User Manual Plantas Huawei
User Manual Plantas Huawei
User Manual
Issue Date
01 2012-06-01
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS" without warranties, guarantees or representations of any kind, either express or implied. The information in this document is subject to change without notice. Every effort has been made in the preparation of this document to ensure accuracy of the contents, but all statements, information, and recommendations in this document do not constitute a warranty of any kind, express or implied.
Issue 01 (2012-06-01)
Intended Audience
This document is intended for:
Symbol Conventions
The symbols that may be found in this document are defined as follows. Symbol Description Alerts you to a high risk hazard that could, if not avoided, result in serious injury or death. Alerts you to a medium or low risk hazard that could, if not avoided, result in moderate or minor injury. Alerts you to a potentially hazardous situation that could, if not avoided, result in equipment damage, data loss, performance deterioration, or unanticipated results. Provides a tip that may help you solve a problem or save time. Provides additional information to emphasize or supplement important points in the main text.
Issue 01 (2012-06-01)
ii
Change History
Changes between document issues are cumulative. The latest document issue contains all the changes made in earlier issues.
Issue 01 (2012-06-01)
This issue is the first official release.
Issue 01 (2012-06-01)
iii
Contents
Contents
About This Document .................................................................................................................... ii 1 Overview......................................................................................................................................... 1
1.1 Designation Explanation .................................................................................................................................. 1 1.2 Typical Networking .......................................................................................................................................... 1 1.3 Configuration ................................................................................................................................................... 2 1.4 Features ............................................................................................................................................................ 8
2 Component Description............................................................................................................... 9
2.1 Cabinet ............................................................................................................................................................. 9 2.2 Temperature Control Unit .............................................................................................................................. 11 2.2.1 Direct-Cooling Unit .............................................................................................................................. 11 2.2.2 TEC ....................................................................................................................................................... 15 2.3 Rectifier .......................................................................................................................................................... 21 2.3.1 Appearance ............................................................................................................................................ 21 2.3.2 Panel...................................................................................................................................................... 22 2.4 Monitoring Unit ............................................................................................................................................. 23 2.4.1 Appearance ............................................................................................................................................ 23 2.4.2 Main Control Module............................................................................................................................ 24 2.4.3 Basic I/O module .................................................................................................................................. 26 2.4.4 GPRS Module ....................................................................................................................................... 29 2.4.5 GPRS antenna ....................................................................................................................................... 32 2.5 PDU................................................................................................................................................................ 32 2.5.1 AC PDU ................................................................................................................................................ 33 2.5.2 DC PDU ................................................................................................................................................ 33 2.6 Intelligent Power Meter .................................................................................................................................. 35 2.6.1 Appearance ............................................................................................................................................ 35 2.6.2 Pins........................................................................................................................................................ 36 2.6.3 Specification ......................................................................................................................................... 37 2.7 Bluetooth electric door lock ........................................................................................................................... 37 2.7.1 Appearance ............................................................................................................................................ 38 2.7.2 Pins........................................................................................................................................................ 38 2.8 Bluetooth controller ....................................................................................................................................... 39 2.8.1 Appearance ............................................................................................................................................ 39
Issue 01 (2012-06-01)
iv
Contents
A Technical Specifications ........................................................................................................... 90 B LCD Menu ................................................................................................................................... 94 C Acronyms and Abbreviations ................................................................................................ 102
Issue 01 (2012-06-01)
1 Overview
1
1.1 Designation Explanation 1.2 Typical Networking
Overview
The TP48200T-D20A1 & D20A2 is an integrated outdoor backup alternating current-to-direct current (AC-to-DC) power system that employs -48 V, 50 A rectifiers and outputs a maximum of 200A current. The TP48200T-D14A1 & D14A2 is an integrated outdoor backup alternating current-to-direct current (AC-to-DC) power system that employs -48 V, 50 A rectifiers and outputs a maximum of 100A current.
The TP48200T-D20A1 & D20A2 & D14A1 & D14A2, AC power supply, automatic transfer switch (ATS), alternating current distribution box (ACDB), storage batteries, and related devices constitute a site power solution. Figure 1-1 shows the positioning of the TP48200T-D20A1 & D20A2 & D14A1 & D14A2 in the typical site power solution. Figure 1-1 TP48200T-D20A1 & D20A2 & D14A1 & D14A2 in the typical site power solution
Issue 01 (2012-06-01)
1 Overview
1.3 Configuration
The TP48200T-D20A1 & D20A2 & D14A1 & D14A2 is a cabinet that houses the fans, rectifiers, monitoring unit, sensors, power distribution unit (PDU), intelligent power meter and Bluetooth electric door lock. Table 1-1 Configuration Item TP48200T-D20A1 Composition
AC input mode
Cabinet (13U space for customer equipments and two-layer rack for storage batteries) R4850G1 (2 to 4 PCS) ECC500 PDU Intelligent power meter Bluetooth electric door lock Battery temperature sensor Temperature sensor in direct-cooling unit Temperature and humidity sensor Door status sensor Water sensor (optional) Smoke sensor (optional) Cabinet (13U space for customer equipments and two-layer rack for storage batteries) R4850G1 (2 to 4 PCS) ECC500 PDU Intelligent power meter Bluetooth electric door lock Battery temperature sensor Temperature sensor in direct-cooling unit Temperature and humidity sensor Door status sensor Water sensor (optional) Smoke sensor (optional) Cabinet (5U space for customer equipments and one-layer rack for storage batteries) R4850G1 (2 PCS) ECC500
220V three-phase five-line (L1, L2, L3, N, PE) 110V three-phase five-line (L1, L2, L3, N, PE) 220V single-phase three-line (L, N, PE)
TP48200T-D20A2
110V dual-live-wire (L1, L2, N, PE) 110V dual-live-wire (L1, L2, PE) 220V single-phase three-line (L, N, PE)
TP48200T-D14A1
220V three-phase five-line (L1, L2, L3, N, PE) 110V three-phase five-line (L1, L2,
Issue 01 (2012-06-01)
1 Overview
Item
Composition
PDU Intelligent power meter Bluetooth electric door lock Battery temperature sensor Temperature sensor in direct-cooling unit Temperature and humidity sensor Door status sensor Water sensor (optional) Smoke sensor (optional) Cabinet (5U space for customer equipments and one-layer rack for storage batteries) R4850G1 (2 PCS) ECC500 PDU Bluetooth electric door lock Battery temperature sensor Temperature sensor in direct-cooling unit Temperature and humidity sensor Door status sensor Water sensor (optional) Smoke sensor (optional)
TP48200T-D14A2
110V dual-live-wire (L1, L2, N, PE) 110V dual-live-wire (L1, L2, PE) 220V single-phase three-line (L, N, PE)
Issue 01 (2012-06-01)
1 Overview
(1) Alternating current power distribution unit(AC PDU) (4) Intelligent power meter (7) Central monitoring unit type A (CMUA) for thermoelectric cooler (TEC) (10) GPRS antenna (13) Monitoring unit (ECC500) (16) Bluetooth Electric door lock
(2) Door status sensor (5) Space for rectifiers (8) TEC
(3) Direct current power distribution unit(DC PDU) (6) Space for customer equipments (9) Base
(11) Fan assembly (14) Temperature and humidity sensor (17) Space for Bluetooth controller
Issue 01 (2012-06-01)
1 Overview
(1) Alternating current power distribution unit(AC PDU) (4) Intelligent power meter (7) Central monitoring unit type A (CMUA) for thermoelectric cooler (TEC) (10) GPRS antenna (13) Monitoring unit (ECC500) (16) Bluetooth Electric door lock
(2) Door status sensor (5) Space for rectifiers (8) TEC
(3) Direct current power distribution unit(DC PDU) (6) Space for customer equipments (9) Base
(11) Fan assembly (14) Temperature and humidity sensor (17) Space for Bluetooth controller
Issue 01 (2012-06-01)
1 Overview
(1) Alternating current power distribution unit(AC PDU) (4) Intelligent power meter (7) Central monitoring unit type A (CMUA) for thermoelectric cooler (TEC) (10) GPRS antenna (13) Air filter (16) Bluetooth Electric door lock
(2) Door status sensor (5) Space for rectifiers (8) TEC
(3) Direct current power distribution unit(DC PDU) (6) Space for customer equipments (9) Base
(11) Fan assembly (14) Monitoring unit (ECC500) (17) Space for Bluetooth controller
(12) CMUA for fan assembly (15) Temperature and humidity sensor
Issue 01 (2012-06-01)
1 Overview
(1) Alternating current power distribution unit(AC PDU) (4) Intelligent power meter (7) Central monitoring unit type A (CMUA) for thermoelectric cooler (TEC) (10) GPRS antenna (13) Air filter (16) Bluetooth Electric door lock
(2) Door status sensor (5) Space for rectifiers (8) TEC
(3) Direct current power distribution unit(DC PDU) (6) Space for customer equipments (9) Base
(11) Fan assembly (14) Monitoring unit (ECC500) (17) Space for Bluetooth controller
(12) CMUA for fan assembly (15) Temperature and humidity sensor
Issue 01 (2012-06-01)
1 Overview
1.4 Features
The TP48200T-D20A1 & D20A2 supplies stable power to -48 V DC equipment and provides a maximum current of 200 A. The TP48200T-D14A1 & D14A2 supplies stable power to -48 V DC equipment and provides a maximum current of 100 A.
