Customer :

Peerless Pump Company 2005 Dr. M. L. King Jr. St., Indianapolis, IN 46202 Vincent L. Runkle Phone 317-924-7262 Fax 317-924-7333 Contact : Project : Quote No. : Type: Pump Model: Nom. Speed: Impeller Dia.: Curve No.: Market : VQ111105C 8196 - ANSI Standard End Suction Peerless - 2x3-13 LTP 8196 3580 RPM, 60 Hz Electric 10.09 inch 8196-032 Process Page No : 3 Phone : Date : Item : Impeller No.: Fluid: Temperature: Viscosity: Sp. Gravity: Your Ref. :

FARECO S.A. Tarata 294, Piso 7 Miraflores Lima Peru

011-511-444-9808 Fax : 011-511-444-1473 Friday, November 11, 2005 Fire Service Pump Water 68 F 1.007 cSt 1.000

D1-13.00 inch, D2-11.00 inch, D3-9.00 inch

Duty Flow

320 US gpm 427 ft 10.09 inch 57.3 hp 11.7 ft 62.1 % 87.7 hp 457.4 ft Hyd InstPeerless Std

90 800 Head - ft 600


D1

Duty Head Imp. Diameter

80 60 50 40 30
D3

Efficiency - %

70

Power Required NPSH Required Efficiency Power end of curve Closed Valve Head Tolerance

400 200

20 10

NPSH - ft

60 40 20
Comments
Performance curve represents typical performance. See Standard Hydraulic Performance document in the selective printing area of RAPID for testing tolerances & contractual guarantees.

Power - hp

150 100 50 200


Flow (US gpm) 112.9 178.4 243.9 309.4 374.9 440.3 505.8 571.3 636.8 Head (ft) 455.5 455.5 451.7 442.0 425.5 402.7 375.4 346.6 320.8

400 600 Flow - US gpm


Efficiency (%) 38.6 50.5 57.4 61.6 64.0 65.0 64.4 62.3 58.8

800
Power Required (hp) 33.7 40.7 48.5 56.1 62.9 68.9 74.4 80.3 87.7

1,000
NPSH Required (ft) 12.7 9.0 8.5 11.0 16.3 24.2 34.5 46.8

Peerless Pump Company - RAPID v8.06 - 5th October 2005.

Customer :

Peerless Pump Company 2005 Dr. M. L. King Jr. St., Indianapolis, IN 46202 Vincent L. Runkle Phone 317-924-7262 Fax 317-924-7333 Contact : Project : Quote No. : VQ111105C Page No : 4 Phone : Date :

FARECO S.A. Tarata 294, Piso 7 Miraflores Lima Peru

011-511-444-9808 Fax : 011-511-444-1473 Friday, November 11, 2005

Item: Model :

Fire Service Pump Peerless - 2x3-13 LTP 8196

Flow (US gpm) 320 Liquid Water

Head (ft) 427 Temp. (F) 68

Eff. (%) 62.1 Sp. Gravity 1.000

Power (hp) 57.27 Visc. (cSt) 1.007

Speed (RPM) 3580 Dia. (inch) 10.09

Technical Information:

Technical Information: 8196 Pump Model ANSI Designation Minimum Casing Thickness Inches Corrosion Allowance Inches Max Diameter Solids Inches Max Liquid Temp without cooling Deg F Max Liquid Temp with cooling Deg F Casing Drain Size Inches Shaft Diameter at Impeller Inches Shaft Sleeve Dia in Stuffing Box Inches Shaft Dia in Stuffing Box Inches Sleeve Type Shaft Dia in Stuffing Box Inches Optional Solid Type Shaft Diameter at Coupling Inches Standard Stuffing Box Bore Inches Standard Stuffing Box Depth Inches Stuffing Box Nearest Obstruction Inches Stuffing Box Packing Size Inches Stuffing Box Lantern Ring Width Inches Stuffing Box Number of Rings Inboard Bearing Radial Single Row Outboard Bearing Double Row Bearing Span Inches Shaft Overhang Inches 2x3-13 LTP B73.1 0.56 0.125 0.38 350 500 0.375 1.2 2.125 1.875 2.125 1.875 2.875 2.625 3 3/8" x 3/8" 0.625 5 311-S Duplex 7310 6.875 8.375

Peerless Pump Company - RAPID v8.06 - 5th October 2005.

