Standard Certification by the Structural Engineer for Periodic Inspection of Buildings

In accordance with Section 28(6) of the Building Control Act (the Act) and Regulations 4 and 5 of The Building Control (Inspection of Buildings) Regulations (the Regulations), I,Er.Dr. Ho. Kok. Koh, the Structural Engineer appointed by the building owner under section 28(3) of the Act have personally conducted an inspection of the condition and structure of the building and hereby submit the report of the results of my inspection. I certify that the inspection was carried out and the report was prepared by me in accordance with the provisions of the Act and the Regulations.

__________________________ Structural Engineer For Periodic Inspection of Buildings (Signature and Stamp)

05/11/2012 Date

1, QUEENSWAY, #03-02, QUEENSWAY SHOPPING CENTRE, SINGAPORE 149053, TEL: 64754266 TEL: 64723228

VISUAL INSPECTION CERTIFICATION (for Non-Structural or Minor Structural Defects) The Building Control Act (Cap 29) [Section 28]
Commissioner of Building Control Building and Construction Authority 5 Maxwell Road #02-00 Tower Block, MND Complex Singapore 069110 INSTRUCTIONS Please use black ink to complete the form (estimated
time required is 10 minutes).

* Delete where not applicable + Tick where appropriate

Building Address

33 CHIN BEE CRESCENT SINGAPORE 619901 N/A

Name of Building (if applicable) :

As required under Section 28 of The Building Control Act (Cap 29), I, Er._Dr.Ho Kok Koh, have carried out a visual inspection of the above building from 5 October to (dates).

I hereby certify that the following were visible to me during my inspection: a) non-structural defects + + b) no remedial work is required remedial works are required

minor structural defects + + remedial work is required remedial and monitoring works are required

In support of the above, I submit my report on the visual inspection of the above building, duly prepared and signed as required under the Act.

______________________________________ Structural Engineer's Stamp & Signature

05/11/2012 Date

cc * Building Owner/Management Corporation

SF_ESID_SIS/SF-D3 [Ver 2.1_Mar_2000]

VI2012/4876

SM2012/09/1865

VISUAL INSPECTION REPORT

ON

BUILDING AT 33 CHIN BEE CRESCENT SINGAPORE 619901

For

OWNER :

Mr. Yoyce Yee Lai Poh AMOS INTERNATIONAL (S) PTE LTD No. 33, Chin Bee Crescent, Singapore 619901 Tel : +65 6262 2323 Fax : +65 6282 2323 BY

ENGINEER :

M/S Building Engineering Consultants 1 Queensway, # 03-02 Queensway Shopping Centre Singapore 149053 Tel : 64754266 Fax: 64723228

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 3 TEL:64754266/64723228

Content Page
Items 1. Certificate by Professional Engineer 2. Form D3 3. Cover Page 4. Content Page 5. Report 6. List of Defects 7. Location Plan 8. Architectural plan 9. Structural Plan 10. Photographic Survey 11. Annex A 12. Certificate by Professional Engineer PAGE 1 2 3 4 5 9 11 13 22 44 80 82

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 4 TEL:64754266/64723228

VISUAL INSPECTION REPORT ON BUILDING AT NO. 33 CHIN BEE CRESCENT, SINGAPORE 619901
(SECTION 28 OF THE BUILDING CONTROL ACT 1989)

Date Your Ref Our Ref

: 05/10/2012 : SM2012/09/1865 : VI2012/4876

1.0GeneralInformationoftheBuilding:
Name of the Building : NIL

Address of the Building:

No. 33 Chin Bee Crescent, Singapore 619901

Description of Building:

The existing building is a two storey office building and ware house.

2.0StructuralSystemoftheBuilding:
The two storeys Office building and warehouse was built with a combination of reinforcement concrete (RC) and steel structure. The building rests on RC foundation with TANA piles and pad footings. The 1st storey floor uses RC suspended slab, the 2nd floor RC slab is support on RC beams and columns. The roofs were built with steel rafters and are supported to the columns. The staircase from the ground floor to the 2nd storey is RC and steel structure.

2.1Presenceofcriticalstructuresandstructureswithout redundancies:
There is no slender column, transfer beam, long span structure or cable structure located on the available plans as well as visual inspection of the office building and slender columns are observed at warehouse area.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 5 TEL:64754266/64723228

3.0DiaryandScopeoftheVisualInspection
We had generally surveyed the building and taken necessary photographs during the inspection. The inspection was carried out on 05/10/2012.