Easy Installation
The modules of monitoring unit (ECC500) and rectifiers are hot-swappable. This facilitates the system installation, saves maintenance time, and reduces the operational expenditure (OPEX).
High Efficiency
The TP48200T-D20A1 & D20A2 & D14A1 & D14A2 uses rectifiers with a 96% efficiency record.
Remote Monitoring
OPEX is reduced when the TP48200T-D20A1 & D20A2 & D14A1 & D14A2 performs comprehensive power management and battery management functions by connecting to the element management system (EMS).
Issue 01 (2012-06-01)
2 Component Description
2
2.1 Cabinet
Component Description
Dimensions (H x W x D) of the TP48200T-D20A1 & D20A2 cabinet (excluding the base) are 2060 mm x 700 mm x 700 mm (81.1 in. x 27.56 in. x 27.56 in.). Dimensions (H x W x D) of the base are 180 mm x 700 mm x 700 mm (7.09 in. x 27.56 in. x 27.56 in.). Figure 2-1 shows the TP48200T-D20A1 & D20A2 cabinet. Figure 2-1 TP48200T-D20A1 & D20A2 cabinet
Issue 01 (2012-06-01)
2 Component Description
Dimensions (H x W x D) of the TP48200T-D14A1 & D14A2 cabinet (excluding the base) are 1400 mm x 700 mm x 700 mm (55.1 in. x 27.56 in. x 27.56 in.). Dimensions (H x W x D) of the base are 180 mm x 700 mm x 700 mm (7.09 in. x 27.56 in. x 27.56 in.). Figure 2-2 shows the TP48200T-D14A1 & D14A2 cabinet. Figure 2-2 TP48200T-D14A1 & D14A2 cabinet
Table 2-1 TP48200T-D20A1 & D20A2 & D14A1 & D14A2 cabinet height distribution Item Customer equipment Storage batteries Embedded power system TP48200T-D20A1 & D20A2 13 U (557.85 mm [21.96 in.]) (not included the space for storage batteries) 16U (755.6 mm [29.75 in.]) for two layers
TP48200T-D14A1 & D14A2 5 U (222.25 mm [8.75 in.]) (not included the space for storage batteries) 8 U (355.6 mm [14.00 in.]) for one layer
1U (44.45mm [1.75in.])
1U (44.45mm [1.75in.])
2U (88.9mm[3.50in.])
2U (88.9mm[3.50in.])
Issue 01 (2012-06-01)
10
2 Component Description
Appearance
Figure 2-3 shows the fan assembly. Figure 2-4 shows a centrifugal fan. Figure 2-3 Fan assembly
Issue 01 (2012-06-01)
11
2 Component Description
Specifications
Table 2-2 Technical specifications of fan assembly Item Rated voltage Rated power Specifications 48 V DC 2 x 34 W
Air flows
Figure 2-5 The direct-cooling unit air flows
Issue 01 (2012-06-01)
12
2 Component Description
PWR SMOKE IN0, IN1, IN2 GATE ELU ALM & Indicators COM_IN COM_OUT TEM.FAN TEC RUN
Power input port. Reserved. Reserved. Reserved. Reserved. Indicate CMUA status. Connects to the monitoring unit. Reserved. Connects to the temperature sensor. Reserved.
Issue 01 (2012-06-01)
13
2 Component Description
Silkscreen
Function
FAN_INT FAN_EXT
Connects to the fan on the left in the fan assembly. Connects to the fan on the right in the fan assembly.
Table 2-4 Indicator description Silk Screen RUN Color Green Status Blinks at 0.5 Hz. Blinks at 4 Hz. Meaning The board functions normally and communicates properly with upper-level equipment. The board functions normally, but fails to communicate with the upper-level equipment. If the board does not communicate with the upper-level equipment within one minute, the communication fails. The board is not performing self-test after being powered on. No alarm is generated. An alarm is generated, and the board must be replaced. An alarm is generated. It may be caused by a fault on the board or in a port. Therefore, the board must be replaced as required.
ALM
Red
Issue 01 (2012-06-01)
14
2 Component Description
Figure 2-8 shows settings for jumper slots on the CMUA. Figure 2-8 Settings for Jumper slots on the CMUA
2.2.2 TEC
A TEC consists of semiconductor refrigeration chips, a cold-end heat sink, a hot-end heat sink, an internal fan (cold-end fan), an external fan (hot-end fan), and a controller. Figure 2-9 shows the TEC components.
Appearance
Issue 01 (2012-06-01)
15
2 Component Description
Specifications
Table 2-5 Technical specifications Item Rated voltage (V DC) Rated refrigeration capacity (L32/L32) Maximum power input Heating capacity Ambient range Humidity range Storage environment Specifications 48 V DC 190 W 380 W 300W 40C to +40C 5%100% RH 40C to +70C Complies with the ETS 300 019-1-1, CLASS 1.2 requirements. Altitude Transportation performance 4700 m Complies with the ETS 300 019-1-2, CLASS 2.3
Issue 01 (2012-06-01)
16
2 Component Description
Item
Specifications requirements.
IP55 (cabinet), which complies with the International Electrotechnical Commission (IEC) 60529.
Circular salt-fog test: The TEC passes the circular salt-fog test required by the IEC68-2-52 for 10 circles. Damp heat test: The TEC passes the damp heat test required by the IEC 68-2-38 for 10 days. Mould growth test: The TEC passes the mould growth test required by the IEC 68-2-10 for 28 days. UL94 HF-1 level of sealing materials. UL94 V0 level of shielding materials and printed circuit board (PCB). UL94 V1 level of other materials. Complies with the IEC 60950-1, EN 60950-1, and UL 60950-1. (The withstand voltage is greater than 750 V DC.) The internal fan is configured with a grille protection cover, which complies with the IP3X requirement (Your fingers do not contact dangerous components in any direction.) Warning signs are attached to the internal fan.
