Catalogue
37258G
Genset Control
for Multiple
Unit Operation
DESCRIPTION
The easYgen-3000 Series are control units for genset management applications. The numerous inputs and
outputs, along with a modular software structure, permit you to use the easYgen-3000 Series for a wide range
of applications with only a single part number. This includes stand-by, AMF, peak shaving, import-export, cogeneration or distributed generation, among others. Also the easYgen-3000 Series is compatible for island, island
parallel, mains parallel and multiple unit mains parallel operations.
The easYgen-3000 Series is able to control up to 32 gensets connected in a network with automatic sequencing.
The easYgen-3000 Series is available in two variants, the easYgen-3100 for cabinet back panel installation,
and the easYgen-3200 with graphical display and soft keys for front panel mounting.
FlexAppTM This feature provides the tools to easily configure the number of operated breakers: None, GCB,
GCB and MCB.
LogicsManagerTM Woodward's LogicsManager software enables to change the operation sequences and
adapt them to specific needs. The LogicsManager accomplishes this by monitoring a range of measuring values and internal states, which are combined logically with Boolean operators and programmable timers. This
enables to create and/or modify control and relay functions.
FlexInTM The analog inputs are configurable to operate with VDO, resistive, and/or 0 to 20 mA senders.
Flexible Outputs Speed and voltage bias outputs are configurable to function with all speed governors and
voltage regulators. The outputs can also be used as freely scalable outputs (e.g. for driving external meters).
FlexCANTM Advanced network interfaces ensure unsurpassed control performance from engine control up
to total plant operation. The easYgen-3000 Series is capable of working with all common industrial interfaces,
including CAN, RS-232, and RS-485. The multiple communication protocols permit the easYgen-3000 Series to
communicate with a vast majority of engine control units (ECUs), external I/O boards, PLCs, and modems.
CANopen, J1939, Modbus RTU, and Modem protocols are supported.
DynamicsLCDTM The adaptive and interactive 5.7", 320x240 pixel graphical LC display with soft keys and a
clear menu structure ensures intuitive user operation and navigation.
Programmable operation
sequences
Features
Operation modes: Auto, Stop, Manual, and Load/No Load test modes via discrete input possible
Breaker control: Slip frequency / phase matching synchronization, open-close control, breaker monitoring
Load transfer features: open / closed transition, interchange, soft loading / soft unloading, mains parallel
Process and load-dependent start/stop logic for diesel and gas engines programmable for spinning or system
reserve with fixed or dynamic priorities.
Real and reactive power load sharing with up to 32 units
Remote control via interface and discrete/analog inputs for adjusting speed, frequency, voltage, power, reactive
power, and power factor set points
Complete integrated engine and generator protection as well as mains monitoring features
Freely configurable PID controllers for various control purposes, such as heating circuit control (CHP applications), water level, fuel level, or pressure and/or other process values
Special Scania S6, MTU ADEC, Volvo EMS2 & EDC4, Deutz EMR2, MAN MFR/EDC7, SISU EEM, Cummins
and Woodward EGS02 ECU support (depending on Package)
Counters for operating hours / engine starts / maintenance / active energy / reactive energy
Configurable trip levels / delay timers / alarm classes for monitoring and protective functions
Clear text display and evaluation of up to 100 J1939 analog values
Discrete and analog I/O expansion board connectivity (Woodward IKD 1 or Phoenix Contact IL series)
Front panel and PC configurable (ToolKit software)
Multi-level password protection for access via HMI or interface
Multi-lingual capability !"#$%&'()*+,-."()/,+"0'()12."%&'()3'%"+&+()4.2."+&+()56.$%."()78,69#9+&+():9,;%&'()<9&&%."()78$%&'=
Event recorder (300 events, FIFO) with real time clock
Multi-lingual capability
CANopen / J1939 ECU
Control
Modbus RTU Protocol
CE marked
UL/cUL Listing
LR & ABS Marine
SPECIFICATIONS
78?+,)&922$@)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)BCDCE)FG0) H)68)EI)FG0=)
5"6,%"&%0)08"&9-26%8")AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)-.JA)BK)L)
M-N%+"6)6+-2+,.69,+) 82+,.6%8"=)AAAAAAAAAAAAAAAAAAAAAAA)OCI)68)KI)P3)D)OE)68)BQH)P/)
M-N%+"6)6+-2+,.69,+) &68,.#+=)AAAAAAAAAAAAAAAAAAAAAAAA)ORI)68)HI)P3)D)OCC)68)BKS)P/)
M-N%+"6)'9-%G%6@AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)TQ)U()"8"O08"G+"&%"#)
Voltage)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)) D"=
100 Vac [1])
<.6+G) F,.6+G=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)STDBCI)F.0)
)
V.JA)W.$9+) F-.J=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)HSDBQI)F.0)
)
) <.6+G)&9,#+)W8$6A F&9,#+=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)CAQ);F)
and 400 Vac [4] <.6+G) F,.6+G=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)CKKDEHI)F.0)
)
V.JA)W.$9+) F-.J=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)RESDSII)F.0)
)
) <.6+G)&9,#+)W8$6A F&9,#+=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)EAI);F)
M009,.0@)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)3$.&&)B)
