Professional Documents
Culture Documents
311h Equipment Layout 14
311h Equipment Layout 14
d e
le C
an r a
e c
im D
n e
i s
n o
w s
th i
P A EV
Introduction
Table of Contents
SECTION PAGE
The location of evaporative cooling equipment is an important consideration when reviewing system design. Since evaporative cooling equipment requires large quantities of air, adequate spacing around the unit must be provided for it to perform properly. An equally important consideration when laying out the equipment is to locate the unit so that recirculation is minimized. This technical manual has been written by EVAPCO engineers to provide recommended layout criteria for EVAPCO induced draft and forced draft equipment installations. Although it deals primarily with the layout of cooling towers, the principles presented apply to EVAPCO evaporative condensers and closed circuit coolers as well.
Recirculation
Recirculation occurs when some of the hot, moist discharge air leaving the cooling tower flows back into the fresh air inlets of the unit. The heat-laden discharge air leaving the cooling tower is saturated and can be at a 10-15F higher wet bulb temperature than the ambient wet bulb. Therefore, any amount of recirculation will increase the entering wet bulb temperature of the air entering the unit. The capacity of the unit is decreased when the entering air wet bulb temperature is increased. For example, if the inlet wet bulb temperature is increased from 78F to 80F, capacity is reduced by 16%, corresponding to an increase in leaving water temperature of 1.5F. As can be seen from this example, a small increase in the entering air wet bulb temperature has a dramatic affect on the units performance. In extreme cases where the entering wet bulb temperature is increased by 5 to 6F, the capacity of the unit is reduced by more than 50%.
Crossflow Units
Single Units .............................................8-9 Multiple Units/Large Installations...........9-10 Special Enclosures..............................10-11 Expansions to Existing Systems ..............11
Minimizing Legionella
It is essential that a regular maintenance program is in place to minimize the potential growth of Legionella bacteria in the cooling tower. The cooling tower should be thoroughly cleaned on a regular basis. If the cooling tower is to be idle for extended periods, it should be drained. If draining is not practical, a system shock with a biocide is required prior to running the fans. Finally, the cooling tower should be located away from fresh air intakes, operable windows, kitchen exhaust, and prevailing winds directed toward public areas.
2
2003 EVAPCO, INC.
The conditions shown in Figures 1 and 2 can be corrected by elevating the unit on structural steel so that the top is higher than the adjacent structures, as shown in Figure 3. Fan cowl extensions can also be provided to elevate the fan discharge of the cooling tower to the proper height, as shown in Figure 4.
Figure 3
CORRECT
INCORRECT
INSTALLATION ELEVATED SO TOP OF UNIT IS HIGHER THAN TOP OF WALL INSTALLATION WITH TOP OF UNIT LOWER THAN TOP OF WALL
Figure 3 Figure 4
Figure 1
When the wind comes from the opposite direction, the resulting negative pressure area created by the wind passing over the building will cause the discharge air to be forced back into the inlets, as shown in Figure 2. Even if neither of these conditions occurs, the presence of much taller structures can potentially inhibit the dissipation of the hot moist discharge air.
CORRECT
INCORRECT
Fan Cowl Extension
FAN DISCHARGE ELEVATED SO TOP OF UNIT IS HIGHER THAN TOP OF WALL WIND EFFECT WITH TOP OF UNIT LOWER THAN TOP OF WALL
Figure 2
Figure 4
When a unit is located Installations Single/Multiple Unitnear a building or wall, the minimum dimensions, D1 from the ends and D2 from the sides, as presented in Table 1, must be maintained. These distances have been developed to EVAPCOS induced draft, counterflow design unit may have air ensure that the unit is provided with unit. When it is located near a be inlets located on all four sides of the adequate air flow. Space must wall provided for piping, removal fresh air panels and for maintenance of or other structure that blocksof access from entering the unit, the mechanical equipment. consideration must be given to the clearance distance between the air Table 1 inlets of the unit and this blockage. In this type of layout, air will be 3 and 4 Foot Wide Models drawn in through the space between the unit and the wall or other Unit Length Minimum Dimension structure as(ft.) as down fromD (from Therefore, it is D (from sides) well above. ends) important to 1 2 provide adequate space in front of each air inlet to ensure proper air to 9 2 3 flow and prevent air recirculation. 2 12 4
8 and 8.5 Foot Wide Models
the minimum distance betweenTwounits, D3 and D4, Unit be CASE 3 - the Walls/Single must maintained to provide adequate airflow as well as space for piping and access for maintenance. Table 2 gives the minimum recommended D2 dimensions for D3 and D4.
