All-In-One PLC
With Next Generation Technology
XGB is a micro PLC that offers maximum performance at minimum cost.
With its high functionality, XGB supports from simple control system to complex task.
Strengthening its communication functions, XGB offers user-oriented integrated control.
Based on its strengths, XGB can be used in many application fields.
2
Contents
▶
Features 4
▶
General specifications 6
▶
Performance specifications 8
▶
Input/output specification 12
▶
Wiring 16
▶
Built-in functions 28
▶
Expansion 35
▶
DC Input 35
▶
Transistor Output 37
▶
Relay Output 39
▶
DC Input / Relay Output 40
▶
Analog Input 41
▶
Analog Output 42
▶
Analog Input / Output 43
▶
RTD 44
▶ Thermocouple 45
▶
Positioning module 46
▶ High Speed counter module 47
▶ Modular type 48
▶ Communication module 49
▶ Option modules/Smart link 51
▶ Software 52
▶
Product list 53
▶
Dimension 56
3
Features
(Unit: mm)
Item W H D
It's Slim
DR/DN16S (16pt)
XBM 30 90 60
DN32S (32pt)
DR/DN32H (32pt) 114 90 64
XBC / XEC
DR/DN64H (64pt) 180 90 64
Relay output / Ethernet 27 90 60
Expansion
Others 20 90 60
Max. 10stages
Max. 2 Stages
4
High performance
With its high-speed processing and system capability,
XGB offers utmost efficiency for your applications.
Option modules
XBO-M2MB Memory
XBO-RTCA RTC(Real Time Clock), Battery
XBO-DC04A DC 24V, Input 4 points
XBO-TN04A Transistor(Sink), Output 4 point
XBO-RD01A RTD(Resistance Temperature Detect, Input 1CH)
Max. 7stages
5
General specifications
*1) Pollution level indicates the degree to which conductive material is generated in the environment where the equipment is used.
Pollution level 2 is the condition that only non-conductive pollution occurred but temporary conductivity may be produced due to
condensing.
*1) Pollution level indicates the degree to which conductive material is generated in the environment where the equipment is used.
Pollution level 2 is the condition that only non-conductive pollution occurred but temporary conductivity may be produced due to
condensing.
6
Names and functions Programmable Logic Controller
7
Performance specifications | Block type unit
8
Programmable Logic Controller
Standard type
Perfprmance specifications XBC-DN20SU XBC-DN30SU XBC-DN40SU XBC-DN60SU
Item XBC-DR20SU XBC-DR30SU XBC-DR40SU XBC-DR60SU
XEC-DN20SU XEC-DN30SU XEC-DN40SU XEC-DN60SU
XEC-DR20SU XEC-DR30SU XEC-DR40SU XEC-DR60SU
Control method Repetitive, cyclic, interrupt, constant scan
I/O control method Refresh mode (Batch processing by scan synchronization), Direct mode by instruction
Programming language Ladder diagram, Instruction List
Processing speed 94 ns/Step
Program capacity 15Kstep
20 30 40 60
Main Unit I/O points
(Input:12, Output:8) (Input:18, Output:12) (Input:24, Output:16) (Input:36, Output:24)
Max. I/O points
244 points 254 points 264 points 284 points
(Main + Expansion 7 stages)
Total program 128
Operation mode RUN, STOP, DEBUG
Self diagnosis Detects errors of scan time, memory error, I/O error, battery error, power error, etc.
Program port RS-232C 1 channel (Loader), USB 1 channel (U-type model)
Retain data at power failure Latch area setting at Basic parameter
RS-232C / RS-485(2CH), Pulse catch, Input filter, External interrupt,
Built-in functions
PID control, High-speed counter, Positioning
253mA 294mA 288mA 340mA
460mA 612mA 684mA 942mA
Internal current consumption
252mA 270mA 288mA 340mA
478mA 626mA 684mA 942mA
475g 474g 578g 636g
514g 528g 594g 804g
Weight
475g 474g 578g 636g
514g 528g 594g 804g
Rated voltage AC 100 ~ 240V
Data memory
XBC XEC
P P0000 ~ P1023F (16,384 points) Symbolic 16KB (Max. 16KB
variable A retain setting abailable)
M M0000 ~ M1023F (16,384 points)
K K0000 ~ K4095F (65,536 points) Input variable I 2KB(%IX 15.15.63)
L L0000 ~ L2047F (32,768 points) Output variable Q 2KB(%QX 15.15.63)
F F0000 ~ F1023F (16,384 points) 8KB
M (Max. retain setting available)
100ms, 10ms, 1ms: T0000 ~ T1023 (1,024) Direct
T variable
Data (Adjustable by parameter setting) R 20KB (1block)
area
C C0000 ~ C1023 (1,024) W 20KB
S S00.00 ~ S127.99 F 2KB
D D0000 ~ D10239 (10,240 word) Flag K 8KB
variable L 4KB
U U00.00 ~ U0A.31
(Analog data refresh area: 352 word) U 1KB
Z Z000 ~ Z127 (128 word) Flash area 20KB (2block)
R N0000 ~ N10236 (10.240 word)
9
Performance specifications | Block type unit
Economic type
Perfprmance specifications Item XBC-DR10E XBC-DR14E XBC-DR20E XBC-DR30E
Control method Repetitive, cyclic , fixed cycle operation, constant scan
I/O control method Refresh mode (Batch processing by scan synchronization), Direct mode by instruction
Programming language Ladder diagram, Instruction List
Processing speed 240 ns/Step
Program capacity 4Kstep
10 14 20 30
Main Unit I/O points
(Input:6, Output:4) (Input:8, Output:6) (Input:12, Output:8) (Input:18, Output:12)
14 18 28 38
Max. I/O points
(Main + 1option) (Main + 1option) (Main + 2 options) (Main + 2 options)
Total program 128
Operation mode RUN, STOP, DEBUG
Self diagnosis Detects errors of scan time, memory error, I/O error, battery error, power error, etc.