V+.&9,.N$+).$6+,".68,)?%"G%"#&)AAA)R2OR?()R2OE?()R2OE?)XY()B2OC?()B2OR?)
1+66%"#),."#+)AAAAAAAAAAAAAAAAAAAAA)2,%-.,@)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAQI)68)SQI(III)F.0)
Z%"+.,)-+.&9,%"#),."#+)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)BACQ[F,.6+G)
V+.&9,%"#)\,+]9+"0@AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)QIDSI)^_) EI)68)HQ)^_=)
^%#')5-2+G."0+)5"296`)<+&%&6."0+)2+,)2.6')AAAAAAA)aBb)IAETH)V#()aEb)CAI)V#)
V.JA)28?+,)08"&9-26%8")2+,)2.6')AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)c)IABQ)L)
Current (Isolated)) <.6+G) 5,.6+G=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)aBb)AADB)M)8,)aQb)AADQ)M)
Z%"+.,)-+.&9,%"#),."#+)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)5#+")d)RAI[5,.6+G)
)
5-.%"&D#,89"G)d)BAQ[5,.6+G)
1+66%"#),."#+)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)B)68)RC(III)M)
e9,G+")AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)c)IABQ)FM)
<.6+G)&'8,6O6%-+)09,,+"6) B)&=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAaBb)QI[5,.6+G()aQb)BI[5,.6+G)
Power)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA))
1+66%"#),."#+)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)IAQ)68)TT(TTTAT);LD;W.,)
Discrete inputs)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)%&8$.6+G)
5"296),."#+)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)BCDCE)FG0) H)68)EI)FG0=)
5"296),+&%&6."0+)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA).22,8JA)CI);X'-&)
)
)
)
Relay outputs)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)%&8$.6+G)
38"6.06)-.6+,%.$)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)M#3GX)
Z8.G) *7=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)CAII)M.0fCQI)F.0)
)
CAII)MG0fCE)FG0)D)IARS)MG0fBCQ)FG0)D)IABH)MG0fCQI)FG0)
7%$86)G96@) 7Y=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA))
)
BAII)MG0fCE)FG0)D)IACC)MG0fBCQ)FG0)D)IABI)MG0fCQI)FG0)
Analog inputs (none isolated))AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA\,++$@)&0.$+.N$+)
:@2+)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)I)68)QII)X'-&)D)I)68)CI)-M)
<+&8$96%8")AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)BB)e%6)
Analog outputs (isolated))AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA\,++$@)&0.$+.N$+)
:@2+)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)g)BI)F)D)g)CI)-M)D)7LV)
5"&9$.6%8")W8$6.#+) 08"6%"989&$@=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)BII)F.0)
5"&9$.6%8")6+&6)W8$6.#+) B&=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)QII)F.0)
<+&8$96%8")AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)BBDBC)e%6) G+2+"G%"#)8").".$8#)896296=)
g)BI)F) &0.$+.N$+=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)%"6+,".$),+&%&6."0+)hB);X'-&)
g)CI)-M) &0.$+.N$+=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)-.J%-9-)$8.G)QII)X'-&)
Housing) RCII=) ) /,8"6)2."+$)\$9&')-89"6%"#)AAAAAAAAAAAAAAAAAA)7$.&6%0)'89&%"#)
Y%-+"&%8"&)
) LJ^JY)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)CHC)[)CBK)[)TT)--)
/,8"6)096896)
) LJ^)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)CET)aiBABb)[)BHR)aiBAIb)--)
38""+06%8")AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)&0,+?D2$9#)6+,-%".$&)CAQ)--j)
/,8"6)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)%"&9$.6%"#)&9,\.0+)
1+.$%"#)
) /,8"6)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)57SS) ?%6')&0,+?)\.&6+"%"#=)
)
) /,8"6)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)57QE) ?%6')0$.-2)\.&6+"%"#=)
)
) e.0;)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)57CI)
L+%#'6)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA).22,8JA)B(HQI)#)
Housing) RBII=) ) 1?%60')0.N%"+6)N.0;)-89"6%"#)AAAAA)1'++6)-+6.$)'89&%"#)
Y%-+"&%8"&)
) LJ^JY)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)CQI)[)CCH)[)HE)--)
38""+06%8")AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)&0,+?D2$9#)6+,-%".$&)CAQ)--j)
7,86+06%8")&@&6+-)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)57)CI)
L+%#'6)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA).22,8JA)C(BQI)#)
Disturbance test) 3!=)AAAAAAAAAAAA)6+&6+G).008,G%"#)68).22$%0.N$+)!k)#9%G+$%"+&)
Listings)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)lZ()0lZ) 0lZ)8"$@)\8,)+.&m#+"ORBII=)
Marine)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)Z<) :@2+)M22,8W.$=()Me1) Y+&%#")M&&+&&-+"6=)
DIMENSIONS
Plastic housing for front panel mounting (3200)
216 mm 181 mm
227 mm
282 mm
247 mm
84 mm
87 mm
99 mm
250 mm
TERMINAL DIAGRAM
)
International
L88G?.,G))
7X)e8J)BQBT)
/8,6)38$$%"&)3X()l1M)
HIQCCOBQBT)
BIII)!.&6)Y,.;+)<8.G)
/8,6)38$$%"&)3X)HIQCQ)
7'n)iB) TKI=)EHCOQHBB)
/.Jn)iB) TKI=)ETHORIQH)
)
Europe
L88G?.,G)*-N^)
^."G?+,;&6,.&&+)CT)
KIQSQ)16966#.,6()*+,-."@)
7'n)iET) I=)KBB)KHT)QEOI)
/.Jn)iET) I=)KBB)KHT)QEOBII)
+-.%$n)&6#6O%"\8f?88G?.,GA08-)
)
L88G?.,G)'.&).")%"6+,".6%8".$)
"+6?8,;)8\)G%&6,%N968,&)."G)
&+,W%0+)\.0%$%6%+&A)/8,)@89,)
"+.,+&6),+2,+&+"6.6%W+()0.$$)6'+)
/8,6)38$$%"&)2$."6)8,)&++)6'+)
L8,$G?%G+)Y%,+068,@)8")89,)
?+N&%6+A
)
)
)
)
www.woodward.com/power)
19No+06)68)6+0'"%0.$)-8G%\%0.6%8"&A)
:'%&)G809-+"6)%&)G%&6,%N96+G)\8,)
%"\8,-.6%8".$)29,28&+&)8"$@A)56)%&)"86)
68)N+)08"&6,9+G).&)0,+.6%"#)8,)
N+08-%"#)2.,6)8\)."@)L88G?.,G)
*8W+,"8,)38-2."@)08"6,.069.$)8,)
?.,,."6@)8N$%#.6%8")9"$+&&)+J2,+&&$@)
&6.6+G)%").)?,%66+")&.$+&)08"6,.06A)
L+).22,+0%.6+)@89,)08--+"6&)
.N896)6'+)08"6+"6)8\)89,)29N$%0.O