D1 D1
Table 2
3 and 4 Foot Wide Models Unit Length (ft.) to 6 9
D2
D4 (side-by-side) 3 4 6
Figure 9
Figure 10
one EVAPCO unit is D1 D2 (from sides) installed at (ft.) same location, the(from ends)for recirculation becomes a the potential to 9 3 3 greater concern. For installations with two or more cooling towers, the 10.5 to 18 3 4 units may21 toplaced in a variety of locations depending on site be 36 3 5 conditions and available space. 42
12 Foot Wide Models
Figure 11
D2
12
Figure 12
Unit Length
D (ft.) 3 D2
Minimum Dimension
D1 D3 (end-to-end) D2 D3 D4 (side-by-side) D1
the various (ft.) D1 (from ends) D2 (from sides) cases of induced draft counterflow layouts. These distances have been 12 14 4 4 developed to&ensure that the units are provided with adequate airflow 18 to 24 4 5 and that recirculation is minimized. Space must also be provided for 28 & 36 4 6 piping, removal of access panels and4 for maintenance of the 42 & 54 7 mechanical 60 equipment.
14 Foot Wide Models Unit improvements confirmed byMinimum testing and years of Product Length factory Dimension (ft.) D1 (from to develop minimum required D2 (from sides) field experience has allowed EVAPCO ends) 24 5 6 distances from the unit and the surrounding walls as well as between 48 5 7 units. Please note that the clearance dimensions for EVAPCOS 24 Foot Wide Models induced draft counterflow products have been significantly Unit Length Minimum Dimension reduced allowing for tighter layouts ends) (ft.) D1 (from . In addition, the (from sides) D2 distances shown in the following tables are dependent on the number6of 18 7 7 7 surrounding24 and the number of units. Therefore, the data presented walls 28 & 2 7 in Tables 1 and36 show the minimum dimensions D1 through D8 required 8 28 Foot Wide for a variety of installation cases. See theModels figures that illustrate following Unit Length Minimum Dimension these various cases. (ft.) 24 48 D1 (from ends) D2 (from sides) 7 8
to 9 10.5 & 12
D2
5 5 5 5 5
D1
5 7 8
D1
9
D4 10
D1
D1
(ft.) 12
Figure 13
Figure 14
6 9
D4 (side-by-side)
Multiple Units 10
12
D3 D4
14
D7
D5
D4
D6
Figure 15
D7
Note: On the connection end or sides with external motors (8 & 8.5 wide models), the minimum distance between the unit and Table 1) must be increased to 4 feet. adjacent walls (D1 and D2 in D1 Sometimes other pieces of equipment such as pumps, filters, D2 piping, etc. are placed in front of the air inlets. These obstructions should not beFigure 5 any closer than the minimum dimensions shown located Figure 6 in Table1. Closer placement can create imbalances in the air flow which can adversely affect unit performance.
D8 D4 (side-by-side)
Figure 16
10 13
CASE 2 - No Obstructions
Single Unit 18
24
12
D3
12 12 D4
14
D 16 4
D7
D7
28 & 36
D8
Figure 17
(ft.) 24 48
Unit Length
D7
12 12
Figure 18
14 16
The guidelines set forth in Tables 1 & 2 are to be used exclusively for EVAPCO equipment. Data from factory testing is based on air discharge velocities and air intake areas that are specific to EVAPCO equipment. Therefore, this data is NOT to be applied to other manufacturers evaporative cooling equipment.
9 FOOT WIDE MODELS UNIT LENGTH All Units (ft.) to 10.5 12 to 28 36 42 D1 3 3 3 3 Minimum Dimension All Units Towers Cond./Coolers* All Units D2 3 3 3.5 4 D3 2 2.5 2.5 2.5 D3 6 6 6 6 D4 6 6 6 6 UNIT LENGTH (ft.) to 18 21 24 & 28 36 42
9 FOOT WIDE MODELS Minimum Dimension D5 D6 D7 3 3 3 3 3 3 3 3 3 3 3.5 3 3 4 3 12 FOOT WIDE MODELS Minimum Dimension D5 D6 D7 3 3 3 3 3 3 3 3.5 3.5 3 4.5 3.5 3 5.5 3.5 3 6 3.5 14 FOOT WIDE MODELS Minimum Dimension D5 D6 D7 3.5 4 4 3.5 6 4 17 FOOT WIDE MODELS Minimum Dimension D5 D6 D7 3 3 3 24 FOOT WIDE MODELS Minimum Dimension D5 D6 D7 4 3 4.5 4 3.5 4.5 4 4 4.5 4.5 5 5 4.5 5.5 5 5.5 7 6 28 FOOT WIDE MODELS Minimum Dimension D5 D6 D7 5 5 5.5 6 7 6.5 DIMENSION KEY D5 & D 7 From Ends of Unit D6 & D 8 From Sides of Unit D6 & D3 Units End to End D6 & D4 Units Side by Side
D8 3 3.5 4 4.5 5
12 FOOT WIDE MODELS UNIT LENGTH All Units (ft.) to 28 36 40 54 60 D1 3 3 3 3 3 Minimum Dimension All Units Towers Cond./Coolers* All Units D2 3 4 4 5 5.5 D3 3 3.5 3.5 4 4 D3 6 6 6 6 6 D4 6 7 7.5 10 10
D8 3 3.5 4 5 6 6.5
D8 4.5 6.5
17 FOOT WIDE MODELS UNIT LENGTH All Units (ft.) All Units D1 3 Minimum Dimension All Units Towers Cond./Coolers* All Units D2 3 D3 3 D3 6 D4 6
D8 3
24 FOOT WIDE MODELS UNIT LENGTH (ft.) to 20 24 28 36 & 40 D1 3 3.5 3.5 4.5 Minimum Dimension D2 3 4 4.5 6 28 FOOT WIDE MODELS UNIT LENGTH (ft.) 24 48 D1 4 5 Minimum Dimension D2 4 6 D3 8 9 D4 8 13 D3 6 6.5 7 9 D4 6 7 8 11
D8 5.5 7.5
* Minimum D3 dimension for Condensers and Coolers Furnished with Pumps. For units without pumps use D3 dimension for towers.
