Professional Documents
Culture Documents
Airflow: Weatherization Assistance Program Indiana Field Guide
Airflow: Weatherization Assistance Program Indiana Field Guide
Airflow: Weatherization Assistance Program Indiana Field Guide
AIRFLOW
Weatherization Assistance Program Indiana Field Guide
Chapter 5 Airflow
5-1
AIRFLOW
STANDARD - AIRFLOW
Controlling airflow for Weatherization requires establishing a strategy that reduces infiltration, yet ensures safe, healthful and efficient operation of the building and the systems within the building.
Procedure - Airflow
Establish a site specific minimum ventilation rate (MVR) and express in CFM 50.
Airflow
Determine pre-weatherization airflow rates using Blower Door and express in CFM 50. If structure is below the MVR, determine if adding mechanical ventilation is appropriate. If structure is below the MVR, airsealing should only be completed where bulk moisture could be delivered to the attic. Perform site specific diagnostics. Perform Blower Door assisted, cost-effective air sealing. Do not airseal below the established MVR. Concentrate efforts on major air leakage such as attic leakage sites, duct systems, interstitial connections, and obvious large holes. Determine post-weatherization airflow rates. Conduct post inspection and detailed health and safety tests including DSTO. Perform client education as needed.
5-2
Airflow
2. .35 ACH (or .4 ACH) = House Volume (cu. ft.) x .35 = cu. ft. building volume aiflow standard per hour cu. ft. hour 60 = CFM Natural CFM Nat x N = CFM 50 3. 15 CFM per person occupant airflow standard = Bedrooms + 1 or Actual # of persons = Occupancy Occupancy x 15 CFM per person = CFM Nat CFM Nat x N = CFM 50 Use the larger of the above four as your airflow standard.
Chapter 5 Airflow
5-3
VENTILATION
STANDARD - VENTILATION
Building performance retrofit strategies may include a mechanical ventilation to protect the building and the occupants in the case of an excessively tight building. Ventilation strategies should protect the occupants health and safety while at the same time enabling optimization of building thermal performance. Adding ventilation shall not be a substitute for source control of pollutants - i.e. moisture, CO, etc.
Airflow
Size fan and select operating speeds that reflect infiltration and mechanical ventilation interaction. Choose a control appropriate for a specific building and client. Perform client education.
Exhaust Fans
Airflow
Sealed-Combustion Heater
Exhaust gases
Combustion air
Sealed-combustion heaters are less affected by depressurization and can reduce the need for ventilation.
Chapter 5 Airflow 5-5
Airflow
Occupants shall be instructed in the use and maintenance of installed ventilation equipment. Vented air must be exhausted totally outside of the building. Exhaust connects should be properly pitched to avoid condensate buildup. Exhaust connects should be insulated where passing through cold areas to avoid condensation. All intake and exhaust openings should be screened to prevent foreign objects from entering. Electrical wiring used to install ventilation equipment will comply fully with current electrical codes.
5-6
Airflow
Automatic cycling or continuous operation along with passive vents makes standard exhaust fans into a ventilation system.
Chapter 5 Airflow
5-7
Airflow
Determine if the occupants complain or show symptoms of building-related illnesses such as upper respiratory problems. If conventional (atmospheric) combustion appliances are in use in the building, perform worst case backdrafting test. (See Health and Safety Chapter) If combustion appliances are present in the living space, consider building walls to partition off a CAZ. Check for smokers living in the building. Encourage outdoor smoking or ventilation of designated smoking rooms.
5-8
Airflow
1. Auto exhaust, chemicals stored in garage. 2. Combustion appliance by-products. 3. Smoke, food odors, moisture. 4. Particulates from solid fuel. 5. Moisture; chemicals.
Chapter 5 Airflow
5-9
Airflow
Fire hazards jeopardize the building. Carbon monoxide levels exceed suggested action levels. Measured drafts of combustion appliances do not meet standards. (See Health & Safety Chapter) Unvented space heaters are in use. Infestations, vermin, or sanitary issues place occupant and crew workers health in danger. The building meets or is lower than the calculated MVR.
5 - 10
Airflow
Insect Infestation
Chapter 5 Airflow
5 - 11
MEASURING AIRFLOW
STANDARD - CFM 50 TEST
A single point blower door test will be conducted on all units at the original building analysis and at the post inspection to quantify airflow, as well as during the retrofit to determine the cost effectiveness of air sealing.
Airflow
Configure the unit in winter modewindows, exterior doors, vents closed, all air registers open. Conduct a building survey and determine the thermal boundary. Identify and repair large problem areas that would hamper blower door test (i.e. - missing window, hole in ceiling). Ensure that all combustion appliances are turned off. Turn off all exhaust systems. Pressure relieve any suspended ceilings. Open all interior doors within the thermal boundary of the house. Close all solid fuel appliance dampers. Select an appropriate exterior doorway and install blower door. Assure that children and pets remain clear of the fan operation area at all times. Perform blower door test. (Refer to Blower Door Manufacturers manual for specifics.)
5 - 12
Airflow
Chapter 5 Airflow
5 - 13
Blower door depressurization is the most common type of air leakage test for a home.
Airflow
Ensure negative
5 - 14
Airflow
Chapter 5 Airflow
5 - 15
Analog manometers measure house pressure and airflow during blower door pressurization.
