THP9045 Wiring Module

INSTALLATION INSTRUCTIONS
WIRESAVER
THERMOSTAT

FEATURES
Can be used when a common wire is required. Mounts easily on or near HVAC equipment.

Rc K C W-O/B Honeywell
THP9045A

INSTALLATION
1. 2. 3. The THP9045 Wiring Module can be equipment- or wall-mounted in any orientation or as dictated by the surroundings. Precise leveling of the THP9045 module is not required. Identify the four wires in the wall and connect to the R, C, W, and K terminals on the thermostat. Wire the K terminal on the thermostat to the K terminal on the THP9045 module. Wire the R and C terminals on the thermostat to the R (power) and C (common) terminals on the THP9045 module and equipment. Wire the W terminal from the thermostat to the W (heat relay) terminal on the HVAC equipment. Wire the Y and G terminals on the Module to the Y (Compressor Relay) and G (Fan Relay) terminals on the HVAC equipment.

Rc Y G C W-O/B

EQUIPMENT
M31301A

4. 5. 6. 7.

APPLICATION
The THP9045 Wiring Module is designed to be used with applicable thermostats in which a 24V common is required and there are not enough wires. The K terminal on the thermostat can be used to operate both the fan and compressor on a single wire, and the module is designed to receive the signal from the K terminal, split that signal and re-route it to operate the compressor, and/or fan for normal operation. Use with the following thermostats: THX9321R THX9321R5000 THX9321R1008 TH8320UP1003 T5060F7088

TERMINALS
R C Y G K 24V 24V Common Cooling relay Fan relay Communication

Place Bar Code Here

69-2065EFS-07

THP9045 WIRING MODULE

THX9321R SUBBASE
CONVENTIONAL O/B AUX/E Y Y2 G L K NOT USED W W2 Y Y2 G NOT USED K NOT USED HEAT PUMP NOT USED C Rc R U1 U1 U2 U2 NOT USED C Rc R U1 U1 U2 U2

WIRESAVER

Rc K C W-O/B Honeywell
THP9045A

Rc Y G C W-O/B

R Y G C W

FURNACE

M31302A

Fig. 1. Example wiring diagram for 1H/1C conventional application.

THX9321R SUBBASE
CONVENTIONAL O/B AUX/E Y Y2 G L K NOT USED W W2 Y Y2 G NOT USED K NOT USED HEAT PUMP NOT USED C Rc R U1 U1 U2 U2 NOT USED C Rc R U1 U1 U2 U2

WIRESAVER

Rc K C W-O/B Honeywell
THP9045A

Rc Y G C W-O/B

W2 R Y G C W

FURNACE

M31305A

Fig. 2. Example wiring diagram for a 2H/1C conventional application.

69-2065EFS07

THP9045 WIRING MODULE

THX9321R SUBBASE
CONVENTIONAL O/B AUX/E Y Y2 G L K NOT USED W W2 Y Y2 G NOT USED K NOT USED HEAT PUMP NOT USED C Rc R U1 U1 U2 U2 NOT USED C Rc R

WIRESAVER

Rc K C W-O/B Honeywell
THP9045A

Rc Y G C W-O/B
U1 U1 U2 U2

AIR HANDLER

R Y G

C O Y2 W2

M31306A

Fig. 3. Example wiring diagram for a 2H/2C conventional application.

THX9321R SUBBASE
CONVENTIONAL O/B AUX/E Y Y2 G L K NOT USED W W2 Y Y2 G NOT USED K NOT USED HEAT PUMP NOT USED C Rc NOT USED C Rc R U1 U1 U2 U2

WIRESAVER

Rc K C W-O/B Honeywell
THP9045A

R U1 U1 U2 U2

Rc Y G C W-O/B

AIR HANDLER

R Y G C

1 REMOVE R/Rc JUMPER

R
M31300A

HEATER

Fig. 4. Example wiring diagram for a 1H/1C system with 2 transformers.