4.0SurveyofLoadingontheBuildingStructure:
The existing loading condition was not excessive for its usage. As this building had been designed for the above usage, it is therefore compatible with the intended purpose of the structure.

5.0SurveyofAdditionorAlterationWorkstoBuildingStructure:
From our visual survey inspection and referring to the available attached plans form, there is addition or alteration to the main building whereby the loading conditions, do not show any sign of structural defects at time of our visual inspection.

6.0SurveyofSignsofStructuralDefects,Damages,Distress, Deformation,orDeterioration:
We observed several sin of structural defects, damages, distress, cracks in the above building. Please refer the list of defects for restoration on page 9 and 10.

6.1GroundBoundaryConditions:
The exiting driveway is generally in good condition. No ground settlement noticeable at the time of inspection.

6.2Faade:
The facade and the outward appearance of the above-mentioned building are generally in good appearance and condition. No sign of structural distress observed.

6.3StructuralElements:
During the inspection, there were some structural defects found on the beams and slabs structure (minor defects). Please refer to the photographs taken on page.

6.4Recommendationfortermitetreatment:
No sign of termite infestation observed at time of our visual inspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 6 TEL:64754266/64723228

7.0Surveyonexposuretoaggressiveenvironment:
There is no presence of column immersed in water or structural elements exposure to aggressive chemicals to the said buildings.

8.0Surveyofretainingwallandslopeprotectionstructure:
There is no retaining wall to the existing buildings.

9.0Methodsforcrackrepairs
All cracks recorded for minor defects are to be stored with non-shrink and non-metallic cementitious grout as follow: a. To provide struts and temporary supports on the existing slabs, beams, columns and walls around the affected area. b. To provide formwork to the affected area if found necessary. c. To remove plaster, concrete and defective bricks (ie. Stained and spalled members) by manual hacking and/or hand electric chisel and clean all loose or any foreign materials. d. Exposed rusty reinforcement, if any, shall be wire brushed to remove the rust and scales and if found necessary additional rebars may be added for strengthening. e. To apply two coats of Zinc-rich anti-rust coating to exposed reinforcement. f. To apply a layer of BONDER to the exposed surfaces.

g. To make good all the exposed surfaces with non-shrink non-metallic cementitious grout. .10.0OthersurveyorCheckCarriedOut

There are no heavy false ceilings found in these building.

11.0Conclusions
The loading conditions were as designed for the building. There is addition or alteration (A & A) work carried out to the buildings on which the loading conditions do not shown any sign of structural defects. The inspected area of the buildings is representative of the overall structural soundness of the buildings.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 7 TEL:64754266/64723228

There are some structural defects found on the beam and slab (Minor defects) and also crack on brick wall( non-structural). Please refer to the photographs taken on page and list of defects for restoration on page 20, 27, and 28. All the key structural elements which had been inspected did not show any sign of distress at the time of building inspection. Hence the building does not require full structural investigation and the Engineer is of the opinion that it is fit for occupancy at the time of inspection. Remedying the visile defects is necessary as highlighted in our comments and illustrated by photographs attached in this report. This includes any other defects in hidden and covered areas of the building which require restoration and rectification in order that the structural stability and integrity of the building to be preserved and maintained at all time. Continuous maintenance of the building to be carried out by the client / owner at all time. In some areas, there is no proper access to open and inspect the roof members and connection. However, as per our visual inspection, roof members and connection do not show any damages or defects during our inspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 8 TEL:64754266/64723228


ITEMS


LOCATION


DEFECTS


CAUSE OF DEFECTS


REMARKS

REMEDIAL WORKS

RC SLAB AT SOFFIT OF 2nd STOREY (ABOVE 1st STOREY CONFERENCE ROOM)

PLASTERING CRACK (MINOR STRUCTURAL DEFECTS)

POSSIBLY DUE TO INSUFFICIENT CONCRETE COVER CAUSING CORROSION OF STEEL REINFORCEMENT

TO BE RESTORED BY THE CONDITIONS AND METHODS FOR CRACK REPAIRS AS PER ITEM 9.0 PAGE 7 OF THE REPORT

PLEASE REFER TO THE PHOTOGRAPHS ON PAGE 47

BRICK WALL AT REAR SIDE OF 1ST STOREY AND WAREHOUSE AREA

PLASTERING CRACKS (NONSTRUCTURAL DEFECTS)