Program port RS-232C 1 channel (Loader)
Retain data at power failure Latch area setting at Basic parameter
Built- in functions RS-232C or RS-485(1CH), Pulse catch, Input filter, External interrupt, High-speed counter
Internal current consumption 250mA 315mA 355mA 485mA
Weight 330g 340g 450g 465g
Rated voltage AC 100 ~ 240V
Data memory
XBC
P P0000 ~ P127F (2,048 points)
M M0000 ~ M255F (4,096 points)
K K0000 ~ K2559F (Special area: K2600~K2559F) (40,960 points)
L L0000 ~ L1279F (20,480 points)
F F000 ~ F255F (4,096 points)
100ms, 10ms, 1ms: T000 ~ T255 (256)
Data area T (Adjustable by parameter setting)
C C000 ~ C255 (256)
S S00.00 ~ S127.99
D D0000 ~ D5119 (5120 word)
U U00.00 ~ U07.31 (Analog data refresh area: 256 word)
Z Z000 ~ Z127 (128 word)
10
| Modular type unit
Programmable Logic Controller
Standard type
Perfprmance specifications Item XBM-DR16S XBM-DN16S XBM-DN32S
Control method Repetitive, cyclic, fixed cycle operation, constant scan
I/O control method Refresh mode (Batch processing by scan synchronization), Direct mode by instruction
Programming language Ladder diagram, Instruction List
Processing speed 160 ns/Step
Program capacity 10Kstep
16 points 16 points 32 points
Main Unit I/O points
(Input:8, Output:8) (Input:8, Output:8) (Input:16, Output:16)
Max. I/O points
240 points 256 points
(Main + Expansion 7 stages)
Total program 128
Operation mode RUN, STOP, DEBUG
Self diagnosis Detects errors of scan time, memory error, I/O error, battery error, power error, etc.
Program port RS-232C 1 channel (Loader)
Retain data at power failure Latch area setting at Basic parameter
RS-232C/RS-485(2CH), Pulse catch, Input filter, External interrupt,
Built- in functions
PID control, High-speed counter, Positioning *1)
Internal current consumption 400mA 250mA 280mA
Weight 140g 100g 100g
Rated voltage DC24V
Data memory
XBM
P P0000 ~ P127F (2,048 points)
M M0000 ~ M255F (4,096 points)
K K0000 ~ K2559F (Special area: K2600~K2559F) (40,960 points)
L L0000 ~ L1279F (20,480 points)
F F000 ~ F255F (4,096 points)
100ms, 10ms, 1ms: T000 ~ T255 (256)
T (Adjustable by parameter setting)
Data area
C C000 ~ C255 (256)
S S00.00 ~ S127.99
D D0000 ~ D5119 (5120 word)
U U00.00 ~ U07.31 (Analog data refresh area: 256 word)
Z Z000 ~ Z127 (128 word)
N N0000 ~ N3935 (3,936 word)
11
Input/output specification | Block type unit
12
Programmable Logic Controller
Standard type
Input specification XBC-DN20SU XBC-DN30SU XBC-DN40SU XBC-DN60SU
Item
XBC-DR20SU XBC-DR30SU XBC-DR40SU XBC-DR60SU
Input point 12 points 18 points 24 points 36 points
Rated input voltage DC24V
Rated input current 4mA(Contact point 0~1 : 16mA, 2~7 : 10mA), DN20SU(DN30SU) : 4mA(Contact point 0~7: 10mA)
Operation voltage range DC 20.4 ~ 28.8V (Ripple rate<5%)
On voltage / On current DC 19V or more / 3mA or more
Off voltage / Off current DC 6V or less / 1mA or less
Input resistance 5.6kΪ(P00 ~ P07 : 2.7kΪ)
Off → On
Response time 1 / 3 / 5 / 10 / 20 / 70/ 100ms (Setting by CPU parameter) Initial value : 3ms
On → Off
13
Input/output specification | Block type unit
Economic type
Input specification Item XBC-DR10E XBC-DR14E XBC-DR20E XBC-DR30E
Input point 10 points 14 points 20 points 30 points
Rated input voltage DC 24V
Rated input current 4mA (Contact point 0 ~ 3: 7mA)
Operation voltage range DC 20.4 ~ 28.8V (Ripple rate < 5%)
