to state the types of communication and protocol to be used as well as the standard(s) with which they comply. Functional Description: The following are required system functions and operating features: 1. Priority of Signals: Accomplish automatic response functions by the first zone initiated. Alarm functions resulting from initiation by the first zone are not altered by subsequent alarms. The highest priority is an alarm signal. Supervisory and trouble signals have second- and third-level priority. Signals of a higher-level priority take precedence over signals of lower priority even though the lower- priority condition occurred first. Annunciate all alarm signals regardless of priority or order received. Noninterfering:Zone, power, wire, and supervise the system so a signal on one zone does not prevent the receipt of signals from any other zone. All zones are manually resettable from the MFAC after the initiating device or devices are restored to normal. Systems that require the use of batteries or battery backup for the programming function are not acceptable. Signal Initiation: The automatic operation of an alarm-initiating or supervisory operating device causes the MFAC to transmit an appropriate signal

F.

H.

2.

3. 4.

Silencing at MFAC: Switches provide capability for acknowledgment of alarm; supervisory, trouble, and other specified signals at the MFAC; and capability to silence the local audible signal and light a light-emitting diode (LED). Subsequent zone alarms _____________________________________________________________________________________ Division 16 Electrical Works Page 16-113

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr cause the audible signal to sound again until silenced in turn by switch operation. Restoration to normal of alarm, supervisory, and trouble conditions extinguish the associated LED and cause the audible signal to sound again until the restoration is acknowledged by switch operation. 5. 6. 7. Loss of primary power at the MFAC sounds trouble signal at the MFAC and indicates when the system is operating on an alternate power supply. Annunciation: Automatic operation of alarm- and supervisory-initiating devices is annunciated both on the MFAC, indicating the location and type device. MFAC Alphanumeric Display: Displays plain-language description of alarms, trouble signals, supervisory signals, monitoring actions, system and component status, and system commands. General Alarm: A system general alarm includes: a. b. c. Indicating the general alarm condition at the MFAC. Identifying the device that is the source of the alarm (or its zone) at the respective MFAC. Initiating audible and visible alarm signals throughout the building.

8.

L.

Remote Detector Sensitivity Adjustment: Manipulation of controls at the MFAC causes the selection of specific addressable smoke detectors for adjustment, display of their current status and sensitivity settings, and control of changes in those settings. The same controls can be used to program repetitive, scheduled, automated changes in sensitivity of specific detectors. Permissible Signal Time Elapse: The maximum permissible elapsed time between the actuation of any fire alarm or fire-detection system alarm-initiating device and its indication at the MFAC is two seconds. Circuit Supervision: Indicate circuit faults by means of both a zone and a trouble signal at the MFAC. Provide a distinctive indicating audible tone and (LED) indicating light. The maximum elapsed time between the occurrence of the trouble condition and its indication at the MFAC is 200 seconds.

N.

O.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-114

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

1.5

SUBMITTALS A. B. General: Submit the following according to Conditions of Contract and Division 1 Specification Sections. Product data for system components. Include dimensioned plans and elevations showing minimum clearances and installed features and devices. Include list of materials and listing data. Wiring diagrams from manufacturer differentiating between factory- and field-installed wiring. Include diagrams for equipment and for system with all terminals and interconnections identified. Indicate components for both field and factory wiring. Shop drawings showing details of graphic annunciator. System operation description covering this specific Project including method of operation and supervision of each type of circuit and sequence of operations for all manually and automatically initiated system inputs and outputs. Manufacturer's standard descriptions for generic systems are not acceptable. Operating instructions for mounting at the MFAC. Operation and maintenance data for inclusion in Operating and Maintenance Manual specified in Division 1. Include data for each type product,. Include recommendations for spare parts to be stocked at the site. Provide the names, addresses, and telephone numbers of service organizations that carry stock of repair parts for the system to be furnished. Product certification signed by the manufacturer of the fire alarm system components certifying that their products comply with indicated requirements.

C.

D. E.

F. G.

H. 1.6

QUALITY ASSURANCE A. B. Installer Qualifications: A factory-authorized Installer is to perform the Work of this Section. Codes and Standards Compliance With Local Requirements: Comply with the applicable building code, local ordinances, and regulations, and the requirements of the authority having jurisdiction. 1. C. Comply with NFPA

Single-Source Responsibility: Obtain fire alarm components from a single source who assumes responsibility for compatibility for system components.

1.7

EXTRA MATERIALS A. B. C. General: Furnish extra materials, matching products installed (as described below), packaging with protective covering for storage, and identifying with labels clearly describing contents. Smoke Detectors, Fire Detectors: Furnish quantity equal to 10 percent of the number of units of each type installed but not less than one of each type. Detector Bases: Furnish quantity equal to 2 percent of the number of units of each type installed but not less than one of each type.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-115

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products which may be incorporated in the Work include, but are not limited to, the following: 1. 2. 3. 4. 2.2 Simplex (USA) Cerberus (SWISS) Edwards (CANADA) Notifier (USA)

MAIN FIRE ALARM CONTROL PANEL (MFAC) A. MFAC TYPE: main control unit and main annunciation panel of modular design to facilitate phasing of work, expansion and servicing, and containing all components of the system including solid-state electronic components, audible and visual unit, relays and interface components, batteries and charger and other components required for operation of system. System operation: the main fire alarm control unit is to be field programmed for different alarm organisation schemes, automatically implemented, each according to the fire alarm activating device, and as described below.

B.

Two-mode operation: In case of activation of automatic detector the system is to operate as follows: 1. In the first mode (stage) of the control unit operation, a response from automatic detectors in designated zones is to be kept as local alarm in the control unit for the period of a programmable time T1. During this delay time (stage), an internal (staff) alarm only is to be given. If the alarm is not acknowledged before timer T1 runs out, this is to result in a general alarm (stage 2) response. If the alarm is acknowledged while T1 is still running, T1 is to be reset and a programmable timer T2 is to be started (stage 2) . T2 is to delay the general alarm further, and so provide time for human investigation of the alarm cause. If no reset action takes place before T1 and/or T2 runs out, a general alarm (stage 2) is to be given, which immediately results in actuating the audible device in the building. In the second mode of operation of the control unit, a general alarm is to be given without delay, releasing immediately the actuation of the object's audible. The delay time T1 (investigation squad check 1) and T2 (investigation squad check2) is to be programmable between 00:00 and 5 minutes respectively. The remaining time of timer T1/T2 is to continuously be displayed at the terminal (count down). The switch-over from first to second mode is to be programmable up to 4 switch-overs.

2.

3.

4. 5. 6. 7. 8.

C. Alarm verification: the main Control Unit is to be programmed for smoke alarm verification _____________________________________________________________________________________ Division 16 Electrical Works Page 16-116

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr such that the first response of an automatic smoke detector is immediately reset, with no alarm initiation. Should a second response in the same zone or detector occur within a fixed time, stage 1 alarm response is to be initiated.

D.

Main fire alarm cabinet is to be designed and programmed to perform extensive automatic self-monitoring. Fire alarm control unit is to give visual and audible warning on main annunciator panel for the following faults: failure of microprocessor unit or program memory failure or disconnection of power supply/charger/battery failure of fuse or protective device removal of detector head trouble condition in any loop break or short circuit in wiring of connecting loop or collectively-addressed spurs connected to the monitor/control modules. Faults are to automatically indicate fault alarm by audible and visual warning. Audible warning is to remain on until silenced by respective cut-off switch whilst red illuminated LED remains on to indicate defective device/loop. When respective device/loop is restored to normal, trouble bell is to sound again until cut-off switch is back to normal, thereby turning off the illuminated LED.

E.

Alarm Activation: means for activating zone alarm and total evacuation alarm are to be provided, as well as reset buttons for silencing alarm sounders and cut-off switches etc. as necessary to supervise and control the system as described. MFAC is to have an LCD display with min. of 2 lines, 20 characters/line to display the alarm information messages, and to enable basic interface between human operator at MFAC and addressable system components, including annunciation supervision and control. Arrange key pad for use in entering and executing commands . Visual Indicators: twin light-emitting diodes (LED), tamper-proof type, with rated life of at least 40 years. MFAC is to provide 24 V d.c. (+/-10%) to all alarm initiating and alarm signaling devices and is to be designed to operate from 220 V a.c., 50 Hz 2-wire, earthed power supply. Overvoltage protection is to be provided to prevent any malfunction or damage which might occur from line power surges.

F.

G. H.

I. Battery back up on power failure is to exceed 8 hours normal load, followed by full alarm load capability of 30 minutes. Voltage is to be 24 V d.c. Battery is to be lead acid, maintenance free type, float charged, with automatic rapid charge at maximum allowable rate for type used. Battery voltmeter, charge/discharge ammeter, low battery alarm bell and pilot light are to be provided, activated when battery voltage drops below 22 V. The connection to the battery is to be automatically switched off when the voltage drops below 20 V to protect battery cells from damage by complete discharge. J.Upon power failure a visible and audible signal is to be generated to indicate that the control unit is operating under emergency power. The master fault indicator on the control unit is to be also illuminated until mains power has been restored. When the AC power is restored, the control unit is to automatically revert to normal operating without any manual restarting procedures. K. Enclosure is to be sheet steel, wall mounted type, finished in bright red baked enamel, with _____________________________________________________________________________________ Division 16 Electrical Works Page 16-117

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr hinged door secured by lock. Smaller lockable door is to be provided in main door for access for routine checking and servicing. Opening of main door is to expose all components for inspection adjustment or replacement, without further dismantling.

L.

Relays are to be plug-in type, fitted with dust-proof covers, operated at 24 V d.c., with auxiliary contacts rated 250 V, 5 A supplied as necessary to operate other systems interconnected to fire alarm system, as required in the Specification or as shown on the Drawings. N. Lamp test buttons are to be provided to test LEDs or other pilot lights on enunciator panels. MFAC is to be equipped for transmitting several auxiliary outputs to other systems. It must also be equipped with a serial data communication modem to enable connection to the central fire alarm control unit. MFAC is to have a minimum of 10% spare capacity for future expansion.

M.

P. 2.3

FIRE ALARM CABLING A. Wires and cables: to have passed IEC 331 and 332 flame resistance and fire retardant tests. Cables are to be silicone rubber insulated, with overall PVC sheath bonding to coated aluminium foil (FP 200 by Pirelli Cables) or other equal and approved. Conductors are to be copper of minimum size 1.5 mm2 and/or as shown on the Drawings.

2.4

OPTICAL SMOKE DETECTOR A. Type : two wire operation, photo-electric type, utilising light scattering principle, with high quality solid state electronic components, completely shielded, protected against false alarms from EMI and RFI, and obtaining operating power from supervisory current in detection loop. Detector is to be analogue addressable and is to have the circuitry for two-way communication with the MFAC. Each time the detector is polled, it is to communicate its individual address, type (ionisation-smoke, optical smoke, etc.) and an analogue/digitally encoded value corresponding to its sensitivity and status with microcomputer processing in the control unit. Detector is to be automatically addressed by its location in the signaling loop. Mounting : surface or semi-recessed ceiling mounted type, located as shown on the Drawings, and comprising mounting base and twist-lock detector head. Removal of detector head is to interrupt supervisory circuit and cause trouble signal at control panel. Normal flat surface coverage is to be over 60 m2 at mounting height of 6 m. Submit detector's characteristic curves of coverage area against ceiling height and air movement speed. Detector is to have constant response sensitivity under all conditions due to adaptive alarm threshold. The automatic sensitivity adjustment is to compensate for soiling and climatic influences. Detector is to have automatic regulation to varying supply voltage (18 V - 32 V d.c.), reverse voltage protection, spike and surge suppression. Detector is to have dual status indicating LED's, flashing under normal operation for 360 degree visual supervision. When detector is actuated, LED is to latch-on 'steady' and at full brilliance until reset from control panel.

B.

C.

D.

E. F.

G Detector is to have at least the following performance: _____________________________________________________________________________________ Division 16 Electrical Works Page 16-118

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

nominal operating voltage: 24 V d.c. alarm current : not greater than 5 mA quiescent current: not greater than 0.2 mA ambient temperature: 0 to 60 deg. C relative humidity: 10% to 90% ambient air velocity: max. 10 m/Sec. horizontal protection category IEC529: IP - 43 smoke entry characteristics: 360 degrees in all directions. 2.5 RATE-OF-RISE AND FIXED TEMPERATURE HEAT DETECTOR A. Type: two wire operation, combined rate of rise fixed temperature detectors is to consist of dual thermistors, designed to automatically compensate changes in ambient conditions. Electronic circuits must be solid state devices and virtually hermetically sealed. All circuitry must be protected from EMI and RFI, and must obtain power from supervisory current in detection loop. Detector is to be analogue addressable and is to have the circuitry for two-way communication with the MFAC. Each time the detector is polled, it is to communicate its individual address, type (ionisation-smoke, optical smoke, etc.) and an analogue/digitally encoded value corresponding to its sensitivity and status with microcomputer processing in the control unit. Detector is to be automatically addressed in its location in the signaling loop. Mounting: surface or semi-recessed ceiling mounted type, located as shown on the drawings, and comprising mounting base and twist-lock detector head. Removal of detector head is to interrupt supervisory circuit and cause trouble signal at control panel. Normal flat surface coverage is to be over 50 m2. Submit detector's characteristic curves of coverage area against ceiling height. Sensitivity: detector is to have constant response sensitivity under all conditions due to adaptive alarm threshold. The automatic sensitivity adjustment is to compensate for soiling and climatic influences. Detector is to have automatic regulation to varying supply voltage (18 V - 32 V d.c.), reverse voltage protection, spike and surge suppression. Detector is to have dual status indicating LED's, flashing under normal operation for 3 full brilliance until reset from control panel. Defector is to have at least the following performance: nominal operating voltage: 24 V d.c. alarm current: not greater than 9 mA quiescent current : not greater than 0.2 mA _____________________________________________________________________________________ Division 16 Electrical Works Page 16-119

B.