POSSIBLY DUE TO WEAR AND TEAR (NON STRUCTURAL)

TO BE RESTORED BY THE CONDITIONS AND METHODS FOR CRACK REPAIRS AS PER ITEM 9.0 OF PAGE 7 OF THE REPORT TO BE RESTORED BY THE CONDITIONS AND METHODS FOR CRACK REPAIRS AS PER ITEM 9.0 PAGE 7 OF THE REPORT

PLEASE REFER TO THE PHOTOGRAPH ON PAGE 60 AND 67

RC BEAM AT 2Nd STOREY (REAR SIDE OF THE BUILDING)

PLASTERING CRACK (MINOR STRUCTURAL DEFECTS)

POSSIBLY DUE TO INSUFFICIENT CONCRETE COVER CAUSING CORROSION OF STEEL REINFORCEMENT

PLEASE REFER TO THE PHOTOGRAPHS ON PAGE 61

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 TEL:64754266/64723228


POSSIBLY DUE TO INSUFFICIENT CONCRETE COVER CAUSING CORROSION OF STEEL REINFORCEMENT POSSIBLY DUE TO INSUFFICIENT CONCRETE COVER CAUSING CORROSION OF STEEL REINFORCEMENT

RC BEAM (TIE BEAM) AT WARE HOUSE

PLASTERING CRACK (MINOR STRUCTURAL DEFECTS)

TO BE RESTORED BY THE CONDITIONS AND METHODS FOR CRACK REPAIRS AS PER ITEM 9.0 PAGE 7 OF THE REPORT TO BE RESTORED BY THE CONDITIONS AND METHODS FOR CRACK REPAIRS AS PER ITEM 9.0 PAGE 7 OF THE REPORT

PLEASE REFER TO THE PHOTOGRAPHS ON PAGE 68

RC BEAM (TIE BEAM) AT WARE HOUSE

PLASTERING CRACK (MINOR STRUCTURAL DEFECTS)

PLEASE REFER TO THE PHOTOGRAPHS ON PAGE 77 AND 78

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 TEL:64754266/64723228

10

Location plan

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 11 TEL:64754266/64723228

Architectural plans

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 13 TEL:64754266/64723228

Structural plans

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 22 TEL:64754266/64723228

Photographic survey

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 44 TEL:64754266/64723228

Figure1:Outerfacadeofthebuilding.Generallyingoodconditionattimeofourvisualinspection.

Figure2:Outercantileverroofinfrontofthebuildings.Generallyingoodconditionattimeofour visualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 45 TEL:64754266/64723228

Figure3:Entrancefalseceiling.Generallyingoodconditionattimeofourvisualinspection.

Figure4:Soffitof2ndstoreyfloorslabandbeamabovewalkway.Generallyingoodcondition.Nosign ofstructuraldefectsorcracksobservedattimeofourvisualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 46 TEL:64754266/64723228

Figure5:2ndstoreyBeamsandcolumnsabovewalkway.Generallyingoodcondition.Nosignof structuraldefectsorcracksobservedattimeofourvisualinspection.

Figure6:Soffit2ndfloorslababove1ststoreyconferenceroom.Signofcracksobservedattimeofour visualinspection(minorStructuraldefects).

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 47 TEL:64754266/64723228

Figure7:Falseceilingabove1ststoreyconferenceroom.Generallyingoodconditionattimeofour visualinspection.

Figure8:Falseceiling,columnandbrickwallat2ndstoreyconferenceroom.Generallyingood conditionattimeofourvisualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 48 TEL:64754266/64723228

Figure9:Falseceilingandportionwallat2ndstoreybathroomarea.Generallyingoodconditionat timeofourvisualinspection.

Figure10:Floorslabandbrickwallat2ndstoreybathroomarea.Generallyingoodconditionattime ofourvisualinspection

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 49 TEL:64754266/64723228

Figure11:Floorslabat2ndstorey.Generallyingoodconditionattimeofourvisualinspection

Figure12:2ndstoreyFloorslabandcolumn.Generallyingoodcondition.Nosignofstructuraldefects orcracksobservedattimeofourvisualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 50 TEL:64754266/64723228

Figure13:Falseceilingabove2ndstoreyofficearea.Generallyingoodconditionattimeofourvisual inspection.

