Professional Documents
Culture Documents
District Heating Substation Guidelines Presentation
District Heating Substation Guidelines Presentation
Chapter 1: GENERAL
The Guidelines address
Those who are running and maintainer a DH system Those who design, purchase, test, install and manufacture substations Those who own or maintain a building connected to the district heating network Those who are responsible for contacts between the district heating utility and the customers
The Guidelines
Aid for investment process in DH Aid for modernization works of heat substation and warm water installations Aid for avoiding technical misstakes during design and calculation Contain principles for dimensioning of heat substations including: domestic warm water, domestic warm water circulation systems, choice of heat exchangers, warm water storage, functional requirements and control valves
Chapter 1: General
Chapter 1: General
Good cooling of the DH water (i.e. the more heat abstracted) and good performance of the district heating substation are in the interests of both the customer and the heat supplier.
Chapter 1: General
65C
10C
60C
<22C
Flow (l/s)
Apartment
Guidelines deal with: Heat exchangers (types, functional requirements), Choice of materials, Control system, Dimensioning, Valves and sensors Radiator and ventilation systems should be built so that the return temperature of the DH water is as low as possible.
Control system
Should assure stable space heating temperature according to customer needs during the whole year, independent of changes in the outside weather conditions or inside heat loads It is an advantage to install a controller with temperature trend log that enables to register controllable parameters in order to carry out technological optimization
Heat losses, Production efficiency, Pipe capacity / construction cost, Pumping capacity, The cost of heat installations, Advantage of low return temperature in all aspects When dimensioning heat substations the operating mode with the highest heating power requirements should be considered
Chapter 3: Radiator and ventilation system
100/80C
43C
70C
40C
28 35C
100/80C
33C
60C*
30C
PUMPS
Domestic Warm Water circulation pumps have to be in operation continuously For all choices of pumps the use of low energy pumps is strongly recommend For sensitive customers (hospitals, retirement homes etc.) where it is crucial to ensure continuous good functioning, it is recommended to use double pumps with automatic start function for the second motor
HTS, LTS
Large
YES
NO
HTS, LTS
Large
One stage heat exchanger One stage heat exchanger, max 60 kW One stage heat exchanger One stage heat exchanger One stage heat exchanger, max 40 kW Heat exchanger inside tank, max 25 kW
NO
NO
NO NO NO
NO NO YES
LTS,
Small house
NO
NO
LTS
Small house
NO
YES
Indirect connection
Direct connection
Without heat exchangers: Same water in primary and secondary sides Recommended to use leakage alarm system
Chapter 5: Connection principles
Indirect connection Design Temperatures Design pressures Cooling of district heating water Differential pressure controller
up to 110C
Direct connection
less than 90C generally 80C
0.6 MPa same temperature as secondary return needed to decrease pressure in secondary side Excessively high pressure may cause pipe or radiator damages and water leakage
1-step connection (parallel) Design Temperatures Design pressures Cooling of district heating water Total pressure loss over substation
No extra pressure drops due to separated flows from DWW and space heating.
2-step connection
No differences, normal values are valid. No differences, normal values are valid. Pre-heater improves the cooling of district heating. Pressure drop on the primary side can become high: if the flow from the space heating side is greater than the dimensioned flow through the DWW heat exchanger.
Cooling of district heating Safe solution to keep good cooling of district heating. water
- inlet temperature for heat exchanger is normal cold water temperature; - running of charging pump is controlled by temperature in bottom of storage tank. - there is a lack of appropriate flow capacity from the DH
Safety in consumption
Pos.
Remark
3 3.1 3.1.1 3.1.2 3.1.3 3.1.4 3.1.5 3.1.6 3.2 3.2.1 3.2.2
Domestic warm water system Pipe system Check for corrosion (look over) Check of insulation (look over) Potential equalisation available (look over) Check of fill-, drain -, und air escape valves (look over) Check of mounting (look over) Check non return valves Shut off - armatures Test function (practicability) Check for leaks (look over)
A tool for...
Energy saving by Invoicing the real consumption of energy Supervision the function of the substation Customer service by Reporting back suspicious levels of consumption Meter contributes to optimizing operation By knowing what happens in the network
The used meters or sub-assemblies must be conform to MID EHP recommends to use EN 1434 to ensure the conformity
Chapter 7: Heat metering
Functional requirements
Use standardised types and dimensions to ensure compatibility and replacing ability Measuring range Temperature: One range fit most needs Flow: Select carefully to avoid over sizing Some flow sensors require a flow conditioner package If you have short peak loads Use fast response flow sensors Use short response time on sensors Use high resolution on flow signal Check the requirements for mains or battery
Documentation requirements
What documents you shall require What information is needed to ensure that you Can select the suitable units Can mix sub-assemblies of different brands Can install the units in a correct way not damaging the metrological function Can check and recalibrate units
Conformity to MID
Examination of type and design Inspection of produced meters Control system Reverification of meters
CONCLUSIONS
Guidelines have direct impact on improving technical performance of DH systems and on significantly decreasing both life-time costs as well as installation costs Correctly carried out installation assures high levels of services and simultaneously reduce maintenance costs Guidelines allow to significantly decrease return temperatures in the DH network Such rationalization will lead to a reduced use of primary energy sources and less greenhouse gases emission