69-2065EFS07

THP9045 WIRING MODULE

THX9321R SUBBASE
CONVENTIONAL O/B AUX/E Y Y2 G L K NOT USED W W2 Y Y2 G NOT USED K NOT USED HEAT PUMP NOT USED C Rc NOT USED C Rc R U1 U1 U2 U2

WIRESAVER

1 R
U1 U1 U2 U2

Rc K C W-O/B Honeywell
THP9045A

Rc Y G C W-O/B

1 E R Y G C O

1 MATCH THE WIRES FROM THE HEAT PUMP TO THE AIR HANDLER AS NORMAL.

AIR HANDLER

M31303A

Fig. 5. Example wiring diagram for a 2H/1C heat pump application.

THX9321R SUBBASE
CONVENTIONAL O/B AUX/E Y Y2 G L K NOT USED W W2 Y Y2 G NOT USED K NOT USED HEAT PUMP NOT USED C Rc NOT USED C Rc R U1 U1 U2 U2

WIRESAVER

Rc K C W-O/B Honeywell
THP9045A

R U1 U1 U2 U2

Rc Y G C W-O/B

1 R Y G C O Y2 E

AIR HANDLER
1
MATCH THE WIRES FROM THE HEAT PUMP TO THE AIR HANDLER AS NORMAL.

M31304A

Fig. 6. Example wiring diagram for a 3H/2C heat pump application.

Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limite 35 Dynamic Drive Toronto, Ontario M1V 4Z9 http://customer.honeywell.com
U.S. Registered Trademark 2010 Honeywell International Inc. 69-2065EFS07 M.S. Rev. 12-10 Printed in U.S.A.

Module de cblage THP9045

NOTICE D'INSTALLATION
PROTECTEUR DE FIL
THERMOSTAT

CARACTRISTIQUES :
Peut tre utilis lorsqu'un fil commun est requis. S'installe facilement sur le systme de CVCA ou proximit.

Rc K C W-O/B Honeywell
THP9045A

INSTALLATION
1. Le module THP9045 peut tre install sur le systme de CVCA ou sur un mur. Le sens de montage n'a pas d'importance et dpend l'emplacement. Il n'est pas ncessaire d'installer le module THP9045 de niveau. Identifier les quatre fils qui passent dans le mur et les raccorder aux bornes R, C, W et K du thermostat. Raccorder la borne K du thermostat la borne K du module THP9045. Raccorder les bornes R et C du thermostat aux bornes R (alimentation) et C (neutre) du module THP9045 et du systme. Raccorder la borne W du thermostat la borne W (relais de chauffage) sur le systme de CVCA. Raccorder les bornes Y et G du module aux bornes Y (relais du compresseur) et G (relais du ventilateur) sur le systme de CVCA.

Rc Y G C W-O/B

2.
QUIPEMENT
MF31301A

3. 4. 5. 6. 7.

APPLICATION
Le module de cblage THP9045 est conu pour tre utilis avec les thermostats compatibles dans lesquels un fil commun de 24 V est requis et lorsqu'il n'y a pas assez de fils. La borne K du thermostat peut servir faire fonctionner le ventilateur et le compresseur au moyen d'un seul fil. Le module, qui reoit le signal de la borne K, spare ce signal et le dirige pour faire fonctionner de faon normale le compresseur et le ventilateur. Ce module peut tre utilis avec les thermostats suivants : THX9321R THX9321R5000 THX9321R1008 TH8320UP1003 T5060F7088

BORNES
R C Y G K 24V 24V Commun Relais de refroidissement Relais de ventilateur Communication

MODULE DE CBLAGE THP9045

PLAQUE DE RACCORDEMENT THX9321R


CONVENTIONAL O/B AUX/E Y Y2 G L K NOT USED W W2 Y Y2 G NOT USED K NOT USED HEAT PUMP NOT USED C Rc R U1 U1 U2 U2 NOT USED C Rc R U1 U1 U2 U2

PROTECTEUR DE FIL

Rc K C W-O/B Honeywell
THP9045A

Rc Y G C W-O/B

R Y G C W

APPAREIL DE CHAUFFAGE
MF31302A

Fig. 1. Exemple de schma de cblage pour une application conventionnelle 1 tage de chauffage/1 tage de refroidissement (1H/1C).