C.

D.

E. F. G.

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr ambient temperature : 0oC to + 70oC relative humidity : 10% + 90% protection category IEC529: IP - 54 Smoke entry characteristics : 360 degrees in all directions.

2.6

ALARM AND SUNDRY DEVICES A Bell type: for indoor applications, vibrating type, with die-cast zinc frames, aircraft aluminium alloy diaphragms, heavy duty tungsten contacts, stress-relieved stainless steel armature springs and Teflon-impregnated plastic moulded strikers and breakers.. Bells are to operate from nominal 24 V d.c. source with voltage variations between 18V and 32 V, and are to give minimum sound level of 90 dB(A) at 3 m.

2.7

ADDRESSABLE INTERFACE DEVICES A. Addressable control module is to be provided to control/activate and supervise the wiring of alarm devices (sounders, emergency voice speaker's zones, etc.). Wiring to control module is to be class A. Module is to be provided with SPDT contact, capable of relaying either 24 V dc, 70.7 V audio signal or two-way telephone signal upon command from the MFAC. Addressing is to be automatic through the location of the control module in the signaling loop. An integral LED is to be provided for visual supervision. Fault isolator module is to be provided within the connecting loops. Module is to isolate the part of the loop upon short circuit in the loop. An integral LED is to be provided for visual supervision, normally blinks and latches ON in alarm.

B.

PART 3 - EXECUTION 3.1 INSTALLATION A. B. C. Connections and terminations of circuits are to be made only at accessible tamper-proof connection boxes and fire alarm cabinets. Detector heads with twist-lock mounting are to be removable from floor level by use of preengineered grip on end of long rod, specially designed for the purpose. Smoke Detectors: Install ceiling-mounted detectors not less than 10 cm from a side wall to the near edge. Install detectors located on the wall at least 10 cm but not more than 30 cm below the ceiling. For exposed solid joint construction, mount detectors on the bottoms of the joint. On smooth ceilings, install detectors not over 10 m apart in any direction. Install detectors no closer than 1.5 m from air registers. Audible Alarm-Indicating Devices: Install not less than 220 cm above the finished floor nor less than 15 cm below the ceiling. Install bells and horns on flush-mounted back boxes with the device- operating mechanism concealed behind a grille or as indicated. Combine audible and visual alarms at the same location into a single unit.

D.

EMain Fire Alarm Control Panel (MFAC): Surface mount with tops of cabinets not more than 6 feet above the finished floor. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-120

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

3.2

WIRING INSTALLATION A. Wiring: Wire sizing schedules and calculations are to be submitted to ensure acceptable voltage drop on all alarm circuits within the system and to indicate various loop wiring layouts in detail. All circuits are to be appropriately labeled and approved before use by Employer's personnel. Wiring Within Enclosures: Install conductors parallel with or at right angles to the sides and back of the enclosure. Bundle, lace, and train the conductors to terminal points with no excess. Connect conductors that are terminated, spliced, or interrupted in any enclosure associated with the fire alarm system to terminal blocks. Mark each terminal according to the wiring diagrams of the system. Make all connections with approved crimp-on terminal spade lugs, pressure-type terminal blocks, or plug connectors. Cable Taps: Use numbered terminal strips in junction, pull or outlet boxes, cabinets, or equipment enclosures where any circuit tap is made. Color Coding: Color-code fire alarm conductors differently from the normal building power wiring. Use one color code for alarm circuits wiring and a different color code for supervisory circuits. Color-code audible alarm-indicating circuits differently from alarm-initiating circuits. Use different colors for visual alarm-indicating devices. Paint fire alarm system junction boxes and covers red.

B.

C. D.

3.3

EARTHING: A. Earthsd equipment and conductor and cable shields. For audio circuits, minimize to the greatest extent possible earth loops, common mode returns, noise pickup, cross talk, and other impairments. Provide 1-ohm earth at main equipment location. Measure, record, and report earth resistance.

3.4

FIELD QUALITY CONTROL A. Manufacturer's Field Services: Provide services of a factory-authorized service representative to supervise the field assembly and connection of components and the pretesting, testing, and adjustment of the system. Pretesting: Upon completing installation of the system, align, adjust, and balance the system and perform complete pretesting. Determine, through pretesting, the conformance of the system to the requirements of the Drawings and Specifications. Correct deficiencies observed in pretesting. Replace malfunctioning or damaged items with new and retest until satisfactory performance and conditions are achieved. Prepare forms for systematic recording of acceptance test results. Report of Pretesting: After pretesting is complete, provide a letter certifying the installation is complete and fully operable, including the names and titles of the witnesses to the preliminary tests. Final Test Notice: Provide a 10-day minimum notice in writing when the system is ready for final acceptance testing.

B.

C.

D.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-121

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Minimum System Tests: Minimum required tests are as follows: 1. 2. Verify the absence of unwanted voltages between circuit conductors and earth. Megger test all conductors other than those intentionally and permanently earthed with electronic components disconnected. Test for resistance to earth. Report readings less than 1-megohm for evaluation. Test all conductors for short circuits utilizing an insulation-testing device. With each circuit pair, short circuit at the far end of the circuit and measure the circuit resistance with an ohmmeter. Record the circuit resistance of each circuit on the record drawings. Verify the control unit is in the normal condition as detailed in the manufacturer's operating and maintenance manual. Test initiating and indicating circuits for proper signal transmission under open circuit conditions. One connection each should be opened at not less than 10 percent of the initiating and indicating devices. Observe proper signal transmission according to class of wiring used. Test each initiating and indicating device for alarm operation and proper response at the control unit. Test smoke detectors with actual products of combustion.

E.

3. 4.

5. 6.

7. F.

Retesting: Correct deficiencies indicated by tests and completely retest work affected by such deficiencies. Verify by the system test that the total system meets the Specifications and complies with applicable standards. Report of Tests and Inspections: Provide a written record of inspections, tests, and detailed test results in the form of a test log. Submit log upon the satisfactory completion of tests. Tag all equipment, stations, and other components at which tests have been satisfactorily completed.

G. H. 3.5

CLEANING AND ADJUSTING A. Cleaning: Remove paint splatters and other spots, dirt, and debris. Touch up scratches and mars of finish to match original finish. Clean unit internally using methods and materials recommended by manufacturer. Occupancy Adjustments: When requested within one year of date of Substantial Completion, provide on-site assistance in adjusting sound levels and adjusting controls and sensitivities to suit actual occupied conditions. Provide up to three visits to the site for this purpose.

B.

3.6

DEMONSTRATION A. Provide the services of a factory-authorized service representative to demonstrate the system and train Owner's maintenance personnel as specified below. 1. Train Owner's maintenance personnel in the procedures and schedules involved in operating, troubleshooting, servicing, and preventive maintaining of the system. Provide a minimum of 8 hours' training.

2. Schedule training with the Owner at least seven days in advance. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-122

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-123

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16740 TELEPHONE SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Specification sections, apply to this Section. B. 1.2 Division-16 Basic Electrical Requirements sections apply to work specified in this section.

SUMMARY A. Telephone system work is indicated by drawings and schedules, and is hereby defined to include, but not be limited to telephone wiring/cabling, control/signal transmission media, attendants' consoles, switching systems, modems, line drives, terminals, telephone instruments (handsets), and ancillary equipment. Types of telephone systems required for project include the following:

B.

Electronic private automatic branch exchange (PABX) Main distribution frame (MDF) Operator's console. Terminal boxes Telephone Sets Wiring/Raceways Power supply any related accessories not specifically mentioned herein. C. D. Raceways, electrical boxes and fittings, and cable trays, which are required in connection with the installation of telephone systems, are specified in other Division-16 sections. Requirements are indicated elsewhere in these specifications for work including, but not limited to cable riser closets, equipment rooms, lateral cable distribution systems, attendants' cabinets and turrets, required in connection with the installation of telephone systems.

1.3

SUBMITTALS: A. B. Product Data: Submit manufacturer's data on telephone systems and components. Shop Drawings: Submit layout drawings of telephone systems and accessories including, but not necessarily limited to, service-entrance penetrations, apparatus, racks, terminals, and switching equipment. Wiring Diagrams: Submit analog and digital data transmission wiring diagrams for telephone systems, including rack and terminal connections. Also show wiring connections to electrical power feeders. Differentiate between portions of wiring that are manufacturer-installed and portions that are field-installed.

C.

D. Agreement to Maintain: Prior to time of final acceptance, the Installer shall submit 4 copies of _____________________________________________________________________________________ Division 16 Electrical Works Page 16-124

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr an agreement for continued service and maintenance of telephone system, for Owner's possible acceptance. Offer terms and conditions for furnishing parts and providing continued testing and servicing, including replacement of materials and equipment, for one-year period with option for renewal of Agreement by Owner.

1.4

QUALITY ASSURANCE: A. Manufacturer's Qualifications: Firms regularly engaged in manufacture of telephone systems and ancillary equipment, of types, ratings and capacities required, whose products have been in satisfactory use in similar service for not less than 5 years. Installer's Qualifications: Firms with at least 5 years of successful installation experience with projects utilizing telephone systems and equipment similar to that required for this project. Codes and Standards: 1. Electrical Code Compliance: Comply with applicable local code requirements of the authority having jurisdiction and NEC, including 800-Series articles as applicable to installation, and construction of telephone systems. FCC Compliance: Comply with Part 68 and Subpart J of Part 15, Federal communications Commission Rules, pertaining to telephone equipment and Class A computer registration by manufacturer. Provide telephone and computer equipment with FCC labels indicating applicable FCC registration and numbering. 3. 4. 5. D. Local Authority Compliance: Coordinate and comply with local authority requirements for telephone systems. CCITT Recommendations: Comply with CCCIT recommendations for the installation and construction of the telephone system. EIA Compliance: Comply with EIA Standards RS-453, 455, and 464 pertaining to installation of telephone systems.

B. C.

2.

DELIVERY, STORAGE AND HANDLING 1. 2. Deliver telephone equipment and components in factory-fabricated containers or wrappings, which properly protect equipment from damage. Store telephone equipment and components in original packaging. Store inside in a well-ventilated space protected from weather, moisture, soiling, humidity, and extreme temperatures. Handle telephone equipment and components carefully to prevent damage, breaking, and scoring of finishes. Do not install damaged units or components; replace with new.

3.

E.

SEQUENCING AND SCHEDULING: 1. Installer shall notify local operating company in writing of telephone interface connection requirements to ensure proper and timely interfacing of building telecommunication systems with the operating company's systems.

2. Coordinate with other electrical work including wires/cables, electrical boxes and _____________________________________________________________________________________ Division 16 Electrical Works Page 16-125

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr fittings, and raceways, to properly interface installation of telephone system with other work. 3. Sequence installation of telephone system with other work to minimize possibility of damage and soiling during remainder of construction.

F.

MAINTENANCE: 1. Agreement to Maintain: Engage Installer who is willing to execute with Owner the required agreement for continued maintenance of the telephone system.

PART 2 - PRODUCTS 2.1 MANUFACTURERS: A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering telephone system equipment which may be incorporated in the work include, but are not limited to, the following: Approved Manufacturers of EPABX Equipment: obtain EPABX, peripherals, and telephone stations from one of the following: Ericsson (Sweden) Northern Telecom (Canada) Philips (Netherlands) Siemens (Germany) or other equal and approved. C. Approved Manufacturers of Cables: obtain cables and accessories from the EPABX supplier, where available, or from one of the following :Liban Cables Pirelli 2.2 (Lebanon) (England)

B.

CONNECTION MODULES A. IDC (Insulation Displacement Contact) Modules will comprise the terminal blocks in the MDF and distribution frames. They will be of high reliability, and will have the following minimum specifications: module size 10 pairs conductor diameter 0.4 to 0.8 mm insulation diameter 0.7 to 1.5 mm number of insertions 1000 times maximum contact resistance 0.02 ohm dielectric strength (60 Hz) 2000 V (r.m.s.) minimum insulation resistance 10000 Mega-ohm, at 500 V (dc)

2.3

DISTRIBUTION COMPONENTS

A. Distribution Cabinets: distribution cabinets will be of high professional quality, metal type, corrosion resistant, wall mounted by screws, with tamper proof removable screw covers, cable holder rings, labelling plates, equipped with relevant connecting strips, and have efficient capacities to fully wire the complete incoming cable and outgoing ones. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-126

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

B.

