Professional Documents
Culture Documents
Pump Armstrong PDF
Pump Armstrong PDF
Pump Armstrong PDF
B O O S T
TIP: Suction pressure can usually be obtained from a copy of the Fire Flow Test which provides suction pressures at various flows. Use the maximum system design flow to determine minimum suction pressure.
Page 1
SECTION III: SYSTEM CONFIGURATIONS Systems are available in the following most common configurations: Simplex = 1 pump system: One pump produces all flow and pressure Duplex = 2-pump system: System flow is usually split amongst (2) pumps, equally and un-equally. Triplex = 3-pump system: System flow is usually split among (3) pumps, equally and un-equally. Quadraplex = 4-pump system: Large system flows are split among (4) pumps, typically un-equally.
Page 2
TDH A. STATIC HEAD - BUILDING HEIGHT B. FRICTION HEAD - FRICTION LOSS C. RESIDUAL PRESSURE REQUIRED (@ TOP) D. SYSTEM REQUIRED PRESSURE (A + B + C) E. MINIMUM SUCTION PRESSURE (SUBTRACT) F. SYSTEM BOOST PRESSURE (D - E) G. PRV LOSSES (5 -10 PSI) H. PUMP HEAD REQUIRED (F + G)
PSI
The table to the left indicates the various requirements in establishing system pressure rating. Typically, all figures are expressed in PSI using the Feet/PSI conversion formula and are then converted back to TDH to select the pumps.
Establish building flow capacity (see fig. #3 & 4) Count the number of fixtures which use domestic water. Bear in mind that different fixtures use water differently. (ex: 1.6 GPF Water Closet, 3.5 GPF Water Closet, Flush Valve, etc.) Determine the type of building from the flow chart which will indicate maximum required GPM. Be careful when selecting systems with a constant load, these systems will not benefit from a drawdown tank and system shutdown. (ex: Cooling tower, commercial laundry facilities, restaurants, night clubs, hydronic water make-up, etc.)
Page 3
TYPE OF FIXTURES
Bathroom Group, 1.6 GPF Gravity Tank Water Closet Bathroom Group, 1.6 GPF Pressure-Tank Water Closet Bathroom Group, 3.5 GPF Gravity Tank Water Closet Bathroom Group, 1.6 GPF Flushometer Valve Bathroom Group, 3.5 GPF Flushometer Valve Kitchen Group (Sink and Dishwasher) Laundry Group (Sink and Clothes Washer) 5.0 5.0 6.0 6.0 8.0 2.0 5.0 3.5 3.5 5.0 4.0 6.0 1.5 3.0
INDIVIDUAL FIXTURES
Bathtub or Combination Bath/Shower Bidet Clothes Washer, domestic Dishwasher, domestic Drinking Fountain or Watercooler Hose Bibb (1/2" Supply Pipe) Hose Bibb, each additional (1/2" Supply Pipe) Kitchen Sink, domestic Laundry Sink Lavatory Service Sink or Mop Basin Shower Shower, continous use Urinal, 1.0 GPF Urinal, greater than 1.0 GPF Water Closet 1.6 GPF Gravity Tank Water Closet 1.6 GPF Pressure Tank Water Closet 1.6 GPF Flushometer Valve Water Closet 3.5 GPF Gravity Tank Water Closet 3.5 GPF Flushometer Valve Whirlpool Bath or Combination Bath/Shower
1995 Change to the National Standard Plumbing Code adopted at NSPC Public Hearing - August 1994
2.5 1.0 1.5 2.0 1.0 3.0 2.0 5.0 4.0 5.0 5.0 6.0 4.0 3.5 8.0 7.0 10.0 1.0
Typical Fixture Unit Chart showing various types of fixtures and their relational fixture unit assignment. This is typically used by consultants to determine a fixture unit load which is interpreted on the building profile curves (fig. #4). This chart is taken from the National Plumbing Code, August 1994.
Page 4
The plumbing designer must consider the activities of the occupants and the building usage. Since this does not consider the human element, we rely on operating data and records compiled over the years by users, manufacturers and trade associations. The graph above is a representation of this information. This is typically what system flows are based on.
The National Bureau of Standards published report BMS-65, Methods of Estimating Loads in Plumbing Systems, by the late Dr. Roy B. Hunter. This report provided tables of loadproducing characteristics (fixture unit weighting) of commonly used domestic water fixtures as well as probability curves to estimate the capacity of the system. These curves are the basis for all manufacturers selection of Pressure Booster Systems. Over the years, the industry has further defined the Hunters Curve changing the probability of maximum flow in accordance with the type of building, since all structures do not use water in the same manner and frequency.