On voltage / On current DC 19V or more / 3mA or more
Off voltage / Off current DC 6V or less / 1mA or less
Input resistance 5.6kΪ(P00 ~ P07: 2.7kΪ)
Off → On
Response time 1 / 3 / 5 / 10 / 20 / 70 / 100 ms (set by I/O parameter) Initial value: 3ms
On → Off
Weight 330g 340g 450g 465g
14
| Modular type unit
Programmable Logic Controller
Standard type
Input specification Item XBM-DR16S XBM-DN16S XBM-DN32S
Input point 8 points 8 points 16 points
Rated input voltage DC24 V
Rated input current 4mA (00 ~ 03: 7mA)
Operation voltage range DC20.4 ~ 28.8V (ripple rate < 5%)
Off → On 1 / 3 / 5 / 10 / 20 / 70 / 100ms
Response time
On → Off (set by CPU parameter) Default: 3ms
Common Method 8 points / COM 16 points / COM
15
Wiring | Block type unit
Transistor output wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DN32H / XEC-DN32H) TB1 AC100
TB2 FG
TB3 ~240V
TB4 DC12/24V
TB5 20
TB6 21
TB7 22
TB8 23
TB9 COM0
TB10 24
TB11 25
TB12 26
TB13 27
TB14 COM1
TB15 28
TB16 29
TB17 2A
TB18 2B
TB19 COM2
TB20 2C
TB21 2D
TB22 2E
TB23 2F
TB24 COM3
Relay output wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DR32H / XEC-DR32H) TB1 AC100
TB2 FG
TB3 ~240V
TB4 NC
TB5 20
TB6 21
TB7 22
TB8 23
TB9 COM0
TB10 24
TB11 25
TB12 26
TB13 27
TB14 COM1
TB15 28
TB16 29
TB17 2A
TB18 2B
TB19 COM2
TB20 2C
TB21 2D
TB22 2E
TB23 2F
TB24 COM3
16
Programmable Logic Controller
Transistor output wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DN64H / XEC-DN64H) TB1 AC100
TB2 FG
TB3 ~240V
TB4 DC12/24V
21 TB5 20
TB6
TB7 22
TB8 23
TB9 COM0
TB10 24
TB11 25
TB12 26
TB13 27
TB14 COM1
TB15 28
TB16 29
TB17 2A
TB18 2B
TB19 COM2
TB20 2C
TB21 2D
TB22 2E
TB23 2F
TB24 COM3
TB25 30
TB26 31
TB27 32
TB28 33
TB29 34
TB30 35
TB31 36
TB32 37
TB33 COM4
TB34 38
TB35 39
TB36 3A
TB37 3B
TB38 3C
TB39 3D
TB40 3E
TB41 3F
TB42 COM5
17
Wiring | Block type unit
Standard type
Input wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DN20SU/ XBC-DR20SU/ TB1 RX
TB2 485+
XEC-DN20S/ XEC-DR20SU) TB3 TX
TB4 485-
TB5 SG
TB6 00
TB7 01
TB8 02
TB9 03
TB10 04
TB11 05
TB12 06
TB13 07
TB14 08
TB15 09
TB16 0A
TB17 0B
TB18 NC
TB19 NC
TB20 NC
TB21 NC
TB22 NC
TB23 NC
TB24 COM
18
Programmable Logic Controller
Transistor output wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DN20SU/ XEC-DN20SU) TB1 AC100
TB2 FG
TB3 ~240V
TB4 COM0
TB5 40
TB6 COM1
TB7 41
TB8 COM2
TB9 42
TB10 43
TB11 P
TB12 COM3
TB13 44
TB14 45
TB15 46
TB16 47
TB17 NC
TB18 NC
TB19 NC
TB20 NC
TB21 NC
TB22 NC
TB23 24V
TB24 24G
Relay output wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DR20SU/ XEC-DR20SU) TB1 AC100
TB2 FG
TB3 ~240V
TB4 COM0
TB5 40
TB6 COM1
TB7 41
TB8 COM2
TB9 42
TB10 43
TB11 NC
TB12 COM3
TB13 44
TB14 45
TB15 46
TB16 47
TB17 NC
TB18 NC
TB19 NC
TB20 NC
TB21 NC
TB22 NC
TB23 24V
TB24 24G
19
Wiring | Block type unit
Standard type
Transistor output wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DN30SU/ XEC-DN30SU) TB1 AC100
TB2 FG
TB3 ~240V
TB4 COM0
TB5 40
TB6 COM1
TB7 41
TB8 COM2
TB9 42
TB10 43
TB11 P
TB12 COM3
TB13 44
TB14 45
TB15 46
TB16 47
TB17 NC
TB18 COM4
TB19 48
TB20 49
TB21 4A
TB22 4B
TB23 24V
TB24 24G
Relay output wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DR30SU/ XEC-DR30SU) TB1 AC100
TB2 FG
TB3 ~240V
TB4 COM0
TB5 40
TB6 COM1
TB7 41
TB8 COM2
TB9 42
TB10 43
TB11 NC
TB12 COM3
TB13 44
TB14 45
TB15 46
TB16 47
TB17 NC
TB18 COM4
TB19 48
TB20 49