7.50 CI ANSI BASE NO 264 19.25 7.50

Weights: Pump 672 lb Mtr., Base, Cplg. 1702 lb 2714 lb Total

61.50 1.00 DIA 4 HOLES

1.25 4.50 2X3-13 LTP 8196

CONDUIT BOX (APPROX LOCATION) 31.31 365TS 3.75

23.50 4.00

2 INCH DISCHARGE 3 INCH SUCTION 11.50

18.50 14.63 4.00 64.00 CPLG GUARD NOTES: 1. UNIT INSTALLATION & FINAL CPLG ALIGNMENT MUST BE IN ACCORDANCE TO BULLETIN 2880549. 2. CUSTOMER MUST FILL BASE WITH GROUT ALLOWING .75 TO 1.50 INCH OF GROUT BETWEEN FOUNDATION AND BOTTOM OF BASE. 3. SEE BARE PUMP DRAWING FOR PUMP DIMENSIONAL DETAILS. *MAXIMUM DIMENS IONS, MAY BE LESS WITH DIFFERENT MAKE MOTORS OR ENCLOSURES.
Dimensions in (inch) Project : Customer: Item No.: Quote No. : Pump Model: FARECO S.A. Fire Service Pump VQ111105C Peerless - 2x3-13 LTP 8196 Capacity: Total Head: Pump Speed: Impeller Dia.: Power: 320 (US gpm) 427 (ft) 3580 (RPM) 10.09 (inch) 100 (hp) Frame/Model: Elec. Spec.: Service Factor: Rotation: Enclosure/Type: ODP 365TS 3 Ph. 230/460 V. 60 Hz 1.15 Peerless Pump Company 2005 Dr. M. L. King Jr. St., Indianapolis, IN 46202 Vincent L. Runkle Phone 317-924-7262 Date : Page No : Friday, November 11, 2005 5

10.00 4.63

SEE NOTE 2

Peerless Pump Company - RAPID v8.06 - 5th October 2005.

Page No : 6

Peerless Pump Company - Indianapolis, IN 46207-7026 ELECTRIC MOTOR DRIVER Performance and Data Sheet Manufacturer Motor Hp Catalog No. Type Synch Rpm Motor Frame Low Voltage High Voltage Volts Phase Hertz Motor Type NEMA Design Enclosure Class Insulation Service Factor Type Starting Type Motor Efficiency Construction Full Load Rpm Full Load Efficiency % Full Load Power Factor % Low Voltage Full Load Amps High Voltage Full Load Amps Low Voltage Locked Rotor Amps High Voltage Locked Rotor Amps Maximum Altitude in Feet Rotation Facing Opposite Shaft End 3 60 SCI B ODP F 1.15 WYE-DELTA EPACT Cl Frame/CI End Shields 3565 93.6 89 226.2 113.1 1450 725 3300 Clockwise US 100 D100E1ES FR 3600 365TS 230 460

The abov e data are not certified being extracted from manufacturer's published catalog data sheets.

Peerless Pump Company - RAPID v8.06 - 5th October 2005.

Customer :

Peerless Pump Company 2005 Dr. M. L. King Jr. St., Indianapolis, IN 46202 Vincent L. Runkle Phone 317-924-7262 Fax 317-924-7333 Contact : Project : Quote No. : Type: Pump Model: Nom. Speed: Impeller Dia.: Curve No.: Market : VQ111105C Page No : 8 Phone : Date : Item : Impeller No.: Fluid: Temperature: Viscosity: Sp. Gravity: Your Ref. :

FARECO S.A. Tarata 294, Piso 7 Miraflores Lima Peru

011-511-444-9808 Fax : 011-511-444-1473 Friday, November 11, 2005 Jockey Pump 412 Water 68 F 1.007 cSt 1.000

J, TMU, CDL3, EVMU - Vertical Close Coupled Diffuser Peerless - EVMU4-12 3481 RPM, 60 Hz Electric 4.00 inch EMVU4-12 Water

D1-4.00 inch, D2-4.00 inch

Duty Flow

16 US gpm 460 ft 4 inch 3.9 hp 4.9 ft 48.8 % 4.9 hp 559.5 ft Hyd InstPeerless Std

90 600 Head - ft 80 60 400


D1

Duty Head Imp. Dia.