Special Services Dont forget that there are sometimes other systems which rely on the plumbing pumps for water make-up, service load, etc. These must be added in after you have determined the domestic fixture load. Examples of this are: Cooling Tower make-up water valve On-Site commercial laundry facility (Hospitals, Hotels, Dorms, etc.) HVAC System make-up load Boiler water make-up load Swimming pools Add these services in addition to the GPM arrived at from the charts.
TIP: Remember that when you add for special services, you will not have fixture unit references. You must add in the additional flow rate in gallons per minute AFTER you have used the fixture unit method to arrive at a total system flow rate. When this step is complete, simply add the additional GPM to the total system capacity for the extra services.
Page 5
PSI
180 140 100 60
PSI
180 140
X
Total Pump Pressure System Working Pressure
20 PSI Design Suction Pressure
X
Design Flow Pump Boost
20 PSI Design Suction Pressure
100 60
20
20
50
100
150
200
250
300
350
GPM
50
100
150
200
250
300
350
GPM
Pump design head is based on the minimum available (worst case) suction pressure plus the pump boost
Additional head is achievable when pump moves to shut-off. Although the PRVs will regulate downstream, upstream pressures can rise.
PSI
180 140 100 60
X X
W.P. #1
In a worst case scenario as shown in the graphic to the left, when suction pressures are underestimated, there is a potential that the pressure could exceed the system rated working pressure.
20
GPM
Page 6
Fig. 7: The above chart represents the maximum recommended flow rates through the Pressure Booster System headers for various manifold sizes.
Rule of Thumb:
Duplex Systems - Un-equal split (33%/67%) becomes more cost effective at 200 GPM or higher. Triplex Systems - Un-equal split (20%/40%/40%) is more cost effective at 300 GPM or higher.
Page 7
Page 8
Vertical In-Line
Vertical Multi-Stage
Vertical Turbine
Note: W.P. stands for working pressure (i.e. suction pressure + boost)
SECTION II: OTHER CONSIDERATIONS 80% of all units will utilize End Suction Pumps. Consider multiple configurations for the pump type available. (ex: 6500, 6600 or 6700 Series, DualPak, QuadPak, etc.) Most systems should be considered to have an 18-20 year life cycle cost. Consider location of unit. (ex: Outdoors require TEFC motors)
Page 9
0.573 0.525 0.478 0.430 0.382 0.334 0.287 0.239 0.191 0.143 0.096 0.048
0.593 0.547 0.501 0.456 0.410 0.365 0.319 0.273 0.228 0.182 0.137 0.091 0.046
0.567 0.523 0.480 0.436 0.392 0.349 0.305 0.262 0.218 0.174 0.131 0.087 0.044
0.585 0.543 0.501 0.459 0.418 0.376 0.334 0.292 0.251 0.209 0.167 0.125 0.084 0.042
0.601 0.561 0.521 0.481 0.441 0.401 0.361 0.321 0.281 0.241 0.200 0.160 0.120 0.080
0.578 0.540 0.501 0.463 0.424 0.386 0.347 0.308 0.270 0.231 0.193 0.154 0.116
0.594 0.557 0.520 0.483 0.445 0.408 0.371 0.334 0.297 0.260 0.223 0.186 0.148
0.608 0.573 0.537 0.501 0.465 0.429 0.394 0.358 0.322 0.286 0.251 0.215 0.179
The chart above is a drawdown calculation chart. The numbers along the left side represent the call on pressure switch setting of the booster system. The top values represent the shut-off (shut-off = Pump shutoff pressure plus maximum suction pressure - best case) The corresponding intersection between any cut-in and cut-out value will give you the actual storage when multiplied by the total tank capacity.
Page 10
Page 11
PRVs
Suction Pressure
Page 12
SECTION II: PUMP SELECTION Typical capacity splits and reasons for choice: Duplex Possible reason for choice
Very economical (especially in system flows over 200 GPM), effective use of pumping power, ability to use 3-Step sequencing control optimizing BHP to Flow need. Preferable in system capacities below 200 GPM since motor H.P.s are typically the same as 33/67 split, allows auto lead alternation (equal wear), parts interchangeable Similar to reasons used in 50/50 split, however, allows for additional redundancy since (1) pump operating alone can handle a larger portion of the load. Provides full stand-by in the event of a pump failure, recommended for packages which are typically very small in H.P. since this is not effective use of BHP.