Safety
Service life Failure rate Fan service life (internal fan L10/25C and external fan L10/40C) Mean time between failures (MTBF) Dimensions (H x W x D, including the flange) Weight Positive polarity protection of DC power supply Operating voltage Temperature sensor
> 100,000 hours 200 mm x 180 mm x 400 mm 6.4kg Supported 36V60V Monitoring range-2080 2
Issue 01 (2012-06-01)
17
2 Component Description
Air flows
Figure 2-10 TEC air flows
Issue 01 (2012-06-01)
18
2 Component Description
PWR SMOKE IN0, IN1, IN2 GATE ELU ALM & Indicators COM_IN COM_OUT TEM.FAN RUN
Power input port. Reserved. Reserved. Reserved. Reserved. Indicate CMUA status. Connects to the monitoring unit. Reserved. Connects to the temperature sensor.
Issue 01 (2012-06-01)
19
2 Component Description
Silkscreen
Function
Connects to the TEC. Connects to the internal fan of the TEC. Connects to the external fan of the TEC.
Table 2-7 Indicator description Silk Screen RUN Color Green Status Blinks at 0.5 Hz. Blinks at 4 Hz. Meaning The board functions normally and communicates properly with upper-level equipment. The board functions normally, but fails to communicate with the upper-level equipment. If the board does not communicate with the upper-level equipment within one minute, the communication fails. The board is not performing self-test after being powered on. No alarm is generated. An alarm is generated, and the board must be replaced. An alarm is generated. It may be caused by a fault on the board or in a port. Therefore, the board must be replaced as required.
ALM
Red
Issue 01 (2012-06-01)
20
2 Component Description
Figure 2-13 shows settings for jumper slots on the CMUA. Figure 2-13 Settings for Jumper slots on the CMUA
2.3 Rectifier
2.3.1 Appearance
The rectifier converts the AC input power into stable -48 V DC power. The TP48200T-D20A1 & D20A2 & D14A1 & D14A2 can be configured with two, three, or four rectifiers. Figure 2-14 shows the rectifier.
Issue 01 (2012-06-01)
21
2 Component Description
2.3.2 Panel
The rectifier panel provides the run indicator, alarm indicator, and fault indicator. Figure 2-15 shows the rectifier panel. Figure 2-15 rectifier panel
Table 2-8 Indicator description of rectifier Indicator Run indicator Color Green Status Steady on Description The rectifier output is normal. The rectifier has no output. No alarm is generated. The rectifier generates a prewarning for power limiting due to overtemperature. The rectifier generates an alarm for shutdown due to ambient overtemperature or undertemperature protection. Measures The rectifier runs properly, and no measure is required. Replace the rectifier if the AC input is normal. No measure is required. Check that the air vent is not blocked and the ambient temperature is within a normal range.
Issue 01 (2012-06-01)
22
2 Component Description
Indicator
Color
Status
Description The rectifier generates an alarm due to AC input overvoltage or undervoltage protection. The rectifier is hibernated.
Measures Check that the electrical grid voltage is within a normal range. No measure is required. No measure is required. Pull out the rectifier and reinsert it after 1 minute. Replace the rectifier. The rectifier automatically recovers after loading, and no measure is required.
Fault indicator
Red
Off Steady on
The rectifier is not faulty. The rectifier is locked due to output overvoltage. There is no output because the rectifier is faulty.
Blinking at 4 Hz
Table 2-9 ECC component functions Component Main control module Silkscreen SMU03A Configuration Mandatory Function
Provides an LCD to query and set local parameters. Monitors and manages input energy. Provides an operating status indicator.
Issue 01 (2012-06-01)
23
2 Component Description
Component
Silkscreen
Configuration
Function
Provides TCP/IP and RS485 ports for northbound communication. TCP/IP stands for transmission control protocol/Internet protocol. Provides RS485 ports for southbound communication. Intelligently manages storage batteries. Generates alarms. Manages intelligent southbound components. Manages assets. Monitors southbound components over serial ports. Receives alarms generated by dry contacts and sensors for detecting battery temperatures, water, smoke, and ambient temperature and humidity. Provides RS485 ports for southbound communication. Enables the ECC500 to communicate with the NetEco in out-of-band (by GPRS) mode. Provides six digital parameter input ports and two dry contact outputs.
Basic IO module
MUS01A
Mandatory
GPRS module
MUC01A
Optional
Issue 01 (2012-06-01)
24
2 Component Description
Indicators
Table 2-10 Indicator description Silk Screen Run indicator Color Green Status Off Blinking (on for 1s and then off for 1s) Blinking (on for 0.125s and then off for 0.125s) Alarm indicator Red Off Steady on Description The main control module is faulty or has no DC input. The main control module runs properly and communicates with the NetEco. The main control module runs properly but does not communicate with the NetEco properly.
LCD
You can view information and set parameters on the LCD. You can set and query parameters using the four buttons on the front panel. Table 2-11 describes the button functions.
Buttons
Table 2-11 Button description Button or Definition Up or down Cancel Enter Description Allows you to view menu items and set the value of a menu item. Returns to the previous menu without saving the settings of the current menu item. Enters the main menu from the standby screen, enters a submenu from the main menu, or saves menu settings.
Note: After a menu is displayed, the standby screen is displayed if no button is pressed for 5 minutes.
After a menu is displayed, the LCD screen becomes dark if no button is pressed for 5 minutes.
Issue 01 (2012-06-01)
25
2 Component Description
Ports
Table 2-12 Port description Silk Screen FE RS485/RS232 COM1 COM2 USB Description Northbound port, connecting to the network or NetEco Reserved Reserved Reserved Reserved
Table 2-13 FE pin definition Pin 1 2 3 6 Signal TX+ TXRX+ RXFE receive Description FE transmit
Issue 01 (2012-06-01)
26
2 Component Description
Indicators
Table 2-14 shows the indicator description of the Basic I/O module. Table 2-14 Indicator description Silk Screen PWR Color Green Meaning Power indicator Status Steady on Off Blinking (on for 1s and then off for 1s) Blinking (on for 0.125s and then off for 0.125s) ALM Red Alarm indicator Off Description The power supply is normal. The input/output (I/O) module is faulty or has no DC input. Communication is normal between the I/O module and the main control module. Communication fails between the I/O module and the main control module.
RUN
Green
Run indicator
Reserved.
Issue 01 (2012-06-01)
27
2 Component Description
Ports
Table 2-15 Port description Silk Screen ELU DI_1 DI_2 DI_3 AI_1 AI_2 TEM_HUM WATER SMOKE CAN 12V COM1 GATE Ambient temperature and humidity Water intrusion Smoke generation Southbound CAN port Power output ports Two-wire RS485 port Gate dry contact input Connects to a humidity and temperature sensor. Connects to a water sensor. Connects to a smoke sensor. Connects to a southbound component. 10.513.5 V Connects to the intelligent power meter. Default setting:
If the dry contact is open, an alarm is generated. If the dry contact is close, no alarm is generated.
If the dry contact is closed, no alarm is generated. If the dry contact is open, an alarm is generated.
Southbound RS485 port Southbound RS485 port RTN+ port: positive DC input terminal NEG: negative DC input terminal
Issue 01 (2012-06-01)
28
2 Component Description
Pin definition
Figure 2-20 Pin definition
WATER
1 2 3 4
TEMHUM
1 2 3 4
Issue 01 (2012-06-01)
29
2 Component Description
Frequency Band
Upstream (module to BTS) : 824-849MHz/880 -915 MHz/1710 -1785 MHz/1850 -1910 MHz Downstream (BTS to module) : 869 -894 MHz/925-960 MHz/1805 -1880 MHz/1930 -1990 MHz
Indicators
The Table 2-17 describes the indicators. Table 2-17 Indicator description Silk Screen PWR1 Color Yellow Status Steady on Off PWR2 Yellow Steady on Off GPRS Green Off Description The power supply is normal. The power supple is faulty or has no DC input. The GPRS module is normal. The GPRS module is faulty or has no DC input. The GPRS module is not powered on.