TB21 4A
TB22 4B
TB23 24V
TB24 24G
20
Programmable Logic Controller
Transistor output wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DN40SU/ XEC-DN40SU) TB1 AG100
TB2 FG
TB3 -240V
TB4 C0M0
TB5 40
TB6 C0M1
TB7 41
TB8 C0M2
TB9 42
TB10 43
TB11 P
TB12 COM3
TB13 44
TB14 45
TB15 46
TB16 47
TB17 NC
TB18 COM4
TB19 48
TB20 49
TB21 4A
TB22 4B
TB23 NC
TB24 COM5
TB25 4C
TB26 4D
TB27 4E
TB28 4F
TB29 24V
TB30 24G
Relay output wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DR40SU/ XEC-DR40SU) TB1 RX
TB2 FG
TB3 TX
TB4 C0M0
TB5 SG
TB6 C0M1
TB7 01
TB8 C0M2
TB9 03
TB10 43
TB11 05
TB12 COM3
TB13 07
TB14 45
TB15 09
TB16 47
TB17 0B
TB18 COM4
TB19 0O
TB20 49
TB21 0F
TB22 4B
TB23 11
TB24 COM5
TB25 13
TB26 4D
TB27 15
TB28 4F
TB29 17
TB30 24G
21
Wiring | Block type unit
Standard type
Input wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DN60SU/ XEC-DN60SU) TB1 RX
TB2 485+
TB3 TX
TB4 485-
TB5 SG
TB6 00
TB7 01
TB8 02
TB9 03
TB10 04
TB11 05
TB12 06
TB13 07
TB14 08
TB15 09
TB16 0A
TB17 0B
TB18 0C
TB19 0D
TB20 0E
TB21 0F
TB22 10
TB23 11
TB24 12
TB25 13
TB26 14
TB27 15
TB28 16
TB29 17
TB30 18
TB31 19
TB32 1A
TB33 1B
TB34 1C
TB35 1D
TB36 1E
TB37 1F
TB38 20
TB39 21
TB40 22
TB41 23
TB42 COM
Transistor output wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DN60SU/ XEC-DN60SU) TB1 AG100
TB2 FG
TB3 -240V
TB4 C0M0
TB5 40
TB6 C0M1
TB7 41
TB8 C0M2
TB9 42
TB10 43
TB11 P
TB12 COM3
TB13 44
TB14 45
TB15 46
TB16 47
TB17 NC
TB18 COM4
TB19 48
TB20 49
TB21 4A
TB22 4B
TB23 NC
TB24 COM5
TB25 4C
TB26 4D
TB27 4E
TB28 4F
TB29 NC
TB30 COM6
TB31 50
TB32 51
TB33 52
TB34 53
TB35 NC
TB36 COM7
TB37 54
TB38 55
TB39 56
TB40 57
TB41 24V
TB42 24G
22
Programmable Logic Controller
Relay output wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DR60SU/ XEC-DR60SU) TB1 AG100
TB2 FG
TB3 -240V
TB4 C0M0
TB5 40
TB6 C0M1
TB7 41
TB8 C0M2
TB9 42
TB10 43
TB11 P
TB12 COM3
TB13 44
TB14 45
TB15 46
TB16 47
TB17 NC
TB18 COM4
TB19 48
TB20 49
TB21 4A
TB22 4B
TB23 NC
TB24 COM5
TB25 4C
TB26 4D
TB27 4E
TB28 4F
TB29 NC
TB30 COM6
TB31 50
TB32 51
TB33 52
TB34 53
TB35 NC
TB36 COM7
TB37 54
TB38 55
TB39 56
TB40 57
TB41 24V
TB42 24G
23
Wiring | Block type unit
Economic type
Input wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DR10E) TB1 RX
TB2 485+
TB3 TX
TB4 485-
TB5 SG
TB6 00
TB7 01
TB8 02
TB9 03
TB10 04
TB11 05
TB12 NC
TB13 NC
TB14 COM
Relay output wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DR10E) TB1 AC100
TB2 FG
TB3 ~240V
TB4 COM0
TB5 40
TB6 COM1
TB7 41
TB8 COM2
TB9 42
TB10 43
TB11 NC
TB12 NC
TB13 24V
TB14 24G
Relay output wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DR14E) TB1 AC100
TB2 FG
TB3 ~240V
TB4 COM0
TB5 40
TB6 COM1
TB7 41
TB8 COM2
TB9 42
TB10 43
TB11 NC
TB12 NC
TB13 24V
TB14 24G
24
Programmable Logic Controller
Relay output wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DR20E) TB1 AC100
TB2 FG
TB3 ~240V
TB4 COM0
TB5 40
TB6 COM1
TB7 41
TB8 COM2
TB9 42
TB10 43
TB11 NC
TB12 COM3
TB13 44
TB14 45
TB15 46
TB16 47
TB17 NC
TB18 COM4
TB19 48
TB20 49
TB21 4A
TB22 4B
TB23 24V
TB24 24G
Relay output wiring Circuit configuration No. Conlact No. Conlact Type
(XBC-DR30E) TB1 AC100
TB2 FG
TB3 ~240V
TB4 COM0
TB5 40
TB6 COM1
TB7 41
TB8 COM2
TB9 42
TB10 43
TB11 NC
TB12 COM3
TB13 44
TB14 45
TB15 46
TB16 47
TB17 NC
TB18 COM4
TB19 48
TB20 49
TB21 4A
TB22 4B
TB23 24V
TB24 24G
25
Wiring | Modular type unit
