Other than the roadways and boundary fences of security establishments any temporary or permanent structures / buildings, parapet walls, Not within 25 Meter Not within 50 Meter
With All Underground services crossing the way leave (from the nearest tower foundation) 35 Meter (Min) 50 Meter (Min)
The nearest side of the road reservation to the nearest tower foundation 25 Meter
35 Meter,50 Meter
The pipelines (water, oil/gas etc.) crossing (respectively away from the nearest base of tower leg). Pipe-lines shall not be laid parallel to the overhead line within the limits of a way leave (ROW). 25 Meter (Min) 35 Meter(Min) ,50 Meter(Min)
Cables crossing the transmission lines way leave (ROW) respectively away from the nearest base of tower leg. 25 Meter 35 Meter,50 Meter
Foundations and civil structures (Temporary or permanent) will not be permitted in the close proximity to the cable circuit. A minimum horizontal distance from such structures to the nearest edge of the cable trench shall be observed Min 1.5 Meter Min 1.5 Meter
0.5 Meter
1.0 Meter
0.5 Meter
Gas pipes
0.6 Meter
Telephone lines
0.5 Meter
LV / 11kV cables
0.5 Meter
Use of heavy mechanical excavators (other than hand operated pneumatic jack hammers) or driving sheet piles
Not less than 3 Meter from the edge of cable, cover, cable joint
operating load/thrust/ weight will not be applied directly on the cable installation
Not permitted unless the Step and Touch Potentials at any point of the pipe line do not exceed 65 Volts.
Distance between underground power cables to wall of gas pipelines in parallel routes.
Voltage 380/220V 20KV 63KV Min Horizontal Distance 1 Meter 2 Meter 3 Meter Min Vertical Distance 0.5 Meter 1 Meter 1.5 Meter
First Class State Road=(22.5 meter from one side of Central Line of Highway)
Second Class State Road=(17.5 meter from one side of Central Line of Highway)
35 Meter
Third Class State Road =(12.5 meter from one side of Central Line of Highway)
25 Meter
Forth Class State Road=(7.5 meter from one side of Central Line of Highway)
15 Meter
to a point of support 33 KV & 66 KV Conductor Joint No tension joints shall be used unless specially approved.
Electrical Safety Clearance (Part-2) Code: Indian Electricity Rules/ Central Electricity Authority:
Right of Way Clearance (As per GETCO Standard):
KV 66 KV 132 KV 220 KV 400KV 400 KV Min ROW 18 Meter 27 Meter 35 Meter 52 Meter (Single Circuit) 48 Meter (Double Circuit)
Flat roof, open balcony, verandah roof ,When the line passes above the building a vertical clearance from the highest point
2.5 Meter
Line passes adjacent to the building a horizontal clearance from the nearest point
1.2 Meter
2.5 Meter
1.2 Meter
11 KV to 33 KV
3.7 Meter
Above 33 KV
Up to 11 KV
The horizontal clearance between the nearer conductor and any part of such building
1.2 Meter
11 KV to 33 KV
The horizontal clearance between the nearer conductor and any part of such building
2.0 Meter
Above 33 KV
The horizontal clearance between the nearer conductor and any part ofsuch building
Across a street
5.8 Meter
High Voltage
Across a street
6.1 Meter
Along a street
5.5 Meter
High Voltage
Along a street
5.8 Meter
4.0 Meter
High Voltage
5.2 Meter
33 KV & EHV
Clearance above ground(Add 0.3 Meter for every 33 KV Volts in 5.2 Meter)
Underground telecommunication cable shall be with underground power cable of voltage exceeding 33 kV.