Connecting Strips will have thermoplastic bodies, nickel plated brass connectors, galvanized screw terminals in both sides, wire guides, and will have the following electrical specifications: rang of conductor diameter up to 1.2mm dielectric Strength (50 Hz) 1500v (r.m.s.) minimum insulation resistance 10000 Mega-ohm, at 500 V (dc) CONDUITS AND RACEWAY are to be provided in accordance with the relevant Section of the Specification.

C.

D. Telephone Outlets are to have modular grid box and cover plates similar to other socket outlets and switches described in Section "Wiring Devices" of the specification, with approved colour, cord-grip cover, wall mounted with screws. They are to be modular flat-oval telephone-jack plugs with compatible base sockets. Plugs will have positive locking latches. The connector will not vibrate loose, and its polarization will prevent improper insertion. Standard male plugs with compatible mural sockets may also be accepted, subject to the approval of the Engineer. 2.4 ELECTRONIC PRIVATE AUTOMATIC BRANCH EXCHANGE SYSTEM (EPABX) A DESIGN 1. NUMBERING: design is to permit station numbers to be assigned to lines at time of installation, in accordance with customer-desired numbering plan, and reassignment while in service to allow personnel moves without requiring number changes. OUTWARD CALL RESTRICTIONS: it is to be possible to assign to each extension, restriction for outward calls as follows: non-restricted: having unrestricted access to external lines for outward calls either by direct dialing or through operator semi-restricted: having access to external lines only for local calls by direct dialing or through operator restricted: having no access to external lines neither through direct dialing nor through operator. 3. SEGREGATION OF EXTERNAL TRUNK LINE: it is to be possible to segregate external trunk lines as follows: lines for outgoing calls accessible only by operators lines for outgoing calls accessible by operators and by all remaining non-restricted and semi-restricted extensions. 4. VOICE MAIL AND MESSAGING EQUIPMENT will be inherent part of the system, interconnected to the exchange so as to provide voice messaging features. The equipment will be modular, and will have 8 ports, 12 hours capacity, up to 100 mail boxes, and supplied by the PABX 48 V DC or the mains supply.

2.

ROOM STATUS SUB-SYSTEM AND HOTEL-FRONT-DESK EQUIPMENT will also be inherent part of the telephone system. The hotel front desk will be installed whereby the guest data, including check-in and checkout, are updated, displayed, and _____________________________________________________________________________________ Division 16 Electrical Works Page 16-127

5.

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr transferred to the exchange. Meanwhile, the front desk equipment will receive, from the exchange, all data related to call accounting, room status sub-system, and wake-up requests.

BHOTEL SPECIAL FEATURES: the system is to have the following minimum hotel features: 1. 2. one-digit hotel services: the numbering plane is to allow single digit dialling to hotel service facilities; such as front-desk, room service, restaurant, laundry, etc. music on hold: incoming calls to the operator console(s), which are placed on hold, are to be connected to music. The music source will be freely selectable by the hotel management. call protection for guests: In general, the guest-extensions will be blocked, by means of software management, against calls from the administration. Certain administrationextensions, such as management, etc.. however, may be entitled to call guests. automatic wake up: it is to be possible to provide an automatic wake up service to any guest. This feature will be initiated/cancelled by dialling a specific code via the guest station or through an authorized service station. The registration of a wake up time will not be affected should the guest use his station, and the feature will remain stored till the designated time, unless cancelled. do not disturb: any guest will be able to request that his telephone station be temporarily given a ""do-not-disturb" status. This feature will be initiated/cancelled by dialling a specific code via the guest station, the operator, or a specialized service station. During the do-not-disturb status, the guest may make internal or external calls from his station. The operator, or an authorized administration station will be able to over-ride the do-not-disturb in case of emergency. message waiting indication: it will be possible to initiate a message waiting indication in a guest room by voice mail, by the operator, or by the reception. This indication will be in a form of built-in light in the guest station. voice mail: the system will allow messages to be left for guests in the calling party's own language and voice. Messages may be left for a guest by an internal station or from outside the hotel. It will be possible to leave more than one message to any guest. room status sub-system: it will be possible to update the status of the guest room by dialling a code via the room station or an authorized administration station. The specification of room-status descriptions and corresponding codes will be according to the hotel administration and will include at least: occupied, vacant, cleaned, cleaning required, maintenance required, ready for sell, reserved, out of service, etc. The room status is directly sent to the hotel front desk equipment for recording and display. VIP service: top priority, at least, may be assigned to certain extensions where the hotel guest is a VIP. This privilege is to affect every necessary feature in order to properly serve a VIP, including dial access to operator, direct outward dialling, etc. call accounting: the system will provide comprehensive facilities for accurate accounting of all telephone costs so as to allow the hotel management to charge all guest usages of the hotel telephony. This feature is to be fulfilled in conjunction with other facilities specified herein.

3.

4.

5.

6.

7.

8.

9.

10.

B. CHARACTERISTICS _____________________________________________________________________________________ Division 16 Electrical Works Page 16-128

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

1.

EPABX is to be fully electronic, digital stored programme, microprocessor controlled with LSI switching circuits. Reed relays, mini-switches, cross-point switching and cross-bar techniques are not acceptable. EPABX is to be designed for use as a universal telephone exchange system for all applications. It is to be possible to connect any combination of DTMF and rotary dial telephones to the EPABX, with the provision of manufacturer-made interface modules as necessary within the EPABX and without the need to modify the assembly. CAPACITY is to be as follows: external trunk lines internal extensions operator's consoles : 20 lines : 200 lines : 2 consoles

2.

3.

GRADE OF SERVICE is to be as follows: incoming traffic outgoing traffic internal traffic : P = 0.01 : P = 0.01 : P = 0.001

traffic capacity per line: more than 0.22 erlang

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-129

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

4.

CHARACTERISTICS: EPABX is to be in accordance with Local Telephone Authorities recommendations and is to have at least the following characteristics: control control functions : stored programme : performed by LSI micro-processors and mini-processors : 1300 ohms (including telephone set) : less than 0.6 dB at 800 Hz, less than 1.5 dB between 300 and 3400 Hz

maximum loop resistance insertion loss

crosstalk attenuation : more than 70 dB (in 200 to 3,200 Hz band) leakage impedance power supplies: primary power battery : 220 V (+/-15%) a.c. single phase; 50 Hz : 48 V d.c. nominal (+/-12%) : more than 40 K ohms

ambient room temperature: 25 deg. C relative humidity : 90 %

compatible station : two-wire and/or three wire standard serial pulse or DTMF dialing. C. SYSTEM PERFORMANCE 1. EPABX FEATURES are to include, but are not limited to, the following: station-to-station calling: station user is to be able to directly dial other stations within EPABX system without assistance of operator direct outward dialing (DOD): non-restricted and semi- restricted station user is to be able to gain access to exchange network, without assistance of operator, by dialing an access code, receiving a second dial tone and then dialing desired network exchange number executive override (break-in): station user is to be able to enter existing two-party busy station connection; this intrusion is to be preceded by a warning tone; if a person called releases his line, he is automatically called back camp on busy: if internal extension called is busy, it is to be possible to dial a digit and to hang up; the two telephone stations are automatically called back as soon as they are simultaneously free _____________________________________________________________________________________ Division 16 Electrical Works Page 16-130

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

enquiry call: when telephone user is in conversation with the outside he is to be able to put his communication on hold, dial an internal number, consult privately, and then take back first communication call transfer: this is to enable any extension in the installation to directly divert an external communication to another extension without going through the operator dial access to operator: station users within switching system are to be able to reach operator by dialing a single digit, and operator may complete these calls to trunk facilities or other stations recall dial tone: this is to indicate to station user the successful use of the switchhook flash when requesting a service feature during an established call, and without causing a re-origination to occur line lockout with warning: this gives 30 seconds warning tone and then holds the line out of service when a station line remains off-hook for longer than 10 seconds without dialing; the hold out-of service is to be released when station goes on-hook splitting: station user is to be able to consult privately with one party on a call without third party hearing serial call: operator is to be able to complete an incoming trunk call to two or more station lines in succession without requiring the outside party to recall operator power failure transfer: this is to allow a limited number of pre-assigned stations to get access to or from the network in case of battery failure callback queuing for trunks: this allows the user to wait for a trunk to be idle: when the trunk is idle, the exchange rings back, then waits for user to go off- hook and dial the number direct distance dialing (DDD): this is to allow user to dial long distance calls without intervention of operator. 2. OPERATOR'S CONSOLE FEATURES are to include at least the following: facility to check status of any individual trunk or extension line ring-when-free facility for external calls transferred to a given busy extension automatic return to operator if an extension does not answer an outside call within 15 seconds time reminders: operator is to be automatically alerted after 30 seconds when an internal or outside call on the console is waiting calling number display: visual display of EPABX station seeking attendant assistance transfer of incoming call to wanted extension made by pushbutton key set priority: operator is to be able to interfere in an established communication for special announcements or transfer of incoming calls; warning tone is to be sent to _____________________________________________________________________________________ Division 16 Electrical Works Page 16-131

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr both conversing parties splitting: operator is to be able to consult privately with one party on a call without the other party hearing operator is to be able to connect any internal extension or outside trunk line with any other internal extension; operator is to be able to place an outgoing call for a station user without requiring the station user to hang up call hold: calls that cannot immediately be extended, are to be placed in a hold buffer; when required extension becomes available, the call is to be retrieved from hold buffer and extended to extension abbreviated dialing: operator is to be able to assign short dial codes for frequently called destinations automatic call supervision: if an unannounced extended call is not answered within a predetermined time, the call is to be automatically returned to the operator fault indication: any fault within the system is to be automatically detected and signalled by an alarm buzzer and an indicating lamp automatic and manual switch-over to night service: incoming CO trunk calls during night operation are to be routed to predetermined answering stations; routings are to be on a flexible basis by the attendant and are to remain in effect until changed.

D. CONSTRUCTION 1. CABINET: exchange components are to be grouped in a modular, totally enclosed, sheet metal cabinet, with lockable front access doors, and whole assembly is to fit into one integrated form. Cabinet is to be dust and insect proof, and ventilation is to be provided as required for specified ambient conditions and air-conditioning facilities. Range of temperatures recommended for continuous operation of the system are to be submitted to the Engineer. PLUG-IN EQUIPMENT: electronic circuits and components are to be plug-in card type, with solid state electronic components. Equipment is to be assembled neatly in racks. Sensitive equipment is to have dust protection covers.

2.

E.

OPERATOR'S CONSOLE 1. TYPE: desk-top, digital compact type, equipped to enable operator to provide all services required and have full control of system operation.

2.5

STANDARD TELEPHONE SETS A. Set Type: desk-type or wall-type as shown on drawings. Dial will be push-button operated, standard serial-pulse and DTMF, switchable. The telephone user will have access to all system features, subject to classes of service as assigned individually to each station.

B. Set Description: set is to be shock-resistant, made of moulded plastic, having approved design _____________________________________________________________________________________ Division 16 Electrical Works Page 16-132

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

and colour, and appropriate for the function intended. It will be dust and insect proof with bell and adjustable volume control. Set is to have lock-in jack ended connector cord, not less than 2.5 m long, for connecting the base to wall-outlet (desk-type sets), and a spiral connector cord between the handset and the base. Jacks are to snap-lock into corresponding mates, and may be released easily without special tools. C. Set Characteristics: push-button telephone pad with radial and mute buttons. Capsules will be sensitive, highly reliable, light weighted and rugged. The set will show a uniform frequency response and an optimum impedance adaption to the extension lines in the whole band from 300 to 3400 Hz. Both the receiver and the microphone will have an insulation resistance that is not less than 10 mega-ohms at 250 V(dc) between the two terminals (linked) and the metal body.

2.6

MANAGERIAL TELEPHONE SETS A. Type of Set: digital station, desk-type, with push-button dialling pads, complete with any interface modules needed for connection to the exchange. Sets will be advanced stations, designed and manufactured by the PABX manufacturer for the purpose. They are to address, and simplify the features offered by the system. B. An Executive Set will be multi-line set, with 12 programmable keys, alphanumeric display (minimum 2 lines), hands free operation, redial, hold, mute, transfer, volume controls, and equipped for message and voice-mail reception.

2.7

HOTEL-GUEST TELEPHONE SETS A HOTEL-GUEST TELEPHONE SETSS: desk-type, equipped for message and voice-mail reception, as detailed in 2.4. Dial will be push-button operated, standard serial-pulse and DTMF, switchable. Set will be designed and manufactured by the PABX manufacturer for the purpose, so as to access all relevant features.

2.8

CABLES AND OTHER ACCESSORIES A. Telephone Cables: will be multi-paired indoor type cables. Conductors will be made of solid plain copper or tinned copper, 0.6 mm diameter, PVC insulated, colour coded, twisted into pairs. Pairs are to be assembled into cable core which is wrapped with an insulating dielectric film, and an aluminium thin screen bonded to a grey PVC outer sheath. A drain wire (bonding wire) will be extended longitudinally between the screen and the PVC sheath. Manufacture's cable marking, including cable code and size, will be printed, every one meter, on sheath. B. Telephone Cables will be Classified: according to their location in the network into two types: riser cables (main cables), and distribution cables. Riser cables will be outgoing from, and incoming to, the MDF; whereas distribution cables will include the cables outgoing from distribution frames (cabinets) to distribution boxes as well as those outgoing to telephone outlets whatsoever. Telephone-Cable Sizes: will be selected to fulfil all the wiring relevant to existing telephone lines plus the spare requirements. The number of spare pairs in the cables shall satisfy the following conjunctive conditions:

C.