Figure14:FalseceilingandFloorslabat2ndstoreystorearea.Generallyingoodcondition.Nosignof structuraldefectsorcracksobservedattimeofourvisualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 51 TEL:64754266/64723228

Figure15:Brickwallat2ndstoreyfloorstorearea.Generallyingoodconditionattimeofourvisual inspection.

Figure16:Floorslabandfalseceilingat2ndstoreyfloorstorearea.Generallyingoodconditionat timeofourvisualinspection

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 52 TEL:64754266/64723228

Figure17:Falseceilingabove2ndstoreyofficearea.Generallyingoodconditionattimeofourvisual inspection.

Figure18:Columnsandfloorarea2ndstoreyofficearea.Generallyingoodcondition.Nosignof structuraldefectsorcracksobservedattimeofourvisualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 53 TEL:64754266/64723228

Figure19:Floorareaat2ndstoreyofficearea.Generallyingoodcondition.Nosignofstructural defectsorcracksobservedattimeofourvisualinspection.

Figure20:Waterproofingandsteelmembersabove2ndstoreyoffice.Generallyingoodconditionat timeofourvisualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 54 TEL:64754266/64723228

Figure21:Steeltrussabove2ndstoreyofficearea.Generallyingoodcondition.Nosignofexcessive deflectionobservedattimeofourvisualinspection.

Figure22:Columnsandbeamsat2ndstorey.Generallyingoodcondition.Nosignofstructural defectsorcracksobservedattimeofourvisualinspection. 1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 55 TEL:64754266/64723228

Figure23:Brickwallat2ndstoreystore.Generallyingoodconditionattimeofourvisualinspection.

Figure24:Rightsideofviewthebuilding.Generallyingoodconditionattimeofourvisualinspection

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 56 TEL:64754266/64723228

Figure25:Columns,beamsandslabsat1ststorey(belowofficearea).Generallyingoodcondition. Nosignofstructuraldefectsorcracksobservedattimeofourvisualinspection.

Figure26:Columns,beamsandslabsat1ststorey(belowofficearea).Generallyingoodconditionat timeofourvisualinspection 1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 57 TEL:64754266/64723228

Figure27:Soffitof2ndstorey(belowofficearea).Generallyingoodcondition.Nosignofstructural defectsorcracksobservedattimeofourvisualinspection.

Figure28:1ststoreyFloorarea.Generallyingoodcondition.Nosignofstructuraldefectsorcracks observedattimeofourvisualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 58 TEL:64754266/64723228

Figure29:1ststoreyFloorslab,columnsandbeam.Generallyingoodcondition.Nosignof structuraldefectsorcracksobservedattimeofourvisualinspection.

Figure30:Rearsideviewofthebuildingsgenerallyingoodconditionattimeofourvisualinspection

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 59 TEL:64754266/64723228

Figure31:Brickwallatrearsideofthebuilding.Signofcracksobservedattimeofourvisual inspection(nonstructuraldefects).

Figure32:Brickwallatrearsideofthebuilding.Signofcracksobservedattimeofourvisual inspection(nonstructuraldefects). 1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 60 TEL:64754266/64723228

Figure33:Cantileverroofatrearsideofthebuilding.Generallyingoodcondition.Nosignof excessivedeflectionobservedattimeofourvisualinspection.

Figure34:Slabandbeamat2ndstoreylevel(rearsideofthebuilding).Signofcracksobservedat timeofourvisualinspection(minorstructuraldefects).Remedialworksarerequired.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 61 TEL:64754266/64723228

Figure35:Slab,beamandcolumnat2ndstoreylevel(rearsideofthebuilding).Generallyingood condition.Nosignofstructuraldefectsorcracksobservedattimeofourvisualinspection.

Figure36:Steelstaircaseinfrontofthebuilding.Generallyingoodcondition.Nosignofexcessive deflectionobservedattimeofourvisualinspection. 1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 62 TEL:64754266/64723228

Figure37:Steelstaircaselanding.Generallyingoodcondition.Nosignofexcessivedeflection observedattimeofourvisualinspection.

Figure38:Connectionofsteelstaircase.Generallyingoodconditionattimeofourvisualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 63 TEL:64754266/64723228

Figure39:Steelstaircase.Generallyingoodcondition.Nosignofexcessivedeflectionobservedat timeofourvisualinspection.