6%8"&A)7$+.&+)&+"G)08--+"6&)
%"0$9G%"#)6'+)G809-+"6)"9-N+,)
N+$8?)68)
&6#6OG80f?88G?.,GA08-)
Woodward
All Rights Reserved
)
RKCQH*)O)CIBIDIQD16966#.,6
FEATURES OVERVIEW
easYgen-3000 Series
V8G+$)
7.0;.#+)
RBII)
7B)
RCII)
7C)
) )
) )
7B)
) )
7C)
Measuring
*+"+,.68,)W8$6.#+) RO2'.&+DEO?%,+=)
*+"+,.68,)09,,+"6) RJ)6,9+),A-A&A=
V.%"&)W8$6.#+) RO2'.&+DEO?%,+=)
V.%"&)8,)#,89"G)09,,+"6) BJ)6,9+),A-A&A=)pB)
e9&N.,)W8$6.#+) BO2'.&+DCO?%,+=)
)
)
)
)
)
Control
e,+.;+,)08"6,8$)$8#%0) 82+")."G)0$8&+G)6,."&%6%8"=)
M968-.6%0()V."9.$()1682()."G)6+&6)82+,.6%"#)-8G+&)
1%"#$+)."G)-9$6%2$+O9"%6)82+,.6%8")
V.%"&)2.,.$$+$)-9$6%2$+O9"%6)82+,.6%8") 92)68)RC)9"%6&=)
MV/) .968)-.%"&)\.%$9,+=)."G)&6."GON@)82+,.6%8"
3,%6%0.$)-8G+)82+,.6%8")
*3e)."G)V3e)&@"0',8"%_.6%8") &$%22%"#)D)2'.&+)-.60'%"#=)
5"6+,0'."#+) %-28,6)D)+J28,6)08"6,8$=)
Z8.GOG+2+"G+"6)&6.,6D&682)
"D\()F()7()q()."G)7/),+-86+)08"6,8$)W%.).".$8#)%"296)8,)%"6+,\.0+)
Z8.GDW.,)&'.,%"#)\8,)92)68)RC)#+"&+6&)
/,++$@)08"\%#9,.N$+)75Y)08"6,8$$+,&)
FlexAppTM)
C)
O)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
C)
)
)
)
)
)
)
)
)
)
)
O)
)
)
)
)
)
)
)
)
)
)
)
C)
)
)
)pC)
)
)
)
)
)
)
)
R)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
O)
) )
) )
)
)
)
)
)
C
)
)
)pC)
)
)
)
)
)
)
)
R
HMI
18\6);+@&) .GW."0+G)Z3)G%&2$.@=)
DynamicsLCDTM)
16.,6D&682)$8#%0)\8,)G%+&+$)D)#.&)+"#%"+&)
389"6+,&)\8,)82+,.6%"#)'89,&)D)&6.,6&)D)-.%"6+"."0+)D).06%W+D,+.06%W+)+"+,#@
38"\%#9,.6%8")W%.)73)pR)
!W+"6),+08,G+,)+"6,%+&)?%6'),+.$)6%-+)0$80;) N.66+,@)N.0;92=)
Protection
Mk15p
*+"+,.68,n)W8$6.#+)D)\,+]9+"0@)
QT)D)CK)D)HBX)D)HBl)
*+"+,.68,n)8W+,$8.G(),+W+,&+D,+G90+G)28?+,)
RC)D)RC<)D)RC/)
*+"+,.68,n)9"N.$."0+G)$8.G)
ES)
*+"+,.68,n)%"&6."6."+89&)8W+,09,,+"6)
QI)
*+"+,.68,n)6%-+O8W+,09,,+"6) 5!3)CQQ)08-2$%."6=)
QB)
*+"+,.68,n)#,89"G)\.9$6)pE)
QI*)
*+"+,.68,n)28?+,)\.068,
QQ)
*+"+,.68,n),86.6%8")\%+$G)
)
!"#%"+n)8W+,&2++G)D)9"G+,&2++G)
BC)D)BE)
!"#%"+n)&2++G)D)\,+]9+"0@)-%&-.60')
)
!"#%"+n)Yi).9J%$%.,@)+J0%6.6%8")\.%$9,+)
)
V.%"&n)W8$6.#+)D)\,+]9+"0@)
QT)D)CK)D)HBX)D)HBl)
V.%"&n)2'.&+)&'%\6)D),86.6%8")\%+$G)
KH)D)
O)
RII)
) )
) )
)
)
)
RII)
) )
) )
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
) )
) )
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
RII)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
) )
) )
) )
) )
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
RII)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
I/Os
)
)
)
12++G)%"296) -.#"+6%0)D)&?%60'%"#`)7%0;92=)
) )
) )
) )
Y%&0,+6+).$.,-)%"296&) 08"\%#9,.N$+=)
BI)
) )
BI)
) )
BI)
) )
BI)
Y%&0,+6+)896296&) 08"\%#9,.N$+=)
LogicsManagerTM) -.JA)BC) ) ) -.JA)BC) ) ) -.JA)BC) ) ) -.JA)BC)
!J6+,".$)G%&0,+6+)%"296&)D)896296&)W%.)3Mk82+") -.J%-9-=)
BS)D)BS) ) ) RC)D)RC) ) ) BS)D)BS) ) ) RC)D)RC)
M".$8#)%"296&)pQ) 08"\%#9,.N$+=))
FlexInTM)
R)
) )
R)
) )
R)
) )
R
M".$8#)896296&) iDO)BIF()iDO)CI-M()7LV`)08"\%#9,.N$+=))
C)
) )
C)
) )
C)
) )
C
!J6+,".$).".$8#)%"296&)D)896296&)W%.)3Mk82+") -.J%-9-=)
O)
) ) BS)D)E ) )
O)
) ) BS)D)E)
Y%&2$.@)8\)4BTRT).".$8#)W.$9+&) "9-N+,)8\)17k&=)
BS)
) )
O)
) )
BS)
) )
O)
Y%&2$.@)."G)+W.$9.6%8")8\)4BTRT).".$8#)W.$9+&) &9228,6+G)17k&=
O)
) ) BII) ) )
O)
) )
BII)
3Mk)N9&)08--9"%0.6%8")%"6+,\.0+&)pS)
FlexCANTM)
C)
) )
C)
) )
C)
) )
C
<1OCRCDEHQ)V8GN9&)<:l)1$.W+)%"6+,\.0+ &=)
B)D)B)
) ) B)D)B) ) ) B)D)B) ) )
B)D)B)
Listings/Approvals
lZ)Z%&6%"#)
0lZ)Z%&6%"#)
Z<)r)Me1)V.,%"+)
3!)V.,;+G
)
)
)
)
) )
) )
) )
) )
) )
) )
)
O)
)
)
) )
) )
) )
)
O)
)
)
Part Numbers
BM)3:)%"296&)D)\,8"6)2."+$)-89"6%"#)?%6')G%&2$.@))pK)
QM)3:)%"296&)D)\,8"6)2."+$)-89"6%"#)?%6')G%&2$.@))pK)
BM)3:)%"296&)D)0.N%"+6)N.0;)-89"6%"#)?D8)G%&2$.@)
QM)3:)%"296&)D)0.N%"+6)N.0;)-89"6%"#)?D8)G%&2$.@)
12.,+)08""+068,);%6)
)
7Dk)HEEIO)
7Dk)HEEIO)
7Dk)HEEIO)
7Dk)HEEIO)
7Dk)HTCRO)
O)
O)
BTRB)
BTRI)
BRBE)
)
)
)
)
)
)
)
)
)
)
O)
O)
BTRR)
BTRC)
BRBE)
) )
)
)
)
)
)
)
)
)
BTCC)
BTCR)
O)
O)
BRBE)
) )
)
)
)
)
)
)
)
)
BTCE)
BTCQ)
O)
O)
BRBE)
pB) -.%"&)8,)#,89"G)09,,+"6)&+$+06.N$+))
pQ) &+$+06.N$+)G9,%"#)08"\%#9,.6%8")N+6?++")FYX) I)68)BHI)X'-()I)68)Q)N.,=()FYX) I)68)BHI)X'-()I)68)BI)N.,=()FYX)
pC) ,+\+,)68)6'+)M22$%0.6%8")V."9.$)RKEKB)\8,)
I)68)RHI)X'-()EI)68)BCIP3=()FYX) I)68)RHI)X'-()QI)68)BQIP3=()76BII()<+&%&6%W+)%"296) 8"+O)8,)6?8O28$+()C26A)
.22$%0.6%8"&)?%6')-8,+)6'.")H)2.,.$$+$)#+"&+6&)
$%"+.,)8,)T26A)9&+,)G+\%"+G)=()8,)CI)-M) IDE)68)CI -M()\,++$@)08"\%#9,.N$+=
N+0.9&+)8\)N9&)$8.G)$%-%6&)
pS) \,++$@)&+$+06.N$+)G9,%"#)08"\%#9,.6%8")N+6?++")3Mk82+")8,)4BTRT`),+]9+&6)%"\8,-.6%8"))
pR) W%.)&+,%.$)08""+06%8")."G):88$s%6)&8\6?.,+) %"0$9G+G=) pK) .)&0,+?)."G).)0$.-2);%6).,+)G+$%W+,+G)?%6')6'+)9"%6)\8,)\.&6+"%"#
pE) -+.&9,+G)#,89"G)09,,+"6)
SIRCOVER and
appli_114_a
svr_059_a_1_cat
svr_099_b_1_cat
SIRCOVER BY-PASS
General characteristics
274
C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:274 Sec1:274
Conformity
to standards
Devices 6 or 8 pole
Devices with oversized neutral ex.:
3 x 250 A + N 400 A.
Devices with
advanced neutral.
Approvals and
certifications (1)
IEC 60947-3
IS 14947-3
EN 60947-3
VDE 0660-107
(1992)
NBN EN 60947-3
BS EN 60947-3
Available
on request
Bureau Vritas
BBJ Poland
(Attestaion of
verification)
(1) Product reference on
request.
15/11/10 16:28:11
svr_136_a_1_x_cat
appli_114_a
A connection kit for copper bars allows the link between the 2 connection
terminals of one pole (fig 1 and 2) and the bridging of the upstream and
downstream link for ratings 2000, 2500 and 3200A (fig 3).
