DeltaV Product Data Sheet

November 2009 Page 1

S-series Electronic Marshalling

S-series Electronic Marshalling

The DeltaV CHARM I/O Card (CIOC)

I/O Anywhere you need it Single Channel granularity Reduces installed cost of system Fully redundant architecture Field mounted capable hardware Plug and Play I/O

Introduction
DeltaVs S-series Electronic Marshalling delivers a new level of control system I/O performance with unprecedented flexibility and ease of use. The CHARM I/O card (CIOC) supports up to 96 individually configurable channels and is designed specifically for multi-core home run cables in centrally located marshalling cabinets. It can also be installed in field junction boxes to further reduce system design and installation costs. All communications are completely redundant from the channel (CHARM) to the DeltaV S-series controller.

www.EmersonProcess.com/DeltaV

DeltaV Product Data Sheet


November 2009 Page 2

S-series Electronic Marshalling


to create the I/O definition automatically in your DeltaV configuration database. CHARMs use a self keying system to automatically set a channel for a specific CHARM type. Users cannot mistakenly insert a CHARM into the wrong terminal block. Assign all, one or any number of channels to a controller with a simple click and drag.

Benefits
I/O Anywhere you need it. DeltaV CHARM I/O
Card (CIOC) provides an unprecedented flexibility in control system I/O topology. Using standard Ethernet infrastructure hardware you can add I/O anywhere you need it. From a local I/O cabinet to remote enclosures miles away, simply install the hardware and connect it to the DeltaV control network. Each I/O card can serve I/O signals to any four controllers in the system with 50 ms updates for fast, reliable control.

Single Channel granularity. The CHARM I/O


architecture allows each individual channel to be characterized for the requirements of the field device. Any instrument signal can be wired to any terminal block. The channel is then electronically marshalled by installing the appropriate CHARM and assigning the channel to one of four controllers. Home run multi-core instrument cables can be landed in order on a series of CHARM terminal blocks without concern for signal types.

Reduces installed cost of system. DeltaVs


Electronic Marshalling helps reduce overall system cost by eliminating internal cabinet cross wiring, reducing overall footprint, simplifying I/O channel assignments, and reducing FAT activities. Electronic Marshalling provides separation between I&E hardware installation schedules and Control Strategy development. Wiring can begin earlier knowing any late changes can be done without lifting a wire. Separation of the controller and I/O allows more efficient cabinet designs knowing late scope changes can add I/O anywhere. Adding addition control capacity does not require re-wiring I/O. Simply assign the control modules and their I/O signals to the new controller, without lifting a wire.

CHARM and Terminal Block installation. Field power is provided through a redundant 24VDC bus to each CHARM, with up to 100 mA per CHARM. Higher current Discrete Channels can be powered through integrated power injection bus local to each CHARM Baseplate.

Fully redundant communications. The CIOC


architecture is fully redundant. This starts with the two I/O cards on a carrier. The carrier has redundant communication modules for primary and secondary network connections. There are two 24 VDC input power connections. The carrier connects to the CHARMS Baseplates and provides redundant power and communication buses to the CHARMs. Everything is redundant down to the individual channel.

Field mounted capable hardware. All


components of the CIOC are rated for installation in Class 1/Div 2 or Zone 2 hazardous locations. The extended operating temperature ranges and G3 environment rating allows them to be installed in field mounted junction boxes. This further reduces the foot print of the central equipment rooms as well as reducing the overall wiring infrastructure of traditional multi-core instrumentation cable.

Plug and Play I/O. The DeltaV CIOC has been


designed for ease of use, both in physical installation and its software tools. Components snap together with secure DIN-rail latches and interlocking carrier connectors. Attach a series of 96 I/O channels to a DIN-rail in a matter of minutes. Insert the CHARMS and auto sense the node