- for any cable, the ratio of the number of pairs used to the number of pairs available should not exceed 80%. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-133

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

D. Characteristics of Telephone Cables: telephone cables are to comply, at least, with the following specifications: Maximum conductor d.c resistance Maximum attenuation Maximum mutual capacitance between pairs Minimum insulation resistance (measured between each conductor against the others connected to the earthed screen) Minimum voltage rating 70 ohm/Km (at 20C) 1.6 db/Km (at 800 Hz) 150 nF/Km

500 Mega-ohms at 200V (d.c) 150 V

E . Jumper Wires: will be used in MDF and distribution frames (cabinets) for cross-connection of terminal blocks. They will be made of tinned copper conductors, 0.6 mm diameters, PVC insulated, twisted into two-colour pairs. F. Raceways: will include all conduits, cable trunking, and cable trays. Comply with the relevant sections of the Specifications.

G. Fixing, Labelling, and Marking Accessories: fixing accessories will include cable ties, clamp ties, push mounted ties, marker ties. Labels and markers will be made of white plastic or polyester, durable type, subject to the approval of the engineer. Each label will indicate, according to an approved labelling designations, the cable-number, and the two distribution units where the cable is coming from and going to.

2.9

MAIN DISTRIBUTION FRAME (MDF) A. DESCRIPTION OF MDF: the MDF will be made of high-quality aluminium alloy. It is to be standing, floor mounted, space saving, on-site assembled, flexible design, of modular sections, swing-out feature of compact terminal blocks as necessary, single sided or double sided, transparent covers for connection modules protection, cable ways, wire guide rings, easy break and test access, numbering plates, labelling strips for all terminal blocks, and frame earthing.

SIZE OF MDF: the MDF is to be large enough to accommodate the ultimate internal and external capacities of the PABX, and to wire the full capacities of all main cables plus 10% spare space. TERMINAL BLOCKS: each block (Head) will be composed of a set of horizontal connection modules. Connections are to be performed by quick-clip IDC (Insulation Displacement Contact) connectors, no soldering will be allowed. It is to be possible to directly access front points for inserting test probes, and provisions will be available for the insertion of over voltage and over current protection devices as necessary. There will be as many connection modules as needed to wire at least the full capacities of all existing cables, including every spare wire. POWER SUPPLY EQUIPMENT

2.10

A. STANDBY POWER SYSTEM: rectifier-charger and batteries are to supply continuous d.c. power at specified voltage to the EPABX. Capacity is to provide minimum eight hours _____________________________________________________________________________________ Division 16 Electrical Works Page 16-134

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

continuous operation without loss of functions or reduction in system capacity after normal power supply failure. Batteries are to be floated on load side of rectifier and kept continuously fully charged. B. RECTIFIER: to be solid state, with sufficient capacity to supply required power to EPABX and maintain batteries in fully charged condition. Quality of output voltage is to be within required limits of EPABX. Following restoration of normal power and full discharge of batteries, rectifier- charger is to return batteries to 90% full charge within 6 hours. BATTERIES: lead-acid, sealed, maintenance free, stationary type. Necessary hardware and wiring are to be provided inside PVC conduit for interconnection. Suitable mounting rack is to be provided for battery installation.

C.

PART 3 - EXECUTION 3.1 EXAMINATION: A. Examine: areas and conditions under which telephone systems are to be installed. Notify Contractor in writing of conditions detrimental to proper completion of the work. Do not proceed with work until unsatisfactory conditions have been corrected in a manner acceptable to Installer. Co-ordination with other Works: the contractor will undertake the proper co-ordination between the installations of the telephony system and those of all other systems. The layout shop-drawings will also reveal the measures taken therein, and every fixation principle, and detail, will be subject to the approval of the engineer. Layout and Fixations of Equipment: cubicles and cabinets will be laid out properly so as to ensure the optimum utilization of room areas and to reserve relevant spaces for maintenance activities as well as future extensions of the system. The availability of adequate lighting levels must also be ensured for all cubicles and cabinets; should it deem difficult to fulfil this condition at some location, a mains outlet will be provided nearby (less than 0.5 apart) so as special lighting can be provided during maintenance. Fixations will be as appropriate; above metallic chassis at the level of false floor for bottom-sided cabling, above floor for top-sided cabling, on wall for wall mounted units, under false floor or above false ceilings where preferable for small distribution boxes. After the layout of equipment is accomplished, all sorts of cubicles, cabinets, and system components will be labelled, and marked properly according to an approved labelling designations and materials. Raceways: telephone cables are to run in dedicated raceways segregated from those where power cables are laid. Moreover, telephone cables will not share undivided trays or paths with any other type of cables. The installation, and fixation will be as per the relevant section of the specification, field and installation work, unless otherwise is indicated herein.

B.

C.

D.

Cable Laying: before the start of cable works, the site will be properly checked in order to ensure that the raceways, whatsoever, are clean and dry. Cables will be carefully unreeled from drums, and pulled-in/laid-on raceways according to the approved shop drawings and work procedure. Specialized rolls and tools will be used for cable works so as the cables will not be dragged on ground or surfaces. Cables are to run concealed above cable trays, and through embedded pipes. Under false floors; if any, they may be arranged above ground, subject to the approval of the engineer. All pipe ends, whether occupied or empty, will be perfectly sealed against dirt, parasites, rates, and insects. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-135

E.

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Sealing material, or elements will be according to every specific site condition, subject to the approval of the Engineer. After the network is satisfactorily completed and tested, cables will be tied to cable trays and labelled as necessary. For any cable, the maximum distance between two successive ties will not exceed five meters except for vertical riser cables where the maximum distance will be two meters. Cables will be labelled at every terminal location, every bent, before every distribution unit, and at every fan-out. Moreover, vertical main cables, along the riser, will be labelled at lease twice in each floor. F. Cable Wiring: cables will be terminated at the distribution units where they will be held, fanned out properly, and wired to the terminal blocks or connecting strips. Wires will be tied into groups, in accordance with the order of pairs as per colour code, and corresponding to the relevant connection modules (or strips). Wiring to the terminal blocks in MDF and distribution frames (cabinets) will be performed by standard IDC connection tools, no soldering will be needed, whereas the wiring of distribution cables to the terminal strips in distribution boxes may be completed by screw drivers.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-136

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

G.

Jumper Wires: are to extend neatly between connection modules, moderately stretched, and guided by the specialized rings and hooks. No jumper will be left loose or imperfectly guided. The final arrangement of jumper wires within any cubicle will allow for an easy trace of any telephone line. Earthing: every cable, distribution unit, and equipment will be properly earthed as necessary and as recommended by manufacturers. Earthing system will ensure safety conditions and will eliminate noise effects. Earthing cables will be characterized by their green/yellow colour.

H.

3.2

ON-SITE TESTS, AND INSPECTION: A. Test Plans: all tests will be carried out according to a detailed test procedures which is submitted by the contractor and approved by the engineer. The tests will cover every aspect related to the specification of the material and their operation; including, but not limited to, visual inspections, insulation tests, measurements, and operation. All instruments to be used during the tests must have been calibrated and certified, by an authorized official laboratory, as complying with the specification of their manufacturers. On-Site Cable Tests: cables are to be tested to ensure that no damage have occurred to them during transportation to site and/or during the course of pulling-in and laying. A complete wire-to-wire continuity test is to be performed for every cable length. The contractor will have to replace any length where the electrical continuity is not verified for all wires. Then, a 10% sample of all cable lengths will be subject to an insulation test, according to the manufacturer specifications. Sampling will be random and as decided by the engineer. The contractor will have to replace a cable should its insulation resistance is below the minimum specified. On-Site System Tests: equipment will be tested to ensure that they are not damaged by transportation, correctly assembled and connected, properly powered, and operating as specified. The complete system tests will include the following minimum checks: Visual inspection of every component (including painting assembly, labelling, etc.) Dielectric strength and insulation resistances. System performance (including all operation features). Any other checks as necessary to ensure full compliance with the technical specifications. It will be demonstrated to the satisfaction of the engineer, that the installed equipment meet the requirements of the specification and is ready for takingover.

B.

C.

3.3

Experimental Period: after the on-site tests are satisfactorily completed in accordance with the technical specifications and approved procedures, and before final acceptance which is leading to provisional taking over; the contractor will assume a one-month experimental period during which the system performance will by fully demonstrated under actual operation conditions. This demonstration is to confirm, to the satisfaction of the engineer, that the system is free of remarks and is ready for provisional taking over. TRAINING, GUARANTEE, AND MISCELLANEOUS ITEMS A.

D.

Training: during the experimental period, the Contractor will undertake to train the client's operation and maintenance staff. This training course will be carried out _____________________________________________________________________________________ Division 16 Electrical Works Page 16-137

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr according to a detailed program to be submitted by the Contractor, at least two months before the commencement of the experimental period, and approved by the Engineer. The training course will fairly cover every aspect and detail concerned with the operation of the complete telephony system, and will provide the client's maintenance team with a first-level maintenance skills. B. Guarantee: during the experimental period, the system will be operating under the Contractor's supervision and responsibility. After the satisfactory completion of this period, the system will be taken over by the client, as per contract conditions, whereby a two-year guarantee period will commence. All spare parts, which might be needed to replace existing components during the guarantee period will be born by the Contractor unless it is proved that the component to be replaced is defected by abuse. As-Built Documents: the Contractor is to submit, on the date of provisional taking over, overall and complete as-built drawings and specifications. The originals plus three copies of those document will be handed over to the Client. Every copy of these documents will cover each unit, sub-unit, connection, installation, wiring and detail, as previously approved on submittals and shop drawings, and as amended (if any) by common agreement due to site conditions. The as-built drawings will also include a detailed description and designation of the wiring and jumpering inside every distribution unit so as to make each single telephone line, whatsoever, easily addressed, located, and identified; to the satisfaction of the Engineer. After-Sale Service: a maintenance contract may be concluded after the guarantee period upon the request of the Client. Therefore, the Contractor must demonstrate the availability of complete after-sale service. This service is to be guaranteed by a recognized local agent.

F.

G.

3.4

ADJUSTING AND CLEANING: A. B. C. Clean telephone equipment and components of dirt and construction debris upon completion of installation. Touch-up scratched or marred enclosure surfaces to match original finishes. Protect installed equipment and components from damage during remainder of construction period.

3.5

DEMONSTRATION: Upon completion of installation of telephone systems, and after telephone wire circuitry has been energized, demonstrate capability and compliance with requirements. Where possible, correct malfunctioning units at site, then retest to demonstrate compliance; otherwise, remove and replace with new units, and proceed with testing. Demonstrate to Owner that requirements for basic output signal levels, and values for attenuation and signal-to-noise ratios, have been achieved. END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-138

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16750 DATA SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Specification sections, apply to this Section. B. 1.2 Division-16 Basic Electrical Requirements sections apply to work specified in this section.

SUMMARY A. B. Data system work is indicated by drawings and schedules, and is hereby defined to include, but not be limited to data wiring/cabling, and ancillary equipment. Types of data system required for project include the following:

Patch panel Data outlets Wiring/Raceways Power supply any related accessories not specifically mentioned herein. C. 1.3 Raceways, electrical boxes and fittings, and cable trays, which are required in connection with the installation of voice and data systems, are specified in other Division-16 sections.

SUBMITTALS: A. B. Product Data: Submit manufacturer's data on system and components. Shop Drawings: Submit layout drawings of system and accessories including, but not necessarily limited to, service-entrance penetrations, apparatus, racks, terminals, and switching equipment. Agreement to Maintain: Prior to time of final acceptance, the Installer shall submit 4 copies of an agreement for continued service and maintenance of system, for Owner's possible acceptance. Offer terms and conditions for furnishing parts and providing continued testing and servicing, including replacement of materials and equipment, for one-year period with option for renewal of Agreement by Owner.

D.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-139

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

1.4

QUALITY ASSURANCE: A. Manufacturer's Qualifications: Firms regularly engaged in manufacture of Data systems and ancillary equipment, of types, ratings and capacities required, whose products have been in satisfactory use in similar service for not less than 5 years. Installer's Qualifications: Firms with at least 5 years of successful installation experience with projects utilizing data systems and equipment similar to that required for this project. Codes and Standards: 1. Electrical Code Compliance: Comply with applicable local code requirements of the authority having jurisdiction and NEC, including 800-Series articles as applicable to installation, and construction of telephone systems. FCC Compliance: Comply with Part 68 and Subpart J of Part 15, Federal communications Commission Rules, pertaining to telephone equipment and Class A computer registration by manufacturer. Provide data equipment with FCC labels indicating applicable FCC registration and numbering. D. DELIVERY, STORAGE AND HANDLING 1. 2. 3. E. Deliver equipment and components in factory-fabricated containers or wrappings, which properly protect equipment from damage. Store equipment and components in original packaging. Store inside in a well-ventilated space protected from weather, moisture, soiling, humidity, and extreme temperatures. Handle equipment and components carefully to prevent damage, breaking, and scoring of finishes. Do not install damaged units or components; replace with new.