Edgewise connection
Top or bottom
C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:275 Sec1:275
Fig 3
acces_231_a_1_cat
Fig 2
acces_229_b_2_cat
acces_226_c_2_cat
Fig 1
275
15/11/10 16:29:07
svr_051_a_1_cat
SIRCOVER I-0-II
Rating
(A)
No. of
poles
Switch body
3P
4100 3013(1)
4P
4100 4013(1)
3P
4100 3016(1)
4P
4100 4016(1)
3P
4100 3019
4P
4100 4019
3P
4100 3025(1)
Direct handle
External
handle
Shaft for
external
handle
Bridging bar*
Terminal
shrouds
Terminals
protection
screen
3P
2694 3014(5)(6)
3P
1509 3012(7)
4P
2694 4014(5)(6)
4P
1509 4012(7)
3P
2694 3021(5)(6)
3P
1509 3025(7)
4P
2694 4021(5)(6)
4P
1509 4025(7)
1st/2nd contact
3P
NO/NC
(5)(6)
4109 0021(4) 2694 3051
3P
1509 3063(7)
4P
2694 4051(5)(6)
4P
1509 4063(7)
Auxiliary
contacts
125 A
160 A
4109 0019
200 A
250 A
4P
4100 4025(1)
3P
4100 3039(1)
4P
4100 4039
(1)
3P
4100 3050(1)
Type S2
Black
4199 5012(2)
Black IP55
1421 2113
Black IP65
1423 2113(2)
400 A
200 mm
1400 1020
4109 0025
320 mm
1400 1032(2)
4109 0039
500 A
4109 0050
4P
4100 4050(1)
3P
4100 3063(1)
630 A
4109 0063
4P
4100 4063(1)
3P
4100 3080(1)
4P
4100 4080(1)
3P
4100 3120(1)
4P
4100 4120
(1)
3P
4100 3160(1)
4P
4100 4160(1)
3P
4100 3180
4P
4100 4180
3P
4100 3200
4P
4100 4200
3P
4100 3250
4P
4100 4250
3P
4100 3320
4P
4100 4320
800 A
3P
1509 3080(7)
4109 0080
1 250 A
Black
2799 7052(2)
S4 type
Black IP65
1443 3113(2)
1 600 A
200 mm
1401 1520
4P
1509 4080(7)
4109 0120
320 mm
1401 1532(2)
3P
1509 3160(7)
4109 0160
4P
1509 4160(7)
1 800 A
2 000 A
2 500 A
Black
2799 7012(2)
Black IP65
2799 7146(2)
3 200 A
320 mm
2799 3018(2)
1st contact
NO/NC
included
included
(3)
2nd contact
NO/NC
4409 0022(4)
276
C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:276 Sec1:276
15/11/10 16:29:43
svr_051_a_1_cat
SIRCOVER I - I+II - II
Rating (A)
No. of
poles
Switch body
3P
4190 3013(1)
4P
4190 4013(1)
3P
4190 3016(1)
Direct handle
External
handle
Shaft for
external
handle
Bridging bar*
Auxiliary
contacts
Terminal
shrouds
Terminal
screens
125 A
160 A
3P
3P
2694 3014(4)(5) 1509 3012(6)
4P
4P
2694 4014(4)(5) 1509 4012(6)
4109 0019
4P
4190 4016(1)
3P
4190 3019
4P
4190 4019
3P
4190 3025(1)
4P
4190 4025(1)
3P
4190 3039(1)
4P
4190 4039(1)
3P
4190 3050(1)
4P
4190 4050(1)
3P
4190 3063(1)
4P
4190 4063(1)
3P
4190 3080(1)
4P
4190 4080(1)
3P
4190 3120(1)
4P
4190 4120(1)
3P
4190 3160(1)
4P
(1)
200 A
250 A
Black
4199 5012(2)
S2 type
Black IP65
1423 2114(2)
200 mm
1400 1020
320 mm
1400 1032(2)
400 A
4109 0025
3P
3P
2694 3021(4)(5) 1509 3025(6)
4P
4P
2694 4021(4)(5) 1509 4025(6)
4109 0039
500 A
4109 0050
630 A
4109 0063
800 A
4109 0080
1 250 A
Black
2799 7052(2)
S4 type
Black IP65
1443 3114(2)
1 600 A
200 mm
1401 1520
4109 0120
320 mm
1401 1532(2)
4190 4160
4109 0160
3P
4190 3180
4P
4190 4180
1 800 A
1st/2nd contact
NO/NC
4109 0021(3)
3P
3P
2694 3051(4)(5) 1509 3063(6)
4P
4P
2694 4051(4)(5) 1509 4063(6)
3P
1509 3080(6)
4P
1509 4080(6)
3P
1509 3160(6)
4P
1509 4160(6)
C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:277 Sec1:277
277
15/11/10 16:29:46
svr_059_a_4_cat
SIRCOVER BY-PASS
Rating (A)
No. of
poles
Switch body
I-0-II
3+6P
4100 7013(1)
4+8P
4100 9013(1)
3+6P
(1)
4100 7016
4+8P
4100 9016(1)
Direct handle
External
handle
Shaft for
external
handle
Bridging bar
Auxiliary
contacts
Terminal
shrouds
Terminal
screens
125 A
160 A
S2 type
Black
4199 5012(2)
Black IP55
1421 2113(2)
Black IP65
1423 2113
3P
2694 3014(4)(5)
200 mm
1400 1020
4109 0019
4P
2694 4014(4)(5)
320 mm
1400 1032(2)
3+6P
4100 7019
4+8P
4100 9019
3+6P
4100 7025(1)
4+8P
4100 9025(1)
3P
2694 3021(4)(5)
3+6P
4100 7039(1)
4P
2694 4021(4)(5)
3P
1509 3012(6)
4P
1509 4012(6)
200 A
250 A
4109 0025
400 A
200 mm
1401 1520
4109 0039
1st/2nd
contact
NO/NC
4109 0021(3)
4+8P
4100 9039(1)
3+6P
4100 7050(1)
4+8P
4100 9050(1)
3P
2694 3051(4)(5)
3+6P
4100 7063(1)
4P
2694 4051(4)(5)
Black
2799 7052(2)
S3 type
Black IP65
1433 3113(2)
500 A
320 mm
1401 1532(2)
630 A
4109 0050
4109 0063
4+8P
4100 9063(1)
3+6P
4100 7080(1)
4+8P
4100 9080(1)
3+6P
4100 7120(1)
800 A
4109 0080
1 250 A
4+8P
4100 9120(1)
3+6P
4100 7160
4+8P
4100 9160
Black
Black IP65
2799 7012(2) 4199 7146(2)
1 600 A
200 mm
2799 3015
4109 0120
3P
1509 3025(6)
4P
1509 4025(6)
3P
1509 3063(6)
4P
1509 4063(6)
3P
1509 3080(6)
4P
1509 4080(6)
450 mm
2799 3019(2)
3P
1509 3160(6)
4109 0160
4P
1509 4160(6)
278
C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:278 Sec1:278
15/11/10 16:29:49
Direct handle
SIRCOVER
Rating (A)
125 630
800 1800
2000 3200
Handle color
Black
Black
Black
Handle type
Single lever
Single lever
Double lever
Reference
4199 5012
2799 7052
2799 7012
Handle type
Single lever
Single lever
Double lever
Reference
4199 5012
2799 7052
2799 7012
acces_153_a_2_cat
acces_129_b_1_cat
SIRCOVER BY-PASS
Rating (A)
125 200
250 630
800 1600
Handle color
Black
Black
Black
Use
The door interlocked external operation handle includes one padlockable handle, one
escutcheon and must be utilised with a shaft extension.
SIRCOVER
S4 type handle
S3 type handle
acces_152_a_2_cat
acces_151_a_1_cat
acces_150_a_1_cat
S2 type handle
Rating (A)
125 630
125 630
125 630
800 1800
800 1800
2000 3200
Switching
type
I - 0 - II
I - 0 - II
I - I+II - II
I - 0 - II
I - I+II - II
I - 0 - II
External
IP(1)
IP55
IP65
IP65
IP65
IP65
IP65
Handle
S2 type
S2 type
S2 type
S4 type
S4 type
Reference
1421 2113
1423 2113
1423 2114
1443 3113(2)
1443 3114(2)
2799 7146(2)
SIRCOVER BY-PASS
Switching
Rating (A)
type
125 200
I - 0 - II
125 200
I - 0 - II
250 ... 630
I - 0 - II
800 1600
I - 0 - II
External
IP(1)
IP55
IP65
IP65
IP65
Handle
S2 type
S2 type
S3 type
Reference
1421 2113
1423 2113
1433 3113
4199 7146
acces_198_a_2_cat
Use
For single lever handles S1, S2, S3 type and for double lever handle S4 type.
Other colours: Consult us.
Color
Light grey
Dark grey
Light grey
Dark grey
To be ordered
in multiples of
50
50
50
50
Handle
S2, S3 type
S2, S3 type
S4 type
S4 type
Reference
1401 0001
1401 0011
1401 0031
1401 0041
acces_187_a_1_cat
Use
Enables S type handles to be fitted in place
of existing older style Socomec handles.
Adapter can also be utilised as a spacer to
increase the distance between the panel
door and the handle lever.
Color
Black
To be ordered
in multiples of
10
Dimensions
Adds 12 mm to the depth.
External IP(1)
IP65
Reference
1493 0000
C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:279 Sec1:279
279
15/11/10 16:29:53
acces_260_a_2_cat
Use
To guide the shaft extension into the external handle.
This accessory enables handle to engage extension shaft with a misalignment of up to 15 mm.
Required for a shaft lenght over 320 mm.
Description
Shaft guide
Reference
1429 0000
acces_143_b_1_cat
Use
Standard lengths:
- 200 mm,
- 320 mm,
- 450 mm.