DeltaV Product Data Sheet


November 2009 Page 3

S-series Electronic Marshalling


The CHARM I/O card carrier is mounted to the top of a vertical DIN rail and up to eight CHARM Baseplates are mounted below it, snapping easily to the DIN rail as they are connected to each other. The bus termination assembly is attached at the bottom. A standard DIN-rail lock to keep the entire assembly in place. Each Baseplate is ordered pre-loaded with 12 terminal blocks that are ready to receive field wires from 2, 3 and 4wire devices. Electronic Marshalling eliminates the need to scramble the field wiring or to partition the I/O in order to match signals to channel types of specific cards. Simply connect field signal multi-cores in an orderly fashion as desired. Insert the appropriate CHARM into each terminal block to complete the field circuit and the signal is ready to be used by any one of 4 S-series controllers. No Cross-Wiring. Each CHARM acts as circuit protection device and field wiring disconnects. Signals are current limited or fused to protect against wiring faults to ground. Each CHARM provides surge protection to meet industry standards in the area of EMC, and is designed to fail during overvoltage conditions due to incorrect field wiring. Signal faults are isolated to the single charm.

Product Description
Electronic Marshalling hardware includes:
CHARM I/O Carrier (DIN rail mounted and supports redundant pair of CHARM I/O Cards) CHARM I/O Card (provides communication between CHARMS and the Ethernet I/O network to S-series controllers) CHARM Base plate (DIN rail mounted with interleaving power and bus connectors. Supports 12 CHARMS and their terminal blocks, as well as connection for injected field power) CHARM Terminal Block (removable terminal block providing terminal connections to field wiring and physical latch for CHARM) CHARMs (Characterizing Module for each field signal. Provides basic analog to digital conversion and signal isolation to the redundant communication bus) Bulk AC to 24 VDC power supply for CIOC and field devices. (connected to the CIOC carrier with optional redundant power connections) Cable Extenders that provide flexibility in carrier mounting.

I/O bus termination (provides bus terminations for redundant I/O bus)

CHARMS can be partially ejected to a locked position that disconnects the field wiring from the system to perform field maintenance actions or to remove power to a field device. Activating the CHARM latch ejects the CHARM to the detent position. Closing the latch locks the CHARM in place and isolates the field wiring for field work.. CHARM Latch mechanism The CIOC communicates over Ethernet with up to 4 controllers, allowing great flexibility and ease of system expansion. Additional controllers can be added to accommodate increased control scope and I/O can be reassigned without changing the physical wiring. CHARMs can be added to any existing base plate position and autosensed online. Additional CIOCs can be added on line.

CHARM I/O Card.

DeltaV Product Data Sheet


November 2009 Page 4

S-series Electronic Marshalling


The Injected Power Terminal block is designed to be used with the Isolated CHARM types, allowing the CHARM to provide up to 1 amp of system power to the field device. Supplemental field power is connected to the baseplates injected power input terminals, located on the Address Plug terminal block, and distributed to the 12 CHARMs through the local power bus of the baseplate. Injected power Terminal Blocks connect to this power bus and provide system power to the circuit. The injected power can be 24 VDC, 120 VAC or 230 VAC and can provide a total of 10 Amps of field power for the 12 channels of the baseplate. Typically, all the CHARMs installed on a base plate will have compatible voltage levels as these signals most likely share the same multi-core cable. It is also common practice to separate low voltage and high voltage signals for safety. Standard Terminal blocks and Injected Power terminal blocks can be used on the same carrier, typically to allow the use of DO 24 VDC isolated CHARMs on higher wattage devices along side of standard 24 VDC instrumentation signals.

CHARM Types
A variety of analog and discrete CHARMs are available to meet your specific requirements. The following CHARMS are available in v11: AI 0/4-20 mA HART AO-0/4-20 mA HART DI NAMUR DI 24 VDC Low Side Detection DO 24 VDC High Side Thermocouple/mV RTD Voltage 0-10V

In addition, the following CHARMs will be available as isolated channels supporting higher current and voltage ratings. DI 24 VDC Isolated DO 24 VDC Isolated DI 120 VAC Isolated DI 230 VAC Isolated DO 120 VAC Isolated DO 230 VAC Isolated

CHARM Keying Posts


The terminal blocks contain keying posts that are automatically set and locked to the unique position of the first CHARM installed. The keys prevent the insertion of an incorrect CHARM during maintenance activities. If needed, the Keys can be manually reset to allow a channel to be re-tasked for a different signal type.