PLAQUE DE RACCORDEMENT THX9321R


CONVENTIONAL O/B AUX/E Y Y2 G L K W W2 Y Y2 G

PROTECTEUR DE FIL

NOT USED
C Rc R U1 U1 U2 U2 HEAT PUMP

NOT USED
C Rc R U1 U1 U2 U2

Rc K C W-O/B Honeywell
THP9045A

Rc Y G C W-O/B

NOT USED
K

NOT USED

NOT USED

W2 R Y G C W

APPAREIL DE CHAUFFAGE
MF31305A

Fig. 2. Exemple de schma de cblage pour une application conventionnelle 2 tages de chauffage/1 tage de refroidissement (2H/1C).

69-2065EFS07

MODULE DE CBLAGE THP9045

PLAQUE DE RACCORDEMENT THX9321R


CONVENTIONAL O/B AUX/E Y Y2 G L K W W2 Y Y2 G

PROTECTEUR DE FIL

NOT USED
C Rc R U1 U1 U2 U2 HEAT PUMP

NOT USED
C

Rc K C W-O/B Honeywell
THP9045A

Rc R

Rc Y G C W-O/B
U1 U1 U2 U2

NOT USED
K

NOT USED

NOT USED

R Y G

C O Y2 W2

SECTION DE TRAITEMENT DAIR


MF31306A

Fig. 3. Exemple de schma de cblage pour une application conventionnelle 2 tages de chauffage/2 tages de refroidissement (2H/2C).

PLAQUE DE RACCORDEMENT THX9321R


CONVENTIONAL O/B AUX/E Y Y2 G L K W W2 Y Y2 G

PROTECTEUR DE FIL

NOT USED
C Rc

NOT USED
C Rc R U1 U1 U2 U2

Rc K C W-O/B Honeywell
THP9045A

R U1 U1 U2 U2

Rc Y G C W-O/B

NOT USED
K

NOT USED

NOT USED HEAT PUMP

SECTION DE TRAITEMENT DAIR

R Y G C

1 RETIRER LE CAVALIER R/Rc

R
MF31300A

CHAUFFAGE

Fig. 4. Exemple de schma de cblage pour un systme 1 tage de chauffage/1 tage de refroidissement avec 2 transformateurs (1H/1C).

69-2065EFS07

MODULE DE CBLAGE THP9045

PLAQUE DE RACCORDEMENT THX9321R


CONVENTIONAL O/B AUX/E Y Y2 G L K W W2 Y Y2 G

NOT USED
C Rc

NOT USED
C Rc R U1 U1 U2 U2

PROTECTEUR DE FIL

1 R
U1 U1 U2 U2 HEAT PUMP

Rc K C W-O/B Honeywell
THP9045A

NOT USED
K

Rc Y G C W-O/B

NOT USED

NOT USED

1 1 FAIRE CORRESPONDRE NORMALEMENT LES FILS DE LA


THERMOPOMPE LA SECTION DE TRAITEMENT DE LAIR.

SECTION DE TRAITEMENT DAIR

E R Y G C O

MF31303A

Fig. 5. Exemple de schma de cblage pour une application thermopompe 2 tages de chauffage/1 tage de refroidissement (2H/1C).