Other lengths: Consult us.
SIRCOVER
Shaft length
(mm)
200 mm
320 mm
200 mm
320 mm
200 mm
320 mm
320 mm
Dimension X
(mm)
210 310
210 430
280 390
280 510
425 577
425 697
653 923
Reference
1400 1020
1400 1032
1400 1020
1400 1032
1401 1520
1401 1532
2799 3018(1)
SIRCOVER BY-PASS
Shaft length
Rating (A)
(mm)
200 mm
125 200
125 200
320 mm
250 400
200 mm
250 400
320 mm
500 630
200 mm
500 630
320 mm
800 1600
200 mm
800 1600
450 mm
Dimension X
(mm)
320 450
320 570
298 420
298 540
417 539
417 659
550 680
550 800
Reference
1400 1020
1400 1032
1401 1520
1401 1532
1401 1520
1401 1532
2799 3015(1)
2799 3019(1)
acces_144_b_1_cat
Rating (A)
125 400
125 400
500 630
500 630
800 1800
800 1800
2000 3200
acces_202_a_1_cat
Bridging bars
svr_068_a_1_x_cat
acces_208_a_2_cat
SIRCOVER BY-PASS
Use
Creation of a common link, on the top or
bottom side of the switch, in order to feed
load with either power supply I or/and II. For
SIRCOVER BY-PASS, two sets of bridging
bars are needed as the switch is composed
of three basic switch frames.
Rating (A)
125 200
250
400
500
630
800
1250
1600 ... 1800
Position I: 6 or 8 poles
Position II: 3 or 4 poles
Section (mm)
20 x 2.5
25 x 2.5
32 x 5
32 x 5
50 x 5
50 x 6
60 x 8
90 x 10
Reference
4109 0019
4109 0025
4109 0039
4109 0050
4109 0063
4109 0080
4109 0120
4109 0160
svr_124_a_1_cat
acces_041_a_1_cat
acces_205_a_2_cat
SIRCOVER
280
C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:280 Sec1:280
15/11/10 16:30:07
acces_226_b_1_x_cat
Use
Enables:
- To allow connection between the two
power terminals from a same pole for
2000 to 3200A ratings (Fig. 1 and Fig 2).
- Top or bottom bridging connection (Fig. 3).
252
74
37 60
Fig. 2
155
acces_232_a_1_cat
74
37
Rating (A)
2 000 2 500
2 000 2 500
Piece
Connection - part A
Bolt set - part B
Quantity to order
per pole(1)
2
2
Reference
2619 1200
2699 1200
3 200
3 200
Connection - part A
Bolt set - part B
included
2699 1200
acces_228_b_1_x_cat
(1) Example for 3 pole device equipped upstream only: order 3 times the indicated quantities.
132
30303030 22
210
acces_233_a_1_cat
30303030
Rating (A)
2 000 2 500
2 000 2 500
2 000 2 500
Piece
Connection - part A
T piece - part C
Right angle - part D
Quantity to order
per pole(1)
2
2
2
Reference
2619 1200
2629 1200(2)
2639 1200(2)
3 200
3 200
3 200
Connection - part A
T piece - part C
Right angle - part D
2
2
included
2629 1200(2)
2639 1200(2)
(1) Example for 3 pole device equipped upstream only: order 3 times the indicated quantities.
(2) Bolt set is provided with the accessories.
Fig. 3
acces_230_b_1_x_cat
148
225
acces_234_a_1_cat
30303030
svr_058_a_1_cat
Auxiliary contacts
Rating (A)
2 000 2 500
2 000 2 500
2 000 2 500
2 000 2 500
Piece
Connection - part A
Bolt set - part B
Bar - piece E
T piece - part C
Quantity to order
per pole(1)
2
2
1
1
Reference
2619 1200
2699 1200
4109 0250(2)
2629 1200(2)
3 200
3 200
3 200
3 200
Connection - part A
Bolt set - part B
Bar - piece E
T piece - part C
2
1
1
included
2699 1200
4109 0320(2)
2629 1200(2)
(1) Example for 3 pole device equipped upstream only: order 3 times the indicated quantities.
(2) Bolt set is provided with the accessories.
Use
Pre breaking and positions I and II
signalling: 1 or 2 NO/NC auxiliary contacts
in each position.
Low level auxiliary contacts: Consult us.
acces_065_a_1_cat
Rating (A)
125 1800
2000 3200
2000 3200
Contact(s)
1st/2nd
1st
2nd
Reference
4109 0021
included
4409 0022
Characteristics
Operating current Ie (A)
Rating (A)
125 3200
C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:281 Sec1:281
Nominal
current (A)
16
A - 250
-13VAC
12
400 VAC
AC-13
8
24 VDC
DC-13
14
48 VDC
DC-13
6
281
15/11/10 16:30:17
Terminal shrouds
Use
Protection against direct contact with
terminals or connecting parts.
acces_206_a_2_cat
Rating (A)
125 200
125 200
250 400
250 400
500 630
500 630
No. of
poles
3P
4P
3P
4P
3P
4P
Advantage
Perforations allowing remote
thermographic inspection without removal.
Position
top / bottom / front (I) / rear (II)
top / bottom / front (I) / rear (II)
top / bottom / front (I) / rear (II)
top / bottom / front (I) / rear (II)
top / bottom / front (I) / rear (II)
top / bottom / front (I) / rear (II)
Reference
2694 3014(1)(2)
2694 4014(1)(2)
2694 3021(1)(2)
2694 4021(1)(2)
2694 3051(1)(2)
2694 4051(1)(2)
(1) To shroud front switch top and bottom 4 references required for a SIRCOVER and 6
references for a SIRCOVER BY-PASS.
(2) To shroud front switch top and bottom 2 references required for a SIRCOVER and a
SIRCOVER BY-PASS.
Terminal screens
acces_207_a_2_cat
Use
Top or bottom protection against direct contact with terminals or connection parts.
Rating (A)
125 ... 200
125 ... 200
250 ... 400
250 ... 400
500 ... 630
500 ... 630
800 ... 1 250
800 ... 1 250
1 600 ... 1 800
1 600 ... 1 800
2 000 ... 3 200
No. of poles
3P
4P
3P
4P
3P
4P
3P
4P
3P
4P
3/4P
Position
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
Reference
1509 3012
1509 4012
1509 3025
1509 4025
1509 3063
1509 4063
1509 3080
1509 4080
1509 3160
1509 4160
included
acces_036_a_1_cat
Use
Safety isolating separation between the terminals, essential for use at 690 VAC
or in a polluted or dusty atmosphere.
The terminal shrouds also provide phase separation from 125 to 630 A.
282
C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:282 Sec1:282
Rating (A)
125 200
125 200
250 ... 400
250 ... 400
500 ... 630
500 ... 630
800 ... 3200
No. of poles
3P
4P
3P
4P
3P
4P
3/4P
Reference
2998 0033 (1)
2998 0034(1)
2998 0023(1)
2998 0024(1)
2998 0013(1)
2998 0014(1)
included
15/11/10 16:30:47
Fig. 2
Lockable in position I, 0 or II
Rating (A)
SIRCOVER
125 630
acces_061_a_1_x_cat
acces_001_a_1_x_cat
Fig. 1
Operation
external
Figure Reference
1
1423 2813
Fig. 3
Rating (A)
SIRCOVER
BY-PASS
125 200
800 1800
2000 3200
125 1800
2000 3200
Fig. 4
Rating (A)
SIRCOVER
BY-PASS
125 200
250 ... 630
800 1600
125 630
800 1600
Operation
direct
direct
direct
direct
external
external
Figure
2
3
3
3
4
4
Reference
4109 1006(1)
consult us
4109 1004(2)
4109 2007
1499 7701
2799 7002
acces_158_a_1_x_cat
acces_132_a_1_x_cat
Use
using padlock (not supplied), this device is factory mounted in the direct or
external operation handle and allows using up to 3 padlocks (Fig.1).
Locking:
- using lock (not supplied)
- using undervoltage coil.
The interlocking positions are either determined as standard or configured by the
user, removing pre-formed tabs.
