INSTAllATION
G A C
The EAM124 interface module is designed to interface CAT engine controls with external controls such as a Variable Speed Input or a Load Sharing & Synchronizing System. The EAM124 can accept two different inputs, a 0-20 mA input (Terminal 4 referenced to Terminal 2) or a 5.0 V DC input (Terminal 3 referenced to Terminal 2). The 0-20 mA input provides the CAT controller with a wide range of PWM for maximum speed changes. The 5.0 V DC input limits the PWM range (around 50% duty cycle) to trim speed for load sharing and synchronizing. The output of the EAM124 is a current sinking PWM, at 500 Hz. The input signal (PWM duty cycle range) can be field adjusted via the 25-turn potentiometer. The EAM124 uses the same 24 V DC battery power source as the CAT control system.
For 0-20 mA input, supply the current signal to Terminal 4. Terminal 3, 5, and 6 are to remain open. For a 5.0 V DC inputs (load sharing sync signal), connect to Terminal 3. Terminals 5 and 6 must be jumpered together. Terminals 4 must remain open.
SPECIFICATIONS
Terminals 1 & 2 DC Supply Voltage Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 - 24 VDC Supply Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 mA Terminals 2 & 3 Load Sharing Input Impedance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .200 K ohms Terminals 2 & 4 Current Input Impedance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 Ohm Maximum Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.0 VDC Terminals 7 & 8 Output Impedance . . . . . . . . . . . . . . . . . . . . . . . <100 ohms (current protected) Nominal PWM ranger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-100% Transfer Function Terminal 4 to 7 . . . . . . . . . . . . . . . . . . . . . . . 20 mA in=adjustable, 0-100@ duty cycle Terminal 3 to 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.0 V in=50% duty cycle, adjustable Environmental Ambient Operating Temperature Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -40 to +85C
Governors America Corp., 720 Silver Street Agawam, MA 01001 phone: 413.786.5600 fax: 413.789.7736 www.governors-america.com info@governors-america.com
1
EAM124
24V DC
-2
(13,9) (51,6)
2.91 2.03
7+ 8
OUTPUT
2.75
mounting
3.44
outside
This document is subject to change without notice. Caution: None of GAC products are flight certified controls including this item. 2
PIB4119 A