PLAQUE DE RACCORDEMENT THX9321R


CONVENTIONAL O/B AUX/E Y Y2 G L K W W2 Y Y2 G

PROTECTEUR DE FIL

NOT USED
C Rc

NOT USED
C

Rc K C W-O/B Honeywell
THP9045A

Rc R U1 U1 U2 U2

R U1 U1 U2 U2

Rc Y G C W-O/B

NOT USED
K

NOT USED

NOT USED
HEAT PUMP

1 R Y G C O Y2 E

SECTION DE TRAITEMENT DAIR


1
FAIRE CORRESPONDRE NORMALEMENT LES FILS DE LA THERMOPOMPE LA SECTION DE TRAITEMENT DE LAIR.
MF31304A

Fig. 6. Exemple de schma de cblage pour une application thermopompe 3 tages de chauffage/2 tages de refroidissement (3H/1C).

Solutions de rgulation et dautomatisation Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limite 35, Dynamic Drive Toronto (Ontario) M1V 4Z9 http://customer.honeywell.com
Marque de commerce dpose aux .-U. 2010 Honeywell International Inc. Tous droits rservs 69-2065EFS07 M.S. Rev. 12-10 Imprim aux tats-Unis

Mdulo de cableado THP9045

INSTRUCCIONES DE INSTALACIN
PROTECTOR DE CABLE
TERMOSTATO

CARACTERSTICAS
Puede utilizarse cuando se necesite un cable comn. Se monta fcilmente en o cerca de un equipo HVAC.

Rc K C W-O/B Honeywell
THP9045A

INSTALACIN
1. 2. El mdulo de cableado THP9045 puede montarse en equipo o en pared en cualquier orientacin o como lo permita el entorno. No es necesario nivelar de forma precisa el mdulo THP9045. Identifique los cuatro cables en la pared y conctelos a los terminales R, C, W, y K en el termostato. Cablee el terminal K en el termostato al terminal K en el mdulo THP9045. Cablee los terminales R y C en el termostato a los terminales R (energa) y C (comn) en el mdulo THP9045 y el equipo. Cablee el terminal W del termostato al terminal W (rel de calor) en el equipo HVAC. Cablee los terminales Y y G en el mdulo a los terminales Y (rel del compresor) y G (rel del ventilador) en el equipo HVAC.

Rc Y G C W-O/B

EQUIPO
MS31301A

3. 4. 5. 6. 7.

APLICACIN
El mdulo de cableado THP9045 est diseado para ser utilizado con los termostatos aplicables en los cuales se requiera un comn de 24V y no existan suficientes cables. El terminal K del termostato puede utilizarse para que opere tanto el ventilador como el compresor con un solo cable y el mdulo est diseado para recibir la seal del terminal K, dividir esa seal y redirigirla para que opere el compresor, y/o el ventilador de manera normal. Utilice con los siguientes termostatos: THX9321R THX9321R5000 THX9321R1008 TH8320UP1003 T5060F7088

TERMINALES
R C Y G K 24 V Comn de 24 V Rel de refrigeracin Rel del ventilador Comunicacin

MDULO DE CABLEADO THP9045

SUBBASE THX9321R
CONVENTIONAL O/B AUX/E Y Y2 G L K NOT USED W W2 Y Y2 G NOT USED K NOT USED HEAT PUMP NOT USED C Rc R U1 U1 U2 U2 NOT USED C Rc R U1 U1 U2 U2

PROTECTOR DE CABLE

Rc K C W-O/B Honeywell
THP9045A

Rc Y G C W-O/B

R Y G C W

SISTEMA DE CALEFACCIN
MS31302A

Fig. 1. Ejemplo del diagrama de cableado para la aplicacin convencional de 1 etapa de calefaccin/1 etapa de refrigeracin (1H/1C).

SUBBASE THX9321R
CONVENTIONAL O/B AUX/E Y Y2 G L K W W2 Y Y2 G

PROTECTOR DE CABLE
NOT USED
C Rc R U1 U1 U2 U2

NOT USED
C Rc R U1 U1 U2 U2 HEAT PUMP

Rc K C W-O/B Honeywell
THP9045A

Rc Y G C W-O/B

NOT USED
K

NOT USED

NOT USED

SISTEMA DE CALEFACCIN

W2 R Y G C W

MS31305A

Fig. 2. Ejemplo del diagrama de cableado para la aplicacin convencional de 2 etapas de calefaccin/1 etapa de refrigeracin (2H/1C).