Issue 01 (2012-06-01)
30
2 Component Description
Silk Screen
Color
Status Steady on Blinking (on for 0.1s and then off for 0.025s) Blinking (on for 0.1s and then off for 2.9s) Blinking (on for 0.1s and then off for 0.9s)
Description A call is being set up over GPRS. Data is being transmitted over GPRS.
The ECC500 is registered with the network, but no data is being transmitted. The ECC500 is searching for a network because of the absence of a subscriber identity module (SIM) card.
Ports
Table 2-18 describes the ports of the GPRS module. Table 2-18 Port description Silk Screen DO_1 DO_2 DI_1 DI_2 DI_3 DI_4 DI_5 DI_6 Figure 2-22 Default setting of DI of GPRS module Dry contact input Default(If the dry contact is closed, an alarm is generated. If the dry contact is open, no alarm is generated.), can be modified. Definitions of DI_1 to DI_6 vary based on solution. You can query their definitions on the LCD, as shown in Figure 2-22. Function Dry contact output Remarks Reserved.
Issue 01 (2012-06-01)
31
2 Component Description
2.5 PDU
PDUs are classified into the DC PDU and AC PDU. The DC PDU distributes DC power to the TP48200T-D20A1 & D20A2 & D14A1 & D14A2, while the AC PDU distributes AC power.
Issue 01 (2012-06-01)
32
2 Component Description
2.5.1 AC PDU
Figure 2-24 AC PDU of TP48200T-D20A1 & D14A1
Table 2-19 Circuit breaker distribution Item AC input AC output TP48200T-D20A1 & D14A1 1 x 63A/3P MCB 3 x 10A MCB 1 x 10 A maintenance socket 1 x 10A RCD
NOTE
TP48200T-D20A2 & D14A2 1 x 100A/2P MCB 3 x 10A MCB 1 x 10 A maintenance socket 1 x 10A RCD
If TP48200T-D20A1 & D20A2 is configured with four rectifiers, the recommended AC output current summation should be less than 14A.
2.5.2 DC PDU
Figure 2-26 shows the DC PDU.
Issue 01 (2012-06-01)
33
2 Component Description
Issue 01 (2012-06-01)
34
2 Component Description
Table 2-20 Circuit breaker distribution Item Battery low voltage disconnection(BLVD) Load low voltage disconnection(LLVD) Specification
10 x 10 A MCB 2 x 100A MCB 1 x 80A MCB 2 x 50A MCB 3 x 25A MCB 2 x 10A MCB
Battery branch
Issue 01 (2012-06-01)
35
2 Component Description
2.6.2 Pins
Figure 2-30 Pins of intelligent power meter
Table 2-21 Pins of the intelligent power meter Pin 12 34 5 6 7 8 10 Definition Working Power RS485 A phase voltage B phase voltage C phase voltage Zero-voltage line The current transformer interface
Issue 01 (2012-06-01)
36
2 Component Description
2.6.3 Specification
Table 2-22 Specifications of the intelligent power meter Category Voltage Item Measurement range Overload capacity Current Measurement range Overload capacity Power Single phase power Total power Measurement range Power factor Accuracy Measurement range Current Voltage Power Power factor Frequency Energy Specifications
Issue 01 (2012-06-01)
37
2 Component Description
2.7.1 Appearance
Figure 2-31 Appearance of Bluetooth electric door lock
2.7.2 Pins
Figure 2-32 RJ45 female connector
Table 2-23 Pins definition of the Bluetooth electric door lock Pin 3 6 8 Definition +12V Signal GND
Issue 01 (2012-06-01)
38
2 Component Description
2.8.2 Pins
Figure 2-34 Pins of the Bluetooth controller
Table 2-24 Pins definition of the Bluetooth controller Pin 1 2 3 4 5 6 7 8 9 Definition AC power input AC power input connect to Pin4 connect to Pin3 -12V +12V control the Bluetooth lock(+) control the Bluetooth lock(-) -
Issue 01 (2012-06-01)
39
2 Component Description
Table 2-25 Connection between the Bluetooth controller and the Bluetooth electric door lock Pins of the Bluetooth controller 7 7 8 Pins of the Bluetooth electric door lock 3 6 8 Definition +12V Signal GND
2.8.3 Specification
Table 2-26 Bluetooth controller specifications Item Rated current Rated voltage Operating Limit voltage Withstanding voltage 1 minute Insulation resistance at 500V DC Contact resistance at 1A DC Solder inter diameter Specifications 4A 125V 200V AC 1500V AC 1500M 3 M 1.2mm 193x110x90 mm -45 C a 85 C
Dimensions
Operating Temperature
Issue 01 (2012-06-01)
40
3 Safety Precautions
3
3.1 Overview
CAUTION
Safety Precautions
To minimize the risk of personal injury and damage to equipment, read and follow all the precautions in this document before performing any installation or maintenance. The "NOTE", "CAUTION", and "WARNING" marks in other documents do not represent all the safety instructions. They are only supplements to the safety instructions. Only trained and qualified personnel are allowed to install, operate, and maintain Huawei equipment, and they must understand basic safety precautions to avoid hazards. To ensure safety of humans and the equipment, pay attention to the safety symbols on the equipment and all the safety instructions in this document. Huawei will not be liable for any consequence caused by the violation of the safety operation regulations and design, production, and usage standards.
NOTE
The safety precautions described in this section are also applicable to other Huawei equipment.
When installing the device, always make the ground connection first and disconnect it at the end. Do not damage the ground conductor or operate the device in the absence of a properly installed ground conductor. Conduct the electrical inspection carefully.
Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd 41
Issue 01 (2012-06-01)
3 Safety Precautions
The device (or system) must be connected permanently to the protection ground before an operation. Before operating the device, check the electrical connection of the device to ensure that it is securely grounded.
Do not operate the device or cables during lightning strikes. To avoid electric shock, do not connect safety extra-low voltage (SELV) circuits to telecommunication network voltage (TNV) circuits. Before operating the device, wear electrostatic discharge (ESD) clothes, ESD gloves, and an ESD wrist strap. Do not wear jewelry or watches when you operate the device. In the case of fire, immediately leave the building or the equipment room, and turn on the fire alarm bell or make an emergency call. Do not enter a building that is on fire. The temperature of some equipment parts may be rather high. Do not touch the surface of such equipment parts to avoid getting burn.
The device must be fixed securely on the floor or to other immovable objects such as walls and mounting racks before operation. Do not block the ventilation while the device is operating. Tighten the thumbscrews by using a tool after initial installation and subsequent access to the panel. After the installation, remove packing materials from the equipment area.
DANGER
The high voltage power supply provides power for the device operation. Direct or indirect contact (through damp objects) with high voltage and AC mains supply may result in fatal danger. Non-standard and incorrect high voltage operations may result in fire and electric shock. The personnel who install the AC facility must be qualified to perform high voltage and AC operations. You must abide by the local rules and regulations when bridging and wiring AC cables. During the installation of the AC power supply facility, follow the local safety regulations.
Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd 42
Issue 01 (2012-06-01)
3 Safety Precautions
Dedicated tools must be used during high voltage and AC operations. Avoid using ordinary tools. When the operation is performed in a damp environment, ensure that the device is dry. When water is found in the rack or the rack is damp, switch off the power supply immediately.
Ground the device before powering it on. Otherwise, personal injury or device damage may be caused by high leakage current. If a "high electrical leakage" tag is present on the power terminal of the device, you must ground the device before powering it on.