Large Installations
For large cooling tower installations that have 4 or more units, it is imperative that the unit layout be carefully examined during the design of the system. Very large multiple unit installations can create their own environment. Under certain weather and atmospheric conditions, the large quantities of discharge air will cause the wet bulb temperature in the immediate area to be higher than the local design data.The minimum dimensions shown in Tables 1 and 2 should be increased whenever possible in order to allow for an additional safety factor. The amount of increase is dependent on the number of units, type of installation, existing equipment and unit surroundings. The surrounding area plays an important part in the design of a large installation. Locating a large installation in a valley or between buildings will increase the chances that the discharge air will recirculate, thereby raising the entering wet bulb temperature. If it is determined that the surrounding conditions could cause recirculation, the units must be spaced properly and sized at the anticipated entering wet bulb conditions. Another important consideration when dealing with larger multiple unit installations is prevailing winds. Although prevailing wind conditions generally change with the season, the wind direction during the hottest part of the year is of utmost importance. To minimize the potential for recirculation, it is best to locate the units so that the prevailing wind is oriented as shown in Figure 19. Consult your local representative or EVAPCOs Marketing Department at 410-756-2600 for recommended layout guidelines for very large multiple unit installations.
Figure 19
Special Enclosures
Occasionally, induced draft counterflow units are installed in an enclosure. These installations require special consideration of the unit layout to ensure trouble free operation. Typical installations consist of units installed in solid wall or louvered enclosures or units that are located in a well.
WELL INSTALLATION
Example: An AT 19-412 is centered in a 20 x 25 well enclosure with the units discharge even with the top of the surrounding walls. Is this an acceptable equipment layout? Unit Area = 102 ft2 D1 = 6.5 feet Unit CFM = 69200 D2 = 5.75 feet Well Area = 500 ft2 Net Usable Well Area = 500 ft2 - 102 ft2 = 398 ft2 Downward Velocity = 69200 CFM 398 SF = 174 FPM
PREVAILING WIND
Figure 19
Since the downward velocity of 174 FPM is less than 400 FPM AND dimensions D1 and D2 are above the recommended minimums, this IS an acceptable layout.
Figure 21
If the downward air velocity into the enclosure is greater than 400 F.P.M., then another formula must be used. This formula, proven by years of field experience, assumes that ALL the air is drawn through the louvers. The total air flow (CFM) for the unit is divided by the net free louver area (ft2). The resultant air velocity must be BELOW 600 F.P.M. In addition to meeting this minimum louver velocity, the installation must also meet the following requirements. The minimum air inlet to louver dimension must be 3 feet and the minimum space requirements, for maintenance, as shown on page 19, must also be maintained.
Figure 22
NOTE: For installations where the minimum recommended distances cannot be maintained, contact your local representative or EVAPCOs Marketing Department at 410-756-2600 for unit selection and layout. Refer to Page 19 for additional information.
CORRECT
INCORRECT
WIND DIRECTION
AIR INLET AIR INLET
AIR INLET
AIR INLET
Figure 25
Figure 23
When the wind comes from the opposite direction, the resulting negative pressure area created by the wind passing over the building will cause the discharge air to be forced back into the inlets, as shown in Figure 24. Even if neither of these conditions occurs, the presence of much taller structures can potentially inhibit the dissipation of the hot moist discharge air.
An induced draft, crossflow design unit usually has air inlets located on two sides of the unit. When it is located near a wall or other structure that blocks fresh air from entering the unit, consideration must be given to the clearance distance between the air inlets of the unit and this blockage, as shown in Figure 26. In this type of layout, air will be drawn in through the space between the unit and the wall or other structure as well as down from above. Therefore, it is important to provide adequate space in front of each air inlet to ensure proper air flow and prevent air recirculation.