69-2065EFS07

10

MDULO DE CABLEADO THP9045

SUBBASE THX9321R
CONVENTIONAL O/B AUX/E Y Y2 G L K W W2 Y Y2 G

PROTECTOR DE CABLE
NOT USED
C

NOT USED
C Rc R U1 U1 U2 U2 HEAT PUMP

Rc K C W-O/B Honeywell
THP9045A

Rc R

Rc Y G C W-O/B
U1 U1 U2 U2

NOT USED
K

NOT USED

NOT USED

R Y G

C O Y2 W2

CONTROLADOR DE AIRE
MS31306A

Fig. 3. Ejemplo del diagrama de cableado para la aplicacin convencional de 2 etapas de calefaccin/2 etapas de refrigeracin (2H/2C).

SUBBASE THX9321R
CONVENTIONAL O/B AUX/E Y Y2 G L K W W2 Y Y2 G

PROTECTOR DE CABLE

NOT USED
C Rc

NOT USED
C Rc R U1 U1 U2 U2

Rc K C W-O/B Honeywell
THP9045A

R U1 U1 U2 U2

Rc Y G C W-O/B

NOT USED
K

NOT USED

NOT USED
HEAT PUMP

CONTROLADOR DE AIRE

R Y G C

1 RETIRE EL PUENTE R/Rc

R
MS31300A

CALENTADOR

Fig. 4. Ejemplo del diagrama de cableado para un sistema de 1 etapa de calefaccin/1 etapa de refrigeracin (1H/1C) con 2 transformadores.

11

69-2065EFS07

MDULO DE CABLEADO THP9045

SUBBASE THX9321R
CONVENTIONAL O/B AUX/E Y Y2 G L K W W2 Y Y2 G

NOT USED
C Rc

NOT USED
C Rc R U1 U1 U2 U2

PROTECTOR DE CABLE

1 R
U1 U1 U2 U2 HEAT PUMP

Rc K C W-O/B Honeywell
THP9045A

NOT USED
K

Rc Y G C W-O/B

NOT USED

NOT USED

1 1 EMPALME LOS CABLES DE LA BOMBA DE CALOR CON LOS DEL


CONTROLADOR DE AIRE COMO LO HACE NORMALMENTE.

CONTROLADOR DE AIRE

E R Y G C O

MS31303A

Fig. 5. Ejemplo del diagrama de cableado para la aplicacin de una bomba de calor de 2 etapas de calefaccin/1 etapa de refrigeracin (2H/1C).

SUBBASE THX9321R
CONVENTIONAL O/B AUX/E Y Y2 G L K W W2 Y Y2 G

PROTECTOR DE CABLE
NOT USED
C

NOT USED
C Rc

Rc K C W-O/B Honeywell
THP9045A

Rc R U1 U1 U2 U2

R U1 U1 U2 U2

Rc Y G C W-O/B

NOT USED
K

NOT USED

NOT USED
HEAT PUMP

1 R Y G C O Y2 E

CONTROLADOR DE AIRE
1
EMPALME LOS CABLES DE LA BOMBA DE CALOR CON LOS DEL CONTROLADOR DE AIRE COMO LO HACE NORMALMENTE.
MS31304A

Fig. 6. Ejemplo del diagrama de cableado para la aplicacin de una bomba de calor de 3 etapas de calefaccin/2 etapas de refrigeracin (3H/2C).

Automatizacin y control desenlace Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limite 35, Dynamic Drive Toronto, Ontario M1V 4Z9 http://customer.honeywell.com
Marca Registrada en los EE. UU. 2010 Honeywell International Inc. todos Los Derechos Reservados 69-2065EFS07 M.S. Rev. 12-10 Impreso en EE. UU.

You might also like