Standard type
Input wiring Circuit configuration No. Conlact Type
(XBM-DR16S) TB1 00
TB2 01
TB3 02
TB4 03
TB5 04
TB6 05
TB7 06
TB8 07
TB9 COM
26
Programmable Logic Controller
27
Built-in functions | High-speed counter
Standard type
Performance specifications Description
Classification Block type unit Modular type
H-type S(U)-type E-type S-type
Signal A-phase, B-phase
Count input
Input type Voltage input (Open collector)
Signal
Signal level DC 24V
Max. count speed 100kpps 100kpps 4kpps 20kpps
1 phase 100kpps 4ch / 20kpps 4ch 100kpps 2ch / 20kpps 6ch 4kpps 4ch 20kpps 4ch
Number of
50kpps 2ch / 10kpps 2ch 50kpps 1ch 2 multiplication: 10kpps
channels 2 phase 2kpps 2ch
50kpps 2ch / 8kpps 2ch 8kpps 3ch 4 multiplication: 8kpps
Count range Signed 32bit (-2,147,483,648 ~ 2,147,483,647)
Count mode Linear count (if 32bit range exceeded, Carry / Borrow occurs)
(Program setting) Ring count (repeated count within setting range)
1-phase input
Input mode
(Program setting) 2-phase input
CW/CCW input
Signal type Voltage
Increasing / decreasing operation setting by B-phase input
1 phase input
Increasing/decreasing operation setting by program
Up/Down
2 phase input Automatic setting by difference in phase
setting
A-phase input: increasing operation
CW/CCW
B-phase input: decreasing operation
1 phase input 1 multiplication
Multiplication
2 phase input 4 multiplication
function
CW/CCW 1 multiplication
Signal Preset instruction input
Control input Signal level DC 24V input type
Signal type Voltage
2 point/channel (for each channel): 1 point/channel (for each channel):
Output points
output contact point of basic unit available output contact point of basic unit available
External
output Select program setting, signal-compared (>, >=, =, <=, <) or section compared output
Type
(included or excluded)
Output Type Relay, Open-collector output (Sink)
Count enable To be set through program
Preset function To be set through terminal (contact) or program
Auxiliary mode Count latch
28
Programmable Logic Controller
29
Built-in functions | High-speed counter
Wiring
30
| Positioning
Programmable Logic Controller
※Economic block type unit (E-type) dose not support built-in Positioning functions
Electrical specification Rated input Load voltage Max. load Max. voltage Leakage Response
Signal
voltage range current/inrush current drop (On) current (Off) time
Output
DC 100mA(1 point) DC 0.3V or 0.1mA or
Output pulse DC 5~24V 100㎲ or less
4.75~26.4V 1A/10ms or less less less
Rated input Load voltage On Off Input Response
Signal
voltage/current range voltage/current voltage/current resistance time
External high limit DC 19V/5.7mA DC 6V/1.8mA
Input DC 24V/7mA 3.3Ϊ
External low limit DC 20.4 ~ or more or less
0.5ms or less
Approximate zero 28.8V DC 19V/3.4mA DC 6V/1.1mA
DC 24V/4mA 5.6Ϊ
zero or more or less
31
Built-in functions | Positioning
I/O specifications | Block type unit
High performance type XBC pin number Direction of
(XBC-H/ XEC-H) (XEC pin number) positioning Operating
Item Signal name condition
signal to
X axis Y axis external
P00008 P0000A
(%IX0.0.8) (%IX0.0.10) Limit L Low limit ←
P00009 P0000B
Limit H High limit ←
(%IX0.0.9) (%IX0.0.11) 4mA /
Input P0000C P0000E 24V
DOG Near point ←
(%IX0.0.12) (%IX0.0.14)
P0000D P0000F ←
(%IX0.0.13) (%IX0.0.15) Origin Zero signal (+24V)
COM Input COM Common ←