1.3 Meter
2.0 Meter
3.0 Meter
4.0 Meter
5.0 Meter
6.0 Meter
3.0 Meter
3.0 Meter
3.0 Meter
4.0 Meter
5.0 Meter
6.0 Meter
Electrical Safety Clearance (Part-3) Standard: Northern Ireland Electricity (NIE), 6/025 ENA
Clearances of Electrical Line to Ground and Roads:
Description of Clearance 0.4 KV Line conductor to any point not over road 5.2 Meter 11 KV 6.1 Meter 33KV 6.4 Meter 110KV 6.4 Meter 220 KV 7.0 Meter 400KV 7.0 Meter
5.8 Meter
6.1 Meter
6.4 Meter
6.4 Meter
7.4 Meter
8.1 Meter
6.9 Meter
6.9 Meter
6.9 Meter
7.2 Meter
8.5 Meter
9.2 Meter
4.6 Meter
4.6 Meter
4.6 Meter
Line conductor or bare live metalwork to any object to which access is not required AND on which a person cannot stand or lean a ladder
0.8 Meter
0.8 Meter
1.2 Meter
2.4 Meter
3.1 Meter
30
30
30
30
30
Meter
Meter
Meter
Meter
Meter
8.5 Meter
8.5 Meter
8.5 Meter
8.5 Meter
8.5 Meter
9.0 Meter
9.0 Meter
9.0 Meter
9.0 Meter
9.0 Meter
15.0 Meter
15.0 Meter
15.0 Meter
15.0 Meter
15.0 Meter
Line conductor or bare live metalwork to trees or hedges capable of supporting a ladder or being climbed.
3.0 Meter
3.0 Meter
3.4 Meter
4.6 Meter
5.3 Meter
Line conductor or bare live metalwork to trees falling towards the overhead line with the line conductors hanging vertically.
0.8 Meter
0.8 Meter
1.2 Meter
2.4 Meter
3.1 Meter
3.0 Meter
3.0 Meter
3.4 Meter
4.6 Meter
5.3 Meter
1.5 Meter
0.3 Meter
1.0 Meter
1.5 Meter
1.7 Meter
1.7 Meter
2.3 Meter
3.3 Meter
4.0 Meter
(ii) Column falling towards line with line conductor hanging vertically only
1.7 Meter
1.7 Meter
2.3 Meter
3.3 Meter
4.0 Meter
0.4 Meter
0.4 Meter
0.8 Meter
1.4 Meter
1.9 Meter
10.5 Meter
10.5 Meter
10.5 Meter
10.5 Meter
10.5 Meter
7.6 Meter
7.6 Meter
7.6 Meter
7.6 Meter
7.6 Meter
7.6 Meter
Clearances to Railways:
Description of Clearance 0.4 KV Line conductor to ground level 6.1 Meter 11 KV 6.1 Meter 33KV 6.1 Meter 110KV 6.7 Meter 220 KV 7.0 Meter 400KV 7.6 Meter
7.6 Meter
8.5 Meter
8.5 Meter
9.1 Meter
9.4 Meter
10.1 Meter
Line conductor to ground level at roads and yards, where road mobile cranes are likely to be employed
10.7 Meter
10.7 Meter
10.7 Meter
11.2 Meter
11.5 Meter
12.2 Meter
7.3 Meter
7.3 Meter
7.3 Meter
8.0 Meter
8.2 Meter
8.8 Meter
Line conductor to the level of buildings, gantries or other structures (including those carrying traction wires) on which a man may be
3.0 Meter
3.0 Meter
3.0 Meter
3.7 Meter
4.6 Meter
6.1 Meter
2.4 Meter
2.7 Meter
2.7 Meter
3.0 Meter
3.7 Meter
5.5 Meter
1.8 Meter
1.8 Meter
1.8 Meter
2.4 Meter
3.0 Meter
3.7 Meter
3.0 Meter
3.0 Meter
3.0 Meter
3.4 Meter
4.6 Meter
5.3 Meter
Vertical clearance from line conductors to fuel oil tanks Please refer Clearances to Objects
Lowest line conductor or earth wire of upper line to earth wire of lower line where erected. 0.7 Meter 1.4 Meter 1.6 Meter 2.5 Meter 3.7 Meter 4.4 Meter
Lowest line conductor or earth wire of upper line to any point on a support of the lower line on which a person may stand. 2.7 Meter 2.8 Meter 3.0 Meter 3.4 Meter 4.6 Meter 5.3 Meter
Support of upper line and any conductor of lower line. 7.5 Meter 7.5 Meter 7.5 Meter 15 Meter 15 Meter 15 Meter