All CHARMs have a bi-color Power/Integrity LED that indicates the health of the CHARM. The indications follow NE44 guidelines and provide clear, actionable instruction to the maintenance personnel. Green Solid: Normal Operation Green Blink: Normal awaiting configuration Red Blink: Fault detected on wiring Red Solid: Internal Fault detected Discrete CHARMs have a Yellow LED to indicate the state of the field signal. All CHARMs meet ISA G3 corrosion specifications by the careful selection of superior electronic components and the use of conformal coating. Discrete input CHARMS support Pulse Counters with a maximum frequency of 10 KHz.

I/O Terminal Block Options


There are 2 different I/O terminal blocks available to meet the wiring needs of field signals. Standard Terminal Block Injected Power Terminal Block CHARM standard Terminal block The keying mechanism consists of two keying posts that rotate and lock into the terminal block base. Each CHARM is assigned a unique key.

The Standard Terminal block can be used with all CHARMS types. For traditional wiring of field instrumentation, the CHARMs provide loop power through the internally distributed 24 VDC field power. Refer to specific CHARM specifications for wiring information.

DeltaV Product Data Sheet


November 2009 Page 5

S-series Electronic Marshalling

Hardware Specifications
Common Environmental Specifications (all components)

Operating temperature Storage temperature Relative humidity Protection rating Airborne contaminants Shock Vibration

-40 to 70 C (-40 to 158 F) -40 to 85 C (-40 to 185 F) 5 to 95% , non-condensing IP 20, NEMA 12 ISA-S71.04-1985 Airborne Contaminants Class G3 Conformal coating 10 g -sine wave for 11 ms 1 mm peak-to-peak from 5 to 16 Hz; 0.5 g from 16 to 150 Hz

CHARM I/O card and carrier

DeltaV Product Data Sheet


November 2009 Page 6

S-series Electronic Marshalling

CHARM I/O Baseplate with CHARMS

CHARM

DeltaV Product Data Sheet


November 2009 Page 7

S-series Electronic Marshalling

CHARM Standard Terminal Block

CHARM Injected Power Terminal Block

DeltaV Product Data Sheet


November 2009 Page 8

S-series Electronic Marshalling

Address Plus

Address Plug Terminal Block

DeltaV Product Data Sheet


November 2009 Page 9

S-series Electronic Marshalling


Specifications for CHARM I//O Carrier

CHARM I/O Card hardware

Number of I/O Cards per carrier Input power (redundant) Redundant Ethernet connections

2 (redundant pair) 24 VDC 10% at 15 A maximum Fiber-optic: 100BASE-FX with MTRJ connectors; - Full duplex operation; - 2 km nominal distance. Copper twisted pair: 10/100BASE-TX with RJ45 connectors; - Full duplex operation - 100 m distance DIN rail Latch to T-type rail Specifications for CHARM IO Card

Mounting

Number of I/O Channels Number of I/O Clients Number or CIOCs per Controller Number or CIOCs per system I/O update rates User memory CIOC input power (24 VDC) CIOC Heat Dissipation

96 Channels, Individually defined signal types 4 (Controllers) 16 300 50ms N/A 0.28 Amps per Redundant CIOC node (CHARM power requirements are in addition) 6.68 Watts per Redundant CIOC node - 2 Watts per CIOC - 1.34 Watts per Communication module 6.3 VDC redundant power, 24 Watts maximum Non-replaceable Fuse 2-wide CHARM I/O Carrier Redundant Ethernet connections via CHARM I/O Carrier Auto Assigned during commissioning LED Indicators:

CIOC output to CHARMS Fuse Protection (internal) Mounting Communication Network Addressing

Green Power Red Error Green Active/Standby Yellow flashing Pri./Sec. CN

Indicates DC power is applied. Indicates an error condition. Indicates operating mode of each CIOC Indicates valid control network communication.