P-1
33% 50% 65% 100%
P-2
67% 50% 65% 100%
P-1
20% 30% 33% 30%
P-2
40% 40% 33% 70%
P-3
40% 40% 33% 70%
Example of System Splits and use of multiple sequences In the following example of a 33/67% system split, a comparison is made on 50/50, 2 Step sequencing versus 33/67, 3 Step. Notice how dramatic the savings are by simply changing the existing system flow to sequence at un-equal capacities, as well as adding an additional step of control to the pump package.
Page 13
12 A M
NOON
11
Typical residential building demand curve showing the relationship of system demand versus time of day. Notice how the system demand falls off in the early morning hours.
System demand is ultimately determined by flow. When a building uses water, it is related directly to the activities and usage habits of people and machines within the building. Since we size all systems to develop pressure, this demand has already been taken into consideration and the system is built to keep this pressure requirement at a constant pulse free state. It only makes sense that, since pressure is constant and the flow varies (requiring additional pumping power), that the sequencing of pumps be directly related to a measurable demand flow. Current sensing relays measure this work (GPM) exerted by the motor through the pump impeller. In figure #13 we can see how this demand fluctuates. You are not required to use the flow splits as shown in the example. Sometimes it is possible to optimize (i.e.: reduce horsepower consumption) by using a 20/80 split, for example. Because we use current sensing relays and we have the option of determining where the split is made, we can choose whichever split fits the application best.
Page 14
12
10
50-50 Split
4
8h00
9h00
10h00
11h00
12h00
13h00
14h00
15h00
16h00
17h00
18h00
19h00
21h00
22h00
Notice that by simply changing the flow split percentages, the pumps now follow the system demand more accurately. This is how to optimize power consumption with constant speed pressure booster packages. The system becomes, in essence, a variable flow package, choosing the best motor (or combination of motors) to run for a given GPM.
SECTION IV: SEQUENCING DEVICES There are currently a multitude of choices for pump sequencing. The most popular of these are flow switches, pressure switches & current sensing relays. Below is a description of each and the type of measurement each utilizes.
23h00
Time
20h00
Syrelec
Amperage
Hysterisis %
Flow Switch - senses water flow against a paddle which is in the water stream. Paddle moves a cam within the body which actuates next sequence. This is an accurate means of measuring flow, however, can be subject to corrosion and obstruction. (Direct Measurement of Flow)
Pressure Switch - The pressure switch senses a drop in pressure and activates a device or relay. They are available in both single point actuation and differential pressure. This mode of control relies primarily on the pump curve characteristics as they relate to pressure output. (Indirect Measurement of Flow)
Current Sensing Relay - The relay monitors amperage draw created by the motor as the flow increases through the pump. This amperage is set to a specific on time based on engineer requested sequencing. It is an indirect measurement of flow, but highly accurate. (Indirect Measurement of Flow via amperage)
Page 15
Pump #1: GPM ________ H.P. ________ vs. GPM ________ H.P. _________ Pump #2: GPM ________ H.P. ________ vs. GPM ________ H.P. _________
Considerations Flow Switch - is in contact with the pumped fluid, therefore, it is subject to corrosion or obstruction. It can also fail mechanically. From a positive standpoint, the flow switch is a direct measurement of flow. Pressure Switch - is also in contact with the fluid and can be come clogged or fail due to corrosion. It is an indirect measurement of flow since it measures the pressure output of the pump as it relates to its curve. Suction pressures must be very accurate to facilitate an accurate sequencing scenario. Current Sensors - read the motor amperage draw as the motor works to generate flow through the pump. Since this work is directly proportionate to the flow the current sensor is measuring this in an indirect fashion, yet the amperage draw is very repeatable and highly accurate. Current sensors are not in contact with the pumped fluid, nor do they have any moving parts. They are also able to sense voltage change.
A word about non-overloading Many engineers (through their association with HVAC systems) have become very careful about specifying pumps which are non-overloading throughout their entire flow curve. If we look at the desired sequence in a system, however, we would like to use as much of the motor as possible before activating additional pumps in sequence.(see Section III of this chapter) This allows us to conserve power by managing the flow load. With a flow based measurement system, this can easily be done, since the consultant can dictate (right down to the exact flow rate) where the next pump will activate. Pressure switch based systems can be fooled by changes in suction pressure (which change the pump performance at any point on its curve) and therefore are unreliable for this purpose. In a properly designed system utilizing FLOW based sequencing, the engineer can indicate thatthe system shall be non-overloading throughout its entire SEQUENCE OF OPERATION rather than the individual pump curve.
