Load
Rated Load Maximum Load under valve wide open (VWO) condition 600 MW 629.2 MW
Construction
Three cylinder reheat condensing turbine Single flow HP Turbine with 14 reaction stages Double flow IP Turbine with 10 reaction stages per flow Double flow LP Turbine (2 no.s) with (5 drum + 3 module) stages per flow 2 Main Stop and Control valves (HP casing mounted) 2 Reheat Stop and Control Valves (Floating) 1 Swing Check Valve in cold reheat line Type : H30-100-2 Type : M30-63 Type : N30-4x6.3
Type : EV 320-1 Type : IV 560 DN-800 Make : BHEL, Trichy Make: CCI Switzerland
2 LP Bypass Stop and Control Valves with actuators & HPSU (High pressure EHA based) Extraction Swing Check Valves Extraction 1 Extraction 2 : No valve : 2 Swing Check Valve with actuator and 2 Swing Check Valve without actuator : 2 Swing Check Valve with actuator and 2 Swing Check Valve without actuator
DN 600 Make : BHEL, Trichy DN 500 Make : BHEL, Trichy DN 500 Make : BHEL, Trichy DN 500 Make : BHEL, Trichy DN 400 Make : BHEL, Trichy
Extraction 3
Extraction 5
: 1 Swing Check Valve with actuator and 1 Swing Check Valve without actuator : No valve
Extraction 6
Extraction 7 : 1 swing check valve with actuator and 1 swing check valve without actuator
BHEL, Hardwar
6.1-0100-99/1
Speed
Rated speed Speed limitation in load and station operation Max. Speed, no time limitation Min. Speed, no time limitation Permissible for maximum 2 hours during the life of LP blading Speed below Speed above Speed exclusion range at operation without load * Standard over speed trip setting 51.5 c/s 47.5 c/s 47.5 c/s 51.5 to 60 c/s 7 to 47.5 c/s Max. 55.5 c/s 50.0 c/s
* This speed range should be passed through in one smooth operation to avoid endangering the
blades due to resonance
Steam Pressures
Rated Initial Steam Before 1 HP drum stage HP cylinder exhaust IP cylinder stop valve inlet Extraction 7 Extraction 6 Extraction 5 Extraction 4 Extraction 3 Extraction 2 Extraction 1 LP cylinder exhaust
st
Unit ata ata ata ata ata ata ata ata ata ata ata ata
170.0 158.6 42.9 38.7 65.8 42.9 19.2 7.6 2.56 0.967 0.392 0.1033
178.5 171.8 49.4 44.8 73.6 49.4 22.6 9.15 3.12 1.21 0.49 0.31
These values correspond to 600 MW load with 3 % make-up and 0.1033 ata back pressure with all heaters in service and rated steam conditions. The safety valves must be set so that short time values are not exceeded. Long time operation: Upper limit value, permissible without time limit. Short time operation: Permissible momentary value. The aggregate duration of such swings must not exceed 12 hours in any one year All pressures are absolute pressures
BHEL, Hardwar
6.1-0100-99/2
Axial shift
Alarm Trip 0.5 mm 1.0 mm
Direction of rotation
Anti clock wise when viewed from Front Pedestal towards the Generator
BHEL, Hardwar
6.1-0100-99/3