DeltaV Product Data Sheet


November 2009 Page 10

S-series Electronic Marshalling


CHARM Baseplate 12 8 One Address Plug (1 through 8) - Standard Terminal Block - Injected Power Terminal Block 1 per channel, plus 1 for cable shield 2 2.1 -0.32 mm / 14 22 AWG Gold plated connectors for shield continuity Shield drain connection in Bus Terminator DIN rail Latch to T-type rail Specifications for Bus Termination

Number of channels per baseplate Number of base plates per CIOC Addressing Terminal blocks Shield connections

Mounting

Number of connections Cross Section Connection type Strip length

2 (Shield Drain wire) 2.1 -0.32 mm / 14 22 AWG Screw Cage 9 - 11 mm / 0.36 0.43 in.
2

DeltaV Product Data Sheet


November 2009 Page 11

S-series Electronic Marshalling


Specifications for Standard Terminal Block 4 2.1 -0.32 mm / 14 22 AWG Screw Cage 1 Amp continuous Black 9 - 11 mm / 0.36 0.43 in. Specifications for Injected Power Terminal Block
* 2

Number of connections Cross Section Connection type Maximum Current Color Strip length

Number of connections Cross Section Connection type Maximum Current Color Strip length

2 -025 -0.32 mm / 14 22 AWG Screw Cage 1 Amp continuous Black 9 - 11 mm / 0.36 0.43 in. Specifications for Address Plug Terminal Block
* 2

Number of connections Cross Section Connection type Maximum Current Color Strip length
*

2 sets of 2 connections -025 -0.32 mm / 14 22 AWG Screw Cage 10 Amp continuous Black 9 - 11 mm / 0.36 0.43 in.
* 2

Maximum Current is limited by CHARM and Baseplate limits

DeltaV Product Data Sheet


November 2009 Page 12

S-series Electronic Marshalling


Specifications for AI CHARM, 0/4 to 20 mA, HART

Analog Input CHARMS

Sensor Types

4-20 mA with or without HART 0-20 mA Supports 2-wire and 4-wire device types 4-20 mA, (0-20 mA optional) 0 to 24 mA 17.4 V at 20 mA @ 24 VDC input 0.1% of span (0-60 C) 0.25% of span (over -40 -70 C) 0.05% of span 16 bit A/D converter None required N/A -3dB at 2.7 Hz, -20.5dB at 20 Hz Current Limiting circuit and field wiring disconnect 30 mA max @ 24 VDC 0.35 W HART v7 pass-through for AMS HART v7 variable and device status available to control 500 ms

Nominal signal range (span) Full signal range Field Power (2-wire) Accuracy over temperature range Repeatability Resolution Calibration DC/50/60 Hz Common mode rejection Rolloff Frequency (Anti Aliasing) Field Circuit Protection CHARM power req. CHARM Heat Dissipation HART support HART data update rates

Simplified circuit and connection diagrams for HART AI-Charm 0/ 4 to 20 mA two wire and four wire transmitters

DeltaV Product Data Sheet


November 2009 Page 13

S-series Electronic Marshalling

RTD CHARMS
Specifications for RTD Input CHARM Sensor types Sensor Configuration Full Scale signal range Accuracy Repeatability Resolution Calibration Sensor excitation current DC/50/60 Hz Common mode rejection Rolloff Frequency (Anti Aliasing) Isolation Open sensor detection Field Circuit Protection CHARM power req. CHARM Heat Dissipation RTD input (Types listed in Table) 2 wire, 3 wire, or 4 wire See Table next page See Table next page 0.05% of span 24 Bit A/D converter None required 500 A in 2-wire and 4 wire configurations 250 A in 3-wire 90dB -3dB at 2.7 Hz, -20.5dB at 20 Hz Each sensor galvanically isolated and factory tested to 1000 VDC Yes Current Limiting circuit and field wiring disconnect 10 mA max @ 24 VDC 0.25 W

DeltaV Product Data Sheet


November 2009 Page 14

S-series Electronic Marshalling

RTD, ohms Sensor Type Specifications Sensor Type Pt100 Pt200 Pt500 Pt1000 Ni120 Ni100 Ni200 Ni500 Ni1000 Cu10 Resistance/user defined Operating Range -200 to 850C -200 to 850C -200 to 850C -200 to 260C -80 to 260C -80 to 260C -80 to 260C -80 to 260C -80 to 150C -200 to 260C 0 to 2,000 25 Reference Accuracy 0.25 C 0.25 C 0.25 C 0.25 C 0.15 C 0.20 C 0.20 C 0.20 C 0.20 C 0.25 C 0.25 Temperature Drift 0.02 C/C 0.02 C/C 0.02 C/C 0.02 C/C 0.01 C/C 0.01 C/C 0.01 C/C 0.01 C/C 0.01 C/C 0.02 C/C 0.03 /C Resolution ~0.02 C ~0.02 C ~0.02 C ~0.01 C ~0.01 C ~0.01 C ~0.01 C ~0.01 C ~0.01 C ~0.01 C ~0.031