Page 16
B V
Page 17
50
Design Point
40
30
V B
PSI
20
10
Flow
Figure 2: Once again, the boost pressure is denoted by B and the variable pressures are denoted by V in the above single pump performance curve. The gray area is the opportunity for energy savings running a pump at variable speed.
Of the above factors, the variable pressure parameters are quite easily calculated; however, flow adds a dimension of complexity to the overall analysis. This is due to the measure of uncertainty in building demand or load profile of the system. To be precise, we would be able to exactly calculate the energy savings yielded by a variable speed system using the following formula (allowing the t time increment approach zero):
Page 18
SECTION II: SEQUENCING CONSIDERATIONS The above analysis simply considers the operating conditions in the plumbing system and neglects one key feature of pressure boosters: pump sequencing or staging. The controls and data available when using VFDs can yield additional energy savings if applied intelligently. The key consideration in sequencing is maximizing pump efficiency. When VFDs are applied and pumps are sequenced based on a single parameter such as speed (as in the case of a system with a single variable speed pump and constant speed lag pumps), pumps operate anywhere on the curve with no opportunity for maximization of pump efficiency. The same is true of pressure, flow, or kW sequencing. Monitoring multiple parameters allows pumps to be sequenced based on the location on the pump curve. In this case pump efficiency can be maximized yielding additional savings. You will note that operating the same pump at 75% efficiency rather than 65% yields 15% in energy savings.
Page 19
SECTION III: PUMP SELECTION By convention, pumps are selected so that the design operating point is to the left of the best efficiency point (BEP). Lets examine why. Traditionally, pumps have been sized with additional pump head to ensure the needs of the system are met. In a traditional constant speed pressure-sequenced system, the second pump would be sequenced on (turned on) when the first pump begins to run to the right of the design point on the pump curve. This is due to the excess head in the initial calculations. Since there was no way to account for this pump head in application other than throttling of the pump, design yielded pumps which operate and are sequenced to the right of the best efficiency point.
Page 20
60
50
40
30
PSI
20
10
Flow
Figure 3: Traditional pump selection does not apply in variable speed pressure boosting if best operating point sequencing is applied. Designing to the right of the best efficiency point maximizes system hydraulic efficiency.
If this same assumptions are applied in a flow-based (current, kW, or flow) or best operating point sequenced system, pumps never operated to the right of the design point. In fact, additional pumps are sequenced on just when the pump begins to perform efficiently. This means that the system runs more pumps than necessary, and that the pumps are operating at less efficient locations on the pump curve. With the above knowledge, it is clear that pumps in a flow-based or best operating point sequenced system should be selected to the right of the BEP. This strategy yields additional savings in two ways. The first is that the system will leave a single pump operating when it is close to its BEP maximizing pump efficiency. The second is that selection further to the right on the pump curve yields additional pump shutoff head. This increased shutoff head increases the gray area in the illustrations. The steeper rise to shutoff yields greater speed reductions at low flows, and consequently additional energy savings.
SECTION IV: ELECTRIC UTILITIES AND BILLING POLICIES The final consideration in the application of VFDs applies for any piece of mechanical equipment that uses an electric motor. Intuition and rudimentary economic theory support a model in which a commodity or service is bought and sold based on an agreed upon price. The total amount paid is proportional to the net amount of commodity or service provided. One apple is $1. Ten apples are $10. In a free market, the price will fluctuate based on the availability (supply) and the need (demand) for the commodity or service. The principle is very intuitive. The problem with the above model is that the bandwidth of the transaction or delivery pipeline is assumed to be infinite. If we apply a capacity constraint to the pipeline, the theory of supply and demand breaks down. Plenty of a particular commodity may be available, but the demand may remain unmet.
Page 21
Page 22
Safety Because of the high voltages required by the motors, safety cannot be emphasized enough in making adjustments to the controls. The Bad News: Some of the wires inside the panel are live, even when the panel door is open. Always consult the instructions on the inside of the panel door or this manual if you are unsure of the proper safety procedures. The Good News: The circuits will not store latent charge when the panel power is off since there are no capacitors in any of the circuits. Result: No nasty shocks from residual charges stored in the circuits.