INCORRECT
WIND DIRECTION
D2
AIR INLET
AIR INLET
WALL OR BUILDING
AIR INLET
AIR INLET
D1
D2 WALL OR BUILDING
INSTALLATION NEXT TO A WALL WIND EFFECT WITH TOP OF UNIT LOWER THAN TOP OF WALL
Figure 24
Figure 26
When a unit is located near a building or wall, the minimum dimensions, D1 from the ends and D2 from the sides, as presented in Tables 3 and 4, must be maintained. Minimum dimension D1 must be provided for piping, removal of access panels and for maintenance of the mechanical equipment.The D2 dimension has been developed to ensure that the unit is provided with adequate air flow. Table Table 33
CELL SIZE WxLxH UNIT WIDTH (ft.) All (ft.) Sizes 14 16 20 CELL SIZE WxLxH (ft.) 22x12x17
Unit Length 22x12x19 Single Cell Units Dimension Minimum
D3
AIR INLET AIR INLET AIR INLET
(ft.)
5 7 8 9
UNIT LENGTH One Cell (ft.) 3.5 7 8 10 14 One Cell 6.5 6.5 7 7.5 7.5 8
D1 Minimum Dimension Two Cell Three Cell Four Cell D 3.5 1 (From Ends) D2 (From Ends) 3.5 3.5 612 6 6 Table 4 7 9 Dimension 8 Minimum 12D2 11 Two Cell 10.5 11 D1 (from ends) 12
3
PREFERRED METHOD
AIR INLET AIR INLET AIR INLET AIR INLET
Three Cell 13
3' Minimum
14 D2 (from sides) 16
3
AIR INLET AIR INLET AIR INLET AIR INLET
12
3 13.5 3
17.5
NOTE: Consult the factory on the D2 dimension for applications 24 3 5 with 5 or more cells.
36 3 12 Foot Wide Models (Sometimes other pieces of equipment such as pumps, filters, piping, etc. are placed in front of the air inlets. These obstructions should not be located any closer than the minimum dimensions shown in Table 4. Closer placement can create imbalances in the air flow which can adversely affect unit performance. 5
36 MULTIPLE UNITS PLACED END-TO-END 5 10 Figure 28 12 Foot Wide Models Unit Length Minimum Dimension D4 (side-by-side) (ft.) D3 (end-to-end) 12 6METHOD 6 ALTERNATE
AIR INLET AIR INLET AIR INLET AIR INLET
18 MULTIPLE UNITS PLACED END-TO-END 6 9 24 10 Figure 6 28a 36 7 12 54 7 14 14 Foot Wide Models Table 5 Minimum Dimension Unit Length D (ft.) D3 (end-to-end)Dimension 4 (side-by-side) CELL SIZE Minimum 24 7 10 WxLxH D3 48 7 13 (ft.) One Cell Foot Two Cell Four Cell 24 Wide Models Three Cell Unit 22x12x17Length 13 21 Minimum Dimension 26 30 (ft.) D3 (end-to-end) 22x12x19 13 21 26 D4 (side-by-side) 30 18 12 12 22x12x23 14 22 28 32 24 12 14 24x14x17& 36 15 24 29 28 12 16 33 24x14x19 15 28 Foot Wide Models 24 29 33 Unit Length Minimum Dimension 24x14x23 16 27 31 35 D4 (side-by-side) (ft.) D3 (end-to-end) 24 12 14
Note: Consult the factory on the D3 dimension for applications with 5 or more cells.
For multiple cooling tower installations that have 3, 4, or more units, it is imperative that the unit layout be carefully examined during the design of the system. Very large multiple unit installations can create their own environment. Under certain weather and atmospheric conditions, the large quantities of discharge air will cause the wet bulb temperature in the immediate area to be higher than the local design data. The minimum dimensions shown in Tables 3, 4 & 5 should be increased whenever possible in order to allow for an additional safety factor. The amount of increase is dependent on the number of units, type of installation, existing equipment and unit surroundings. The surrounding area plays an important part in the design of a large installation. Locating a large installation in a valley or between buildings will increase the chances that the discharge air will recirculate, thereby raising the entering wet bulb temperature. If it is determined that the surrounding conditions could cause recirculation, the units must be spaced properly and sized at the anticipated entering wet bulb conditions. Another important consideration when dealing with larger multiple unit installations is prevailing winds. Although prevailing wind conditions generally change with the season, the wind direction during the hottest part of the year is of utmost importance. To minimize the potential for recirculation, it is best to locate the units so that the prevailing wind is oriented as shown in Figure 29. Consult your local representative or EVAPCOs Marketing Department at 410-756-2600 for recommended layout guidelines for very large multiple unit installations.
Figure 17
AIR INLET
AIR INLET
AIR INLET
50
AIR INLET
RANGE OF PREVAILING WIND DIRECTION 10
TOWER UNIT
AIR INLET
AIR INLET
AIR INLET
AIR INLET 50
WELL INSTALLATION
Figure 30
PREVAILING WIND
Figure 29
Special Enclosures
Occasionally, induced draft crossflow units are installed in an enclosure. These installations require special consideration of the unit layout to ensure trouble free operation. Typical installations consist of units installed in solid wall or louvered enclosures or units that are located in a well.
