High Voltage Cross-Linked Polyethylene Three Cores Cable 12/20 (24) KV, Copper Conductor with Double Steel Tape Armor
PE Sheath
Armor Double steel tape Sheath Black polyethylene (ST 7) (Optional: Polyvinyl chloride)
Application
Preferably used for urban networks. Exposed in aerial, direct burial, conduit, open tray and underground duct installation.
Marking
12/20 (24) KV HXLP-DSTA 3 X SIZE SQ.MM., PHELPS DODGE.
Installation
HXLP-DSTA cable can be installed in aerial, direct burial, conduit, open tray and underground. It is recommended that the installation instructions indicated by the Local Electric Code, or any equivalent, be followed, so that the safe guarding of persons and the integrity of the product will not be affected by deciencies in the installation.
www.pdic.com
PDIC01114 | 10.08.04
Thickness of Insulation
Thickness of Sheath
Standard Packing
mm
mm
mm
mm
mm
mm
mm
M - km
kg / km
m / reel
7 7 18 18 18 18 34 34 34 55
6.9 8.0 9.7 11.4 12.9 14.2 16.0 18.4 20.5 23.4
5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
18.7 19.8 21.5 23.2 25.0 26.2 28.1 30.5 32.8 36.2
2x0.5 2x0.5 2x0.5 2x0.5 2x0.5 2x0.5 2x0.5 2x0.8 2x0.8 2x0.8
51.3 53.8 57.5 61.3 65.2 69.1 73.2 79.8 84.9 92.6
58 61 65 69 73 77 81 88 94 102
0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470
1417 1297 1146 1031 929 870 795 716 652 578
160 190 230 275 310 345 385 435 480 530
175 205 255 305 350 390 445 510 575 645
3934 4500 5438 6510 7558 8745 10181 13166 15479 18735
500 500 500 250 250 250 250 250 250 250
www.pdic.com