Page 23
Page 24
C O N T R O L /L O W V O L T A G E S ID E
PO W ER TRA N SFO RM ER AN D P A N E L P R O T E C T IO N
M O T O R /H IG H V O L T A G E S ID E
M A IN D IS C O N N E C T AND M OTOR P R O T E C T O R C IR C U E T S
P U M P S E L E C T IO N A N D S H U N T IN G C IR C U IT S
P U M P P R O T E C T IO N A N D A LA RM S
G rou n d
Page 25
The block diagram on the previous page depicts this schematic. As each component is discussed, refer back to this schematic to identify where each element is located.
Page 26
POWER
TRANSFORMER
MAIN DISCONNECT SWITCH SHORT CIRCUIT PROTECTOR
OVERLOAD PROTECTOR
Main Disconnect Switch The main disconnect is the main power switch for the entire booster system. All Panel and Motor servicing should be performed with the main disconnect in the OFF position. Setting the HAND-OFF-AUTO (H-O-A) switches to the OFF position does not disconnect power from the controls. The main disconnect switch releases the control panel, motors, and pumps from the power supply. As a safety feature, the panel door cannot be opened without first switching to the open (OFF) position. The main disconnect dial/switch is located at the top right hand corner of the panel. Warning: Though the open panel is not live, the wires entering the panel to the disconnect at the top of the panel are LIVE. DO NOT TOUCH.
Schematic of Disconnect Switch. The location of the switch on the panel is indicated by the arrow.
Page 27
The short circuit protector (left) and overload protector (middle) combine to form a complete motor protector circuit (right). Within the controller, these components are integrated into a single component called an overload relay. The device has a setting for the maximum allowable amperage, and a two push button circuit breaker (pushing in the red button opens the circuit / pushing in the white button closes the circuit).
These circuits are separated from the actual motor starter by a set of contacts which turn individual pumps on and off as required by the flow demand conditions. The logic for pump switching is contained in the pump shunting circuit and relays discussed in Sections IV and V. A schematic showing the main disconnect and motor protection circuits is shown below.
Main Disconnect and Motor Protection Circuit. Note that the lower segment of the diagram (marked P1 and P2) represents the motors and their respective starters.
Page 28
POW ER ON
C o n tr o l P a n e l C ir c u it
Control Transformers The control transformer separates the motor side (high voltage) from the control side (low voltage) of the booster system. The control transformer steps down the voltage to the control panel. Though the motor may use three phase 208V to 600V power, the control portion of the panel always runs on single phase 115V power. The transformer takes care of this voltage conversion.
Control Transformer. The left side is the low voltage side providing power to the panel. The right side is the high voltage supply which powers the motors.
Control Circuit Breakers A control circuit breaker protects the more sensitive components (relays and contacts) from being damaged by current surges. This standard circuit breaker trips at 0.5 amps to 3.0 amps depending on the systems combined horsepower.
The control circuit breaker prevents current overloads in the controls' sensitive components.
Page 29
The Power On pilot light informs the controls operator that the panel is live.
We now are able to discuss the fundemental panel protection and motor protection circuits. On the schematic, the main power source is supplied at the right of the disconnect switch. This power supplies the motors via the motor protector circuit and is stepped down to the panel voltage via the transformer. This is the junction that separates the high voltage (motor) side from the low voltage (control) side of the control panel. The control circuit breaker then protects the controls from current surges. All things being normal, the panel is supplied with power lighting the Power On pilot light. This circuit can be seen below.
Control Protection, Transformer and Motor Protector Circuits. The portion of the schematic on the left side of the dashed line was discussed in this section.
Page 30
ALTERN ATO R S W IT C H
LA M P
F r o m P r e s s u r e S w itc h
Manual Alternator Switches Manual alternator switches are standard for 50-50 capacity split Duplex systems and for the two lag pumps in the Triplex systems. The switch allows selection of which pump is the lead pump. This allows the operator of the system to equalize wear on the motors and pumps by periodically changing the alternator setting. The switch is a standard selector switch (marked either P1-P2 or P2-P3) located at the bottom center of the panel.
Automatic Alternator Switches Automatic alternator switches are optional on units requiring alternation of the lead or lag pumps. The switch serves the same purpose as the manual selector switch. The switch is designed to alternate on every no-flow condition and on shutoff of one pump after a full flow condition.
Page 31
Pump Shunting Circuit holds key to pump sequencing. The circuit is only activated when the pumps are placed in the AUTO position.