Simplified circuit diagram for RTD CHARM

DeltaV Product Data Sheet


November 2009 Page 15

S-series Electronic Marshalling

Thermocouple/mV CHARMS
Specifications for Thermocouple/mV Input CHARM, Sensor types Thermocouple mV B, E, J, K, N, R, S, T, uncharacterized Low level voltage source See Table next page See Table next page 0.05% of span 24 Bit A/D converter None required 1.0 C -40 to 85 C Local/Remote 90dB -3dB at 2.7 Hz, -20.5dB at 20 Hz Each sensor galvanically isolated and factory tested to 1000 VDC Yes Field wiring disconnect 10 mA max @ 24 VDC 0.25 W

Full Scale signal range Accuracy Repeatability Resolution Calibration Cold junction compensation(CJC) Accuracy Range Location DC/50/60 Hz Common mode rejection Rolloff Frequency (Anti Aliasing) Isolation Open sensor detection Field Circuit Protection CHARM power req. CHARM Heat Dissipation

DeltaV Product Data Sheet


November 2009 Page 16

S-series Electronic Marshalling

Sensor Type Specifications Sensor Type B E J K N R S T 100 mV 50 mV 20 mV


1

25 Reference 1 Accuracy 0.8 C 0.4 C 0.6 C 0.4 C 0.6 C 0.8 C 0.8 C 0.5 C 0.025 mV 0.020 mV 0.010 mV

Temperature Drift 0.03 C/ C 0.03 C/ C 0.04 C/ C 0.03 C/ C 0.04 C/ C 0.05 C/ C 0.05 C/ C 0.02 C/ C 0.002 mV/ C 0.001 mV/ C 0.0005 mV/ C

Nominal Resolution ~ 0.024 C ~ 0.018 C ~ 0.022 C ~ 0.025 C ~ 0.024 C ~ 0.028 C ~ 0.028 C ~ 0.01 C ~ 0.0031mV ~ 0.0015mV ~ 0.0006mV

Full Scale 250 to 1810 C -200 to 1000 C -210 to 1200 C -270 to 1372 C -270 to 1300 C -50 to 1768 C -50 to 1768 C -270 to 400 C -100 to 100 mV -50 to 50 mV -20 to 20 mV

Operating Range 500 to 1810 C -200 to 1000 C -190 to 1200 C -200 to 1372 C -190 to 1300 C -50 to 1768 C -40 to 1768 C -200 to 400 C -100 to 100 mV -50 to 50 mV -20 to 20 mV

Total error is made up of the 25 C reference accuracy value, plus the CJC accuracy value, plus the sensor accuracy value

Simplified circuit diagram of Thermocouple/mV CHARM

DeltaV Product Data Sheet


November 2009 Page 17

S-series Electronic Marshalling

Analog Output CHARMS


Specifications for HART AO CHARM, 0/4 to 20 mA Sensor Types Nominal signal range (span) Full signal range Accuracy over temperature range Resolution Calibration Available field power Open-Loop Detection Field Circuit Protection CHARM power req. CHARM Heat Dissipation HART support HART data update rates 4 to 20 mA with or without HART 0 to 20 mA 4 to 20 mA, (0 to 20 mA option) 0 to 24 mA 0.25% of span (0 to 60 C) 0.5% of span (-40 to 70 C) 16 bit D/A converter Non required 20 mA at 15 VDC supply into 750 load < 0.70 mA (on 4 to 20 mA signal) Current Limiting Circuit and field wiring disconnect 30 mA max @ 24 VDC 0.42 W HART v7 pass-through for AMS HART v7 variable and device status available to control 500 ms

Simplified circuit and connection diagram for HART AO CHARM

DeltaV Product Data Sheet


November 2009 Page 18

S-series Electronic Marshalling

Discrete Input CHARMS


Specifications for DI CHARM, 24 VDC, NAMUR Sensor Types Detection level for On Detection level for Off Channel Impedance Wetting Voltage Fault Detection capable Configurable channel types: Discrete input Pulse Count Dry contact or discrete state sensor changing <2 Hz Pulse train 0.1 Hz to 10 KHz, 50 sec min pulse width Current Limiting circuit with field disconnect 26 mA max @ 24 VDC 0.58 W NAMUR Sensors, Dry Contacts 2.1 mA 1.2 mA 1.5 K (approximate) 12 Volts ( 5%) NAMUR Sensors or field resistor pack