Power Cable
Do not install or remove power cables when the device is on. Transient contact between the core of the power cable and the conductor may generate electric arcs or sparks, which may cause fire or hurt human eyes. Before installing or removing the power cable, turn off the power switch. Before connecting a power cable, check that the label on the power cable is correct.
Power Output
All output circuits are evaluated as SELV circuits.
CAUTION
Outputs are energy hazards (>240 VA)
Electrostatic Discharge
CAUTION
The static electricity generated by human bodies may damage the electrostatic-sensitive components on boards, for example, the large-scale integrated (LSI) circuits.
Human body movement, friction between human bodies and clothes, friction between shoes and floors, or handling of plastic articles causes static electromagnetic fields on human bodies. These static electromagnetic fields cannot be eliminated until the static is discharged. To prevent electrostatic-sensitive components from being damaged by the static on human bodies, you must wear a well-grounded ESD wrist strap when touching the device or handling boards or application-specific integrated circuits (ASICs).
Issue 01 (2012-06-01)
43
3 Safety Precautions
Figure 3-1 shows how to wear an ESD wrist strap. Figure 3-1 Wearing an ESD wrist strap
Issue 01 (2012-06-01)
44
The detailed installation and commissioning refer to the TP48200T-D20A1 & D20A2 & D14A1 & D14A2 Quick Installation Guide.
Issue 01 (2012-06-01)
45
5 Maintenance
5
5.1 Routine Maintenance
Table 5-1 Routine maintenance Maintenance Item Maintenance Task Check Item Whether the output voltage of the DC PDU is within the range of 42 V DC to 58 V DC. Check Method Measure the voltage.
Maintenance
Maintain TP48200T-D20A1 & D20A2 & D14A1 & D14A2 periodically based on site requirements. The recommended maintenance interval is 6 months. If faults are identified, clear them immediately.
Measures
Output voltage
Switch on the circuit breaker on the DC PDU, set the multimeter to DC, and then measure the output voltage of the DC PDU.
Issue 01 (2012-06-01)
46
5 Maintenance
Maintenance Item
Maintenance Task Check Item Whether a component burns, smokes, sparks, or produces an unusual odor Check Method Observe and smell the component. Repair When A component burns, smokes, sparks, or produces an unusual odor. Measures
Component
If a short circuit occurs, rectify the fault. If a cable diameter does not match the load, replace it. If there is a burnt componen t, replace it.
Fan
Whether the fan is covered by dust Whether the fan surface is damaged and whether the rotational speed, noise, and vibration are in the normal range
Cabinet surface
Whether the paint and the electroplated coating on the surface of the cabinet are in good condition Whether surface rust appears on the door lock and rust continues to spread over the surface
Door lock
Issue 01 (2012-06-01)
47
5 Maintenance
Maintenance Item
Measures Clean up stains, fingerprints, and foreign matter using a brush or cotton cloth.
Whether there are fingerprints or any other stains on the interior of the cabinet Whether there is unnecessary adhesive tape or cable ties on the cables Whether there is tape, cable ties, wastepaper, or packing bags in the cabinet
Air filter
Overtemperature alarms are frequently raised for the power system, and the temperature inside the cabinet is much higher than the ambient temperature. Dust accumulates on the air filter.
Issue 01 (2012-06-01)
48
5 Maintenance
5.2 Troubleshooting
Common Faults
Table 5-2 Common faults and troubleshooting methods Fault Type AC phase loss Fault Analysis
Handling Method 1. Check whether the DC input cable is correctly and securely connected. If the cable is not correctly and securely connected, reconnect the cable. If the insulation layer is aged, replace the cable. Check whether the AC input voltage is excessively low using a multimeter, and check whether the AC undervoltage (lower than 180V AC) alarm is generated. If the AC input voltage is excessively low and the AC undervoltage alarm is generated, check whether there is short-circuit or electric leakage on the AC input loop. If there is short-circuit or electric leakage, replace the cable. If the AC input is the mains supply, contact the mains supplier for troubleshooting. If the AC input is from the D.G., check the D.G. by referring to the Diesel Generator User Manual. Check whether the DC input cable is correctly and securely connected. If the cable is not correctly and securely connected, reconnect the cable. Check whether the AC input switch is OFF. If the AC input switch is OFF, check whether faults such as short-circuit or open circuit exist on the AC input loop. If the AC input is the mains supply, contact the mains supplier for troubleshooting. If the AC input is from the D.G., check the D.G. by referring to the Diesel Generator User Manual. If the power-off duration is short, supply DC power using batteries. If the power-off duration is long, start other systems for power supply.
2.
3.
AC power off
1.
2.
3.
4.
Issue 01 (2012-06-01)
49
5 Maintenance
Fault Analysis
Handling Method 1. Check whether the AC undervoltage or overvoltage alarm threshold is properly set. If the threshold is excessively high or low, lower or raise the threshold according to the actual conditions. If the AC input is the mains supply, contact the mains supplier for troubleshooting. If the AC input is from the D.G., check the D.G. by referring to the Diesel Generator User Manual. Check the alarm thresholds of the DC overvoltage and undervoltage. If the thresholds are not proper, reset the thresholds according to the actual conditions. When the storage battery is powering the load, remove all the rectifiers, and then insert each rectifier one by one. If an overvoltage alarm is generated after a rectifier is inserted, the voltage of the rectifier exceeds the upper threshold. Then replace the rectifier. Check whether the rectifier module is in position or whether contact is proper. If the monitoring unit is inserted in an incorrect position, insert it correctly. If the contact is not proper, remove and then insert it. Check whether the battery loop is short-circuited or has other faults. Check whether the batteries are faulty. If the batteries are faulty, replace them.
Improper setting of monitoring unit AC undervoltage or overvoltage threshold Mains supply grid fault or D.G. fault Improper setting of monitoring unit DC undervoltage or overvoltage threshold Rectifier module fault
2.
DC overvoltage or DC undervoltage
1.
2.
Charging overcurrent
1.
2. 3.
Issue 01 (2012-06-01)
50
5 Maintenance
Fault Analysis
Handling Method 1. Check whether the load detection cable is securely connected. If the cable is not connected securely, connect it correctly. If the load circuit breakers switch to OFF, check whether the load circuit is short circuit or overcurrent. Switch the load circuit breakers to ON after repairing the load circuit. Check whether the contactor is faulty and whether it can be connected and disconnected. If the contactor is faulty, replace it. Check whether the monitoring unit load shutdown voltage is set excessively high. If it is set excessively high, set it according to the actual situation. Check whether the load power is higher than the configured rectifier module power. If the load power is higher than the configured rectifier module power, add a rectifier module. If the load power exceeds the maximum supported power of the system, lower the load power. Check whether the mains supply is off or the voltage of storage batteries is lower than the Battery Shutdown Voltage. Check whether the battery shutdown permission is set. Check whether the battery cables or the connectors are faulty. If the cables or connectors are faulty, replace them. Check whether the contactor is faulty and whether it can be connected and disconnected. If the contactor is faulty, replace it. Check whether cables of the battery loop or connectors are faulty. If the cables or connectors are faulty, replace them. Check whether the contactor is faulty and whether it can be connected and disconnected. If the contactor is faulty, replace it. Check whether batteries are faulty. If the batteries are faulty, replace them. Check whether temperature sensor is faulty. If the temperature sensor is faulty, replace it.
Load circuit breaker set to OFF Contactor fault Excessively high setting of monitoring unit load shutdown voltage
2.
3.
Output undervoltage due to greater load power than 4. configured rectifier module power 5.
Battery shutdown
1.
2. 3.
4.
Battery loop fault 1. Contactor fault Battery fault Temperature sensor fault 2.
3. 4.