Figure40:Mainstaircasetoofficearea.Generallyingoodcondition.Nosignofexcessivedeflection observedattimeofourvisualinspection. 1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 64 TEL:64754266/64723228

Figure41:Soffitofmainstaircase.Generallyingoodcondition.Nosignofexcessivedeflection observedattimeofourvisualinspection.

Figure42:Staircaseatrearsideofthebuilding.Generallyingoodcondition.Nosignofexcessive deflectionobservedattimeofourvisualinspection. 1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 65 TEL:64754266/64723228

Figure43:Soffitofstaircaseatrearsidethebuildings.Generallyingoodcondition.Nosignof excessivedeflectionobservedattimeofourvisualinspection.However,paintdiscoloration observed.

Figure44:SteelroofaboveWarehousestore.Generallyingoodcondition.Nosignofexcessive deflectionobservedattimeofourvisualinspection. 1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 66 TEL:64754266/64723228

Figure45:ColumnandbeamatWarehousestore.Generallyingoodcondition.Nosignofstructural defectsorcracksobservedattimeofourvisualinspection.

Figure46:Column,brickwallandbeamatWarehousestore.Generallyingoodcondition.Signof cracksobservedatbrickwallattimeofourvisualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 67 TEL:64754266/64723228

Figure47:BeamaboveWarehousestore.SignofcracksobservedatBeamattimeourvisual inspection(structuraldefects).Remedialworksarerequired.

Figure48:FloorslabatWarehousestore.Generallyingoodcondition.Nosignofstructuraldefects orcracksobservedattimeofourvisualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 68 TEL:64754266/64723228

Figure49:FalseceilingandbeamaboveWarehousestore.Generallyingoodconditionattimeof ourvisualinspection

Figure50:Cantileversteelroof,brickwall,beamandcolumninfrontofWarehousestore.Generally ingoodcondition.Nosignofstructuraldefectsorcracksobservedattimeofourvisualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 69 TEL:64754266/64723228

Figure51:FalseceilingaboveWarehousestoreoffice.Generallyingoodconditionattimeofour visualinspection

Figure52:RoofaboveWarehousestoreoffice.Generallyingoodconditionattimeofourvisual inspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 70 TEL:64754266/64723228

Figure53:SteelroofaboveWarehousestore.Generallyingoodcondition.Nosignofexcessive deflectionobservedattimeofourvisualinspection.

Figure54:slabs,ColumnsandbeamsatWarehousestore.Generallyingoodcondition.Nosignof structuraldefectsorcracksobservedattimeofourvisualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 71 TEL:64754266/64723228

Figure55:Slababovewarehousestore.Generallyingoodcondition.Nosignofexcessivedeflection orcracksobservedattimeofourvisualinspection.However,paintdiscolorationobserved.

Figure56:FloorandcolumnsatWarehousestore.Generallyingoodcondition.Nosignofstructural defectsorcracksobservedattimeofourvisualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 72 TEL:64754266/64723228

Figure57:Beams,column,brickwallandslabatWarehousestore.Generallyingoodcondition.No signofstructuraldefectsorcracksobservedattimeofourvisualinspection.

Figure58:FloorslabandsteelplatformofWarehousestore.Generallyingoodcondition.Nosignof excessivedeflectionordistressobservedattimeofourvisualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 73 TEL:64754266/64723228

Figure59:Timberandsteelplatform(mezzaninefloor)atWarehousestore.Generallyingood condition.Nosignofexcessivedeflectionordistressobservedattimeofourvisualinspection.

Figure60:Steelplatformconnectioninsidewarehouse.Generallyingoodconditionattimeofour visualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 74 TEL:64754266/64723228

Figure61:Mezzanineflooratwarehouse.Generallyingoodcondition.Nosignofexcessive deflectionordistressobservedattimeofourvisualinspection.

Figure62:steelStaircasetomezzaninefloorofWarehousestore.Generallyingoodcondition.No signofexcessivedeflectionordistressobservedattimeofourvisualinspection.

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 75 TEL:64754266/64723228

Figure63:SteelroofandcolumnatWarehousestore.Generallyingoodcondition.Nosignof excessivedeflectionordistressandstructuraldefectsorcracksobservedattimeofourvisual inspection.

Figure64:SlendercolumnandtiebeamatWarehousestore.Generallyingoodcondition.Nosignof structuraldefectsorcracksobservedattimeofourvisualinspection. 1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 76 TEL:64754266/64723228

Figure65:TiebeamatWarehousestore.Generallyingoodcondition.Nosignofstructuraldefectsor cracksobservedattimeofourvisualinspection.