Field Circuit Protection CHARM power req. CHARM Heat Dissipation

Simplified circuit and connection diagram for DI NAMUR CHARM

DeltaV Product Data Sheet


November 2009 Page 19

S-series Electronic Marshalling

Specifications for DI CHARM 24 VDC, Low Side Detect Sensor Types Detection level for On Detection level for Off Channel Impedance Wetting Voltage Fault Detection capable Configurable channel types: Discrete input Pulse Count Dry contact or discrete state sensor changing <2 Hz Pulse train 0.1 Hz to 10 KHz, 50 sec min pulse width Current Limiting circuit with field disconnect 15 mA max @ 24 VDC 0.30 W 24 VDC Dry Contacts 2.25 mA 1.75 mA 4.8 K (approximate) 22.5Volts ( 5%), current limited to 12.5 mA nominal field resistor pack (optional)

Field Circuit Protection CHARM power req. CHARM Heat Dissipation

Simplified circuit and connection diagram for DI 24 VDC, CHARM

DeltaV Product Data Sheet


November 2009 Page 20

S-series Electronic Marshalling

Specifications for DI CHARM, 24 VDC, Isolated

Detection level for On Detection level for Off Wetting Current Output Impedance Field circuit power per card Isolation Internally fused CHARM power req. CHARM Heat Dissipation

1.4 mA 0.56 mA 2 mA @ 24 VDC 60 K (approximately) 15 mA max @ 24 VDC Each channel is optically isolated from the system at 250 VAC 2.0 A 15 mA max @ 24 VDC 0.30 W

TBD
Simplified circuit and connection diagram for DI CHARM, 24 VDC, isolated

DeltaV Product Data Sheet


November 2009 Page 21

S-series Electronic Marshalling

Specifications for DI CHARM, 120 VAC, Isolated

Detection level for On Detection level for Off Wetting Current Output Impedance Field circuit power per card Isolation Internally fused CHARM power req. CHARM Heat Dissipation

1.4 mA 0.56 mA 2 mA at 120 VAC 60 K (approximately) 15 mA max at 120 VAC Each channel is optically isolated from the system at 250 VAC 2.0 A 15 mA max @ 24 VDC 0.30 W

TBD
Simplified circuit and connection diagram for DI CHARM, 120 VAC, isolated

DeltaV Product Data Sheet


November 2009 Page 22

S-series Electronic Marshalling

Specifications for DI CHARM, 230VAC, Isolated Detection level for On Detection level for Off Wetting Current Input Impedance Field circuit power per card Isolation Internally fused CHARM power req. CHARM Heat Dissipation 84 to 130 VAC 0 to 34 VAC 2 mA at 120 VAC 60 K (approximately) None Each channel is optically isolated from the system at 250 VAC and from other channels at 250 VAC. 2.0 A

TBD
Simplified circuit and connection diagram for DI CHARM 230 VAC, Isolated

DeltaV Product Data Sheet


November 2009 Page 23

S-series Electronic Marshalling

Discrete Output CHARMS


Specifications for DO CHARM 24 VDC, High Side Device Type On State Output rating Off-state leakage Line Fault Detection Configurable output behavior 24 VDC Solenoid coils 100 mA continuous @ 24 VDC 1 mA maximum Short Circuit < 50 Ohms load Open Circuit > 20 K Ohms load Latching Output Momentary Output Continuous Pulse Output Current Limiting circuitry and field disconnect (Short Circuit protected to 200 mA) 110 mA max @ 24 VDC 0.30 W

Field Protection CHARM power req. CHARM Heat Dissipation

Simplified circuit and connection diagram for DO 24 VDC CHARM

DeltaV Product Data Sheet


November 2009 Page 24

S-series Electronic Marshalling


Specifications for DO CHARM 24 VDC, Isolated

Device Type Output range Output rating Off state leakage Configurable channel types: Discrete output Momentary output Continuous pulse output