P00020 P00021 Pulse/CW
Pulse (Open collector) →
(%QX0.0.0) (%QX0.0.1)
DC5~24V
P00022 P00023 Direction/CCW
Direction →
Output (%QX0.0.2) (%QX0.0.3) (Open collector)
P DC12V External power supply →
COM 0 ~ 3 Output COM External 24V GND →
32
| PID/Pulse catch/Input filter/Task/RTC
Programmable Logic Controller
Cascade Improved control precision by serial connection between Master loop and Slave loop
Function SV Ramp Preventing overload caused by excessive SV change by setting variation slope
Improved control stability with various alarm function such as MV high limit/low limit,
Alarm
PV high limit/low limit, PV variation width
Auto tuning Auto tuning with improved auto-tuning algorithm
Additional function PWM output, PV Tracking, �MV, �PV, etc
※Economic block type unit (E-type) dose not support built-in PID functions
Pulse catch When the On-condition time of input signal is shorter than 1 scan time (Min. 50㎲), Pulse catch processes the
input signal as normal input.
Description
Item Block type unit Modular type
H-type S(U)-type E-type S-type
10㎲: 4 points 10㎲: 2 points
(P00000~P00003) (P00000~P00001) 50㎲: 4 points 50㎲: 8 points
Pulse catch
50㎲: 4 points 50㎲: 6 points (P00000~P00003) (P00000~P00007)
(P00004~P00007) (P00002~P00007)
Input filter Input filter prevents processing of the input signal that is shorter than the filtering time. (Filtering time is set by
parameter) In the application site where noise is frequently generated, input filter prevents wrong input caused by noise.
Description
Classification Block type unit Modular type
H-type S(U)-type E-type S-type
No. of setting points Every input contact
Input filtering time setting Assigning for each module
Setting range 1 ~ 100㎳ (1,3,5,10,20,70,100)
33
Built-in functions | PID/Pulse catch/Input filter/Task/RTC
Task Task function is the processing method of internal/external signal generated periodically or aperiodically.
It stops operation of scan program for the moment and then execute the assigned task.
Description
Classification Block type unit Modular type
H-type S(U)-type E-type S-type
Initial task 1(_INT)
Cyclic task 8
I/O task 8 8 4 8
Internal device task 8
10㎲: 4 points 10㎲: 2 points
(P00000~P00003) (P00000~P00001) 50㎲: 4 points 50㎲: 8 points
External interrupt
50㎲: 4 points 50㎲: 6 points (P00000~P00003) (P00000~P00007)
(P00004~P00007) (P00002~P00007)
RTC RTC function is for time management of system and error log. RTC function is executed steadily when power is
off or instantaneous power cut status. Current time of RTC is renewed every scan by system operation status
information flag.
Description
Classification Block type unit Modular type
H-type S(U)-type E-type S-type
34
Expansion | DC Input Programmable Logic Controller
XBE-DC08A
XBE-DC16A
XBE-DC32A
35
Expansion | DC Input
36
| Transistor Output
Programmable Logic Controller
Specification Model
Specification XBE-TN08A XBE-TP08A XBE-TN16A XBE-TP16A XBE-TN32A XBE-TP32A
37
Expansion | Transistor Output
38
| Relay output
Programmable Logic Controller
39
Expansion | DC Input / Relay output
XBE-DR16A
Wiring
8-point DC input 8-point Relay Output
(XBE-DR16A)
40
| Analog Input
Programmable Logic Controller
Wiring
Wiring with 2-wire sensor Wiring with 4-wire sensor
※Use 22AWG, 2 conductor, twist shielded cable when wiring between analog module and external device.