Padlocking and locking can be combined.
Rating (A)
SIRCOVER
BY-PASS
800 1600
Operation
direct
Figure
3
Reference
consult us
Rating (A)
SIRCOVER
BY-PASS
125 630
800 1600
Operation
external
external
Figure
4
4
Reference
1499 7702
2799 7003
bd_03_04_01
C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:283 Sec1:283
283
15/11/10 16:30:52
125 to 500 A
Thermal current Ith (40C)
Rated insulation voltage Ui (V)
Rated impulse withstand voltage Uimp (kV)
125 A
160 A
200 A
250 A
400 A
500 A
800
8
800
8
800
8
800
8
800
8
1000
12
A/B(1)
125/125
125/125
125/125
125/125
125/125
125/125
63/80
125/125
125/125
125/125
125/125
125/125
125(3)/125(3)
125(3)/125(3)
125(4)/125(4)
A/B(1)
160/160
160/160
160/160
160/160
160/160
125/125
63/80
160/160
160/160
160/160
125/125
160/160
125(3)/125(3)
125(3)/125(3)
125(4)/125(4)
A/B(1)
200/200
200/200
160/160
200/200
160/160
125/125
63/80
200/200
160/160
160/160
125/125
200/200
125(3)/125(3)
125(3)/125(3)
125(4)/125(4)
A/B(1)
250/250
250/250
250/250
250/250
200/250
125/160
100/125
250/250
250/250
250/250
200/200
250/250
200(3)/200(3)
200(3)/200(3)
200(4)/200(4)
A/B(1)
400/400
400/400
250/250
400/400
200/250
125/160
100/125
400/400
250/250
250/250
200/200
400/400
200(3)/200(3)
200(3)/200(3)
200(4)/200(4)
A/B(1)
500/500
500/500
500/500
500/500
400/400
250/315
160/200
500/500
500/500
400/500
400/400
500/500
400(3)/400(3)
315(3)/400(3)
400(4)/400(4)
63/63
55/75
80/80
55/75
80/80
55/75
132/132
90/110
132/132
90/110
280/280
150/185
55
75
90
115
185
230
100
160
50
200
50
250
18
400
100
500
Overload capacity
Rated short-time withstand current 0.3 s. ICW (kA eff.)
Rated peak withstand current (kA peak) (6)
15
20
15
20
15
20
17
30
17
30
25
45
Connection
Minimum Cu cable section (mm2)
Minimum Cu busbar section (mm2)
Maximum Cu cable section (mm2)
Maximum Cu busbar width (mm)
Tightening torque min (Nm)
35
50
50
95
185
240
50
25
9
95
25
9
95
25
9
150
32
20
240
32
20
240
40
20
Mechanical characteristics
Durability (number of operating cycles)(7)
Weight of 3 P switch (kg)
Weight of 4 P switch (kg)
10 000
1.5
1.6
10 000
1.6
1.7
10 000
1.8
1.9
10 000
2
2.1
10 000
3
3.5
5 000
3.5
4
(1) Category with index A = frequent operation - Category with index B = infrequent operation.
(2) With terminal shrouds or phase barrier.
(3) 3-pole device with 2 pole in series for the "+" and 1 pole for the "-".
(4) 4-pole device with 2 pole in series by polarity.
(5) The power value is given for information only, the current values vary from one manufacturer to another.
(6) For a rated operational voltage Ue = 400 VAC.
(7) Increased endurances: please consult us.
284
C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:284 Sec1:284
15/11/10 16:30:53
630 to 3200 A
Thermal current Ith (40C)
Rated insulation voltage Ui (V)
Rated impulse withstand voltage Uimp (kV)
630 A
800 A
1250 A
1600 A
1800 A
2000 A
2500 A
3200 A
1000
12
1000
12
1000
12
1000
12
1000
12
1000
12
1000
12
1000
12
A/B(1)
630/630
630/630
500/500
630/630
500/500
315/315
160/200
630/630
630/630
500/500
500/500
630/630
500(3)/500(3)
500(3)/500(3)
500(4)/500(4)
A/B(1)
800/800
800/800
800/800
800/800
800/800
800/800
200/250
800/800
800/800
800/800
800/800
800/800
800(3)/800(3)
800(3)/800(3)
800(3)/800(3)
A/B(1)
1250/1250
1250/1250
1250/1250
1250/1250
800/800
800/800
200/250
1250/1250
1250/1250
1250/1250
1250/1250
1250/1250
1250(3) /1250(3)
1250(3)/1250(3)
1250(3)/1250(3)
A/B(1)
1600/1600
1600/1600
1250/1250
1600/1600
1000/1000
1000/1000
500/500
1600/1600
1250/1250
1250/1250
1250/1250
1600/1600
1250(3)/1250(3)
1250(3)/1250(3)
1250(3) /1250(3)
A/B(1)
1800/1800
1800/1800
1250/1250
1800/1800
1000/1000
1000/1000
500/500
1800/1800
1250/1250
1250/1250
1250/1250
1800/1800
1250(3) /1250(3)
1250(3)/1250(3)
1250(3)/1250(3)
A/B(1)
2000/2000
2000/2000
1600/1600
2000/2000
2000/2000
1000/1000
800/800
2000/2000
2000/2000
1250/1600
1250(3)/1250(3)
2000/2000
2000/2000
1250(3) /1250(3)
1000(3)/1000(3)
A/B(1)
2500/2500
2000/2500
1600/1600
2500/2500
2000/2500
1000/1000
800/800
2500/2500
2000/2500
1250/1600
1250(3)/1250(3)
2500/2500
2000/2000
1250(3) /1250(3)
1000(3)/ 1000(3)
A/B(1)
3200/3200
2500/3200
1600/1600
3200/3200
2000/2500
1000/1000
800/800
3200/3200
2000/2500
1250/1600
1250(3)/1250(3)
3200/3200
2000/2000
1250(3) /1250(3)
1000(3) /1000(3)
280/280
150/185
450/450
185/220
710/710
185/220
710/710
475/475
710/710
475/475
710/710
750/750
710/710
750/750
710/710
750/750
290
365
575
100
1250
100
2 x 800
100
2 x 800
100
2 x 1000
100
2 x 1250
Overload capacity
Rated short-time withstand current 0.3 s. ICW (kA eff.)
Rated peak withstand current (kA peak) (6)
25
45
50
55
65
80
100
110
100
110
100
110
100
110
110
120
Connection
Minimum Cu cable section (mm2)
Minimum Cu busbar section (mm2)
Maximum Cu cable section (mm2)
Maximum Cu busbar width (mm)
Tightening torque min (Nm)
2 x 150
2 x 30 x 5
2 x 300
50
20
2 x 185
2 x 40 x 5
2 x 300
63
2 X 60 X 5
4 X 185
63
20
2 x 80 x 5
6 x 185
100
40
2 x 80 x 5
6 x 185
100
40
3 x 100 x 5
4 x 100 x 5
4 x 100 x 5
125
40
125
40
125
40
Mechanical characteristics
Durability (number of operating cycles)(7)
Weight of 3 P switch (kg)
Weight of 4 P switch (kg)
5 000
3.5
4
3 000
17.5
21
3 000
22.5
27.5
4 000
34
42
4 000
34
42
3 000
50
60
3 000
50
60
3 000
50
60
(1) Category with index A = frequent operation - Category with index B = infrequent operation.
(2) With terminal shrouds or phase barrier.
(3) 3-pole device with 3 pole in series for the "+" and 1 pole for the "-".
(4) 4-pole device with 2 pole in series per polarity.
(5) The power value is given for information only, the current values vary from one manufacturer to another.
(6) For a rated operational voltage Ue = 400 VAC.
(7) Increased endurances: please consult us.
C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:285 Sec1:285
285
15/11/10 16:30:54
A
M
II
10
8.5
CA
350
125
CA
svr_072_i_1_x_cat
L1
AC
AA
BA
II
HA
H
T
T
J
E min.
Rating
(A)
Overall dimensions
A
A
3p.