Pump Run Indicators and Motor Contactors Pump run indicator lamps (Pilot Lights) are placed in parallel with the contactor coil for each motor. The contactor coil actuates a contact located between the motor protector circuit and the motor to close. The closed contact supplies power to the motor and starts the pump running. This connection also lights the pump run lamp on the panel allowing the operator to know the status of each pump of the system.
Pump run indicator and contact coil in parallel. The coil closes contacts starting a motor.
Page 32
Pressure Booster Systems Designers Handbook SECTION V: CURRENT SENSING and CONTROL RELAYS
CONTROL RELAY #1
CONTROL RELAY #2
Current Sensing Transformers One leg of each motor lead is passed through a current transformer coil. These coils measure the current drawn by each motor, indirectly measuring the GPM flow through each pump. The current sensing relays supplied by the current transformers are factory set to an upper and lower current threshold. When the current exceeds the upper threshold, an additional pump is turned on to cope with the increased flow. Likewise, when the current drops below the lower threshold, a pump is shut down to conserve energy. The upper threshold controls the turn-on of the next pump and is adjusted by the dial marked Threshold on the current sensing relay. The lower threshold controls the shut-off of a running pump. It is set as a percentage of the upper threshold using the dial marked Hysteresis on the current sensing relay.
Current Sensing Relay. In combination with a control relay, the CSR activates a current transformer in the starter (part of the contact arrangement) to start the motor. The numbers 19 and 20 marking the arrows indicate a connection to the matching numbers on the motor lead.
Page 33
TIP: The number of current sensing relays in a system can be determined by the formula: DUPLEX: ONE RELAY + ONE RELAY PER STEP OF SEQUENCING TRIPLEX: TWO RELAYS + ONE RELAY PER STEP OF SEQUENCING EXAMPLE: A Duplex System on 33-67 capacity split supplies a peak demand of 300GPM. The system is designed for conventional sequencing (i.e. The lead pump runs constantly. The lag pump turns on and off as the flow demand requires). The motors are 5 and 10 hp and run on a 208V supply voltage. At full flow, the lead pump draws 50 amps. The system has one current sensing relay. The current sensing relay turn-on threshold would be set to 50 amps. This would cause the lag pump to turn on when the lead pump draws 50 amps. The shutoff threshold would be set to about 60 amps. This would cause the lag pump to shut off when both motors together draw 60 amps. The Hysteresis setting would be 20%. Reason: 20% of 50 amps is 10 amps. Fifty amps (upper threshold) plus 10 amps gives a shutoff threshold of 60 amps. Why is the shutoff threshold set higher than the turn-on threshold? This is because two motors working at the same flow rate as one motor alone will draw more amps.
Current Sensing Relay Switches Every time a current sensing relay coil reads a threshold current, it actuates a current sensing relay switch to either open or closed (depending on whether the switch is normally open or normally closed).
Current sensing relay switch closes actuating a control relay to start or shut down a motor.
As the relay coil requires, this relay switch will open or close causing one of the following to happen: a) The switch closes causing a control relay to turn on a pump.. b) The switch opens starting the countdown on the minimum run timer. When the timer runs down, a control relay turns the pump off.
MOTOR CONTACT
Page 34
Control Relay Coil actuates the motor starter contacts inside the shunting circuit.
Contacts A contact corresponding to each control relay is located in the pump shunting circuit. The contact reacts to the coil in turn actuating the motor contactors and will do one of the following: a) Turn on a new pump and shut the running pump off. b) Turn on a new pump and leave the running pump on. c) Shut off the running pump after the set time.
Contacts (RP2) close to start the motor running or open to shut one down. This action opens or closes the motor contactors (C1).
Page 35
Timing Relay holds the contact for a set period of time in order t o prevent pump cycling.
Page 36
Transformer
PUMP SYSTEM
AQUASTAT
SOLENOID VALVE
Low Suction Pressure Warning A pressure switch protects the pumps from the effects of low suction pressure. If the suction pressure feeding the system drops below a minimum threshold the low suction pressure switch will open, shutting all pumps down. The minimum suction pressure cut-out is factory set to 5 psi but may be adjusted, though this is strongly advised against. The low suction switch will turn all pumps off and light the low suction lamp warning. The pressure switch has two settings: a) Cut-out value: This opens the contacts shutting down the pumps (set at 5 psi). On the switch itself, this setting is adjusted by turning the top screw. The actual setting is read on the scale on the side of the switch. b) Cut-in value: This is adjusted relative to the cut-in value using the Differential setting. (Cut-out value + Differential Setting = Cut-in Value) The differential is set after the cut-out value has been set, and should be set to its minimum to begin adjustments. After the cut-out has been set, turn the bottom screw to the letter corresponding to the desired differential. (Factory set to 5 psi above the cut-out pressure.) Warning: If the low suction pressure switch is set too close to the minimum NPSH, pump cycling will occur. If the situation is not corrected, damage to the motor starters can be expected. The same problem will occur if the Differential setting is too low.