10
AIR INLET
NEW UNIT
EXISTING UNIT
Figure 31
AIR INLET
AIR INLET
AIR INLET
AIR INLET
If the layout does not meet the requirements of a well installation, then another formula must be used. This formula, proven by years of field experience, assumes that ALL the air is drawn through the louvers. The total air flow (CFM) for the unit is divided by the net free louver area (ft2). The resultant air velocity must be BELOW 600 F.P.M. In addition to meeting this minimum louver velocity, the installation must also meet the following requirements. The minimum air inlet to louver dimension must be 3 feet and the minimum space requirements, for maintenance, as shown on page 19, must also be maintained.
Figure 32
NOTE: For installations where the minimum recommended distances cannot be maintained, contact your local representative or EVAPCOs Marketing Department at 410-756-2600 for unit selection and layout. Refer to Page 19 for additional information.
11
INCORRECT
INCORRECT
Figure 34
There are two simple methods to correct this recirculation problem. The first method is to elevate the unit on structural steel so that the top is higher than the adjacent structure, as shown in Figure 35.
CORRECT
Figure 33
When the wind comes from the opposite direction, the resulting negative pressure area created by the wind passing over the building will cause the discharge air to be forced back into the inlets, as shown in Figure 34. Even if neither of these conditions occurs, the presence of much taller structures can inhibit the dissipation of the hot moist discharge air.
Figure 35
12
The second method is to install a tapered discharge hood (Figure 36) which discharges the air above the height of the structure. The discharge hood increases the discharge air velocity, which works to minimize the potential of recirculation. However, the addition of a discharge hood increases the external static pressure that the fans must overcome which may require the next larger size fan motor.
This dimension can be reduced because the end area is effectively increased by the amount the unit is elevated. Elevating an axial fan unit has no impact on the D1 dimension.
CORRECT
Figure 38
Table 6
INSTALLATION WITH TOP OF DISCHARGE HOOD ABOVE TOP OF WALL
MINIMUM DISTANCE D1 FROM UNIT TO WALL WITH AIR INLET FACING WALL 3 AND 5 FOOT WIDE MODELS - LR - End Air Inlet UNIT WIDTH (ft.) 3 5 5 UNIT LENGTH (ft.) 6* 6* 9 & 12* UNIT ELEVATION - (ft.) 0 4 4 5 2 4 4 4.5 3 3.5 3.5 4.5 4 & UP 3.5 3.5 4
Figure 36
When a cooling tower is located near a wall, it is best for the air inlet to face away from the wall, as shown in Figure 37.
4 AND 5 FOOT WIDE MODELS - SINGLE FAN SIDED 8 FOOT WIDE MODELS - DOUBLE FAN SIDED
INSTALLATION NEXT TO WALL BEST ORIENTATION
Figure 37
Note: EVAPCOS LR End Air Inlet Unit is shown. Note: EVAPCOS LR End Air Inlet is shown. If this is not possible and the air inlets must face the wall, as shown in Figure 38, then a minimum distance D1 must be maintained between the wall and the unit, as listed in Table 6. Table 6 provides the minimum dimension D1 for all of the various sizes of both centrifugal and axial fan forced draft units. For installations next to walls, all of the air consumed by the unit is drawn in through the space between the unit and the wall and also down from above. The downward draw of air to the unit is why it is so critical to provide the minimum D1 dimension to prevent recirculation of the discharge air. When a tower is selected with air inlets on two sides, care must be taken to analyze each air inlet side independently. For example, with a tower that measures 8 feet wide from air inlet to air inlet, enter Table 6 to determine the minimum distance D1 between one air inlet side and its facing wall. Repeat this procedure for the opposite fan side. The distances for D1 in Table 6 have been developed using a formula based on years of successful experience that assumes all the air is fed in from the ends at less then 600 F.P.M. As can be seen from the data in Table 6, elevating a centrifugal fan unit on structural steel will allow the D1 dimension to be reduced.
8 and 10 FOOT WIDE MODELS - SINGLE FAN SIDED UNIT LENGTH (ft.) to 12 18 24 36 0 7 8 10 14 UNIT ELEVATION - (ft.) 2 6.5 7 9 12 4 6 6 8 11 6 & UP 6 6 7 10
12 FOOT WIDE MODELS - SINGLE FAN SIDED UNIT LENGTH (ft.) to 12 18 24 36 0 8 9 11 16 UNIT ELEVATION - (ft.) 2 7 8 10 14 4 7 7 9 12 6 & UP 7 7 8 11
*Note: The length for the LR end air inlet unit includes the casing section only, not the entire unit length.
