Professional Documents
Culture Documents
8 Flushing and Domestic Water Supply Calculation
8 Flushing and Domestic Water Supply Calculation
DOCUMENT NO
DATE
10.12.2009
1-H-T-N36A-PL-DC-010
Calculations of flow and head loss based on cumulative fixture unit
TITLE:
DESIGNED
CHECKED
SVD
AVBC
APPROVED
SHEET
SVn
The cumulative F.U through each pipe is worked out and corresponding flow through the pipe is arrived.The head loss through each pipe section will be
worked out based on flow rate through that pipe stretch.
Sl.No.
Pipe reference
From
To
Flow
through
Q
AssumedPipe
Pipe
Level at Length of
Velocity
Dia.
roughn
Input
Pipe
D
C
V
Elevation
L
Equivalent
length
Le = 1.25 L
Frictional
loss
hf
Lps
mm
PPR
m/s
Cumulative
Total Head
Frictional
hf
H
m
m
Residual
head
P
m
Available
head after
PRV
Available
Residual
head after
PRV
lvl-0
lvl-1
lvl-1
lvl-2
lvl-1 to 2
lvl-2
1
2
3
4
3
5
2
3
4
A
5
B
40
23.5
7
7
7
7
45
45
27.5
16
4.5
2.97
2.29
1.7
1.7
1.7
1.7
65
45.6
36.2
36.2
36.2
36.2
120
120
120
120
120
120
0.895
1.403
1.653
1.653
1.653
1.653
-1
3.2
3.2
3.2
12.4
12.4
67.1
17.1
1.5
1.5
8.15
1.5
83.875
21.375
1.875
1.875
10.1875
1.875
1.59
1.41
0.22
0.22
1.19
0.22
1.59
3
3.22
3.44
4.19
4.41
105
105
105
105
105
105
104.41
98.8
98.58
98.36
88.41
88.19
55
55
55
55
55
48.8
48.58
48.36
38.41
38.19
lvl-1
lvl-1
lvl-1
lvl-1 to 2
lvl-2
lvl-2 to 3
lvl-3
3
6
7
6
8
8
9
6
7
C
8
D
9
E
9.5
2.5
2.5
7
2.5
4.5
4.5
45
17.5
9.5
7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
36.2
36.2
36.2
36.2
36.2
36.2
36.2
120
120
120
120
120
120
120
1.653
1.653
1.653
1.653
1.653
1.653
1.653
3.2
3.2
3.2
12.4
12.4
16.6
16.6
4.5
1.5
1.5
8.15
1.5
4.2
1.5
5.625
1.875
1.875
10.1875
1.875
5.25
1.875
0.66
0.22
0.22
1.19
0.22
0.61
0.22
3.66
3.88
4.1
4.85
5.07
5.46
5.68
105
105
105
105
105
105
105
98.14
97.92
97.7
87.75
87.53
82.94
82.72
55
55
55
55
55
55
55
48.14
47.92
47.7
37.75
37.53
32.94
32.72
lvl-1 to 18
lvl-18
lvl-1
lvl-19
lvl-19 to 21
lvl-21
2
10
10
11
11
12
10
F
11
G
12
H
16.5
7.5
9
4.5
4.5
4.5
45
2.03
1.7
1.7
1.7
1.7
1.7
54.2
45.6
45.6
45.6
45.6
45.6
120
120
120
120
120
120
0.880
1.041
1.041
1.041
1.041
1.041
69.95
69.95
73.95
73.95
81.85
81.85
65.7
1.5
4
1.5
7.9
1.5
82.125
1.875
5
1.875
9.875
1.875
1.87
0.07
0.19
0.07
0.38
0.07
3.46
3.53
3.65
3.72
4.03
4.1
105
105
105
105
105
105
31.59
31.52
27.4
27.33
19.12
19.05
17.5
4.5
Remarks
DOCUMENT NO
DATE
10.12.2009
1-H-T-N36A-PL-DC-010
Calculations of flow and head loss based on cumulative fixture unit
TITLE:
DESIGNED
CHECKED
SVD
AVBC
APPROVED
SHEET
SVn
Pipe reference
Sl.No.
From
Fixture Unit
Flow
in each pipe through
FU
Q
To
AssumedPipe
Pipe
Level at Length of
Velocity
Dia.
roughn
Input
Pipe
D
C
V
Elevation
L
Equivalent
length
Le = 1.25 L
Frictional
loss
hf
Cumulative
Total Head
Frictional
hf
H
Lps
mm
PPR
m/s
Residual
head
P
m
Available
head after
PRV
Available
Residual
head after
PRV
lvl-0
lvl-1
lvl-1
lvl-2
lvl-1 to 2
lvl-2
1
2
3
4
3
5
2
3
4
A
5
B
120
88
8
28
28
28
4.6
4.06
2.51
2.51
2.51
2.51
79.6
54.2
45.6
45.6
45.6
45.6
140
140
140
140
140
140
0.925
1.761
1.538
1.538
1.538
1.538
-1
3.2
3.2
3.2
12.4
12.4
67.1
17.1
1.5
1.5
8.15
1.5
83.875
21.375
1.875
1.875
10.1875
1.875
1
1.32
0.11
0.11
0.6
0.11
1
2.32
2.43
2.54
2.92
3.03
105
105
105
105
105
105
105
99.48
99.37
99.26
89.68
89.57
55
55
55
55
55
49.48
49.37
49.26
39.68
39.57
lvl-1
lvl-1
lvl-1
lvl-1 to 2
lvl-2
lvl-2 to 3
lvl-3
3
6
7
6
8
8
9
6
7
C
8
D
9
E
32
8
8
24
8
16
16
2.66
1.7
1.7
2.3
1.7
2.016
2.016
45.6
45.6
45.6
45.6
45.6
45.6
45.6
140
140
140
140
140
140
140
1.630
1.041
1.041
1.409
1.041
1.235
1.235
3.2
3.2
3.2
12.4
12.4
16.6
16.6
4.5
1.5
1.5
8.15
1.5
4.2
1.5
5.625
1.875
1.875
10.1875
1.875
5.25
1.875
0.37
0.05
0.05
0.51
0.05
0.21
0.07
2.69
2.74
2.79
3.2
3.25
3.41
3.48
105
105
105
105
105
105
105
99.11
99.06
99.01
89.4
89.35
84.99
84.92
55
55
55
55
55
55
55
49.11
49.06
49.01
39.4
39.35
34.99
34.92
lvl-1 to 18
lvl-18
lvl-1
lvl-19
lvl-19 to 21
lvl-21
2
10
10
11
11
12
10
F
11
G
12
H
32
16
16
8
8
8
2.66
2.016
2.016
1.7
1.7
1.7
54.2
45.6
45.6
45.6
45.6
45.6
140
140
140
140
140
140
1.153
1.235
1.235
1.041
1.041
1.041
69.95
69.95
73.95
73.95
81.85
81.85
65.7
1.5
4
1.5
7.9
1.5
82.125
1.875
5
1.875
9.875
1.875
2.32
0.07
0.2
0.05
0.28
0.05
3.32
3.39
3.52
3.57
3.8
3.85
105
105
105
105
105
105
31.73
31.66
27.53
27.48
19.35
19.3
Remarks
The cumulative F.U through each pipe is worked out and corresponding flow through the pipe is arrived.The head loss through each pipe section will be
worked out based on flow rate through that pipe stretch.