Page 37
Fig.# 21: Low suction pressure switch shuts down system and warns by lighting pilot.
High and Low System Pressure Warnings Two further pressure switches with warning pilots are available as options (see Section VII of this chapter). These switches are also factory set and can be complimented by corresponding low and high system pressure warning lamps. Aquastats and Solenoid Valves During normal operation, a steady flow of water through the pumps carries away the waste heat they generate. Because of this, high temperatures are occasionally generated during periods of low flow. High temperature water can affect the performance of and even damage the pumps. An aquastat is available as an option and is installed on the suction header to measure the temperature of the water in booster system. The aquastat is set for a certain temperature (120F) at which it actuates a solenoid valve located on the side of the control panel. This valve opens bleeding the potentially harmful hot water. In No-Flow Shutdown Systems (Option X), the aquastat is used to trigger a pressure switch which shuts down the system. In this case, no solenoid valve is required since the aquastat is set to a much lower temperature (90F).
Aquastat and Solenoid valve act together to bleed high temperature water from the pumps. On No-Flow shutdown systems, the solenoid valve is not necessary since the pumps shut down long before high temperatures are generated.
Page 38
Page 39
Option T adds four step sequencing to a Triplex system using a 20-40-40 capacity split between the three pumps. The arrangement yields the following pump configurations subject to demand conditions: Step 1: Pump 1 running, Pumps 2 and 3 off (20% capacity) Step 2: Pump 2 running, Pumps 1 and 3 off (40% capacity) Step 3: Pumps 2 and 3 running, Pump 1 off (80% capacity) Step 4: Pumps 1, 2, and 3 running (full capacity)
Option U takes full advantage of the Triplex 20-40-40 capacity split by breaking the supplied flow into five steps: Step 1: Pump 1 running, Pumps 2 and 3 off (20% capacity) Step 2: Pump 2 running, Pumps 1 and 3 off (40% capacity) Step 3: Pumps 1 and 2 running, Pump 3 off (60% capacity) Step 4: Pumps 2 and 3 running, Pump 1 off (80% capacity) Step 5: Pumps 1, 2, and 3 running (full capacity)
Page 40
NEMA 1 General Purpose - Indoor Intended for indoor use. Provides protection from accidental contact of personnel with enclosed equipment. Standard Armstrong enclosure. NEMA 2 Dripproof - Indoor Intended for indoor use. Protects equipment from falling dirt and falling non-corrosive liquids. NEMA 3 Dust, Rain, and Sleet resistant Outdoor Intended for outdoor use. Protects enclosed equipment from wind-blown dust and water. Limited resistance to snow, sleet, and ice. (NOT SLEET PROOF) NEMA 3R Rainproof / Sleet-resistant - Outdoor Same as NEMA 3 with added resistance to rain and snow. NEMA 4 Water/Dust-tight - Indoor/Outdoor Intended for indoor/outdoor service. Protects equipment from splashing, seeping, falling, or hose-directed water and from severe external condensation. Limited resistance to snow, sleet, and ice. NEMA 4X Water/Dust-tight - Indoor/Outdoor Corrosion Resistant Same provisions as NEMA 4 with the addition of resistance to corrosion. NEMA 12 Indoor Industrial - Dust and Drip-tight Intended for indoor use. Protects equipment from fibers, flyings, lint, dust and dirt, and light splashing, seepage, dripping and external condensation of noncorrosive liquids. NEMA 13 Indoor Industrial -Dust and Drip-tight Intended for housing pilot devices such as limit switches, foot switches, pushbuttons, selector switches, pilot lights, etc. and to protect these devices from lint and dust, seepage, external condensation, and spraying of water, oil or coolant.