Issue 01 (2012-06-01)
51
5 Maintenance
Fault Type Ambient overtemperature or undertemperature alarm (The alarm is generated only when the temperature sensor is installed.)
Fault Analysis
Handling Method 1. Check whether monitoring temperature alarm thresholds are according to local conditions. If thresholds are not proper, set thresholds accordingly. unit set the the
Overtemperature or 2. undertemperature in the shelter with the temperature sensor Temperature sensor fault Improper setting of monitoring unit humidity alarm parameters Overhumidity or underhumidity in the shelter with the humidity sensor Humidity sensor fault Battery cabin overtemperature Improper setting of monitoring unit battery temperature alarm parameters Battery charging overcurrent Temperature sensor fault 3. 1. 3.
Check whether the temperature control device in the shelter is faulty. If the temperature control device is faulty, repair it. The alarm is automatically cleared when the temperature in the shelter is adjusted to the proper range. Check whether the temperature sensor is faulty. If the temperature sensor is faulty, replace it. Check whether monitoring unit humidity alarm thresholds are set according to local conditions. If the thresholds are not proper, set the thresholds accordingly. Check whether the floor of the shelter is wet. If the floor is wet, use a cotton cloth to wipe the floor and ensure it is dry or use other dehumidifiers. If the alarm persists when the humidity is proper, check whether the humidity sensor is faulty. Check whether monitoring unit battery temperature alarm thresholds are properly set. If the thresholds are not proper, set the thresholds accordingly. Check whether the temperature in battery room is excessively high. If temperature is excessively high, alarm can be cleared when temperature is lowered. the the the the
Ambient overhumidity or underhumidity alarm (The alarm is generated only when the humidity sensor is installed.)
1.
2.
3.
2.
Check the charging current. If the current is excessively strong, switch equalized charging to float charging and check whether the charging current is weakened. If the charging current is still excessively strong, adjust the current limit to reduce the charging current. If the preceding steps do not work, replace the faulty battery. Check whether the temperature sensor is faulty. If the temperature sensor is faulty, replace it.
4.
Issue 01 (2012-06-01)
52
5 Maintenance
Fault Type Door alarm (The alarm is generated only when the door status sensor is installed.) Water immersion alarm (The alarm is generated only when the water sensor is installed.) Smoke alarm (The alarm is generated only when the smoke sensor is installed.)
Fault Analysis
Handling Method 1. 2. The alarm is cleared after the cabinet door is closed. If the alarm persists after the cabinet door is closed, check whether the door status sensor is faulty. Check whether the floor of the shelter is wet. If the floor is wet, use a cotton cloth to wipe the floor and ensure it is dry or use other dehumidifiers. If the alarm persists after the water is drained, check whether the water sensor is faulty. Check whether the smoke caused by fire pervades in the shelter. If there is fire, extinguish the fire and ventilate the shelter. If the alarm persists when there is no smoke, check whether the smoke sensor is faulty. Check whether the ALM indicator on the panel of the rectifier module is on. If the ALM indicator is on, remove the rectifier module and insert the rectifier module after the indicator is off. Disconnect AC input to the rectifier module and restart the rectifier module later on. If the alarm persists, replace the rectifier module. Check whether the mains voltage is over the AC overvoltage alarm threshold (300 V) of the rectifier module or below the AC undervoltage alarm threshold (85 V). For the power supply network with long-time overvoltage or undervoltage, negotiate with the maintenance personnel of the electricity department to improve the power supply network. If the alarm persists when the input voltage of the rectifier module is proper, check whether the rectifier module is proper. If the rectifier module is faulty, replace it.
1.
2.
1.
2.
1.
2.
1.
2.
Issue 01 (2012-06-01)
53
5 Maintenance
Fault Analysis
Handling Method 1. Check whether the rectifier module is in position or whether contact is proper. If the monitoring unit is inserted in an incorrect position, insert it correctly. If the contact is not proper, remove and then insert it. If the alarm persists, replace the rectifier module.
Signal cable connection fault of the rectifier module Rectifier module out of position Poor contact of the rectifier module Rectifier module fault The load fuse is faulty. Load circuit breaker set to OFF
2.
1.
Check whether the load fuse detection cable is securely connected. If the cable is not connected securely, connect it correctly. Check whether the load circuit breaker is in the OFF position. If it is, switch it to the ON position. Check whether the load fuse is damaged. Use a multimeter to measure the voltage at both ends of the fuse. If the voltage is close to 0 V, the fuse is normal. Otherwise, the fuse is blown. Replace the fuse. If the alarm persists after the fuse is replaced, check the new fuse. If the new fuse is blown or the load circuit breaker is automatically switched to the OFF position, the load power on this route may be excessive or a short circuit may occur. In this case, you need to rectify the fault on this load loop. Check the observation window on the AC surge protector. If the color of the window is red, replace the surge protector. Check whether the fault detection cables of the AC surge protector are correctly connected or whether the cables are in good condition. If the cables are not in good condition, replace and reconnect them. If the cable connection is proper, it indicates that the alarm loop is faulty. Replace the user interface module.
2.
3.
4.
1.
2.
3.
Issue 01 (2012-06-01)
54
5 Maintenance
TEC faults
When a TEC becomes faulty, it transmits alarm signals over one dry contact to EMS software, and the ALM indicator turns on. The spare parts for a TEC includes temperature sensor,internal fan, external fan and TEC refrigeration module. Table 5-3 describes the TEC faults and troubleshooting measures. Table 5-3 TEC faults and troubleshooting measures Symptom The internal and external fans rotate properly, the semiconductor refrigeration chips do not work, the RUN indicator turns on, and no alarm is generated. The external fan rotates properly, the TEC circuit breaker trips, the RUN indicator turns on, and no alarm is generated. The semiconductor refrigeration chips refrigerate properly, the internal and external fans rotate properly, the ALM indicator turns on, and an alarm is generated. Possible Cause The semiconductor refrigeration chips are faulty. Measures
Check that no input undervoltage or overvoltage occurs. Check that cables properly connect to the semiconductor refrigeration chips. If no fault is located, replace the CMUA.
The input voltages before and after the internal and external fans start are not within normal ranges.
If the input voltage is greater than 4 V, replace the damaged power cable. If the input voltage is lower than 4 V, replace the CMUA.
The cables to the temperature sensor are damaged. Cables to the fans are damaged.
If the cables to the fans are damaged, replace the cables. If all components are normal but an alarm is generated, reinstall internal and external fans. If an alarm is still generated, replace the TEC refrigeration module or control board .
CMUA faults
When a CMUA is working properly, the resistance in the dry contact is low and the RUN indicator is steady on.When a CMUA is transmitting alarm signals, the resistance in the dry contact is high and the ALM indicator is steady on.
Issue 01 (2012-06-01)
55
5 Maintenance
Table 5-4 CMUA faults and troubleshooting measures Symptom The host generates an alarm, and the ALM indicator and RUN indicator turn off. Possible Cause
Measures
Measure the input voltage. Check the power supply circuit breaker. Check that power cables connect to the correct polarities. If no fault is located, replace the control board.
The host generates an alarm, and the RUN indicator turns on.
Load disconnection is prohibited when you replace the main components. Take measures to ensure that important loads are always connected during the replacement. For example, keep the circuit breaker of important loads set to ON and storage batteries and AC input are not cut off. If a load must be disconnected, ask for the customer's prior permission. The rectifier and the monitoring unit are hot-swappable.