24 VDC Inductive Load 4 VDC to 32 VDC 1.0 A continuous ( 2 A inrush for < 100 msec) 1 mA maximum Output signal profile Output stays in last state submitted by the control logic. Output remains active for a pre-configured time period. Output is active as a percentage of a pre-configured base time period (100 ms to 100 s). Resolution = 5 ms The output channel is galvanically isolated and factory tested to 1000 VDC. Current Limiting circuitry and field disconnect 10 mA max @ 24 VDC 0.24 W

Isolation Field Protection CHARM power req. CHARM Heat Dissipation

Simplified circuit and connection diagrams for DO 24 VDC, Isolated CHARM

DeltaV Product Data Sheet


November 2009 Page 25

S-series Electronic Marshalling

Specifications for DO CHARM 120/230 VAC, Isolated Sensor types Off state leakage Output range Output rating Configurable channel types: Discrete output Momentary output Continuous pulse output Output signal profile Output stays in last state submitted Output remains active for a pre-configured time period. Output is active as a percentage of a pre-configured base time period (100 ms to 100 s). Resolution = 5 ms Each channel is optically isolated from system at 1500 VDC and from other channels at 1500 VDC Current Limiting circuitry and field disconnect TBD TBD 120 VAC Inductive load 2 mA maximum at 120 VAC 20 to 250 VAC 1.0A maximum continuous per channel; (inrush 5A for < 100 ms: 20A for < 20 ms)

Isolation Field Protection CHARM power req. CHARM Heat Dissipation

TBD
Simplified circuit and connection diagram for DO CHARM, 120 VAC, Isolated

DeltaV Product Data Sheet


November 2009 Page 26

S-series Electronic Marshalling

Voltage Charms
Specifications for Input CHARM 0-10 Volts Isolated Sensor types Full Scale signal range Accuracy Input Impedance Repeatability Resolution Calibration Common mode rejection Isolation Open sensor detection Field Circuit Protection CHARM power req. CHARM Heat Dissipation Voltage device See Table next page See Table next page 10 M 0.05% of span 24 bit A/D converter None required 90dB at 50/60 Hz Each sensor galvanically isolated and factory tested to 1500 VDC Yes Field wiring disconnect 10 mA max @ 24 VDC 0.25 W

DeltaV Product Data Sheet


November 2009 Page 27

S-series Electronic Marshalling


Isolated Input mV/V Sensor Type Specifications

Sensor Type 20 mV 50 mV 100 mV 0-5V 0 - 10 V 1-5V 1V 5V 10 V


1

25 Reference 1 Accuracy 0.010 mV 0.020 mV 0.025 mV 0.025 mV 0.005 V 0.010 V 0.0005 V 0.0025 V 0.005 V

Temperature Drift 0.0005 mV/ C 0.001 mV/ C 0.002 mV/ C 0.002 mV/ C 0.0002 V/ C 0.0004 V/ C 0.0002 V/ C 0.0002 V/ C 0.0002 V/ C

Nominal Resolution ~ 0.0006mV ~ 0.0015mV ~ 0.0031mV 0.00009 V 0.00016 V 0.00009 V 0.00015 V 0.00017 V 0.0003 V

Full Scale -20 to 20 mV -50 to 50 mV -100 to 100 mV 0 to 5 V 0 to 10 V 1 to 5 V 1V 5V 10 V

Operating Range -20 to 20 mV -50 to 50 mV -100 to 100 mV 0 to 5 V 0 to 10 V 1 to 5 V 1V 5V 10 V

Total error is made up of the 25 C reference accuracy value, plus the sensor accuracy value

TBD
Simplified circuit diagram of Isolated Voltage CHARM

DeltaV Product Data Sheet


November 2009 Page 28

S-series Electronic Marshalling


Marine Certifications: IACS E10:2006 Rev.5 Control, protection & Safety
ABS Certificate of Design Assessment Bureau Veritas Certificate DNV Marine Certificate Lloyds Register

System Compatibility
CHARM I/O hardware requires:

SX or SD Plus controllers

S-series Controllers with CHARMS I/O and M-series controllers can be installed on the same DeltaV Area Control Network in v11 and beyond. Control modules can be assigned to either series of controller and intercontroller references are fully supported between controller series.