4p. C
E min
125
160
200
250
400
500
630
800
1250
1600
1800
221
221
221
262
262
319
319
386
386
478
478
251
251
251
312
312
379
379
466
466
598
598
218
218
218
218
218
295
295
375
375
375
375
Terminal
shrouds
45
60
18
1. Terminal shrouds
2. Direct handle operation:
- 125 to 630 A: L1 = 140 mm,
- 800 to 1800 A: L1 = 210 mm.
AC
Switch body
J
H
HA 3p.
J
4p.
Switch mounting
M
M
3p.
4p.
N
X
3p.
X
4p.
Z1
AA
BA
AC
235
235
235
280
280
401
400
459
459
461
461
148
148
148
148
148
225
225
298
298
298
298
212
212
212
273
273
332
332
386.5
386.5
388.5
518.5
156
156
156
196
196
246
246
255
255
347
347
36
36
36
50
50
65
65
80
80
120
120
20
20
20
25
35
32
45
50
60
90
90
25
25
25
30
35
37
50
60.5
65
43.5
43.5
8.5
8.5
8.5
11
11
13
13
15
16x11
12.5x5
12.5x5
56
56
56
61
61
70.5
70.5
48
48
54
54
50
50
50
61
61
65.5
65.5
48
48
54
54
3,5
3,5
3,5
3,5
3,5
5
5
7
7
8
8
28
28
28
30
30
43
43
66.5
66.5
66.5
66.5
124
124
124
124
124
180
180
253.5
255.5
255.5
255.5
135
135
135
160
170
235
260
321
330
288
288
115
115
115
130
140
205
220
10
10
10
15
15
15
20
26.5
29.5
15
15
25
25
25
25
25
25
25
29
29
29
29
182
182
182
223
223
272
272
306.5
306.5
306.5
388.5
186
186
186
246
246
306
306
336
336
467
467
101
101
101
116
116
176
176
250
250
250
250
Connection
A
436.5
51.5
svr_128_c_1_x_cat
330
330
380
461
258
250
120
120
120
425
425
53.5
103
653
Rating (A)
Overall dimensions
A
3p.
A
4p.
Switch mounting
M
3p.
M
4p.
2000 3200
478
598
347
467
286
C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:286 Sec1:286
15/11/10 16:30:55
Z2
A
10
M
II
Z1
Y
CA
Z
8.5
II
CA
L1
AA
BA
AC
H
C
18
svr_070_i_1_x_cat
210
125
330
HA
45
103
E min.
61
Terminal
shrouds Switch body
Overall dimensions
A
A
Rating (A) 3+6p. 4+8p. C
E
min AC
125
160
200
250
400
500
630
800
1250
1600
320
320
320
298
298
417
417
550
550
550
243
243
243
243
243
362
362
479
479
479
221
221
221
262
262
319
319
386
386
478
251
251
251
312
312
379
379
466
466
598
313
313
313
313
313
432
432
560
560
560
235
235
235
280
280
401
400
459
459
461
Switch mounting
Connection
HA
J
J
M
3+6 p. 4+8 p. 3+6 p.
M
4+8 p. N
X
3+6p.
X
4+8p.
Z1
Z2
AA
BA
AC
25
25
25
25
25
25
25
29
29
29
182
182
182
223
223
272
272
306.5
306.5
388.5
186
186
186
246
246
306
306
335
335
467
36
36
36
50
50
65
65
80
80
120
20
20
20
25
35
32
45
50
60
90
25
25
25
30
35
37
50
60.5
65
43.5
8,5
8,5
8,5
11
11
13
13
15
16x11
12.5x5
56
56
56
61
61
70.5
70.5
48
48
54
50
50
50
61
61
65.5
65.5
48
48
54
3.5
3.5
3.5
3.5
3.5
5
5
7
7
8
28
28
28
30
30
43
43
66.5
66.5
66.5
124
124
124
124
124
180
180
253.5
253.5
253.5
219
219
219
219
219
317
317
439.5
439.5
439.5
135
135
135
160
170
235
260
321
320
288
115
115
115
130
140
205
220
10
10
10
10
15
15
20
26.5
29.25
15
212
212
212
273
273
332
332
386.5
386.5
518.5
156
156
156
196
196
246
246
255
255
347
101
101
101
116
116
176
176
250
250
250
Connection terminals
SIRCOVER and SIRCOVER BY-PASS 800 A
16 x 11
33
8.5
50
C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:287 Sec1:287
15.75
28.5
60
15.75
12.5
5
15
12.5
svr_098_a_1_x_cat
8.5
15 28.5
svr_077_a_1_x_cat
15
svr_078_b_1_x_cat
10 33
25 25
30
30
45
45
90
287
15/11/10 16:30:56
Front operation
Direction of operation
Door drilling
With lock
RONIS EL11AP
0
o
I+II
S2 type
20 20
26
37
4 5.5
47
2 6.5
28
37
37
47
47
79
14 14
73
.5
svr_138_a_1_gb_cat
D (1)
45
5
3.
45
45
26
14 14
24
II
1414
125
.5
28
90
90
78
With lock
CASTELL K
22
Handle type
20 20
20 20
Front operation
Door drilling
Direction of operation
0
or
I+II
With lock
RONIS EL11AP
20 20
26
4 7 (2)
1414
37
47
24
.5
26
14 14
73
45
5
3.
45
20 20
60
22
90
350
.5
2 6.5
37
47
II
D (1)
svr_139_a_1_gb_cat
28
37
4 5.5
90
28
78
With lock
CASTELL K
79
S4 type
14 14
Handle type
20 20
Front operation
Handle type
Direction of operation
Door drilling
With lock
CASTELL K
C type
50
50
II
96
28
4 6.5
svr_140_a_1_gb_cat
50
C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:288 Sec1:288
90
288
25
0
50
300
90
31
4 x 6.5
31
3 x 6.5
15/11/10 16:30:58
Front operation
Direction of operation
Door drilling
With lock
RONIS EL11AP
0
20 20
26
37
37
47
24
47
26
73
.5
5
3.
45
D (1)
45
svr_141_a_1_gb_cat
14 14
125
1414
37
45
.5
28
II
2 6.5
28
4 5.5
47
22
90
90
78
With lock
CASTELL K
79
S2 type
14 14
Handle type
20 20
20 20
Front operation
Handle type
Direction of operation
S3 type
Door drilling
With lock
RONIS EL11AP
90
90
With lock
CASTELL K
20 20
78
26
37
37
47
22
14 14
20 20
61
79
73
D (1)
45
.5
26
14 14
24
47
5
3.
45
svr_142_a_1_gb_cat
210
1414
37
.5
2 6.5
28
4 5.5
II
28
47
20 20
Front operation
Handle type
Direction of operation
Door drilling
With lock
CASTELL K
C type
50
50
II
96
28
4 6.5
50
25
0
50
300
90
svr_143_a_1_gb_cat
90
C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:289 Sec1:289
31
4 x 6.5
31
3 x 6.5
289
15/11/10 16:30:59
ANSI code 87
Type RMC-131D
4921240104G
Non-stabilised measurement
Application
Relay output
Measuring principle
Latch circuit
The contact can then be locked in its warning position,
even if the input currents return to normal (add L to
contact type in order specifications, if this is required).
DEIFA/S
RMC-131D
Timer function
When the set point has been exceeded, the associated
timer starts and will run as long as the fault condition
prevails.
The delay (3 ranges) does not depend on the exceeding
of the set point. If the fault disappears, the timer is
reset. When the timer expires, the contact is activated
and the associated red LED is lit.
Type RMC-131D
Settings and indication
Technical specifications
Meas. range (In):
0.3-0.4-0.5-0.6-0.8-1.0-1.3-1.5-2.02.5-3.0-4.0-5.0A AC
Adjusted range:
Frequency range:
40...45...65...70Hz.
Differential current:
0.04...0.4 x In.
4 x
20 x
80 x
Load:
Output:
1 maximum contact.
Contact type:
Contact B, contact C:
Normally energised (NE), or
normally de-energised (ND)
with or without latch circuit (L)
Relay contact:
Contact ratings:
250V-8A-2000VA (AC)
24V-8A-200W (DC)
3
(200 x 10 change-overs at resistive
load)
Contact voltage:
Hysteresis:
Response time:
<50 ms.