Issue 01 (2012-06-01)
56
5 Maintenance
Issue 01 (2012-06-01)
57
5 Maintenance
Step 6 Fold the handle. Step 7 Tighten the captive screws using the M3 screwdriver, as shown in Figure 5-4. Step 8 Connect the cables to the module according to the labels on the cables. Step 9 If the main control module is replaced, set parameters by referring TP48200T-D20A1 & D20A2 & D14A1 & D14A2 Quick Installation Guide. ----End Figure 5-3 Pulling out the old module
Issue 01 (2012-06-01)
58
5 Maintenance
Issue 01 (2012-06-01)
59
5 Maintenance
Issue 01 (2012-06-01)
60
5 Maintenance
Step 3 Open the top cover and secure the butterfly nut, as shown in Figure 5-10.
Issue 01 (2012-06-01)
61
5 Maintenance
Step 4 Remove the power cables of the fans. Step 5 Loosen the screws on top of the fan assembly, as shown in Figure 5-11.
Issue 01 (2012-06-01)
62
5 Maintenance
Step 6 Install the new fan assembly, as shown in Figure 5-12. Figure 5-12 Installing the fan assembly
Step 7 Install the power cables of the fans. Step 8 Close the top cover. Step 9 Tighten the screws on top of the cabinet as shown in Figure 5-13.
Issue 01 (2012-06-01)
63
5 Maintenance
----End
Replacing TEC
To replace the TEC, perform the following steps: Step 1 Power off the TEC. 1. 2. Switch off the TEC circuit breaker on the DC PDU or power system. Remove the power cables and alarm cables.
Issue 01 (2012-06-01)
64
5 Maintenance
Step 3 Install a new TEC refrigeration module. 1. 2. 3. 4. Secure a new TEC refrigeration module to the door using the removed screws. Reinstall the cover to the temperature control door using the removed screws. Install power cables to the correct poles. Install the dry contact alarm cables to the correct poles.
Step 4 Power on the TEC. 1. 2. 3. 4. Switch on the TEC circuit breaker on the DC PDU or power system. Power on the TEC for a self-check and a refrigeration function test. Check that the ALM indicators on the temperature controller and monitoring device turn off. After the TEC runs properly for 5 minutes, check the refrigeration function.
----End
Replacing CMUA
To replace the CMUA, perform the following steps: Step 1 Switch off the CMUA circuit breaker on the DC PDU or power system. Step 2 Remove the CMUA. 1. Remove the two M4 screws from the CMUA cover, and then remove the CMUA cover, as shown in Figure 5-15.
Issue 01 (2012-06-01)
65
5 Maintenance
2. 3.
Label the cables and then remove these cables. Remove the four M3 screws on CMUA board and then remove the CMUA board , as shown in Figure 5-16.
Step 3 Install a new CMUA board. 1. 2. 3. 4. Install a new CMUA board using the four removed screws. Install jumper caps on the jumper slot, by referring to 2.2.1 CMUA Jumper Slot or 2.2.2 CMUA Jumper Slot. Connect all the removed cables to the CMUA. Reinstall ther cover using the two removed screws.
Step 4 Power on the CMUA. 1. 2. 3. 4. Switch on the CMUA circuit breaker on the DC PDU or power system. Power on the CMUA for a self-check and a refrigeration function test. Check that the ALM indicators on the temperature controller and monitoring device turn off. After the CMUA runs properly for 5 minutes, check the refrigeration function.
----End
Issue 01 (2012-06-01)
66
5 Maintenance
Issue 01 (2012-06-01)
67
5 Maintenance
Issue 01 (2012-06-01)
68
5 Maintenance
Step 3 Remove the door lock. Step 4 Secure a new lock using screws. Step 5 Connect the cable between the Bluetooth controller and the door lock. ----End Figure 5-20 Replacing the door lock
Step 2 Record the connections of the alarm cables and then disconnect them. Step 3 Loosen the screws on the door status sensor and then remove the sensor. Step 4 Install a new door status sensor in position and tighten the screws.
Issue 01 (2012-06-01) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd 69
5 Maintenance
Step 5 Install the alarm cables of the new door status sensor according to the recorded connections, and then install the case. ----End
Step 3 Press the contact plate at the bottom of the intelligent power meter using a flat-head screwdriver again to install the new intelligent power meter in the correct position. Step 4 Install the baffle plate and tighten the screws. ----End Figure 5-23 Installing the intelligent power meter
Issue 01 (2012-06-01)
70
5 Maintenance
Step 2 Remove the GPRS antenna, as shown in Figure 5-25. Figure 5-25 Removing the GPRS antenna
Issue 01 (2012-06-01)
71
5 Maintenance
Step 3 Install the GPRS antenna, as shown in Figure 5-26. Figure 5-26 Installing the GPRS antenna
Step 4 Installing the GPRS cable to the GPRS module, as shown in Figure 5-27. Figure 5-27 Installing the GPRS cable
Issue 01 (2012-06-01)
72
5 Maintenance
Issue 01 (2012-06-01)
73
6 Monitoring Function
6
6.1 LCD User Interface
Selecting a Display Language Querying Active Alarms
Monitoring Function
After the ECC500 is powered on, the screen for selecting a display language is displayed. You can select Chinese, English or other language by pressing or and enter the standby screen by pressing Enter.
This section describes how to query active alarms on the LCD, as shown in Figure 6-1. The parameter values in Figure 6-1 are for reference only. Figure 6-1 Querying active alarms
NOTE
110215 indicates February 15, 2011. The alarm severity and date are displayed alternatively.
Issue 01 (2012-06-01)
74
6 Monitoring Function
NOTE
To open the Settings page, Quick Setting page, and Control page, you need to enter a password. The default user name is admin and the default password is 001. You can add or delete users, and change the user name and password.
Issue 01 (2012-06-01)
75
6 Monitoring Function
Issue 01 (2012-06-01)
76
6 Monitoring Function
Issue 01 (2012-06-01)
77
6 Monitoring Function
Active Alarm
Running Status
Settings
Control
Quick Settings
Site Summary
Alarm Setting
Site Summary
Qty of Battery
PSU Summary
Site Summary
Batt Summ
Rated Capacity
PSU
PSU Summary
PSU Summary
Set Date
Batt Summ
PSU
Set Time
VRLA Batt
LVD Setting
IP Address
ECC500
ECC500
Subnet Mask
GPRS
Comm Para
Gateway
Alarm History
System Para
View the system status, including the PSU status, battery status, and active alarm information. Configure system parameters. Configure network parameters, including IP addresses, host communications addresses and baud rates under master/slave protocol. Control the system, such as choosing battery boost or floating charge and resetting PSUs. Add or delete users, and change user names and passwords. Upgrade software online. Query and export historical logs and alarms. Configure alarm parameters, alarm severities, and the relationship between alarms and dry contacts. Set the system date and time, site and storage battery type, save, download, and upload configuration files. Query electronic label information. Configure site information including date and site name and deal with configuration files and so on.
Set the IP address, gateway, and subnet mask of the SMU on the LCD before logging into the WebUI.
Issue 01 (2012-06-01)
78
6 Monitoring Function
Step 4 On the login page shown in Figure 6-6, set User Name to admin and Password to 001, and then press Login. Figure 6-6 Login page
Issue 01 (2012-06-01)
79
6 Monitoring Function
Issue 01 (2012-06-01)
80
6 Monitoring Function
Issue 01 (2012-06-01)
81
6 Monitoring Function
Issue 01 (2012-06-01)
82
6 Monitoring Function
Managing Users
You can create and delete users and modify user information in the User Management pane shown in Figure 6-12. Users are classified into three types: admin, engineer, and operator. Different user types have different operation rights. Only admin users have user management rights.
