Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

g

GE Power Management
Technical Notes

Stator Differential Protection during Transformer Inrush Conditions in the 489


GE Publication No. GET-8403
Copyright 2002 GE Power Management

DESCRIPTION OF PROBLEM

A common configuration for small generation is as follows:

489 2

Load

FIGURE 1. Typical small generation connection

In this configuration the generator can be subjected to a significant inrush current when the transformer is energized on closing of Breaker 2. Each of the generator CTs will see the same current. However, the current can be as large as 10 pu If the CTs have different characteristics; or, if there is a significant difference in the CT burdens, the CTs may saturate unequally. The following example shows a typical waveform as seen by the 489 during transformer inrush conditions.

GET-8403: Stator Differential Protection during Transformer Inrush Conditions in the 489

Phase C (Output)

Phase C (Neutral)

FIGURE 2. Example generator CT currents in presence of transformer inrush

Ideally, the currents in the output and neutral CTs would be mirror images of one another. Unequal saturation creates a false differential current. Increasing the slope in these cases may not solve the problem since there are intervals when the currents are summating. This would require a slope setting greater than 100%. SOLUTION 1 The 489 differential element has an associated time delay setting. This can be used to delay the operation of the differential element long enough to ride through the inrush event. The drawback of this solution is an increased clearing time for in-zone faults. This can be avoided by taking advantage of the dual settings feature available in the 489. A digital input (ideally, the transformer breaker close command) is required to predict the onset of the saturation event. This input forces the 489 to change to an alternate setting group with an extended delay time (20 cycles is usually sufficient). A dropout timer is necessary to maintain the signal for the duration of the inrush. The associated relay settings and wiring are shown below.

FIGURE 3. Settings for Solution 1

GE Power Management

GET-8403: Stator Differential Protection during Transformer Inrush Conditions in the 489

CB CLOSE COMMAND

POTTER & BRUMFIELD CNS-35-96 OR EQUIVALENT

TDDO

D16 D17 D18 D19 D20 D21 D22 D23 D24 C1 C2 C3 C4

ASSIGNABLE INPUT 1 ASSIGNABLE INPUT 2 ASSIGNABLE INPUT 3 ASSIGNABLE INPUT 4 ASSIGNABLE INPUT 5 ASSIGNABLE INPUT 6 ASSIGNABLE INPUT 7 COMMON SWITCH +24Vdc + + ACCESS BREAKER STATUS

DIGIT AL INPUT S

FIGURE 4. Connections for Solution 1

SOLUTION 2

If an additional digital input and contact output are available, then the dropout time delay can be incorporated into the 489. A general purpose input can be programmed as a control element. The desired dropout time would be entered as the dwell time setting.

FIGURE 5. Settings for Solution 2

GE Power Management

GET-8403: Stator Differential Protection during Transformer Inrush Conditions in the 489

R1 TRIP

R2 AUXILIARY

R3 AUXILIARY

R4 AUXILIARY

CB CLOSE COMMAND

D16 D17 D18 D19 D20 D21 D22 D23 D24 C1 C2 C3 C4

ASSIGNABLE INPUT 1 ASSIGNABLE INPUT 2 ASSIGNABLE INPUT 3 ASSIGNABLE INPUT 4 ASSIGNABLE INPUT 5 ASSIGNABLE INPUT 6 ASSIGNABLE INPUT 7 COMMON SWITCH +24Vdc + ACCESS + BREAKER STATUS

R5 ALARM

R6 SERVICE

E2 F1 E1 F2 E3 F3 E5 F4 E4 F5 E6 F6 E8 F7 E7 F8 E9 F9

DIGITAL INPUTS

FIGURE 6. Connections for Solution 2

Either solution requires that the settings for all elements be entered in both setting groups. The Group 2 Phase Differential element would be programmed with an extended time delay.

GE Power Management

You might also like