Dale Power Solutions plc

Erskine E+00 Series UPS - Three Phase 20 to 80kvA


Dale Power Solutions plc reserves the right to make changes in specification without notice or liability. All information is subject to Dale Power Solutions plc own data & is considered accurate at time of publishing.

Dale Power Solutions plc
Salter Road, Eastfield Industrial Estate, Scarborough, North Yorkshire, YO11 3DU, UK
Telephone: +44 (0) 1723 583511
Email: info@dalepowersolutions.com
Website: www.dalepowersolutions.com S5264EU06rev1

Features
High frequency & double conversion on-line technology
Fully digitized microprocessor control
Double conversion or ECO mode of operation
Wide input voltage range
LCD display
Cold start
Parallel capacity (maximum of 4 units)
Advanced battery management
Automatic battery charge in UPS off mode
Lightning & surge protection
Short circuit and overload protection
Fan speed auto control when loads varies
EMI/RFI noise filter
Smart RS232 communication with monitoring software
External battery
Optional battery temperature compensation.
Optional SNMP Card slot

Common Specifications
Voltage Range 184V AC to 276V AC Line-Neutral
Phase 3 Phase 4 Wire & Earth
Frequency 45Hz to 65Hz
Input
Power factor > 0.99

Voltage 220/230/240V AC Line-Neutral (user adjustable)
Phase 3 Phase 4 Wire & earth
Frequency 50/60Hz (user adjustable)
THD (linear load) < 1%
THD (non-linear mode) < 5%
Wave form Sine wave
Overload Capacity 110%: 60 mins, 125%: 10 mins, 150%: 1 min
Crest factor 3:1 (max)
Power Factor 0.8
Short circuit protection Yes
Output
Transfer time 0 ms

Battery External Configurable 32/34/36/38/40 X 12V monoblocks (192V/204V/216V/228V/240V nominal)

Operating altitude 1000m at rated power An (-1% for each 100m over 1000m) max 4000m
Operate Temperature 0C to 40C
Storage Temperature -25C to +55C
Environment
Relative humidity 95%

Communication Standard: RS232, Optional: SNMP

LCD Screen Display

Measurements: Input & output voltage/frequency, battery voltage, load power & kVA, UPS temperature
Operation mode: i.e. Online, On Battery, Bypass

Operation mode Double conversion or ECO mode operation (user selectable)

LED Indication Mimic of UPS operation

Noise Level <56dBA

Safety & EMC CE Marked to 2006/95/EC & 2004/108/EC Tested to EN62040-1-1:2003 & EN62040-2:2006

Standard Accessories Control software, Data lead, & User manuals


Specifications

Output Battery Environment Weights & Dimensions Model Part
Number
Output
kVA
Ratings
kW Efficiency
(full load)
DC Voltage
(Volts)
Noise (dBA) Weight (kg)
Net/Gross
Unit (mm)
(H x W x D)
E420 20 16 92% 384 - 480 < 56 186 / 226 1200 x 600 x 730
E430 30 24 92% 384 - 480 < 56 192 / 232 1200 x 600 x 730
E440 40 32 92% 384 - 480 < 56 203 / 243 1200 x 600 x 730
E460 60 48 93% 384 - 480 < 56 280 / 328 1200 x 600 x 730
E480 80 60 93% 384 - 480 < 56 289 / 357 1200 x 600 x 730