B. C.

2.

SEQUENCING AND SCHEDULING: 1. Installer shall notify local operating company in writing of telephone interface connection requirements to ensure proper and timely interfacing of building telecommunication systems with the operating company's systems. Coordinate with other electrical work including wires/cables, electrical boxes and fittings, and raceways, to properly interface installation of telephone system with other work. Sequence installation of voice and data system with other work to minimize possibility of damage and soiling during remainder of construction.

2.

3.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-140

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

F.

MAINTENANCE: 1. Agreement to Maintain: Engage Installer who is willing to execute with Owner the required agreement for continued maintenance of the system.

PART 2 - PRODUCTS 2.1 MANUFACTURERS: A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering system equipment which may be incorporated in the work include, but are not limited to, the following: Approved Manufacturers of Cables: obtain cables and accessories from the EPABX supplier, where available, or from one of the following :Liban Cables Pirelli 2.2 (Lebanon) (England)

B.

WIRE CROSS-CONNECT PATCH PANELS A. DESCRIPTION: Patch panels shall be similar to AT&T 110 Connector System which will be used to terminate and interconnect cables and to route circuits throughout the distribution system. The basic components of the 110 Connector System will be the 110 Wiring Block, patch cords, and label inserts. B. THE 110 WIRING BLOCK (CATEGORY 5) is to be a fire retardant, moulded plastic block with 4 horizontal index strips that secure and organize 25 cable pairs each. The index strips are to be marked with five tip colours that help locate pairs quickly and they are to accommodate 22 through 26 AWG cable conductors. THE 110 CONNECTING BLOCK (CATEGORY 5) is to be a 3, 4 or 5 pair connecting blocks rated to EIA/TIA-568A Category 5, for 100 MHz. Each is to consist of a 1-piece fire retardant moulded plastic housing containing solder-plated quick clips that slice through the insulation on conductors as they are pushed onto the wiring block. It is to be double-ended, one end to accept 22 through 26 AWG jumper wire or patch cords and the other to terminate the cable conductors. The front of the connecting block is to be color coded allowing rapid pair identification and termination. The blocks will fasten onto the 110 wiring block to provide an electrically tight connection between cable connectors terminated on the wiring block and jumper wires or patch cords.

C.

D. THE 110 CONNECTOR SYSTEM will be of two basic types the 110 Cross Connect System and the 110 Patch Panel System. E. F. THE 110 CROSS CONNECT SYSTEM: typically used for low-speed data applications because it requires short lengths of jumper wires to link the cable pairs at two circuit termination points.

THE 110 PATCH PANEL SYSTEM: typically used with high speed applications because patch cords are needed for circuit termination. They are to be equipped with 12, 36 and 108-8 position modular jacks. Patch panels will be provided with 2x4 pair and 2x1 pair factory assembled patch leads for each information point. Patch leads will be colored separately for voice and data. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-141

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

2.3

HORIZONTAL WIRING A. HORIZONTAL CABLING is to extend from the patch panel to the work area information (data) outlet. It includes cross connects in the patch panel, the horizontal cable and the outlet at the work areas. B. HORIZONTAL CABLES will connect the work area outlet to the cross connect system in the patch panel. Cables will be unshielded twisted pair (UTP). Each cable will be formed of four pairs category 6 plenum rated when installed on cable trays and zero halogen when installed in conduits and trunking to EIA/TIA 568A. HORIZONTAL CABLES: for each data outlet two cables 4 pair will be required

C. 2.4

DATA OUTLETS A. DATA OUTLET is to have a modular grid box & cover plate similar to devices as described in Section 16143 of the specifications. Jacks are to be modular 8 - position RJ45.

PART 3 - EXECUTION 3.1 EXAMINATION: A. Examine: areas and conditions under which data system is to be installed. Notify Contractor in writing of conditions detrimental to proper completion of the work. Do not proceed with work until unsatisfactory conditions have been corrected in a manner acceptable to Installer. Co-ordination with other Works: the contractor will undertake the proper co-ordination between the installations of the data system and those of all other systems. The layout shop-drawings will also reveal the measures taken therein, and every fixation principle, and detail, will be subject to the approval of the engineer. Raceways: data cables are to run in dedicated raceways segregated from those where power cables are laid. Moreover, data cables will not share undivided trays or paths with any other type of cables. The installation, and fixation will be as per the relevant section of the specification, field and installation work, unless otherwise is indicated herein. Jumper Wires: are to extend neatly between connection modules, moderately stretched, and guided by the specialized rings and hooks. No jumper will be left loose or imperfectly guided. The final arrangement of jumper wires within any cubicle will allow for an easy trace of any data line. Earthing: every cable, distribution unit, and equipment will be properly earthed as necessary and as recommended by manufacturers. Earthing system will ensure safety conditions and will eliminate noise effects. Earthing cables will be characterized by their green/yellow colour.

B.

C.

D.

E.

3.2

ON-SITE TESTS, AND INSPECTION:

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-142

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr A. Test Plans: all tests will be carried out according to a detailed test procedures which is submitted by the contractor and approved by the engineer. The tests will cover every aspect related to the specification of the material and their operation; including, but not limited to, visual inspections, insulation tests, measurements, and operation. All instruments to be used during the tests must have been calibrated and certified, by an authorized official laboratory, as complying with the specification of their manufacturers. On-Site System Tests: equipment will be tested to ensure that they are not damaged by transportation, correctly assembled and connected, properly powered, and operating as specified. The complete system tests will include the following minimum checks: Visual inspection of every component (including painting assembly, labelling, etc.) System performance (including all operation features). Any other checks as necessary to ensure full compliance with the technical specifications. It will be demonstrated to the satisfaction of the engineer, that the installed equipment meet the requirements of the specification and is ready for takingover.

B.

D.

Experimental Period: after the on-site tests are satisfactorily completed in accordance with the technical specifications and approved procedures, and before final acceptance which is leading to provisional taking over; the contractor will assume a one-month experimental period during which the system performance will by fully demonstrated under actual operation conditions. This demonstration is to confirm, to the satisfaction of the engineer, that the system is free of remarks and is ready for provisional taking over.

3.3

GUARANTEE, AND MISCELLANEOUS ITEMS A. Guarantee: during the experimental period, the system will be operating under the Contractor's supervision and responsibility. After the satisfactory completion of this period, the system will be taken over by the client, as per contract conditions, whereby a two-year guarantee period will commence. All spare parts, which might be needed to replace existing components during the guarantee period will be born by the Contractor unless it is proved that the component to be replaced is defected by abuse. As-Built Documents: the Contractor is to submit, on the date of provisional taking over, overall and complete as-built drawings and specifications. The originals plus three copies of those document will be handed over to the Client. Every copy of these documents will cover each unit, sub-unit, connection, installation, wiring and detail, as previously approved on submittals and shop drawings, and as amended (if any) by common agreement due to site conditions. The as-built drawings will also include a detailed description and designation of the wiring and jumpering inside every distribution unit so as to make each single telephone line, whatsoever, easily addressed, located, and identified; to the satisfaction of the Engineer. After-Sale Service: a maintenance contract may be concluded after the guarantee period upon the request of the Client. Therefore, the Contractor must demonstrate the availability of complete after-sale service. This service is to be guaranteed by a recognized local agent.

B.

C.

3.4 ADJUSTING AND CLEANING: _____________________________________________________________________________________ Division 16 Electrical Works Page 16-143

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

A. B. C.

Clean equipment and components of dirt and construction debris upon completion of installation. Touch-up scratched or marred enclosure surfaces to match original finishes. Protect installed equipment and components from damage during remainder of construction period. END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-144

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16770 PUBLIC ADDRESS SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Requirements of the following Division 16 Sections apply to this Section: 1. Basic Electrical Requirements. 1.2 SUMMARY A. This Section describes the Public Address System. The systems is components include, but are not limited to: 1. 2. 3. 4. 5. 6. 7. 8. B. Operators console/microphone Playback Cassette AM/FM tuners CD Player Mixer Preamplifier Central Rack and Cabinets Wiring Speakers.

Related Sections: The following Division 16 Section contains requirements that relate to this Section: 1. "Raceways", for raceways used for public address system cables. 2. "Electrical Boxes and Fittings", for boxes, cabinets, and fittings used with public address systems.

1.3

SYSTEM DESCRIPTION A. General: The Public Address System shall be a complete system for amplifying sound signals from input devices and distributing them to loudspeakers at various locations. B. System Performance Objectives: System is to be designed for Music Background and paging under normal conditions, Pre-Recorded messages via the digital announcer or on the cassette recorder are to be manually switched in, and are to have automatic priority over the AM/FM tuner. By using the microphone, operator is to have priority over audio or message cassette inputs within the system. In case of fire alarm the interface should be provided to over ride the system by a fire message coming from fire alarm system. Sound distribution to zones is to be controlled by zone selector controls. System Design Criteria: the performance criteria are to be achieved as summarised below:-

C.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-145

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr average sound pressure level: 85 dB with respective amplifiers set at 50% of maximum volume uniformity coverage: within +/-5 dB frequency response to be achieved in coverage area: 500 Hz - 15 kHz (+/-3 dB bandwidth).

1.4

SUBMITTALS A. General: Submit the following in accordance with Conditions of Contract and Division 1 Specification Sections. B. C. Product data for each type of product specified. Shop drawings detailing Public Address System including, but not limited to the following: 1. 2. 3. 4. 5. Exact and final location of all equipment and apparatus Block diagrams indicating the proposed interconnection of equipment. Fabrication and assembly information Rack arrangements. Proposed mounting method for loudspeakers and other items of substantial weight.

D. Wiring Diagrams detailing wiring for power, signal, and control differentiating clearly between manufacturer-installed wiring and field-installed wiring. Identify terminal numbers and wiring color codes to facilitate installation, operation, and maintenance. E. Maintenance data for materials and products, for inclusion in Operating and Maintenance Manual specified in Division 1 and Division 16 Section "Basic Electrical Requirements." Provide complete manual material concurrently with system submittal and provide updated final versions of manuals one month before completion of construction and final system turnover.

1.5

QUALITY ASSURANCE A. Installer Qualifications: Engage an experienced Installer who is a factory-authorized sales and service representative to perform the work of this Section. Refer to Division 1 Section "Definitions and Standards" for definition of experienced Installer. Upon request, submit evidence of such qualifications to the Engineer. B. C. Electrical Component Standard: Provide work complying with applicable requirements of NFPA 70 "National Electrical Code." EIA Compliance: Comply with the following Electronics Industries Association Standards: 1. Public Address Systems, EIA-160. 2. Loudspeaker, Dynamic Magnetic Structures, and Impedance, EIA-299-A. 3. Racks, Panels, and Associated Equipment, EIA-310-A. 4. Amplifiers for Public Address Equipment, SE-101-A.

5. Speakers for Public Address Equipment, SE-103. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-146

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

6. Microphones for Public Address Equipment, SE-105. 1.6 DELIVERY, STORAGE, AND HANDLING A. Deliver products in factory containers. Store in clean, dry space in original containers. Protect products from fumes and construction traffic. Handle carefully to avoid damage. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated in the work include, but are not limited to the following: B. Manufacturers: Subject to compliance with requirements, provide products by one of the following: (Netherland) (Germany) (Japan)

Philips Siemens TOA 2.2 SYSTEM REQUIREMENTS

A. General: Provide complete and fully functional Public Address System using materials and equipment of types, sizes, ratings, and performances as indicated. Use materials and equipment that comply with referenced standards and manufacturers' standard design and construction in accordance with published product information. Coordinate the features of materials and equipment so they form an integrated system with components and interconnections matched for optimum performance of specified functions. B C Quality Products: High quality products, fully professional standard shall be provided for this Contract. Standard Products: The equipment provided shall be standard products of manufacturers regularly engaged in the manufacture of the products and shall essentially duplicate material and equipment that have been in satisfactory use for at least two years. In as far as possible, all components in the system shall be standard commercial design that comply with the requirements stated herein. Standard Equipment Racks: Where multiple racks are required, such as amplification racks, these are to be configurated as follows:-

Identical layout of rack-mounting equipment, to ease documentation and maintenance. Use of identical equipment, such as standard amplifiers for example. Allow a minimum of 20% of unused space for future expansion, these being filled with
blank panels.

Meet the ventilation requirements specified elsewhere.