Airflow
5 - 16
Airflow
Chapter 5 Airflow
5 - 17
Airflow
Around chimneys
Plumbing penetrations
Airflow
Recessed lights
Inspect attics for bypasses and airseal before insulating. Ensure proper clearance to combustible materials.
Chapter 5 Airflow
5 - 19
Airflow
5 - 20
Airflow
Poly encases fiberglass to restrict airflow. Foam around edges to finish sealing process. Wood, sheetrock, foam, metal are all alternative blocking materials to use.
Chapter 5 Airflow
5 - 21
Airflow
5 - 22
Airflow
Seal between sheet metal and joist Panned floor joists leak through the many cracks and seams within the framed cavity. They are best sealed on their interior surfaces with the sheet metal removed.
Chapter 5 Airflow
5 - 23
Airflow
5 - 24
Airflow
Insignificant Leak
Significant Leak
Chapter 5 Airflow 5 - 25
Airflow
5 - 26
Airflow
Duct leaks in mobile homes are easily located using diagnostic smoke in a pressurized environment.
Chapter 5 Airflow
5 - 27
Airflow
5 - 28
Airflow
Temperature should be taken out of direct line from the heat exchanger. This will minimize high readings due to radiant energy.
Chapter 5 Airflow
5 - 29
Airflow
5 - 30
Activate airhandler fan, measure change in pressure from base condition, record as dominant duct test. A positive change in pressure indicates more return leakage from the exterior, and a negative indicates relatively more supply leakage to the outside. This indicates incomplete duct sealing work, or an intentional opening such as a fresh air intake cut into the return. Close all interior doors, activate air handler fan, measure main body to outside pressure change from base condition, and record. Measure each room to main body pressure, record. Pressure balancing must be considered whenever there is a change in pressure greater than 2 Pascals with reference to the outside. Perform combustion appliance zone depressurization and worst case draft test after any modifications.
Airflow
Chapter 5 Airflow
5 - 31
Airflow
5 - 32
Pressurized Bedroom
Airflow
Large positive pressures in an individual room with a closed door and distribution fan running is caused by the inability of air to return to the central return grille.
Chapter 5 Airflow
5 - 33
Airflow
5 - 34
Airflow
-33
Pressure testing the basement zone tells the relative air tightness of the floor versus the foundation walls. ( P) x (A) x (1.06) = CFM when A = square inches of opening and P = pressure. 1.06 = constant.
Chapter 5 Airflow
5 - 35
Airflow
Results - no or low pressure difference means: the ceiling of the main body of the house is the more effective air barrier or the attic to outdoors is leakier than the attic to house or the leakage between the house and the attic is less than leakage from attic to outdoors. Results - high pressures (above 35 Pa) indicates that the attic roof is serving as the air barrier and that the leakage between the house and attic is greater than leakage between the attic and outdoors. Consideration - if you can approximate the size hole or collection of all holes from the outside to this zone in square inches, then applying P x A x 1.06 will indicate the relative leakage from this zone to the house.
5 - 36
Airflow
Measuring the pressure difference between the attic and outdoors during a blower door test helps evaluate the ceilings airtightness.
Chapter 5 Airflow
5 - 37
Airflow
Record pressures created in attic WRT outdoors. Results - If negative pressures within the attic increase from those noted in the attic WRT outdoors test, then bypasses from the basement to the attic are indicated. A modification of this test can indicate if side attics communicate.
5 - 38
Airflow
Using the attic hatch to add a hole to the ceiling during a blower door test helps estimate leakage area.
Chapter 5 Airflow
5 - 39
Airflow
5 - 40
Airflow
Many porch roofs do not have sheathing here. This area can hide a major conduit for air leakage.
Chapter 5 Airflow
5 - 41
AIRSEALING ECONOMICS
Cost Effective Airsealing - refers to the energy saved over the lifetime of the materials installed in relation to the cost of installing them. All of the previously mentioned air sealing procedures will most likely be performed in a high priority within our waiver audit protocol (furnace repair and efficiency, duct sealing or major air/bypass sealing) and have a high and long-lasting impact. However, additional air sealing may be beneficial if it is found to be cost effective. The last priority in our waiver audit protocol is Minor Air Sealing. It should be performed when appropriate and only if the measures installed are cost effective. FSSAs intention is that airsealing crews will proceed with Minor Air Sealing using the blower door both as a diagnostic tool and a device to measure the crews relative effectiveness.
Airflow
Use manometers to test attic and crawl/basement areas WRT main body to assess relative connections to those areas. Air seal the building in relatively small increments of time, retesting with the blower door. Continue until the MVR is reached, or you are no longer getting CFM reduction, or the cost of sealing exceeds your limit. Document what you are doing, the materials used and the justification for either continuing or stopping. Take a final CFM 50 reading. Always perform a Daily Safety Test Out on combustion appliances once finished air sealing.
Airflow
Chapter 5 Airflow
5 - 43
EVALUATION/POST INSPECTION
STANDARD - POST INSPECTION
All completed airsealing work shall be evaluated for its effectiveness and its impacts on the buildings operation as a system.
Airflow
3) Perform heating systems final inspection and record findings in inspectors column.
5 - 44
Discuss the importance of not using unvented appliances for space heating. Demonstrate procedures for performing a rudimentary draft test showing occupant how to identify spillage and CO indicators. Review manufacturers literature of equipment installed. Review maintenance schedules for mechanical systems. Discuss smoking issues within airsealed houses.
Airflow
Chapter 5 Airflow
5 - 45
Notes
Airflow
5 - 46