Temperature:
-25...70C (operating).
Temperature drift:
Set points:
max. 0.2% of full scale per 10C.
Galvanic separation:
57.7-63.5-100-110-127-200-220-230240-380-400-415-440-450-660-690V
AC 20% (max. 3.5VA)
In, continuously,
In for 10 s (max. 75A)
In for 1 s (max. 300A).
24-48-110-220V DC -25/+30%
(max. 2W).
Climate:
EMC:
To EN 50081-1/2, EN 50082-1/2,
SS4361503 (PL4) and IEC 255-3.
Connections:
Max. 4 mm (single-stranded).
Max. 2.5 mm (multi-stranded).
Materials:
Protection:
Type approval:
Setting of
Differential current
set point:
(440%) of ln
Time delay:
(0T1) in seconds
01/05/010 s
LED/relay
l> yellow LED is lit when the set
point has been exceeded, but the
contact not yet activated.
Contact is activated and red LED lit
after the timer has expired.
Order specifications
Type Measuring current (ln) Relay Time delay (T1)
Supply voltage
Example:
RMC-131D 5A AC NEL - 5 s 440V AC
MK203A
Microprocessor based numerical relay
Current measurement based on
fundamental frequency
Technical Data
RATINGS
: 5A
: 50 Hz
: < 0.3 VA at In
: 4 x In continuous
Rated current ( In )
Rated frequency
Burden
Thermal withstand
AUXILIARY SUPPLY
Model MK203A-240A
Model MK203A-110A
Supply frequency
VA rating
: 198 ~ 265 V AC
: 94 ~ 127V AC
: 50 Hz
: 3 VA typical
SETTING RANGES
Low-set ( I > )
: 2.0 A to 6.0 A
: 40% to 120%
Time multiplier ( TM ) : 0.05 to 1.0
High-set ( I >> )
: I > to 10 x I > or disable
High-set delay time (t >>) : Instantaneous
CONTACTS
Trip contact (R1)
: Manual reset type
Contact Arrangement : Change-over
Contact rating
: 5 A, 250 V AC ( cosJ = 1 )
: Silver alloy
Contact material
Expected electrical life : 100,000 operations at
rated current
Expected mechanical life: 5 x 106 operations
INDICATORS
Auxiliary supply
Pick-up
Trip
: Green indicator
: Red indicator
: Red indicator
PERFORMANCE
Adjustable accuracy : Less than 5%.
Repeatability
: Less than 0.5% of full scale.
MECHANICAL
Mounting
Front panel
: Panel mounting
: Standard DIN
96 mm x 96 mm
Approximate weight : 0.7 kg
ENVIRONMENTAL CONDITIONS
Temperature
Humidity
: -5C to +55C
: 56 days at 93% RH and
40C non-condensing
Features
MK 203A
NO
NORMAL INVERSE
NC COM
4
14
15
16
R1
10
11
12
13
L1
L2
L3
N
MK 203A
NO
AUX
NC COM
10
11
12
MK 202A
NO
NC COM
14
15
16
10
11
12
13
14
15
16
R1
R1
13
L1
L2
L3
N
96 mm
110 mm
100 mm
91.0 p 0.5 mm
Front
Side
Panel Cutout
Ordering Information
MODEL
DESCRIPTION
MK203A - 240A
MK203A - 110A
91.0 p 0.5 mm
CASE DIMENSIONS
96 mm
HLC
- min. tensile strength 500MPa
- steel galvanized to min. 5 microns
- Bolt steel grade 8.8
- steel galvanized to min. 5 microns
Basic loading data (for Single anchor) in concrete:HLC, HLC-H, HLC-EC/EO, HLC-L, HLC-SK, HLC-T
25 N/mm2
Anchor Size
6.5
10
12
16
20
Tensile NRk
kN
2.1
3.5
4.5
7.2
10.0
13.2
Shear VRk
kN
3.8
7.0
8.8
14.4
20.0
20.0
6.5
10
12
16
20
25 N/mm2
Anchor Size
Tensile NRd
kN
1.2
2.0
2.5
4.0
5.5
7.4
Shear VRd
kN
2.1
3.9
4.9
8.0
11.1
11.1
25 N/mm2
6.5
10
12
16
20
Tensile NRec
kN
0.8
1.4
1.8
2.8
4.0
5.2
Shear VRec
kN
1.5
2.8
3.5
5.7
7.9
7.9
Anchor Size
Page 1
Issue 2008
19 N/mm2
Anchor Size
Tensile NRec
kN
6.5
0.3
8
0.5
10
0.6
12
0.7
16
0.8
Shear VRec
kN
0.45
1.0
1.2
1.4
1.6
29 N/mm
Anchor Size
Tensile NRec
kN
6.5
0.4
8
0.5
10
0.6
12
0.8
16
0.8
Shear VRec
kN
0.65
1.0
1.2
1.6
1.6
1)
The technical data for the HLC sleeve anchors are reference loads for MZ 12 and KS 12. Due to the large variation of natural stone solid bricks,
on site anchor testing is recommended to validate technical data.
2)
For brick walls where anchor position in brick can not be determined, 100% anchor testing is recommended.
3)
The HLC anchor was installed and tested in center of solid bricks as shown. The HLC anchor was not tested in the mortar joint between solid
bricks or in hollow bricks, however a load reduction is expected.
Setting Details
Anchor position in concrete
5.5 cm
scr
11 cm
5.5 cm
5.5 cm
11 cm
5.5 cm
5.5 cm
24 cm
Page 2
Issue 2008
HLC-SK
Sw
d
20x150/95
20x115/60
20x80/25
16x140/90
16x100/50
16x60/10
12x100/60
12x75/35
12x55/15
10x100/65
10x80/45
10x60/25
10x50/15
10x40/5
8x85/55
8x70/40
8x55/25
8x40/10
6.5x60/40
6.5x40/20
Anchor Size
6.5x25/5
Setting details
M5
M6
M8
M10
M12
M16
mm
6.5 (1/4")
10
12
16
20
mm
30
40
50
65
75
85
mm
mm
mm
30 45 65 46 61 76 91 48 58
68 88 108 65 85
110
165
lc
mm
25 40 60 40 55 70 85 40 50
60 80 100 55 75
100
150
tfix
mm
5 20 40 10 25 40 55 5
25 45 65 15 35
60
10 50
95
Tinst
Nm
25
40
50
80
Tinst
Nm
2.5
13
20
25
Sw
10
13
19
24
Thread diameter
d0
h1
hef
HLC
df
HLCH
31
26
15
33
41
41
90 25 60
15
mm
17
mm
Clearance hole
mm
11
13
17
21
hmin
mm
60
70
80
100
100
120
ccr
mm
30
50
60
65
80
80
scr
Critical Spacing
mm
60
100
120
130
160
160
1)
When setting long anchors to achieve intermediate fixing length be advised of the base material thickness, use caution when drilling boreholes to
the maximum depth, to avoid back side blow out.
1)
For anchrors loaded in shear towards the edge the critiacl edge distance must be doubeled
Page 3
Issue 2008
12x55/15
10x130/95
10x105/65
10x85/45
10x45/5
8x90/55
8x75/40
8x60/25
6.5x85/60
6.5x65/40
Anchor Size
6.5x45/20
HLC-SK
Setting details
M5
M6
M8
M10
mm
6.5 (1/4")
10
12
mm
30
40
50
65
mm
mm
mm
45 65 85 60 75 90 45 85 105 130
80
tfix
mm
20 40 60 25 40 55 5 45 65
35
Tinst
Nm
25
40
Tinst
Nm
2.5
13
20
PZ 3
T 30
T 40
T 40
Thread diameter
d0
h1
hef
Setting Driver
,max
26
31
33
95
Installation equipment
Rotary hammer ( TE2, TE6, TE6A, TE7, TE 7A, TE16, TE 16-C, TE 16-M, TE 35 ), a drill ( see table above), a
hammer and a torque wrench
Setting operations
Page 4
Issue 2008