_____________________________________________________________________________________ Division 16 Electrical Works Page 16-147

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Adequate Ventilation: is to be provide for all equipment. At least one 1-3/4 in. perforated or louvered ventilation panel shall be mounted above and below each amplifier or between each amplifier when adjoining when adjoining one another vertically in a common equipment rack. In addition, ventilation panels shall be mounted at the top and bottom of the equipment rack to further facilitate connective cooling. Physical Security: All equipment and components shall be firmly secured in place with all mounting supports and fastenings. Manufacturer's Installation Recommendations: Shall be adhered to unless explicitly in conflict with these specifications in which case the conflicts shall be brought to the attention of the Engineer for a decision. Loudspeaker Cable Sizing: Submit drawings illustrating the proposed cable runs, the cable size utilized will provide no more than 0.5 dB insertion loss when used with the loudspeaker power distribution supplied: (calculated as a function of the DC-loop resistance of the cable and the nominal impedance of the loudspeaker load, transferred to the primary), a minimum size of 0.9 mm diameter will be used in any case, to be increased as necessary in case of lengths being extended beyond what is expected. Loudspeaker Distribution Circuits: Conductors, Loudspeaker circuits are to be untinned stranded copper. Each conductor is to BCE individually insulated and each cable shall be provided with an overall jacket. Each cable is to meet the Code requirement for the voltage level applied. Cables providing common functions are to be colour-coded identically and each cable shall be clearly, permanently, and logically marked at both end with an appropriate cable designation. Labeling methods must be approved by the Contracting Officer. Termination is to be made with self-insulating mechanical connectors. All termination techniques must be approved by the Contract officer. Signal Earthing: The equipment cabinets will be earthed to a true earth providing less than 0.1 ohm resistance between it and the system's electrical earth. Interference Protection: All equipment shall be installed so as to prevent electromagnetic, electro-acoustic or other outside interference from causing anomalous system performance. Nameplates inscribed in English are to be firmly affixed to each major equipment item. Each nameplate is to include the manufacturer's name, address, model or catalogue number, and a definition of the equipment type ("amplifier", equalizer", etc.). The Nameplates are to be labeled by means of silk-screening, engraving, or by "metal-photo" process. Fixed Equipment are to have all controls, indicators an cable termination points, clearly, logically and permanently labeled by silk-screening, engraving or other methods specified herein. Portable Equipment: are to be marked with durable plastic tags to identify its function and the system or subsystem with which it is associated. This equipment shall be delivered when the installed system has been tested and accepted. Alignment: All equipment is to be mounted square and plumb and in alignment with other building fixtures. Conflicts with other building elements must be addressed to the Engineer who will approve the resolution.

G H

M N O P

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-148

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr Touch-up Paint: From the manufacturers of the equipment is to be supplied and applied in the event that the equipment becomes marred during shipping, handling and/or installation and until the installation is accepted by the Engineer.

2.3

MICROPHONE CONSOLE A The microphone station is to be limited to the matrix controller, providing sample set-up regardless of the number of control zones, equipment or circuiting switches. Functions and the number of function switches on the microphones touch screen on the LCD, can be easily setup to meet a particular application, assuming greater operational flexibility that can be found in a conventional mechanical system. Microphone shall be equipped with interface, memory-card. Specification: Operation Microphone Speaker output Recording output B

Touch screen method -70 -50 dBv, adjustable in 2 dB steps. 200 mW. 600 3dB. ,

The operator's console is to have, in addition to the standard Microphone station, level meters, one LED for each zone output.

2.4

PLAYBACH CASSETTE A Type: rack mounted, high quality, auto-reverse/auto-stop, 4-track, mono/stereo type with speed tolerance of 10%, complying with IEC 94 or other approved standard and accepting standard cassettes through front panel selector switch. B Heads and Motors: recorder is to have separate heads for play, record and erase functions, three motors (two for fast winding in two directions and third for record/playback at two speeds), and noise reduction system. C Controls: recorder is to have fast wind and re-wind, playback, record and stop controls, two illuminated peak level indicators, pause control, resettable digital counter, level controls for recording and play-back, on/off switch, microphone/headphone sockets and radio and line inputs. D Protection is to be provided against input overloads to reproduce strong signals without distortion. E Edit/Cue Facility is to be provided to permit listening to tape during fast forward or backward winding and to identify particular parts of tape for editing.

2.5

AM/FM TUNER A Type: AM/FM Tuner is to be with digital display shows currently tuned radio band and frequency and automatic tuning mode selects available stations. Tuner is to have 5 AM & 5 FM stations memory and to be internally microcomputer - controlled PLL synthesized circuit prevents signal deviation. Tuner is to include AM Antenna, FM antenna, antenna combiner and antenna cables.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-149

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

B. Technical Specifications: Tuning range Power Supply 2.6 : : AM 522 to 1620 kHz FM 87.5 to 108 MHz 220 V, 50 Hz.

COMPACT DISK (CD) PLAYER A. Type: rack mounted, high quality, compact disk playback type with 5-disk cartridge standard, single beam laser assembly and auto playback program facilities. B. Characteristic: minimum requirements are to be as follows: playback system : compact disk 2 Hz - 20 kHz +/-0.1 dB +/-0.5 degrees not less than 100 dB not less than 96 dB 96 dB (kHz) not greater than 0.0025% (1 kHz) -90 dB (at max. output level) not less than 60 dB 2 V (rms) : : 10 kohm

frequency range amplitude linearity : phase linearity signal-to-noise ratio dynamic range channel separation T. H. D. : : : : :

intermodulation distortion out-bank rejection : Max. audio line out Min. load impedance Power supply 2.7 :

220 V, 50 Hz.

MIXING AMPLIFIER AND PREAMPLIFIER EQUIPMENT A mixing preamplifier: completely integrated, four line level audio inputs. Printed circuit boards (PCBs) are to allow different inputs e.g. microphone balanced/unbalanced, music in/out etc. Each channel is to have sliding pre-set logarithmic potentiometer, treble and bass tone control, auto-faders, VU meter and programmed priority operation between the inputs, using plugged-in programmable priority board. Mixing preamplifier is to be connected to zone selector unit. B. mixing preamplifier performance is to be at least as follows: effective frequency range (+/-3 dB): 50-15000 Hz signal/noise ratio, all controls down (50-15000 Hz flat): 80 dB

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-150

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

total harmonic distortion (nominal loudspeaker power, at 1000 Hz): output level (load impedence): input sensitivity: microphone: others: outputs: power supply voltage: 2.8 A. B. C. POWER AMPLIFIER

less than 0.1% 0 dB m/0.775 (600 ohm) (600 ohm)/0.5 mV (adjustable) 2.5 mV (adjustable) 2 lines, 600 ohm 220 V, 50 Hz.

INPUT LEVEL: to be adjustable with a preset potentiometer on front panel. Illuminated VU meter is to be mounted on front panel. OUTPUT: to be fully protected against failure due to mismatch, short circuits, thermal and electrical overloads, overdrive or eventual transients. PERFORMANCE: each power amplifier is to have at least the following performance: output power effective frequency range input input impedance output voltage (load impedance) signal/noise ratio (all controls closed) total harmonic distortion at 1000 Hz intermodulation distortion ambient temperature power supply : 85 dB : less than 0.5% : less than 1% : 30 deg. C : 220 V, 50 Hz : To suit the rating of loudspeakers : 50 Hz to 18000 Hz : 0 dBm line level (0.775 V) : 50 k.ohm : 70 V (50 ohm)

2.9

LOUDSPEAKERS

A. Projector type Loudspeaker: is to be of use for column mounting, with primary transformer taps of 12, 6 and 3 watts of audio power. The Loudspeakers are to have the following _____________________________________________________________________________________ Division 16 Electrical Works Page 16-151

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

performance: a. power rating b. frequency response c. pressure sensitivity d. opening angle e. voice coil : : : : : 12 watts 100 Hz to 16000 kHz 92 dB (1W, 1m, 1kHz) 90 copper

B. Baffle type Loudspeaker: is to be of use for ceiling mounting, with primary transformer taps of 6, 3 and 1.5 watts of audio power. The Loudspeakers are to have the following performance: a. power rating b. frequency response c. pressure sensitivity d. opening angle e. voice coil : : : : : 6 watts 100 Hz to 16000 kHz 92 dB (1W, 1m, 1kHz) 90 copper

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-152

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

B. Speaker Layout: is shown for tender purposes. Tenderer to advise on the suitability of the proposed layout and recommended any changes which may improve intelligibility to meet the design criteria. 2.10 CENTRAL RACKS AND CABINETS A. Central racks are to contain mixing preamplifiers, preamplifiers, zone selector (if any) relay modules, power supply module, power amplifier modules and output terminal module. Racks are to be 19-inch standard frame racks, withdrawable and hinged. Equipment is to be mounted and designed for 19- inch rack mounting. Cabinets are to be 19-inch frame, totally enclosed, with side and rear panels removable, and cable entrance at rear, top or bottom. Surface finish is to be textured and of approved colour. Frames are to be anodized aluminum sections. Each frame is to be provided with ventilation rack, including automatically operated fan with thermostatic control. Suitable ventilation openings are to be provided. Enclosure is to be IP 42 to IEC 144 for indoor installation. Storage: rack cabinets are to have storage drawers for cables and accessories. Mains wiring: equipment is to operate from 220 V, 50 Hz mains and is to be capable of continuous operation under any load conditions with variations of +/- 10% of nominal voltage. Mains wiring inside console is to be totally segregated from low-level signal wiring. Electric connections: other than those for low-level signals, are to be by push-on spade clips or multi-connector blocks. Low-level signal wiring: heavily braided, PE insulated, screened cable, PVC sheathed with standard DIN plug connections. Amplifier output lines are to be run within the console as twisted pairs heavily screened with tinned copper braid. Hum-producing earth return loops are to be avoided. Power supply: complete power supply unit is to be provided, independently fused on the live conductor, with mains front indicator light, on/off switch, cartridge-type fuse and fuse-holder with blown fuse indicator lamp.

B.

C. D.

E. F.

G.

2.11

PUBLIC ADDRESS SYSTEM CABLING A. Conduits And Raceways to comply with Section 16110 of the Specification. B. Cables For Public Address Distribution: rated for 200 V (maximum) operating voltage, finely stranded tinned copper, 0.9 mm diameter (minimum), polyethylene insulated, twisted pair and aluminized polyester shield, stranded tinned drain wire, PVC oversheathed, as Belden 8762 or other equal and approved. Microphone Cable: PE insulated, finely stranded tinned copper conductor, with copper braid screen and PVC oversheath.

C.

PART 3 - EXECUTION _____________________________________________________________________________________ Division 16 Electrical Works Page 16-153

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

3.1

EXAMINATION A. Examine conditions, with the Installer present, for compliance with requirements and other conditions affecting the performance of Public Address system work. B. Do not proceed until unsatisfactory conditions have been corrected. INSTALLATION A. General: Install system in accordance with NFPA 70 and other applicable codes. Install equipment in accordance with manufacturer's written instructions. B. C. Wiring Methods: Install wiring in raceway except within consoles, desks, and counters. Conceal wiring. Impedance and Level Matching: Carefully match input and output impedances and signal levels at signal interfaces. Provide matching networks where required.

3.2

D. Control Circuit Wiring: Install control circuits in accordance with NFPA 70 and as indicated. Provide number of conductors as recommended by system manufacturer to provide control functions indicated or specified. E. Install exposed cables parallel and perpendicular to surfaces or exposed structural members, and follow surface contours. Secure and support cables by straps, staples, or similar fittings so designed and installed as not to damage the cables. Secure cable at intervals not exceeding 75 cm and not more than 15 cm from every cabinet, box, or fitting. Wiring Within Enclosures: Provide adequate length of conductors. Bundle, lace, and train the conductors to terminal points with no excess. Provide and use lacing bars.

F.

G. Provide physical isolation from each other for line level, speaker, and power wiring. Run in separate raceways or provide 30 cm minimum separation where exposed or in same enclosure. Provide additional physical separation as recommended by equipment manufacturer. H. Splices, Taps, and Terminations: Make splices, taps, and terminations on numbered terminal strips in junction, pull, and outlet boxes, terminal cabinets, and equipment enclosures. I. Identification of Conductors and Cables: Use color coding of conductors and apply wire and cable marking tape to designate wires and cables so all media are identified in coordination with system wiring diagrams. Weatherproofing: Weatherproof units to be mounted out-of-doors or exposed to weather in any degree.

J.

K. Repairs: Wherever walls, ceilings, floors, or other building finishes are cut for installation , repair, restore, and refinish to original appearance.

3.3

EARTHING A. Provide equipment earthing connections for Public Address System as required or indicated. Tighten connections to comply with tightening torques specified in UL Standard 486A to assure permanent and effective earthing.

B. Earthing equipment, conductor, and cable shields to eliminate shock hazard and to minimize to _____________________________________________________________________________________ Division 16 Electrical Works Page 16-154

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr the greatest extent possible, earth loops, common mode returns, noise pickup, cross talk, and other impairments. Provide 5-ohm earth at main equipment location. Measure, record, and report earthing resistance.

3.4

FIELD QUALITY CONTROL A. Manufacturer's Field Services: Provide services of a factory- authorized service representative to supervise the field assembly and connection of components and the pretesting, testing, and adjustment of the system. B. Pretesting: Upon completing installation of the system, align, adjust, and balance the system and perform complete pretesting. Determine, through pretesting, the conformance of the system to the requirements of the Drawings and Specifications. Correct deficiencies observed in pretesting. Replace malfunctioning or damaged items with new, and retest until materials satisfactory performance and conditions are achieved. Testing: Upon completion of pretesting, notify the Engineer a minimum of 10 days in advance of acceptance test performance. Schedule and conduct tests in his presence. Provide a written record of tests results.