CSA 1 Indoor General purpose enclosure providing protection from accidental contact of personnel with enclosed equipment. CSA 2 Drip Resistant - Indoor Enclosure constructed to provide a degree of protection from dripping and light splashing of non-corrosive liquids and falling dirt. CSA 3 Rain-resistant - Indoor/Outdoor Indoor/Outdoor enclosure constructed to provide a degree of protection from rain, snow, and windblown dust. Undamaged by external ice formation. CSA 3R Rainproof - Indoor/Outdoor Same as CSA 3 with higher resistance to rain and snow. Also undamaged by external ice formation. CSA 4 Rainproof - Indoor/Outdoor Indoor/Outdoor enclosure constructed to provide a degree of protection from rain, snow, windblown dust, splashing and hose-directed water. Also undamaged by external ice formation. CSA 4X Corrosion-resistant - Indoor/Outdoor Same as CSA 4 enclosure with added resistance to corrosion. CSA 12 Indoor Industrial Constructed so as to provide a degree of protection from circulating dust, lint fibers, and flyings; dripping and light splashing of noncorosive liquids; not provided with knockouts. CSA 13 Indoor Industrtial Constructed so as to provide a degree of protection against circulating dust, lint fibers, and flyings; seepage and spraying of noncorrosive liquids including oils and coolants.
UL 50/UL 508 Type 1 Indoor Indoor enclosure providing a degree of protection from contact with enclosed equipment and from limited amounts of falling dirt. UL 50/UL 508 Type 2 Water-resistant - Indoor Enclosure resistant to limited amounts of falling water and dirt. UL 50/UL 508 Type 3 Outdoor Outdoor enclosure providing a degree of protection from windblown dust, rain, and sleet. Undamaged by external ice formation. UL 50/UL 508 Type 3R Rain-resistant - Outdoor Same as UL 50/UL 508 Type 3 also providing a degree of protection from falling rain and sleet. UL 50/UL 508 Type 4 Indoor/Outdoor Indoor/Outdoor enclosure providing protection from splashing or hose-directed water, rain and windblown dust. Undamaged by the formation of ice on the enclosure. UL 50/UL 508 Type 4X Indoor/Outdoor Indoor/Outdoor enclosure same as Type 4 with added resistance to corrosion.
UL 50/UL 508 Type 12 Indoor Industrial Indoor enclosure providing a degree of protection from dust, falling dirt, and dripping noncorrosive liquids. UL 50/UL 508 Type 13 Indoor Industrial Indoor enclosure providing a degree of protection form dust and spraying of water, oil and noncorrosive coolants.
Page 41
PRV Components The PRV can be broken down into two main assemblies: a) The main body valve assembly b) The pilot assembly
The dashed line seperates the internal main body valve and the external pilot assembly.
Page 43
(b)
(a) (c)
(d)
(f)
(e)
(g)
The pilot assembly controls the opening and closing of the main body valve. The main body valve is, in fact, slave to the pilot setting. Opening the pilot valve will open the main body valve. Closing the pilot will close the main body valve.
Page 44
(d)
(b) (a)
(b)
SECTION II: HOW the PRV WORKS To effectively regulate the system pressure, the PRV must change the amount of pressure reduction depending on the pressure of the incoming flow. This is accomplished by the opening and closing of the main body valve. As the pressure of the flow entering the PRV increases, the main body valve closes causing a greater reduction in the out-flow pressure. Conversely, as the in-flow pressure decreases, the main body valve opens causing a lesser reduction in the out-flow pressure.
Page 45
FLOW
OPENING CLOSING
Flow through the main body valve is controlled by varying the pressure in the pilot assembly. This is done by turning the set screw on the pilot pressure reducing valve. Closing the screw (as shown by the dark arrows) prevents flow through the top piloting tube. This causes pressure to build up on top of the diaphragm, closing the main valve. Opening the screw (as shown by the light arrows) increases flow through the top piloting tube. This reduces the pressure on top of the diaphragm causing the main valve to open.
The action of the main body valve is regulated by the piloting system. As the incoming pressure increases, so does the pressure in the pilot circuit. This pressure is transmitted to the top of the diaphragm forcing the valve closed. A reduction in pressure causes the reverse effect opening the valve. Why does the pilot win out over the main valve? The pressure above the diaphragm is exerted over an area 1.5 times greater than the seat area through which the main flow must travel. This area differential gives the pilot an advantage (a type of hydraulic leverage), enabling it to control the action of the main valve.
Pilot Pressure Diaphragm Area (Pilot Area)
Flow Pressure
Fig.# 5: The pilot pressure wins out over the flow pressure due to hydraulic leverage advantage.
Page 46
Page 47
Page 48