Vertical Passing Clearance (sites where vehicles will pass below the lines):
Description of Clearance <33 KV 0.8 Meter Passing clearance: fixed height loads 110KV 1.4 Meter 220KV 2.4 Meter 400 KV 3.1 Meter
3.2 Meter
4.1 Meter
5.0 Meter
Horizontal Clearance (sites where there will be no work or passage of plant under lines):
Description of Clearance <33 KV 6.0 Minimum horizontal distances to safety barriers Meter 110KV 9.0 Meter 220KV 12.0 Meter 400 KV 14.0 Meter
Distance between Conductors (Taken down from Pole to other Support, on Transformer):
Voltage Distance between Circuits 11 KV & LV Line 22 KV & LV Line 33 KV & LV Line 0.60 Meter 0.75 Meter 0.90 Meter
Clean &unobstructed Passages at side or under any earthed enclosure containing Bare Conductor
< 1 KV
11 KV
1.5 Meter
22 KV
2.0 Meter
33 KV
2.5 Meter
66 KV
3.0 Meter
110 KV
4.0 Meter
>220 KV
6.0 Meter
Sewer Pipe
0.300 Meter
0.300 Meter
Water Pipe
0.600 Meter
0.600 Meter
Sewer Pipe
1.0 Meter
1.0 Meter
Water Pipe
0.600 Meter
0.600 Meter
0.450 Meter
Carriageways (including road crossings) Low Voltage Normal agricultural land (not deep ploughing)
0.600 Meter
1.0 Meter
1.2 Meter
0.600 Meter
Carriageways (including road crossings) 11 KV to 20 KV Normal agricultural land (not deep ploughing)
0.750 Meter
1.0 Meter
1.2 Meter
0.900 Meter
Carriageways (including road crossings) 33 KV to 132 KV Normal agricultural land (not deep ploughing)
0.900 Meter
1.0 Meter
1.2 Meter
0.450 Meter
0.600 Meter
1.0 Meter
20 mm
150 mm
33 kV to 66 kV
6 Meter
6 Meter
66 kV and Above
8 Meter
8 Meter
8 Meter
2.2 to 5 Meter
6 to12 Meter
2.2 Meter
6 Meter
2.2 Meter
6 Meter
6 Meter
9 Meter
8 Meter
12 Meter
2.2 Meter
2.2 Meter
5 Meter
5 Meter
4.0 Meter
Carin movement
4.0 Meter
4.0 Meter
4.0 Meter
Stay wires
5.5 Meter
Conductors up to 33 kV
6.5 Meter
7.5 Meter
8 Meter
Min Approach Distance for Non-Competent Person near exposed Live Parts:
Voltage Below 110 kV Distance (min) 4.0 Meter
6.0 Meter
Min Approach Distance for Competent Person near exposed Live Parts:
Voltage Below 1 kV Distance (min) 0.5 Meter
11 kV
1.5 Meter
22 kV
2.0 Meter
33 kV
2.5 Meter
66 kV
3.0 Meter
110 kV
4.0 Meter
6.0 Meter
Up to 750 V
1.5 Meter
750 V to 15 KV
4.0 Meter
15 KV to 230 KV
5.0 Meter
0.7 Meter
1 V to 6.6 KV
0.7 Meter
6.6 KV to 11 KV
0.7 Meter
11 KV to 22 KV
0.7 Meter
22 KV to 33 KV
1.0 Meter
33 KV to 66 KV
1.0 Meter
66 KV to 132 KV
1.2 Meter
132 KV to 220 KV
1.8 Meter
220 KV to 330 KV
3.0 Meter
Up to 1 KV
3.0 Meter
1 V to 6.6 KV
3.0 Meter
6.6 KV to 11 KV
3.0 Meter
11 KV to 22 KV
3.0 Meter
22 KV to 33 KV
3.0 Meter
33 KV to 66 KV
3.0 Meter
66 KV to 132 KV
3.0 Meter
132 KV to 220 KV
4.5 Meter
220 KV to 330 KV
6.0 Meter
Minimum Approach Distance for Vehicle & Plant for Ordinary Person:
Distance (min) Voltage Mobile Plant Vehicle
Up to 1 KV
3.0 Meter
0.6 Meter
1 V to 6.6 KV
3.0 Meter
0.9Meter
6.6 KV to 11 KV
3.0 Meter
0.9Meter
11 KV to 22 KV
3.0 Meter
0.9Meter
22 KV to 33 KV
3.0 Meter
0.9Meter
33 KV to 66 KV
3.0 Meter
2.1 Meter
66 KV to 132 KV
3.0 Meter
2.1 Meter
132 KV to 220 KV
3.0 Meter
2.9 Meter
220 KV to 330 KV
6.0 Meter
3.4 Meter