Intel Corporation

Schematic Design Development Guadalajara Design Center Life Safety System (LSS)

SYSTEM OUTPUTS
Control unit Annunciation Notification Actuate Lab Building ZPN3 specific Lab blue evacuation signals Fire Safety Controls Supplementary

Actuate Building ZPN4 / Annex buildings evacuation signals

Actuate Lab Building ZPN3 Data Center evacuation signals

Actuate overall Lab Building ZPN3 evacuation signals

Actuate Building ZPN1 local floor evacuation signals

Actuate Building ZPN2 local floor evacuation signals

Recall elevators to alternate recall floor

Actuate common alarm signal/indicator

Actuate audible common trouble signal

Activate Building ZPN1 smoke exhaust

Activate Building ZPN2 smoke exhaust

Actuate audible supervisory signal

Shutdown process Building ZPN1

Shutdown process Building ZPN2

Overall Input / Output Matrix

SYSTEM INPUTS
PULL STATIONS

Z AA BB CC DD EE FF GG HH JJ KK LL MM

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35

Manual Pull Station Building ZPN1 Manual Pull Station Building ZPN2 Manual Pull Station Lab Building ZPN3 Manual Pull Station Building ZPN4 / Annex buildings Heat / smoke detectors Building ZPN1 Heat / smoke detectors Building ZPN2 Heat / smoke detectors 1st floor lobby (buildings 1 & 2) Heat / smoke detectors Lab Building ZPN3 Heat / smoke detectors Building ZPN4 / Annex buildings Data Center VESDA Fault Data Center VESDA Alert / Action Data Center VESDA Fire 1 & 2 Oxygen level detector / Fault Oxygen level detector / Alarm LP Gas detector / Fault LP Gas detector / Alarm Below Ceiling Photo Beams Above Ceiling Photo Beams In-duct smoke detector Building ZPN1 (north) In-duct smoke detector Building ZPN2 (center) In-duct smoke detector Lab Building ZPN3 In-duct smoke detector Data Center Waterflow Building ZPN1 Waterflow Building ZPN2 Waterflow Lab Building ZPN3 Sprinkler control valve Building ZPN1 Sprinkler control valve Building ZPN2 Sprinkler control valve Lab Building ZPN3 Fire pump running Fire pump power failure / phase reversal Fire alarm AC power failure Fire alarm system low battery Open circuit Ground fault Notification appliance circuit short

HEAT & SMOKE DETECTORS

Pressurize stairwells

Important note: Contractor is responsible of estimating quantities of each device listed in this matrix.

VESDA DATA CENTER


Depends on location of photobeam

PHOT IN-DUCT GAS O SMOKE BEAM DETECTORS DETECTORS S

CONTROL PANEL & CIRCUITS

SPRIN KLER FIRE PUMP CONTRO L VALVE

WATER FLOW DETEC TORS

Actuate specific lab shutdown process

Actuate Building ZPN1 alarm indicator

Actuate Building ZPN2 alarm indicator

Shutdown process Lab Building ZPN3

Recall elevators to primary recall floor

TABLE LSS-A

Shutdown process Building ZPN4 / Annex buildings

Actuate Pump House / Guard Post alarm indicator

Transmit supervisory signal to supervising station

Actuate overall Building ZPN1 evacuation signals

Actuate overall Building ZPN2 evacuation signals

Transmit fire alarm signal to supervising station

Actuate common supervisory signal/indicator

Transmit trouble signal to supervising station

Activate graphics system - Display floor map

Activate Lab Building ZPN3 smoke exhaust

Actuate Lab Building ZPN3 alarm indicator

Close smoke / fire dampers in rated walls

Actuate common trouble signal/indicator

Release magnetically held smoke doors

Shutdown process Data Center

Display / print change of status

Actuate audible alarm signal

Unlock exits