41
Expansion | Analog Output
Wiring
XBF- XBF-
2kΩ or more 510Ω or less
DV04A DC04A
42
| Analog Input/Analog Output
Programmable Logic Controller
Specification XBF-AH04A
Item
Input Output
❶ Analog channel 2 channels 2 channels
❷ DC 1 ~ 5V, DC 0 ~ 5V, DC 0 ~ 10V DC 1 ~ 5V, DC 0 ~ 5V, DC 0 ~ 10V
(Input resistance: 1 MΪmin.) (Load resistance ≥ 2kΪ)
❽ Analog range
DC 4 ~ 20mA, DC 0 ~ 20mA DC 4 ~ 20mA, DC 0 ~ 20mA
(Input resistance 250Ϊ) (Load resistance ≤510Ϊ)
❸ Analog range Selection XG 5000 I/O parameter and External switch
Unsigned value 0 ~ 4000
❹ Signed value -2000 ~ 2000
Digital data 100 ~ 500 (DC 1 ~ 5V), 0 ~ 500 (DC 0 ~ 5V), 0 ~ 1000 (DC 0 ~ 10V)
Precise value
400 ~ 2000 (DC 4 ~ 20mA), 0 ~ 2000 (DC 0 ~ 20mA)
❺
Percentile value 0 ~ 1000
1.25mV (DC 1~5V, 0~5V), 2.5mV (DC 0~10V)
Resolution(1/4000)
5 (DC4~20mA, 0~20mA)
❻ Max. conversion speed ±15V, 25mA
Max. absolute output 1ms / channel
Accuracy ±0.5% or less
Insulation method Photocoupler insulation between I/O terminal and power supply
❼
Connection terminal 11-point terminal block
Occupied I/O points Fixed type: 64 points
XBF-AH04A Current DC 5V 120mA
consumption DC 24V 130mA
Wiring
Wiring with 2-wire sensor (for analog input) Wiring with 4-wire sensor (for analog input)
※Use 22AWG, 2 conductor, twist shielded cable when wiring between analog module and external device.
43
Expansion | RTD
XBF-RD04A
Wiring
2 Wire 3 Wire 4 Wire
Terminal Terminal
Terminal
44
| Thermocouple
Programmable Logic Controller
Wiring
Compensation Shield
Module
cable Terminals cable Sensor
45
Expansion | Positioning module
46
| High Speed counter module
Programmable Logic Controller
Specification Specification
Item
XBF-HO02A XGF-HD02A
❶ Signal A-phase, B-phase
◀ ▶ Count Input type Differential input (Line Drive):
Voltage input (Open Collector)
Input signal
Signal level DC 5/12/24V RS-422A Line Drive/HTL LEVEL Line Drive
Maximum coefficient speed 200kpps 500kpps (HTL input : 250kpps)
Number of channels 2 Channels
Coefficient range Signed 32-bit (-2,147,483,648 ~ 2,147,483,647)
Linear Count (When 32-bit range exceeded, Carry/Borrow occurs, the count value stopped)
❷ Count mode
◀ ▶
Ring Count (repeated count within setting range)
1-phase input
Input pulse mode 2-phase input
CW/CCW input
Increasing/decreasing operation setting by B-phase input
1-phase input
Increasing/decreasing operation setting by program
Up/down
2-phase input Automatic setting by difference in phase
Setting
A-phase input: increasing operation
CW/CCW
B-phase input: decreasing operation
XBF-HO02A Multiplica- 1-phase input 1/2 multiplication
XBF-HD02A tion 2-phase input 1/2/4 multiplication
function CW/CCW 1-multiplication
Signal Preset instruction input, auxiliary mode instruction input
Control
input Signal level DC 5V/12V/24V (by terminal selection) input type
Signal type Voltage
Output points 2-point/channel (for each channel): terminal output available
External
Type Select single-compared (>, >=, =, =<, <) or section compared output (included or excluded)
output
Output type Open collector output (Sink)
Operation Input Signal A-phase input, B-phase input, Preset instruction input, auxiliary mode instruction input
Status Output Signal External output 0, External output 1
Display Busy Status Module Ready
Count Enable To be set through program (count available only in enable status)
Preset function To be set through terminal or program
Count clear,
Count latch,
Section count(time setting value: 0~60000㎳),
auxiliary mode function
Measurement of input frequency(for respective input phase),
Measurement of counts per hour(time setting value: 0~60000㎳)
Count prohibited function
Terminal 40 pin connector
I/O occupied points Fixed point: 64
Internal consumed current 200 mA 260 mA
Weight 90g
47
Expansion | Modular type
48
| Communication
Programmable Logic Controller
XBL-EMTA
RS-232C, RS-422 / 485 Item Built-in RS-232C XBL-C21A Built-in RS-485 XBL-C41A
Interface RS-232C 1Ch RS-232C 1Ch RS-485 1Ch RS-422 / 485 1Ch
MODEM Function Remote communication via the external MODEM (XBL-C21A Only)
Dedicate 1:1 or 1:N via the dedicated protocol