13
If the required D1 distance shown in Table 6 is too large for the available space, the use of a tapered discharge hood (Figure 39) can reduce the distance. The tapered discharge hood should be at least 3 feet tall with an exit air velocity between 1200 and 1500 F.P.M. The use of a tapered discharge hood will allow the distances given in Table 6 to be reduced by 20 percent. However, the minimum D1 distance should never be less than: 3 and 5 Foot Wide Models - LR - End Air Inlet = 3 Feet 4 and 5 Foot Wide Models - Single Fan Sided = 4 Feet 8 Foot Wide Models - Double Fan Sided = 4 Feet (Each Side) 8 Foot Wide Models - LR - End Air Inlet = 3 Feet 8 and 10 Foot Wide Models - Single Fan Sided = 6 Feet 12 Foot Wide Models - Single Fan Sided = 7 Feet In some installations, other pieces of equipment such as receivers, compressors, piping, etc. are placed in front of the fan inlet. These should not be any closer than the above minimum dimensions. Closer placement can create imbalances in the air flow which has an adverse affect on fan performance.
Figure 40
Figure 41
Figure 39
Figure 42
Figure 43
14
Table 7 covers 3, 5 and 8 foot wide LR end air inlet units, 4 and 5 foot wide units with air inlets on one side, and units up to 8 feet wide with air inlets on two sides. When towers with air inlets on two sides are selected, both fan inlets must be considered. Table 7 also covers larger 8, 10 & 12 foot wide units with air inlets on one side. These tables are based on formulas which assume all the air flows to the units from the ends at velocities of less than 600 F.P.M. This criteria has been proven through years of successful experience with evaporative cooling installations.
3 and 5 FOOT WIDE MODELS - LR - END AIR INLET UNIT WIDTH (ft.) 3 5 5 UNIT LENGTH (ft.) 6* 6* 9 & 12* UNIT ELEVATION - (ft.) 0 8 8 10 2 8 8 9 3 7 7 9 4 & UP 7 7 8
8 FOOT WIDE MODELS - LR - END AIR INLET UNIT LENGTH (ft.) 9 & 12* 0 12 UNIT ELEVATION - (ft.) 2 11 3 11 4 & UP 10
4 and 5 FOOT WIDE MODELS - SINGLE FAN SIDED 8 FOOT WIDE MODELS - DOUBLE FAN SIDED UNIT LENGTH (ft.) to 9 12 18 0 8 10 12 UNIT ELEVATION - (ft.) 2 7 8 10 4 6 7 8 6 & UP 6 6 6
3 & 5 Foot Wide Models - LR - End Inlet = 6 Feet - Side Inlet = 4 feet 4 and 5 Foot Wide Models - Single Fan Sided = 6 Feet 8 Foot Wide Models - Double Fan Sided = 6 Feet (Each Side) 8 Foot Wide Models - LR - End Inlet = 10 Feet - Side Inlet = 4 feet 8 and 10 Foot Wide Models - Single Fan Sided = 10 Feet 12 Foot Wide Models - Single Fan Sided = 11 Feet Very large multiple unit installations can create their own environment. Under certain weather and atmospheric conditions the large quantities of discharge air will cause the wet bulb temperature in the immediate area to be higher than local design data. The minimum dimensions shown in Tables 6 and 7 should be increased whenever possible in order to allow for an additional safety factor. The amount of increase is dependent on the number of units, type of installation, existing equipment, and unit surroundings. The surrounding area plays an important part in the design of a large installation. Locating a large installation in a valley, or between buildings will increase the chances that the discharge air will recirculate, thereby raising the entering wet bulb temperature. Another important consideration when dealing with larger multiple unit installations is prevailing winds. Although prevailing wind conditions generally change with the season, the wind direction during the hottest part of the year is of utmost importance. To minimize the potential for recirculation, it is best to locate the cooling tower so that the air inlets are nearly perpendicular to the prevailing wind direction (Figure 44). The object is to orient the units so that the prevailing wind does not blow the discharge air into the fan inlets.
8 and 10 FOOT WIDE MODELS - SINGLE FAN SIDED UNIT LENGTH (ft.) to 12 18 24 36 0 14 16 20 28 UNIT ELEVATION - (ft.) 2 13 14 18 24 4 12 12 16 22 6 & UP 10 10 14 20
12 FOOT WIDE MODELS - SINGLE FAN SIDED UNIT LENGTH (ft.) to 12 18 24 36 0 16 18 23 32 UNIT ELEVATION - (ft.) 2 15 16 20 27 4 14 14 18 25 6 & UP 11 11 16 23
LARGE INSTALLATION - UNITS END-TO-END
Figure 44
For installations where the units are laid out back-to-back, the best orientation of the prevailing wind is shown in Figure 45.
Table 7 *Note: The length for the LR end air inlet unit includes the casing section only, not the entire unit length. If there is not enough room to meet the minimum distances given in Table 7, the use of tapered discharge hoods may provide a good solution. These hoods should be designed as previously described, i.e. a minimum of 3 feet tall with an exit air velocity between 1200 and 1500 F.P.M. The distances in Table 7 can be reduced 20%. However, the spacing between the fan inlets even with discharge hoods, cannot be less than the minimums shown at the top of the next column.
Figure 45
15
6' MAX
UNIT WIDTH
6' MAX
Special Enclosures
Many times cooling towers are installed in an enclosure. These installations require special consideration of the unit layout to ensure trouble free operation.