C.

D. Operational Test: Perform an operational system test to verify conformance of system to these Specifications. Perform tests that include originating program and page material at microphone outlets, all preamplifier program inputs, and all other inputs. Observe sound reproduction for proper volume levels and freedom from noise. E. Signal-To-Noise Ratio Test: Measure the ratio of signal to noise of the complete system at normal gain settings using the following procedure: 1. Disconnect a microphone at the connector or jack closest to it and replace it in the circuit with a signal generator using a 1,000-Hz signal. Replace all other microphones at the corresponding connectors with dummy loads, each equal in impedance to the microphone it replaces. Measure the ratio of signal to noise. Repeat the test for each separately controlled zone of loudspeakers. The minimum acceptance ratio is 50 dB.

2. 3. F.

Distortion Test: Measure distortion at normal gain settings and rated power. Feed signals at frequencies of 50, 200, 400, 1,000, 3,000, 8,000, and 12,000, Hz into each pre-amp channel and measure the distortion in the power amplifier output. The maximum distortion at any frequency is 3 percent total harmonics.

G. Acoustic Coverage Test: Feed pink noise into the system using octaves centered at 4,000 and 500 Hz. Use a sound level meter with octave band filters to measure the level at five locations in each zone. For spaces with seated audiences, the maximum permissible variation in level is plus or minus 2 dB and the levels between locations in the same zone and between locations in adjacent zones must not vary more than plus or minus 3 dB. H. Power Output Test: Measure the electrical power output of each power amplifier at normal gain setting at 50, 1,000, and 12,000 Hz. The maximum variation in power output at these frequencies must not exceed plus or minus 1 dB. I. Inspection: Make observations to verify that units and controls are properly labeled, and interconnecting wires and terminals are identified. Provide a list of final tap settings of speaker line matching transformers.

J. Retesting: Rectify deficiencies indicated by tests and completely retest work affected by such _____________________________________________________________________________________ Division 16 Electrical Works Page 16-155

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr deficiencies at Contractor's expense. Verify by the system test that the total system meets the Specifications and complies with applicable standards. Provide a written record of all retest results.

3.5

COMMISSIONING A. Train Owner's maintenance personnel in the procedures and schedules involved in operating, troubleshooting, servicing, and preventative maintenance of the system. Provide a minimum of three hours training. B. C. Schedule training with Owner through the Engineer, with at least 7 days advance notice. Occupancy Adjustments: When requested by the Engineer within one year of date of Substantial Completion, provide on-site assistance in adjusting sound levels, resetting matching transformer taps, and adjusting controls to suit actual occupied conditions. Provide up to three visits to the site for this purpose.

3.6

CLEANING AND PROTECTION A. Prior to final acceptance, clean system components and protect from damage and deterioration.

END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-156

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16780 MASTER ANTENNA AND DISH SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section.

1.2

SUMMARY A. distribution network comprising cables, amplifiers, tap-offs, outlets and related accessories

1.5

SUBMITTALS A. B. General: Submit the following according to the Conditions of the Contract and Division 1 Specification Sections. Product data for products specified in this Section. Include data on features, switching technique, system expandability, components, ratings, and performance. Include dimensioned plan and elevation views of components and enclosures and details of control panels. Show access and working space requirements. All Construction and installation details. Complete and detailed cable routing with calculations for signal attenuation, connector losses and signal levels. Maintenance data for systems and products to include in "Operating and Maintenance Manual" specified in Division 1. Include the following: 1. 2. 3. F. Detailed operating instructions covering operation under both normal and abnormal conditions. Routine maintenance requirements for system components. Lists of spare parts and replacement components recommended to be stored at the site for ready access.

C. D. E.

Wiring diagrams and schematic diagrams detailing internal and interconnecting wiring for power, signal, and control and that distinguishes between field-installed and factory-installed wiring. Product certificates signed by manufacturer certifying products comply with specified requirements.

G.

1.6

QUALITY ASSURANCE

A. Manufacturer Qualifications: Firms experienced in manufacturing systems and equipment of _____________________________________________________________________________________ Division 16 Electrical Works Page 16-157

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

the same types and capacities used for this Project that have a record of successful in-service performance. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. B. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated in the Work include, but are not limited to, the following: Manufacturers: Subject to compliance with requirements, provide products by the following or other equal and approved: Master Antenna Systems: Philips Katherein Wisi Siemens 2.3 MATV SYSTEM I. J. Distribution Power Amplifiers: Variable gain. Powered through signal distribution cable or by an integral power supply with 220-V, 50-Hz nominal input. Line Taps: Signal power splitters and isolation taps are directional couplers, metal enclosed with brass connector parts. Power throughput capacity exceeds load by 25 percent minimum for items in signal circuits used to supply cable-powered amplifiers. Comply with the following: 1. 2. 3. K. L. M. N. Return Loss: 17 dB. RFI Shielding: 100 dB, minimum. Isolation: 24 dB, minimum. (Netherland) (Germany) (Germany) (Germany)

Signal Traps: Packaged filters tuned to interference frequencies encountered in Project. Attenuators: Adjustable to eliminate overload. Terminating Resistors: Enclosed units rated 1/2 watts. Outlets: Flush type with the following features and characteristics except as otherwise indicated. 1. 2. 3. 4. Wall Plates: Match materials and appearance of power convenience receptacle outlets in the same space. Connectors: Female type with metallic parts of anodized brass, beryllium copper, or phosphor bronze. Attenuation: Less than 0.1 dB. VSWR: Less than 1.15 to 1.

2.11 SIGNAL TRANSMISSION COMPONENTS _____________________________________________________________________________________ Division 16 Electrical Works Page 16-158

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

A.

Cable, General: Coaxial cables have 75 ohm (+/- 1%)nominal impedance and are 100 percent factory sweep tested, 5 to 450 MHz, by the structural return loss method. Cables run in environmental air spaces are listed for use in plenums. The following types are included: 1. 2. 3. MATV Outdoor Antenna Cable: RG 59/U, solid polyethylene dielectric, foil plus tinned copper braid shield with 100 percent shielding factor, No. 20 or 22 solid copper or copper-clad steel conductor, and black PVC jacket. MATV Indoor Trunk Cable: RG 11/U, cellular polyethylene dielectric, bare copper braid shield with 95 percent minimum shielding factor, 2,5 mm2 solid bare copper conductor, and PVC jacket. MATV Indoor Branch Cable: RG 6/U, cellular polyethylene dielectric, bare copper braid shield with 95 percent minimum shielding factor, 0,75 mm2 solid copper covered steel conductor, and PVC jacket.

B.

MATV Coaxial Cable Connectors: Type F, 75 ohms.

PART 3 - EXECUTION 3.1 INSTALLATION, GENERAL A. B. Outdoor Installation: Conform to ANSI C2, "National Electrical Safety Code." Surge Suppressors Installation: Where AC power-operated devices are not protected against voltage transients by integral surge suppressors, install surge suppressors at the devices' power line terminals. Wiring Method: Cable. Conceal cable in accessible ceilings, walls, and floors wherever possible. Wiring Within Enclosures: Bundle, lace, and train the conductors to terminal points with no excess. Provide and use lacing bars and distribution spools. Pulling Cable: Do not exceed manufacturer's recommended pulling tensions. Do not install bruised, pinked, scored, deformed, or abraded cable. Do not splice cable between indicated termination, tap, or junction points. Remove and discard cable where damaged during installation and replace it with new cable. Exposed Cable: Install parallel to building lines, follow surface contours, and support as recommended by manufacturer. Equalization of Video Signals: Where system performance may be degraded in certain operating modes because of varying connections of multiple devices from mode to mode, revise component connections and install video distribution amplifiers and attenuators as required to provide consistent high-level performance. Splices, Taps, and Terminations: For power and control wiring use numbered terminal strips in junction, pull, and outlet boxes, terminal cabinets, and equipment enclosures. Tighten connections to comply with tightening torques specified in UL Standard 486A. Grounding: As recommended by manufacturers except as otherwise indicated.

C. D. E.

F. G.

H.

I.

3.2 MATV SYSTEM INSTALLATION _____________________________________________________________________________________ Division 16 Electrical Works Page 16-159

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

A. F.

Mount system components in cabinets or racks as recommended by manufacturer except as otherwise indicated. Antenna Cable Entrance: Use entrance fittings and seal and waterproof penetrations of the building envelope.

3.4

IDENTIFICATION A. Identify system components, wiring, cabling, and terminals according to Division 16 Section "Electrical Identification."

3.5

FIELD QUALITY CONTROL A. Manufacturer's Field Services: Provide services of factory-authorized service representatives to supervise the field assembly and connection of components and system pretesting, testing, and adjustment. Inspection: Verify that units and controls are properly labeled and interconnecting wires and terminals are identified. Pretesting: Align and adjust the system and pretest all components, wiring, and functions to verify they conform to specified requirements. Replace malfunctioning or damaged items with new items. Retest until achieving satisfactory performance and conditions. Operational Acceptance Tests: Perform operational system tests to verify it conforms to specifications. Include all modes of system operation. Methodically test for proper system operation in all functional modes. MATV System Acceptance Tests: Include the following: 1. 2. 3. Instrumentation: Use appropriate professional-quality instruments with documentation of recent calibration against recognized standards. Signal Level: Use a field-strength meter to make random measurements of signal level at taps from trunk RF signal lines. Readings on each of the channels designated to be received must be within limits specified in Part 1 for outlets. Signal-to-Noise Ratio Test: Use a field-strength meter to make a sequence of measurements at the output at the last distribution amplifier or another agreed location in the system. With the system operating at normal levels, tune the meter to the picture carrier frequency of each of the designated channels in turn and record the level. With the signal removed and the input set to the corresponding headend amplifier terminated in 75 ohms, measure the level of the noise at the same tuning settings. With the meter correction factor added to the last readings, the differences from the first set must not be less than 45 dB.

B. C.

E.

F.

H. 3.6

Retest: Correct deficiencies identified by tests and observations and retest until specified requirements are met.

CLEANING A. Clean all system components including camera housing windows, lenses, and monitor screens. Use methods and materials recommended by manufacturer.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-160

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

3.7

ADJUSTMENT A. Occupancy Adjustments: When requested within 1 year of date of Substantial Completion, provide on-site assistance in adjusting the system to suit actual occupied conditions. Provide up to 2 requested adjustment periods at the site for this purpose without additional cost.

END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-161

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

SECTION 16950 ELECTRICAL TESTS PART 1 - GENERAL 1.01 SUMMARY A. Provide labor, materials, temporary wiring, testing equipment, load bank, technical supervision and services, and perform operations required for testing of electrical equipment and installations and related work as specified herein and as shown on the drawings. Work Included: The work shall include, but not be limited to, the following: 1. 2. 3. C. Preliminary inspections and tests. Electrical acceptance tests. Operational tests.

B.

Related Work Specified Elsewhere 1. 2. 3. Basic Electrical Requirements - Section 16010. Basic Electrical Materials and Methods - Section 16050. Other Division 16 sections.

1.02

DESCRIPTION A. B. Preliminary testing and visual inspections shall be conducted prior to acceptance and operational tests to avoid delays. Electrical acceptance tests shall be conducted to assure that electrical materials, and their installations are in accordance with contract documents, regulatory agencies, applicable codes and standards listed herein, and that they may be energized. Operational tests shall be conducted to assure capability of equipment and systems to perform as specified and designed.

C. 1.03

QUALITY ASSURANCE A. Testing and testing equipment shall conform to the latest edition of reference specifications specified herein and to applicable codes and requirements of local authorities having jurisdiction. 1. 2. Regulatory Requirements: Comply with provisions of the applicable code and the Occupational Safety and Health Administration (OSHA).

International Electrical Testing Association: Comply with applicable provisions of NETA Standard ATS-latest edition. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-162

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

3. B.

National Fire Protection Association: NFPA 70B and NFPA 70E.

Comply with applicable provisions of

Personnel engaged in the testing of electrical equipment and systems shall have a minimum of five (5) years of continuous experience in the testing of the equipment and systems to be tested. Submit evidence of such qualifications to the Engineer. Contractor shall furnish testing equipment as required. Testing equipment, meters and instruments shall have been properly calibrated and certified within (6) months prior to testing and shall be in satisfactory condition to perform its functions. Contractor shall provide an appropriate and stable source of electrical power to the test locations. Perform tests in the presence of the Employer's Representative. Electrical equipment and installation shall meet acceptance and operational tests. Promptly repair or replace defective work and repeat the tests until the particular system and component parts thereof receive the approval of the Engineer. Any damages resulting from tests shall be repaired and/or damaged materials replaced, to the satisfaction of the Engineer. It is essential that certain trades and manufacturer's technical representatives be present during the testing. These representatives shall include: 1. 2. 3. Electrical subcontractor who is thoroughly familiar with the project as to its intent, what equipment has been provided and how it is supposed to operate. Supplier of equipment particularly where packaged equipment has been provided. Manufacturer's representative who is thoroughly familiar with the operation of the equipment.