Efficiency - %

70 50 40 30 20 10

Power Required NPSH Required Efficiency Peak Power Closed Valve Head Tolerance

200

D2

NPSH - ft

10 5
Comments
Performance curve represents typical performance. See Standard Hydraulic Performance document in the selective printing area of RAPID for testing tolerances & contractual guarantees.

Power - hp

4 3 2 1 0
Flow (US gpm) 7.5 11.1 14.8 18.5 22.1 25.8 29.5 33.1 36.8

10
Head (ft) 528.9 511.3 492.3 470.9 445.6 414.8 377.3 332.2 279.9

20 Flow - US gpm
Efficiency (%) 37.0 43.4 48.5 53.1 56.6 58.5 58.2 56.5 55.1

30
Power Required (hp) 2.7 3.3 3.8 4.1 4.4 4.6 4.8 4.9 4.7

40
NPSH Required (ft) 4.6 4.7 4.8 5.2 5.9 7.0 8.6 10.9 13.9

Peerless Pump Company - RAPID v8.06 - 5th October 2005.

Customer :

Peerless Pump Company 2005 Dr. M. L. King Jr. St., Indianapolis, IN 46202 Vincent L. Runkle Phone 317-924-7262 Fax 317-924-7333 Contact : Project : Quote No. : VQ111105C Page No : 9 Phone : Date :

FARECO S.A. Tarata 294, Piso 7 Miraflores Lima Peru

011-511-444-9808 Fax : 011-511-444-1473 Friday, November 11, 2005

Item: Model :

Jockey Pump Peerless - EVMU4-12

Flow (US gpm) 16 Liquid Water

Head (ft) 460 Temp. (F) 68

Eff. (%) 48.8 Sp. Gravity 1.000

Power (hp) 3.92 Visc. (cSt) 1.007

Speed (RPM) 3481 Dia. (inch) 4.00

Technical Information:

Technical Information: EVMU4-12 Pump Model Number of Pump Stages Impeller Dia A Inch Impeller Number A Impeller Quantity A Impeller Dia B Inch Impeller Number B Impeller Quantity B Maximum Working Pressure Mech Seal 0-180F. Maximum Working Pressure Mech Seal 181-225F. Maximum Working Pressure Mech Seal 226-250F. Maximum Working Pressure Packed 0-230F. Shaft Diameter Inch Maximum Pump Rpm Casing Drain NPT Stuffing Box Vent NPT Impeller Eye Area Sq In Sphere Size Inch Suction Connection Discharge Connection Minimum Flow USGpm 1-1/4 300 Lb Flg 1-1/4 300 Lb Flg 6.7 3600 360 360 360 0 Ebara EVMU4-12 12

Peerless Pump Company - RAPID v8.06 - 5th October 2005.

No of Stgs

12

Pump-Motor Total Wt Lbs. 270 lb 16.00 MAX

3.94

23.16

7.09 1-1/4 INCH x 300 LB ANSI FLG SUCTION AND DISCHARGE 0.80 0.72

2.95

8.27

0.47

4 HOLES

5.88 9.84

Dimensions in (inch) Project : Customer: Item No.: Quote No. : Pump Model: FARECO S.A. Jockey Pump VQ111105C Peerless - EVMU4-12 Capacity: Total Head: Pump Speed: Impeller Dia.: Power: 16 (US gpm) 460 (ft) 3481 (RPM) 4.00 (inch) 5 (hp) Frame/Model: Elec. Spec.: Service Factor: Rotation: 184TCV 3 Ph. 230/460 V. 60 Hz 1.15 Clockwise Peerless Pump Company 2005 Dr. M. L. King Jr. St., Indianapolis, IN 46202 Vincent L. Runkle Phone 317-924-7262 Date : Page No : Friday, November 11, 2005 10

Enclosure/Type: ODP

Peerless Pump Company - RAPID v8.06 - 5th October 2005.