Mode XG5000 mode Program download, upload and control via the remote control
P2P Communication defined by the protocol using XG-PD XGT / Modbus master
Operation Server (slave) XGT / Modbus Server, User-defined communication
Mode Client (master) XGT / Modbus P2P Master, User-defined communication
Start Bit 1
Data Bit 7 or 8
Data format Stop Bit 1 or 2
Parity Even / Odd / None
Setting Setting by XG-PD parameter
Synchronous Asynchronous
XBL-C21A Speed (bps) 1,200 / 2,400 / 4,800 / 9,600 / 19,200 / 38,400 / 57,600 / 115,200 bps
XBL-C41A Station number Setting by XG-PD, Max. 32 stations
Distance RS-232C: Max.15m (Expansion by MODEM), RS-422/485: Max 500m
MODEM communication - Support - -
Network 1: 1 1: N
Diagnostic Via LED and XG-PD
Max. expansion Built-in 2 stages Built-in 2 stages
49
Expansion | Communication
50
| Option modules / Smart link
Programmable Logic Controller
Option modules
XBO-M2MB Memory
XBO-RTCA RTC(Real Time Clock), Battery
XBO-DC04A DC 24V, Input 4 points
XBO-TN04A Transistor(Sink), Output 4 point
XBO-RD01A RTD(Resistance Temperature Detect, Input 1CH)
Smart link
Connection cable
Terminal board
Terminal XBM-DN16S
Connection cable XBE-DC32A XBE-TN32A XBE-TP32A Cable length
board XBM-DN32S
R40H/20HH-05S-XBM3 ● - - - 0.5m
TG7-1H40S
(Terminal R40H/20HH-10S-XBM3 ● - - - 1.0m
board) C40HH-05SB-XBI - ● ● ● 0.5m
C40HH-10SB-XBI - ● ● ● 1.0m
TG7-1H40CA
(Terminal C40HH-15SB-XBI - ● ● ● 1.5m
Board, C40HH-20SB-XBI - ● ● ● 2.0m
Common)
C40HH-30SB-XBI - ● ● ● 3.0m
C40HH-05SB-XBI - - ● - 0.5m
R32C-NS5A-40P C40HH-10SB-XBI - - ● - 1.0m
(Relay C40HH-15SB-XBI - - ● - 1.5m
board: sink) - - ● - 2.0m
C40HH-20SB-XBI
C40HH-30SB-XBI - - ● - 3.0m
51
Software
Variable Monitor
Ladder Monitor
Forced I/O
Fast Ethernet
XGT Panel
Cnet
Other PLC
52
Product list Programmable Logic Controller
Block type unit XBC-DR60SU AC110/240V , 36-point DC input, 24-point Relay output
(Standard type) XEC-DN20SU AC110/240V , 12-point DC input, 8-point TR output
XEC-DR20SU AC110/240V , 12-point DC input, 8-point Relay output
XEC-DN30SU AC110/240V , 18-point DC input, 12-point TR output
XEC-DR30SU AC110/240V , 18-point DC input, 12-point Relay output
XEC-DN40SU AC110/240V , 24-point DC input, 16-point TR output
XEC-DR40SU AC110/240V , 24-point DC input, 16-point Relay output
XEC-DN60SU AC110/240V , 36-point DC input, 24-point TR output
XEC-DR60SU AC110/240V , 36-point DC input, 24-point Relay output
XBC-DR32H AC110~220V, 16-point DC input, 16-point Relay output
XBC-DN32H AC110~220V, 16-point DC input, 16-point TR output
XBC-DR64H AC110~220V, 32-point DC input, 32-point Relay output
XBC-DN64H AC110~220V, 32-point DC input, 32-point TR output
XBC-DR32H/DC DC24V, 16-point DC input, 16-point Relay output
XBC-DN32H/DC DC24V, 16-point DC input, 16-point TR output
Block type unit
(High XBC-DR64H/DC DC24V, 32-point DC input, 32-point Relay output
performance XBC-DN64H/DC DC24V, 32-point DC input, 32-point TR output
type)
XEC-DR32H AC110~220V, 16-point DC input, 16-point Relay output
XEC-DN32H AC110~220V, 16-point DC input, 16-point TR output
XEC-DR64H AC110~220V, 32-point DC input, 32-point Relay output
XEC-DN64H AC110~220V, 32-point DC input, 32-point TR output
XBC-DR32H/D1 DC12/24V, 16-point DC input, 16-point Relay output
XBC-DR64H/D1 DC12/24V, 32-point DC input, 32-point Relay output
XBM-DR16S DC24V, 8-point DC24V input, 8-point relay output
Modular type
unit XBM-DN16S DC24V, 8-point DC24V input, 8-point TR output
XBM-DN32S DC24V, 16-point DC24V input, 16-point TR output
XBE-DC08A 8-point DC24V input
Expansion
I/O module XBE-DC16A 16-point DC24V input
XBE-DC32A 32-point DC24V input
53
Product list
54
Programmable Logic Controller
55
Dimension
XBC-S type
56
Programmable Logic Controller
XBC-E type
(DR10E, DR14E)
XBC-E type
(DR20E, DR30E)
57
Worldwide Network
� For your safety, please read user's manual thoroughly before operating.
� Contact the nearest authorized service facility for examination, repair, or adjustment.
� Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself !
Safety Instructions � Any maintenance and inspection shall be performed by the personnel having expertise concerned.