C.

D. E. F.

G.

H.

The operation of the electrical installation by the Employers does not constitute an acceptance of the electrical installations. Final acceptance will depend on Contractor's demonstration of compliance with contract documents, completion of adjustments as specified and required, and submission of required documentation and certification of approval by governing authorities. Continuity tests shall be performed using direct current and audible bells or buzzers. Use of telephones is not acceptable.

I. J. 1.04

Safety devices such as rubber gloves and blankets, glow detectors, hot sticks, helmets, eye shields, protective screens and barriers, danger signs, etc. shall be used to adequately protected and warn personnel in the vicinity of the tests. SCHEDULING A. B. C. Scheduling of tests shall be as approved by the Engineer. Schedule tests so that equipment can be energized immediately after completing the tests and approval of the reports. Notify the Engineer two (2) weeks prior to testing.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-163

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

1.05

SUBMITTALS A. Submit the following in accordance with the requirements specified under "Submittals" in Section 16010. 1. 2. 3. Submit two (2) copies of test reports including actual readings and corrected readings after each test period. Submit four (4) bound copies of final approved test reports at the completion of tests. Test reports shall be signed by the persons performing the tests and the witnesses to the tests and include but not be limited to the following data: a. b. c. d. e. f. 4. Date of test. Description of equipment tested. Description of test. Test results. Conclusions and recommendations. Identification of test equipment.

Include copies of the final approved test reports in the maintenance manuals.

PART 3 - EXECUTION 3.01 EXAMINATION A. Examine conditions at the job site where work of this Section is to be performed to insure proper arrangement and fit of the work. Start of work implies acceptance of job site conditions.

3.02

PREPARATION A. B. C. Examine the Contract Drawings and specifications in order to insure the completeness of the work required under this Section. Cooperate in the coordination and scheduling of the work of this Section with the work of related trades, so as not to delay job progress. Testing of outdoor equipment shall not be performed during inclement weather. Ground resistance tests on direct buried ground conductors or rods shall not be performed within 48 hours after rainfall. Megger and high potential testing shall not be performed during periods of high relative humidity. A guard shall be stationed at each location where exposed cables, buswork, connections or other components exist during megger and high potential testing. Equipment shall be thoroughly cleaned prior to testing. Vacuum the interiors of cubicles and remove foreign material. Insulators, bushing and bus supports shall be wiped clean with a lint free cloth.

D.

E.

Preliminary tests and visual inspections of the electrical installation including verification checks of factory wiring shall be conducted prior to electrical acceptance and operational tests to avoid delays, and to assure that equipment and installations are free of faulty conditions prior to the application of test voltages. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-164

F.

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr

G.

Where the equipment or system under test is interrelated with and depends upon other equipment, systems and/or controls for proper operation, functioning and performance, the latter shall be operated simultaneously with the equipment or system under test. Test fuses for continuity. Test current transformers for continuity and proper polarity. Test potential transformers for continuity and absence of short circuits. Set protective devices in accordance with the approved coordination study. If generators, motors or transformers require drying out to obtain the required insulation valves, the drying method shall be in accordance with the manufacturer's recommendations. Verify that shipping devices and restraints have been removed. Check for proper interconnection and tightness at connections of shipping sections.

H. I. J. K. L.

M. N. 3.03

APPLICATION A. Equipment that can be paralleled under any conditions including interlock defeat shall be tested for proper phasing using hot-phase hot-stick or other approved methods. This includes, but is not limited to, primary selector switches, automatic transfer switches, tie breakers and busses, etc. at medium and low voltage levels. Full load currents of feeders serving single phase loads shall be measured to assure an equal load balance on each phase. Branch circuits shall be reconnected if necessary to achieve this balance. Megger values specified are minimum acceptable values at an ambient temperature of 60 degrees F and low relative humidity. Contractor shall convert readings to equivalent values at 60 degrees F if measurements are taken under other conditions.

B.

C.

3.04

TESTS A. Low Voltage Wire and Cable (600 Volts and Less) 1. Wire and cable shall be tested for continuity, freedom from short circuits and grounds and meggered to assure adequate insulation resistances for each conductor. Test Voltages: Megger instrument shall be 1000 volts DC applied for one minute. Acceptable Test Results: Insulation resistance between phase conductors and any phase conductor to ground shall be not less than 2 megohms for connected conductors and 100 megohms for disconnected conductors.

2. 3.

B.

Metal Enclosed Busways, Motor Control Centers and Panelboards

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-165

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr 1. 2. 3. Equipment shall be tested for continuity, freedom from short circuits, and grounds and meggered to assure adequate resistances. Test Voltages: Megger instrument shall be 1,000 volts DC for equipment rated 480 volts and 500 volts DC for equipment rated 250 volts, applied for one minute. Acceptable Test Results: Insulation resistance phase and any phase to ground shall be not less than 100 megohms for equipment rated 480 volts and 25 megohms for equipment rated 208 volts.

C.

Switchboards and Switchgears 1. 2. 3. 4. Test electrical and mechanical interlock systems for proper operation and sequencing . Test ground connections as specified under "Grounding System." Perform ratio and polarity tests on instrument current and potential transformers. Perform insulation resistance tests on each bus section, phase to phase and phase to ground as specified under "Metal Enclosed Busways, Motor Control Centers and Panelboards." Prior to performing insulation resistance tests on buswork, isolate the buswork by racking out or opening circuit breakers and disconnects, short circuit and ground current transformer secondaires, remove potential transformer primary fuses and assure grounding of the enclosure. Perfrom control wiring performance test using the approved manufacturer's elementary diagrams. For selective switchboard and switchgear arrangements, verify proper phasing between the line and load stabs of the tie breaker cubicle busses using hot-phase hot-stick techniques, A-A, B-B, C-C. Test disconnect switches as specified under "Circuit and Motor Disconnects." Perform an insulation resistance test at 1000 volts DC on each circuit breaker for one (1) minute from pole-to-pole and from each pole-to-ground with breaker closed and across open contacts of each phase. Insulation resistance shall not be less than 100 megohms. Set, calibrate and adjust protective device setting of each circuit breaker in accordance with the approved coordination study using secondary current injection. Ammeters shall be tested as follows: Check connections from current transformer for AC shunts for DC to ammeters. Check ammeter scale with current transformer ratio for AC and shunt millivolt rating for DC. Set pointer on zero scale with no load. Voltmeter tests shall include the following:

5. 6.

7. 8.

9.

10. a. b. c. 11.

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-166

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr a. b. c. 12. a. b. c. 13. a. b. Check voltmeter scale with potential transformer ratio. Set pointer on zero scale with no voltage. Check voltmeter reading with test voltmeter when energized. Wattmeter and watthour meter tests shall include the following: Check with current transformer and potential transformers ratio. Set wattmeter pointer on zero scale with no load. Check rotation on watthour meter. Tests of instrument transformers shall include the following: Physically check polarity mark orientation on CTs and PTs with three line diagram on the plans and with manufacturer's drawings. Check CT and PT polarity makings.

14.

Electrical controls shall be tested by trial operation of control equipment after wiring is completed to see that each interlock and control function operates according to the manufacturer's operating instructions. Motors 1. 2. Motors shall be tested for freedom from short circuits and grounds meggered to assure adequate resistances. Test Voltages: Megger instrument shall be 2,500 volts DC for testing 4,000 volt motors, 1,000 volts DC for testing 460 volt motors and 500 volts DC for testing 200 volt motors, applied for one minute. Acceptable Test Results: Insulation resistance phase to ground shall be not less than 100 megohms for 4,000 volt motors, 20 megohms for 460 and 200 volt 3phase motors and 5 megohms for 115 volt single phase motors. Apply voltage momentarily and check each motors for correct direction of rotation. Correct if necessary. Measure full load current reading of each motor and verify that the correct size heater elements have been provided for each starter overload relay. Where current flow exceeds the motor's nameplate value, install a "DO NOT OPERATE" tag, advise the Engineer and notify the Contractor to immediately correct the condition. If power factor correction capacitors are connected on the load side of the overload heaters, include the capacitive reactances in determining the proper overload heater size. Submit a tabulation of each motor indicating the equipment identification, motor horsepower, voltage, measured full load current and heater rating and manufacturer's catalog number.

D.

3.

4. 5.

6.

E.

Grounding System

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-167

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr 1. a. b. General Tests on individual ground rods shall be performed with each rod isolated from each other and the grounding system. Tests on the grounding system shall be made after installation and interconnection of the ground system elements including individual ground rods, ground grid cables, connections to structural steel, reinforcing bars, incoming water piping, ground busses on walls and within equipment, etc. Tests of Individual Ground Rods Measure the resistance to earth of each individual ground rod using a Biddle Co. ground tester or two auxiliary ground rods as described in IEEE Standard 550 paragraph 3.4.2 using an alternating test current. Locate the auxiliary rods at sufficient distance from the rod under tests to insure that the regions in which their resistances are localized do not overlap. Calculated resistances to earth shall not exceed 25 ohms. If the resistance is greater than 25 ohms, it shall be reduced by lengthening the rod or driving additional rods with a minimum separation of 10 feet and cadwelding the rods together until the resistance is less than 25 ohms.

2. a.

b.

3.

Tests of the Grounding System: Test ground system for continuity by applying a low voltage DC source of current, capable of furnishing up to 100 amperes. The ground path using structural steel must conduct 100 amperes. Resistance as calculated from the current and voltage shall not exceed 5 ohms. Circuit and Motor Disconnects: Upon completion of the installation of electrical disconnects, energize circuits and demonstrate capability and compliance with requirements. Except as otherwise indicated, do not test switches by operating them under load. However, demonstrate switch operation through six opening/closing cycles with circuit unloaded. Open each switch enclosure for inspection of interior, mechanical and electrical connections, fuse installation and for verification of type and rating of fuses installed. Correct deficiencies, then retest to demonstrate compliance. Remove and replace defective units with new units and retest. Receptacles Upon completion of wire tests, check receptacles for proper voltages and phasing, utilizing a receptacle tester for 120 volt 15 and 20 ampere devices and a voltmeter for other devices. Test three phase receptacles for proper phase rotation using a phase sequence meter. Grounded receptacle shall be tested for location and the effectiveness of the ground insert.

F.

G. 1.

2. 3.

4. Test ground fault circuit interrupter receptacles with both local and remote fault _____________________________________________________________________________________ Division 16 Electrical Works Page 16-168

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr simulations in accordance with the manufacturer's recommendations. H. I. K. L. 1. 2. Lighting Switches: Test lighting switches for correct operation with special emphasis on 3-and 4-way switches. Lighting Fixtures: Verify proper operation of lighting fixtures. Control Circuits: operation. Fire Alarm System Provide the services of a factory-authorized service representative to supervise the field system pretesting, testing, adjustment and programming. Pretesting: Upon completing installation of the system, align and adjust the system and perform pretesting. Determine, through pretesting, the conformance of the system to the requirements of the drawings and specifications. Correct deficiencies by replacing malfunctioning or damaged items with new items and retest until satisfactory performance and conditions are achieved. Test control circuits for proper functioning and fail safe

3.

Testing a. Perform electrical and mechanical tests required by the equipment manufacturer's certification form. In addition, measure and adjust each of the ionization detectors to the maximum stable sensitivity setting. This shall be performed with the detector at its operational location and under normal operational environmental conditions in the area. Bench settings are not acceptable. b. The completed smoke detection system shall be tested to insure that it is operating properly. This test shall consist of exposing the installed units to a standard fire test. Failure of the devices to detect smoke shall be considered a failure of the system and detectors in that system shall be re-adjusted or replaced. Acceptance of the system shall also require a demonstration of the stability of the system. This shall be adequately demonstrated if the system operates for a ninety (90) day test period without any unwarranted alarms. Should an unwarranted alarm(s) occur, the Contractor shall readjust or replace the detector(s) and begin another ninety (90) day test period. The Contractor shall recheck the detectors using the fire test after each readjustment or replacement of detectors using the fire test after each readjustment or replacement of detectors. This test shall not start until the Employer has obtained beneficial use of the building under tests. Wiring shall be checked and tested to insure there are no grounds, opens or short circuits. A checkout report shall be prepared and submitted, one copy of which shall be registered with the equipment manufacturer. The report shall include, but not be limited to:

c. d.

A list of equipment installed and wired. Indication that equipment is properly installed and functions and conforms with these specifications. 3) Test of individual zones as applicable. 4) Serial numbers, locations by zone and model number for each installed detector. _____________________________________________________________________________________ Division 16 Electrical Works Page 16-169

1) 2)

Month Year

Projects Name City Country Phase Nbr - Blocks Nbr 5) 6) 7) e. 1) 2) 3) 4) Voltage (sensitivity) settings for each ionization and photoelectric detector as measured in place with the HVAC system operating. Response time on thermostats and flame detectors. Technician's name, certificate number and date. After completion of the tests and adjustments listed above, submit the following information to the Engineer: "As-built" conduit layout diagrams including wire color code and/or number. "As-built" wiring diagrams. Detailed catalog data on installed system components. Copy of the test report. END OF SECTION

_____________________________________________________________________________________ Division 16 Electrical Works Page 16-170

You might also like