Customer :

Peerless Pump Company 2005 Dr. M. L. King Jr. St., Indianapolis, IN 46202 Vincent L. Runkle Phone 317-924-7262 Fax 317-924-7333 Contact : Project : Quote No. : Type: Pump Model: Nom. Speed: Impeller Dia.: Curve No.: Market : VQ111105C 8196 - ANSI Standard End Suction Peerless - 1.5x3-10 MTP 8196 3571 RPM, 60 Hz Electric 8.36 inch 8196-021 Process Page No : 13 Phone : Date : Item : Impeller No.: Fluid: Temperature: Viscosity: Sp. Gravity: Your Ref. :

FARECO S.A. Tarata 294, Piso 7 Miraflores Lima Peru

011-511-444-9808 Fax : 011-511-444-1473 Friday, November 11, 2005 Booster Pumps Water 68 F 1.007 cSt 1.000

D1-10.00 inch, D2-8.00 inch, D3-6.00 inch

Duty Flow

111 US gpm 302 ft 8.36 inch 19.2 hp 5.9 ft 45.5 % 33.6 hp 328.7 ft Hyd InstPeerless Std

90 400 Head - ft 300


D1

Duty Head Imp. Diameter

80 60 50 40 30 20 10 Efficiency - % 70

Power Required NPSH Required Efficiency Power end of curve Closed Valve Head Tolerance

200 100

D3

NPSH - ft

15 10 5
Comments
Performance curve represents typical performance. See Standard Hydraulic Performance document in the selective printing area of RAPID for testing tolerances & contractual guarantees.

Power - hp

50 40 30 20 10 100
Flow (US gpm) 57.3 91.9 126.4 160.9 195.5 230.0 264.6 299.1 333.7 Head (ft) 321.3 315.1 307.4 297.7 284.6 266.4 240.8 205.0 155.6

200 300 Flow - US gpm


Efficiency (%) 29.7 40.9 48.5 53.4 56.1 56.4 54.2 48.8 39.0

400
Power Required (hp) 15.7 17.9 20.2 22.6 25.1 27.4 29.7 31.7 33.6

500
NPSH Required (ft) 6.0 6.0 6.5 7.6 8.9 10.7 12.6

Peerless Pump Company - RAPID v8.06 - 5th October 2005.

Customer :

Peerless Pump Company 2005 Dr. M. L. King Jr. St., Indianapolis, IN 46202 Vincent L. Runkle Phone 317-924-7262 Fax 317-924-7333 Contact : Project : Quote No. : VQ111105C Page No : 14 Phone : Date :

FARECO S.A. Tarata 294, Piso 7 Miraflores Lima Peru

011-511-444-9808 Fax : 011-511-444-1473 Friday, November 11, 2005

Item: Model :

Booster Pumps Peerless - 1.5x3-10 MTP 8196

Flow (US gpm) 111 Liquid Water

Head (ft) 302 Temp. (F) 68

Eff. (%) 45.5 Sp. Gravity 1.000

Power (hp) 19.18 Visc. (cSt) 1.007

Speed (RPM) 3571 Dia. (inch) 8.36

Technical Information:

Peerless Pump Company - RAPID v8.06 - 5th October 2005.

Customer :

Peerless Pump Company 2005 Dr. M. L. King Jr. St., Indianapolis, IN 46202 Vincent L. Runkle Phone 317-924-7262 Fax 317-924-7333 Contact : Project : Quote No. : VQ111105C Page No : 15 Phone : Date :