GOST Hazardous Area certification Zone 2 (Russian)


Other country specific certifications may also be available. Verify with your local Emerson sales office to confirm any certification requirements not listed here.

Certifications
The following certifications are pending for CHARM I/O products. Please verify with the appropriate certifying agency for a specific list of approved components.

CE: - EMC- EN 61326-1:2006 - LVD- EN 61010-1:2001 CSA: - CLASS 2252 05 - PROCESS CONTROL EQUIPMENT:
CAN/CSA-C22.2 No. O-M91 General RequirementsCanadian Electrical Code, Part II CAN/CSA-C22.2 No. 61010-1-04 Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use, Part 1: General Requirements

CENELEC Zone 2 ATEX EN 60079-15:2005


Certifying agency: Nemko Certificate Number: TBD

Refer to document TBD "DeltaV Scalable Process System Zone 2 Installation Instructions" FM Approval Class 1 Division 2 Hazardous Locations
Certifying agency: FM Approvals Certificate Number: TBD

Refer to document TBD "DeltaV Scalable Process System Class 1 Division 2 installation Instructions

DeltaV Product Data Sheet


November 2009 Page 29

S-series Electronic Marshalling

Ordering Information
CHARM I/O CARD Description Redundant CIOC, includes 2 CHARMS I/O Cards, CHARMS I/O Carrier with screw terminals, two dual port Communications modules for twisted copper, and DIN-Rail Stop with Integrated Bus Terminators Redundant CIOC with fiber optics, includes 2 CHARMS I/O Cards, CHARMS I/O Carrier with screw terminals, two single port Communications modules for multi mode fiber optic cable, and DIN-Rail Stop with Integrated Bus Terminators CHARMS Baseplate Assembly, includes CHARMS Baseplate, CHARM Address Terminal Block with screw terminals, and 12 Standard CHARM Terminal blocks CHARMS Baseplate Assembly with Injected Field Power, includes CHARMS Baseplate, CHARM Address Terminal Block with screw terminals, and 12 Injected Power CHARM Terminal blocks CHARMS Addressing Plugs, includes Address Plugs 1 through 8 CHARMS Baseplate DIN-Rail Stop with Integrated Bus Terminators CHARMS Baseplate DIN-Rail Stop with Cable Connections CHARMS Baseplate DIN-Rail Cap with Integrated Bus Terminators CHARMS Baseplate Cable Extender Low Voltage Instrumentation CHARMS DI NAMUR DI 24 VDC Low Side Detection DO 24 VDC High Side DO 24 VDC Isolated AI 0/4-20 mA HART Thermocouple/mV RTD AO-0/4-20 mA HART DI 24 VDC Isolated High Voltage Instrumentation CHARMS DI 120 VAC Isolated DI 230 VAC Isolated DO 120 VAC Isolated DO 230 VAC Isolated Specialty Instrumentation CHARMS AI 0-10 Volt Isolated RTQ RTQ RTQ RTQ RTQ SE4301T01 SE4301T02 SE4302T01 SE4302T02 SE4303T01 SE4303T02 SE4303T03 SE4304T01 RTQ Model Number SE6501T01

SE6501T02

SE4601T01 SE4601T02

SE4602 SE4603T01 SE4603T02 SE4604T01 SE4605T01

DeltaV Product Data Sheet


November 2009 Page 30

S-series Electronic Marshalling

Prerequisites
S-Series Electronic Marshalling hardware requires DeltaV v11.3 or later software.

To locate a sales office near you, visit our website at: www.EmersonProcess.com/DeltaV Or call us at: Asia Pacific: 65.777.8211 Europe, Middle East: 41.41.768.6111 North America, Latin America: +1 800.833.8314 or +1 512.832.3774

For large power, water, and wastewater applications contact Power and Water Solutions at: www.EmersonProcess-powerwater.com Or call us at: Asia Pacific: 65.777.8211 Europe, Middle East, Africa: 48.22.630.2443 North America, Latin America: +1 412.963.4000

Emerson Process Management 2009. All rights reserved. For Emerson Process Management trademarks and service marks, go to: http://www.emersonprocess.com/home/news/resources/marks.pdf. The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warrantees or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the design or specification of such products at any time without notice.