WELL TOWER
3' Maximum
USABLE INTAKE AREA AIR INLET
WELL INSTALLATION
Figure 46b
Note: Units with solid bottom panels or inlet sound attenuation, the usable well area is reduced. Only utilize the space in the front of the air inlets.
The first step in checking a louvered type enclosure is to treat it as a well enclosure and calculate the downward air velocity assuming that all the air comes down from the top. If the downward air velocity is equal to or less than 300 F.P.M., then the louvered enclosure will work regardless of the size of the louvers.
Figure 34
WELL INSTALLATION
Figure 47
Figure 46
Figure 34a
WELL Figure 34b INSTALLATION
Note: Units with air inlets on two sides may require louvers on both the front and back wall of the enclosure. If the downward air velocity into the enclosure is greater than 300 F.P.M, then another formula is used. This formula, proven by years of field experience, assumes that ALL of the air is drawn through the louvers. The total air flow (CFM) for the unit is divided by the net free louver area (ft2). The resultant air velocity must be BELOW 600 F.P.M. The installation must also meet the minimum fan inlet to louver dimension (D3) as shown in Table 8 on page 17 and the minimum space requirements for maintenance as shown on page 19.
Figure 46a
16
Table 8
MINIMUM DISTANCE D3 FROM LOUVERS TO FAN INLETS TYPE OF UNIT 3 Ft. Wide Models - LR - End Air Inlet 5 and 8 Ft. Wide Models - LR - End Air Inlet 4 and 5 Ft. Wide Models - Single Fan Sided 8 Ft. Wide Models - Double Fan Sided 8 and 10 Ft. Wide Models - Single Fan Sided 12 Ft. Wide Models - Single Fan Sided DISTANCE (ft.) 3 4 4 4 (Each Side) 6 7
Indoor Installations
Occasionally, centrifugal fan cooling towers are installed indoors where they normally require ductwork to and from the unit. In these instances, the fan motor size and fan speed must be increased due to the external static pressure imposed by the ductwork. Most centrifugal fan towers can handle up to 12 of external static pressure by increasing the fan motor one size with a corresponding increase in fan speed. For cases where external static pressure exceeds 12, the tower manufacturer should be consulted. In all cases, the manufacturer must be advised what external static pressure the unit will be subjected to so that the fan motors and drives can be properly sized. The outside air for the unit can travel from a louver or slotted opening either through ductwork or by having the room act as a plenum. In the second case, where the room is acting like a plenum (Figure 50), the air velocity through the louvers feeding air to the unit should be limited to a maximum of 800 F.P.M. When a room is used as a plenum, other equipment may be located in front of the air inlets. This equipment should not be closer than the minimum distances shown below.
INCORRECT
Single/Double Fan Sided Units 4 and 5 Wide Models 3 feet 8 and 10 Wide Models 5 feet 12 Wide Models 6 feet LR - End Air Inlet Units 3 Wide Models5 Wide x 6 Long Models5 Wide x 9 & 12 Long Models8 Wide Models-
Figure 48
CORRECT
Figure 49 Figure 50
17
When the inlet and discharge air are ducted to and from the unit, it is important to minimize pressure losses in the ductwork by keeping the air velocities low and by avoiding changes in direction whenever possible. The duct should be sized for a maximum of 800 F.P.M. for the inlet air and a maximum of 1000 F.P.M. for the discharge air. Any horizontal turns at the unit should be designed by using the 70% rule as shown in Figures 51 and 52. NOTE: Make sure that adequately sized access doors are located in both the inlet and discharge ductwork which will allow the unit to be accessed for maintenance.
Figure 51
Figure 53
Figure 52
Note: The length for the LR end air inlet unit includes the casing section only, not the entire unit length.
NOTE: For installations where the minimum recommended distances cannot be maintained, contact your local representative or EVAPCOs Marketing Department at 410-756-2600 for unit selection and layout. Refer to Page 19 for additional information.
18
There are some general rules for sound that can aid in evaluating sound data. Also, in addition to the periodic maintenance items, unit drawings must General Rules be reviewed to ensure there is room for any future major repair work. Space should be provided to allow for the replacement of a fan motor, 1. Doublingor fan shaft. pump, fan, the sound pressure from a single source results in a 3 dB rise in the sound pressure level. Ex. (2) 60 dB sounds will generate a 63 dB sound. 2. Doubling the distance from the source of the sound will reduce its sound level by 6 dB. Ex. 60 dB @ 100 ft., 54 dB @ 200 ft. 3. A 1 to 2 dB change in sound pressure level is barely perceptible to the human ear. 4. A 10 dB rise in sound level indicates that the sound perceived by the * SEE TABLES 1 & 2 ear is twice as loud.
MINIMUM CLEARANCE DIMENSIONS INDUCED DRAFT COUNTERFLOW UNITS
Figure 56
If noise is a concern for a cooling tower installation, there are Figure 43 several solutions that can ensure a proper unit 3.5' layout.