Figure66:TiebeamatWarehousestore.Signofcracksobservedattimeofourvisualinspection (minorstructural).

1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 77 TEL:64754266/64723228

Figure67:TiebeamatWarehousestore.Signofcracksobservedattimeofourvisualinspection (minorstructural).

Figure68:StaircasetoMezzaninefloorofWarehousestore.Generallyingoodconditionattimeof ourvisualinspection. 1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 78 TEL:64754266/64723228

Figure69:StaircasetoMezzaninefloorofWarehousestore.Generallyingoodconditionattimeof ourvisualinspection.

Figure70:Boundarycondition.Nosignofdifferentialsettlementobservedattimeofourvisual inspectiontime. 1QUEENSWAY,#0302QUEENSWAYSHOPPINGCENTRE,SINGAPORE149053 79 TEL:64754266/64723228

ANNEX A CHECKLIST1 FOR PERIODIC STRUCTURAL INSPECTION OF EXISTING

31 CLUB STREET SINGAPORE 069468 BUILDING AT_________________________ __________________________________

I declare that I have addressed in my visual inspection report all the checklist items as ticked2 below. 1. Structural plans and details. a) Reference to structural layout plans b) Description of foundation system c) Description of structural system (including storey height) d) Any flat slab system (to state location)

2. Presence of critical structures and structures without redundancies (eg. transfer girders, small/ narrow/ slender columns3, cantilever structures, long span structures, cable structures, timber structures, etc)

3. Loading: a) Compatibility of existing usage with the design loading b) Deviation from intended use or supporting higher design imposed load as recommended in BS 6399 (to recommend design check by a PE and display of signage for allowable imposed loading) c) Signs of overloading (to show affected locations on plan) d) Recommended remedial actions to be taken

4. Addition and Alteration works (A&A): a) Presence of A&A (to show locations on plan) b) Impact of A&A on the building structure 5. Signs of structural defects and deterioration: a) Building tilt/ settlement b) Structural deformation c) Major structural defects (e.g. structural cracks, decayed timber member)
1

This checklist is to be included in the inspection report. All checklist items are to be ticked and addressed in inspection report. 3 Supplementary Checklist for Critical Columns in Residential Buildings built before 1 Jan 1989 to be included where applicable
2

CHECKLIST FOR PERIODIC STRUCTURAL INSPECTION

i Page 80

d) Minor structural defects


e) Non-structural defects f) Recommended remedial actions to be taken

6. Termite Attack: a) Need for inspection by anti-termite specialist b) Need for termite treatment by anti-termite specialist 7. Exposure to aggressive environment: a) Column immersed in water (eg. ground floor water tank, sea water, lakes, etc) b) Aggressive chemical which may accelerate the deterioration of elements, particularly in industrial buildings 8. Retaining walls and slope protection structures: a) Defects of retaining wall and other slope protection structures (e.g. cracks, tilt, displacement, etc.) b) Signs of undesirable condition surrounding retaining wall (e.g. tension cracks in soil, weephole chokage, presence of big trees nearby, inadequate surface drainage etc.) 9. Safety Barriers (i.e. parapets & railings): a) Any defects b) Any continuous handrail for full glass barriers 10. Record of previous strengthening works done 11. Standard Certification on first and last page of report structural

__________________________
Structural Engineer For Periodic Inspection of Buildings (Signature and Stamp)

_________________
Date

CHECKLIST FOR PERIODIC STRUCTURAL INSPECTION

ii Page 81

Standard Certification by the Structural Engineer for Periodic Inspection of Buildings


In accordance with Section 28(6) of the Building Control Act (the Act) and Regulations 4 and 5 of The Building Control (Inspection of Buildings) Regulations (the Regulations), I,Er.Dr. Ho. Kok. Koh, the Structural Engineer appointed by the building owner under section 28(3) of the Act have personally conducted an inspection of the condition and structure of the building and hereby submit the report of the results of my inspection. I certify that the inspection was carried out and the report was prepared by me in accordance with the provisions of the Act and the Regulations.

__________________________ Structural Engineer For Periodic Inspection of Buildings (Signature and Stamp)

05/11/2012 Date

1, QUEENSWAY, #03-02, QUEENSWAY SHOPPING CENTRE, SINGAPORE 149053, TEL: 64754266 TEL: 64723228