Professional Documents
Culture Documents
Calculation Note
Calculation Note
1. General This Document is Included Structural calculation notes for Analysis & Design of Foundation And required Structures of the bandar emam Silos Project. This Silos is Located in bandar emam City near mahidasht oil company.
2. Codes and Standards Iranian Seismic Code. ( 2800 Iranians Codes) 519 Iranians Codes. Iranian Concrete Design Code. (ABA Code) 9th topic of Iranians National Building Codes. General and Technical of Silo Construction. 3. Materials 3.1. Reinforcing Bars Deformed high tensile strength Steel bars, with minimum yield strength of 4200 kg/cm3 in accordance with ASTM A 615 or approved equivalent.
3.2.
Concrete Tow Type of concrete are considered for the design of structures. In analyses and Design, is minimum compressive characteristic strength at 28 days on cylinder Specimen.
4. Soil Parameter
Soil parameters are available in soil report that provided by Banian pey. 5. Input Data 5.1. Muyang Group Data 5.1.1 Silo Diameters: 14560 millimeter (others data According the figures).
5.1.2 Small Silo Diameters:4550 millimeter (others Data According the figures )
6. Loading 6.1.1 Design loading data for silo Foundation design have been provided from Muyang Group.
Main silo Load KN,m Silo and roof gravity Roof Live Load and grain friction Grain vertical pressure Load for catwalk
6.1.2 The lateral loadings calculate as follow: 6.1.2.1 Wind Load Calculation: 6.1.2.1.1. Wind load calculation: According To 519 Iranian Code
P CeCq q q 0.00005v 2
Ce = combined height, exposure and gust factor coefficient Cq = pressure coefficient for the structure or portion of structure under consideration P = design wind pressure.
v = wind stagnation pressure
v 110 Km
hr
Khoozestan station
z Ce 2( )0.16 2 10
Ce
H<20 2.2
20<H<30 2.4
m2
P Ce C q q
0-20 1.0648
20-28 1.1616
0-20 310.06
20-28 40.80
Fwind 350.86KN
6.1.2.2 Earthquake Load Calculation: Design base shear: The total design base shear in a given direction shall be determined from the following formula According to 2800 Iranian Code
V C W A B I R A B I V W R T0 2 B 2.5( ) 3 2.5 T q T 1.79h 2 gEI s C
I = importance factor g = acceleration due to gravity. R = numerical coefficient representative of the inherent over strength and global ductility capacity of lateral forceresisting systems V = the total design lateral force or shear at the base W = the total seismic dead load E= Elastic modules of silo q= mass per length of silo A 0.2 I 1 R 5 B 2.5
T0
0.5
h 26.565
g 9.81
c 0.1
V 0.1W
7. Load Combination : 7.1. Load Combination for Stability and Soil pressure check
8. Analysis 0f Main Silos Foundation 8.1. Modeling Software Sap 2000 version 12.0.0 is used for Analyses purpose in this project.
Silo.emp (KN)
8.3. Soil Bearing capacity check Because of poor site soils and soil report recommendation, pile foundation used for this structure.
Pile Force KN 1330.562 1004.729 1329.44 1003.913 1111.724 571.869 1112.596 572.711 1169.079 844.361 1157.005 850.522 1106.228 749.837 1116.294 740.027 1167.798 843.357 1156.687 850.203 1115.189 738.842 1105.9 749.463 1412.614 1090.287 1108.929 487.339 1412.66 1090.308 1109.17 487.544 1365.782 1044.902 1248.198 924.529 1109.685 646.203 1220.134
8.4. Ring wall 400mm Reinforcement calculation 8.4.1. Ring Wall Moment Resultant M1-1Diagram (KN.m)
1.1. wall 250mm Reinforcement calculation 1.1.1. Wall Moment Resultant M1-1Diagram (KN.m)
1.1. Slab 600mm Reinforcement calculation 1.1.1. Slab Moment Resultant M1-1Diagram (KN.m)
Cappile Reinforcement Calculation 1.1.3. Footing Moment Resultant M1-1 Diagram (KN.m)