VARIES*
1) Face fans away from potential problem area. 2) Avoid amphitheater type locations.
3.5'
VARIES*
3) Provide natural sound barriers such as trees, SEE TABLEor a small hill * shrubs 4 Figure 44 between the unit and neighbors. MINIMUM CLEARANCE DIMENSIONS
*SEE TABLE 4
4) Consult the manufacturer forFigure 57 alternative selection of a a possible quieter unit. 5) In extreme cases, install a wall-type sound barrier or have the Space Requirements for Unit Piping cooling tower manufacturer provide a factory-built attenuation The piping design for each installation can be an important aspect package. in locating evaporative cooling equipment. There are two key piping considerations which should always be reviewed.
Minimizing Legionella
* SEE TABLE 6
Figure 54
3'
Air Inlet
3'
Varies*
Figure 54 3'
* SEE TABLE 6 *SEE TABLE6
MINIMUM CLEARANCE DIMENSIONS FORCED DRAFT UNITS Typical -Sound Data Sheet (LR END AIR INLET)
A. Sufficient Unit Elevation It isThe location ofaaregular often influenced by the is in place to essential that unit is maintenance program piping design. minimize unit elevation is required Legionella bacteria in the and Adequatethe potential growth of theto prevent pump cavitation cooling tower. The cooling tower should be thoroughly cleaned on a provide free drainage of the water from the cold water basin.regular basis. If the cooling tower is to be condenser, the height required forbe When locating an evaporative idle for 3 or more days, it should piping is If draining isimportant. Unitaelevationshock be sufficient tois drained. particularly not practical, system must with a biocide provide adequate height for the trapped liquid line and the sloping of required prior to running the fans. Finally, the cooling tower should the located away from fresh air pressure windows, kitchen exhaust, be drain line leading to the high intakes, receiver. For additional information concerning directed to public areas. layout, see and prevailing winds refrigeration pipe sizing and EVAPCO Bulletin 130A Piping Evaporative Condensers. B. Spacing for Future Expansion SUMMARY Space for piping of additional units should be reserved in the initial plan. When installing a single unit, it is important to consider where To produce full capacity, a cooling tower requires large quantities of additional units would be placed and locate the single unit so that air at the lowest possibleas simple wetpossible. If the expansion is future expansion will be entering as bulb temperature. planned intechnical manualitwe normally more the necessary guidelines In this the near future, is have provided economical to install branch connections with valves during the initial installation rather than to ensure that the unit installation minimizes the potential for with the expansion.hot discharge air.room for piping the futurewill be recirculation of the Not only should Although no installation unit be considered free from the layout should be treated as a multiple unit completely but, also some small amounts of recirculation following installation with the required provide installations with practical layouts, these recommendations will spacing that will allow proper airflow for the existing and possible future units. and trouble-free operation.
Figure 55
19
2
Bulletin 311H
7500/0704/YGS
EVAPCO Europe, N.V. Heersterveldweg 19 Industriezone Tongeren-Oost 3700 Tongeren, Belgium Shanghai Hezhong-EVAPCO Phone: 32 (0)11-395029 Refrigeration Co., Ltd. Fax: 32 (0)11-238527 E-mail: evapco.europe@evapco.be 855 Yang Tai Road Bao Shan Area Shanghai, P.R. China - Code 201901 Refrigeration Valves & Systems EVAPCO Europe, S.r.l. Phone: (86)21 5680-5298 1520 Crosswind Dr. Via Ciro Menotti 10 Fax: (86)21 5680-6642 Bryan, TX 77808 USA 20017 Passirana di Rho E-mail: evapcosh@evapcochina.com Phone: (979) 778-0095 Milano, Italy Fax: (979) 778-0030 Phone: (39) 02-939-9041 EVAPCO S.A. (Pty.) Ltd. E-mail: rvs@rvscorp.com Fax: (39) 02-935-00840 18 Quality Road E-mail: evapcoeurope@evapco.it Isando 1600 McCormack Coil Company Republic of South Africa P.O. Box 1727 EVAPCO Europe, S.r.l. Phone: (27)11 392-6630 6333 S.W. Lakeview Blvd. Via Dosso 2 Fax: (27)11-392-6615 Lake Oswego, OR 97035 USA 23020 Piateda Sondrio Italy E-mail: evapco@icon.co.za Phone: (503) 639-2137 Fax: (503) 639-1800 Air EVAPCO (Ltd.) E-mail: mail@mmccoil.com 92 Asma Fahmi St., ARD El-Golf Heliopolis, Cairo, Egypt Phone: (202) 291-3610 Fax: (202) 290-0892 E-mail: manzgroup@tedata.net.eg
EVAPCO, INC. ( World Headquarters ) P.O. Box 1300 Westminster, Maryland 21158 USA Ph: 410-756-2600 Fax: 410-756-6450 Visit Evapcos Website at http://www.evapco.com