Design Parameters Concrete Grade Concrete Cover Density of Concrete Strength of Structural steel Method of construction Imposed Loads

Description Old design Design review 25N/mm2 25mm 25kN/m3 275N/mm2 Propped

Live load

5kN/m2

5.0 kN/m2

Wall loads

5 kN/m

15.75 kN/m2

Steel sections PB 350X175 x49.6kg/m PB1 350X175 x 41.4 kg/m SB 250x125 x25.7 kg/m Analysis Models

Design and Analysis Out put Cross Girder SB Deflections old Deflections review Ultimate Moments Shear Force SLS LL SLS LL Mu old Mu review Fu old Fu review 51 29 64 42 162 162 92 92 mm mm mm mm kNm kNm kN kN Main Girder PD Deflections old Deflections review Ultimate Moments Shear Force SLS LL SLS LL Mu old Mu review Fu old Fu review 16 9 21 13 358 358 187 187 mm mm mm mm kNm kNm kN kN

Description old Bending Strength Shear Strength %Composite Action Strength Strength for Full comp action Capacity ratio Full

Status review 0.94 0.34 74.10% 179 100% 196 0.826 0.94 0.34 74.10% 179 100% 196 0.826

Description old Bending Strength Shear Strength %Composite Action Exist strength Strength for Full comp action Capacity ratio Full

Status review 1.15 0.38 21.30% 321 100% 416 0.86 1.15 0.38 21.30% 321 100% 416 0.86

Design Models

Perimeter Cross Beam Deflections old Deflections review Ultimate Moments Shear Force SLS LL SLS LL Mu old Mu review Fu old Fu review 20 11 55 16 89 241 52 141 mm mm mm mm kNm kNm kN kN Description old Bending Strength Shear Strength %Composite Action Strength Strength for Full comp action Capacity ratio Full 0.54 0.2 74.10% 171 100% 181 0.49 Status review 1.41 0.53 74.10% 171 100% 181 1.33

Conclusion Girder PB Provided structural steel sections for main Girders are satisfy for both strength and deflection if full composite action is being used. But due to lack of shear studs used in the constructions, full composite action is not mobilized, consequently moment capacity and stiffness of the composite beams reduces. Therefore, provided steel girder fail under then reduce design ultimate loading. While make the adjustment to the live load to consider the stores of height equivalent to 3m, Girder will not further satisfy. However, for working load, the provided section is satisfied subjected to plastic moments and large deformations. Therefore it is recommended to increase the capacity of the section by adding additional section (same size) or welding additional plate (10mm) to the bottom of flange of the girder. Contractor is asked to submit the method statement for review. Cross girder SB Provided section is marginally satisfy for the given loading. But, full composite action is not mobilized due to lack of shear studs. Although relative deflection is satisfy, overall deflection (50mm) is passing the code limit. Therefore, damages to the underneath partition is expected. Slight modifications is required to satisfy the additional live loads Perimeter Cross Beam In the design, light weight partitions along the perimeter have been considered, but at the site, solid block work was used. Therefore perimeter beam is subjected to unexpected additional load and the existing steel structural beam is not adequate for the purpose. Therefore it is recommended to increase the capacity of the section by adding additional section (same size) or welding additional plate (10mm) to the bottom of flange of the girder. Contractor is asked to submit the method statement for review.

Recommendations Contractor is asked to submit the method statement about the rectifications to be done. All the rectifications should be done at the zero imposed loading conditions, as structure is safe without imposed loads. It is recommended to jack the beams where higher amount of deflections were detected before doing the rectifications. Following recommendations will be adopted as possible rectifications methods Perimeter Cross Girder Weld 125X10mm steel plate 10mm Thick) along the bottom flange of the Steel Girders SB at the edge of the slabs and weld stiffeners (5mm thick plates) to the web at the either side of the girders (all the SB Girders) at the interval of 300mm between first 2m from the supports and rest of the beams at the interval of 600mm Girder PB Weld 175X10mm steel plate 10mm Thick) along the bottom flange of the Steel Girders SB at the edge of the slabs and weld stiffeners (5mm thick plates) to the web at the either side of the girders (all the SB Girders) at the interval of 300mm between first 2m from the supports and rest of the beams at the interval of 600mm.