FARECO S.A. Tarata 294, Piso 7 Miraflores Lima Peru

011-511-444-9808 Fax : 011-511-444-1473 Friday, November 11, 2005

Technical Information: 8196 Pump Model ANSI Designation Minimum Casing Thickness Inches Corrosion Allowance Inches Max Diameter Solids Inches Max Liquid Temp without cooling Deg F Max Liquid Temp with cooling Deg F Casing Drain Size Inches Shaft Diameter at Impeller Inches Shaft Sleeve Dia in Stuffing Box Inches Shaft Dia in Stuffing Box Inches Sleeve Type Shaft Dia in Stuffing Box Inches Optional Solid Type Shaft Diameter at Coupling Inches Standard Stuffing Box Bore Inches Standard Stuffing Box Depth Inches Stuffing Box Nearest Obstruction Inches Stuffing Box Packing Size Inches Stuffing Box Lantern Ring Width Inches Stuffing Box Number of Rings Inboard Bearing Radial Single Row Outboard Bearing Double Row Bearing Span Inches Shaft Overhang Inches 1.5x3-10 MTP B73.1 0.5 0.125 0.22 350 500 0.375 1 1.75 1.5 1.75 1.125 2.5 2.625 3 3/8" x 3/8" 0.625 5 309-S 5309 6.25 8.375

Peerless Pump Company - RAPID v8.06 - 5th October 2005.

7.50 CI ANSI BASE NO 258 18.25 7.50

Weights: Pump 1020 lb Mtr., Base, Cplg. 2063 lb 3482.8 lb Total

55.50 1.00 DIA 4 HOLES

1.25 4.50 1.5X3-10 MTP 8196

CONDUIT BOX (APPROX LOCATION) 26.06 284TS 3.75

23.50 4.00

1.5 INCH DISCHARGE 3 INCH SUCTION 8.50

14.75 12.88 4.00 58.00 CPLG GUARD NOTES: 1. UNIT INSTALLATION & FINAL CPLG ALIGNMENT MUST BE IN ACCORDANCE TO BULLETIN 2880549. 2. CUSTOMER MUST FILL BASE WITH GROUT ALLOWING .75 TO 1.50 INCH OF GROUT BETWEEN FOUNDATION AND BOTTOM OF BASE. 3. SEE BARE PUMP DRAWING FOR PUMP DIMENSIONAL DETAILS. *MAXIMUM DIMENS IONS, MAY BE LESS WITH DIFFERENT MAKE MOTORS OR ENCLOSURES.
Dimensions in (inch) Project : Customer: Item No.: Quote No. : Pump Model: FARECO S.A. Booster Pumps VQ111105C Peerless - 1.5x3-10 MTP 8196 Capacity: Total Head: Pump Speed: Impeller Dia.: Power: 111 (US gpm) 302 (ft) 3571 (RPM) 8.36 (inch) 30 (hp) Frame/Model: Elec. Spec.: Service Factor: Rotation: Enclosure/Type: ODP 284TS 3 Ph. 230/460 V. 60 Hz 1.15 Peerless Pump Company 2005 Dr. M. L. King Jr. St., Indianapolis, IN 46202 Vincent L. Runkle Phone 317-924-7262 Date : Page No : Friday, November 11, 2005 16

8.25 4.63

SEE NOTE 2

Peerless Pump Company - RAPID v8.06 - 5th October 2005.

Page No : 17

Peerless Pump Company - Indianapolis, IN 46207-7026 ELECTRIC MOTOR DRIVER Performance and Data Sheet Manufacturer Motor Hp Catalog No. Type Synch Rpm Motor Frame Low Voltage High Voltage Volts Phase Hertz Motor Type NEMA Design Enclosure Class Insulation Service Factor Type Starting Type Motor Efficiency Construction Full Load Rpm Full Load Efficiency % Full Load Power Factor % Low Voltage Full Load Amps High Voltage Full Load Amps Low Voltage Locked Rotor Amps High Voltage Locked Rotor Amps Maximum Altitude in Feet Rotation Facing Opposite Shaft End 3 60 SCI B ODP F 1.15 WYE-DELTA EPACT Stl Frame/CI End Shields 3555 91 88.6 0 0 0 0 3300 Clockwise US 30 D30E1DS FD 3600 284TS 230 460

The abov e data are not certified being extracted from manufacturer's published catalog data sheets.

Peerless Pump Company - RAPID v8.06 - 5th October 2005.

You might also like