Issue 01 (2012-06-01)
83
6 Monitoring Function
Upgrading Software
You can upgrade SMU and PSU software in the Upgrade pane shown in Figure 6-13 To upgrade software, perform the following steps: Step 1 Click Browse to select the software and then click Send. Step 2 After the software information is displayed under Available package active, select the software and click Activate. The software upgrade progress is displayed. A message is displayed when the upgrade is successful. ----End
Issue 01 (2012-06-01)
84
6 Monitoring Function
Issue 01 (2012-06-01)
85
6 Monitoring Function
Issue 01 (2012-06-01)
86
6 Monitoring Function
Issue 01 (2012-06-01)
87
6 Monitoring Function
Energy Saving
You can set Basic Parameters, Control For Different Rates, Control for Exceeding Max Power, Daily Electric Consum Mode, Monthly Electric Consum Mode in the Energy Saving pane shown in Figure 6-18. Figure 6-18 Energy Saving
Issue 01 (2012-06-01)
88
6 Monitoring Function
Issue 01 (2012-06-01)
89
A Technical Specifications
A
Table A-1 Technical specifications Category Environmental conditions Item Operating temperature Storage temperature Transportation temperature Operating humidity
Technical Specifications
Specifications 10 C to +45 C (14 F to +113 F) 40 C to +70 C (40 F to +158 F) 40 C to +70 C (40 F to +158 F) 5%100% RH 5%100% RH 0-4000 m (0-13123.2 ft) When the altitude ranges from 2000 m (6561.6 ft) to 4000 m (13123.2 ft), the operating temperature is derated by 1 C (1.8 F) for each additional 200 m (656.16 ft).
AC input
Input mode
220V three-phase five-line (L1, L2, L3, N, PE) 110V three-phase five-line (L1, L2, L3, N, PE) 220V single-phase three-line (L, N, PE) 110V dual-live-wire (L1, L2, N, PE) 110V dual-live-wire (L1, L2, PE) 220V single-phase three-line (L, N, PE)
Input voltage
85V AC - 300 V AC
Issue 01 (2012-06-01)
90
A Technical Specifications
Category
200-240/346-415V AC for 220V three-phase five-line (L1, L2, L3, N, PE) 100-127/200-240 V AC for 110V three-phase five-line (L1, L2, L3, N, PE) 200-240 V AC for 220V single-phase three-line (L, N, PE) 100-120/200-240 V AC for 110V dual-live-wire (L1, L2, N, PE) 100-120/200-240 V AC for 110V dual-live-wire (L1, L2, PE) 200-240 V AC for 220V single-phase three-line (L, N, PE)
Input frequency Rated frequency Power factor DC output Output voltage range Default output voltage Maximum output power Regulated voltage precision Peak-to-peak noise voltage AC input protection AC input overvoltage protection threshold AC input overvoltage recovery threshold AC input undervoltage protection threshold
4565 Hz 50/60 Hz 0.99 42 V DC to 58V DC 53.5 V DC Number of rectifiers multiplied by the output power of a single rectifier. 1% 200 mV (020 MHz) Overvoltage protection is performed when the single-phase AC input voltage exceeds the AC input overvoltage protection threshold (300 V AC by default). When the voltage is restored to 290 V AC, the output resumes.
Undervoltage protection is performed when the single-phase AC input voltage is below the AC input undervoltage protection threshold (85 V AC by default).
Issue 01 (2012-06-01)
91
A Technical Specifications
Category
DC output protection
58.560.5 V DC
Rectifier (R4850G1)
3000W 58.560.5 VDC (can be set by monitoring unit ) 1.If the overvoltage occurs inside the rectifier due to a fault, the rectifier will latch off. 2.If the output voltage is higher than 63 V and lasts for more than 500 ms, the rectifier will latch off.
EMC
CE
CISPR 22/EN 55022 class B (AC terminal) CISPR 22/EN 55022 class A (DC output terminal)
CISPR 22/EN 55022 Class B IEC 61000-3-12 IEC 61000-3-3 Contact discharge voltage: 6kV (Class B); air discharge voltage: 8 kV (Class B); Contact discharge voltage: 8kV (Class B); air discharge voltage: 15 kV (Class R); standard: IEC61000-4-2
EFT RS CS SURGE
The voltage at signal ports is 1 kV, and the voltage at the power ports is 2 kV (criterion B). 10 V/m (criterion A) The voltage at signal ports is 3V and power ports is 10 V (criterion A). It complies with the IEC61000-4-5 standard. The voltage at the AC power ports in differential mode is 2 kV. The voltage at the AC power ports in common mode is 4 kV (criterion B).
Issue 01 (2012-06-01)
92
A Technical Specifications
Category Others
Specifications
Differential mode: 10 kA Common mode: 20 kA MTBF Structure Dimensions (H x W x D) 200,000 hours (at 30 C) TP48200T-D20A1 & D20A2:
Cabinet: 2060 mm (81.1 in.) x 700 mm (27.56 in.) x 700 mm (27.56 in.) Base: 180 mm (7.1 in.) x 700 mm (27.56 in.) x 700 mm (27.56 in.) Cabinet: 1400 mm (55.1 in.) x 700 mm (27.56 in.) x 700 mm (27.56 in.) Base: 180 mm (7.1 in.) x 700 mm (27.56 in.) x 700 mm (27.56 in.)
Weight
TP48200T-D20A1 & D20A2: 200 kg (excluding rectifiers and storage batteries) TP48200T-D14A1 & D14A2: 160 kg (excluding rectifiers and storage batteries)
Cooling capacity
Issue 01 (2012-06-01)
93
B LCD Menu
B
Table B-1 LCD Menu Main Menu Active Alarm Running Status Second-Lev el Menu Site Summary Third-Level Menu System Voltage Total Load Ambient Humi 1 Ambient Temp 1 Qty of Battery Sys. Efficiency Peak Power Peak Power Time System Type PSU Summary Total Current Used Capacity AC Voltage AC Total Curr AC Frequency DC Total Power PSU Batt Summ Total Current Pre Disch Time BattChargeSta Fourth-Le vel Menu Default Value -
LCD Menu
Range -
Issue 01 (2012-06-01)
94
B LCD Menu
Main Menu
Second-Lev el Menu
Default Value -TP48200T_D1 4A2 58.0 V 60.0 V 45.0 V 43.0 V 300 A 75 mV 1 280 V
VRLA Batt
VRLA Batt 1
ECC500 GPRS
MUC01A_DI_6 GPRS Slot ID GPRS Cur Signal GPRS Status SIM Card Status GPRS IP Address
Alarm Relay Site Summary PSU Summary PSU Batt Summ VRLA Batt
Site Summary
System Type DC Over Volt DC Ultra Over V DC Under Volt DC Ultra UnderV Shunt Current Shunt Voltage Qty of Battery AC Over Volt
Issue 01 (2012-06-01)
95
B LCD Menu
Main Menu
Second-Lev el Menu
Third-Level Menu AC Under Volt System AC Type AC Fail Time Dial-up Network Amb Hi Temp Pt Amb Low Temp Pt Amb Hi Humi Pt Amb Low Humi Pt Amb V-Hi Temp High Power Pt D.G. Function Diesel Capaciey D.G. start Cap D.G. stop Cap Air-Con. StPwr Air-Con. WtPwr Max Charge Time Min Charge Time D.G. Working E04A_ D (0108)Alm Act Record Interval Alarm Voice Dly Alarm Voice En DST Enable Forbid All Alm
Default Value 180 V Single Phase 10Min Disable 40degC 0degC 80% 10% 50degC 80% Non 12.5KVA 30% 90% 3.0KW 0.6KW 12H 0H Close Open 15Min 10Min No Disable No Disable 0s 59.5V
Range 60-300 V Single Phase, ThreePhase 0-30Min Disable,Enable 25 - 80degC -20 -20 degC 0%-100% 0%-100% 25 - 80degC 1%-120% NonCurrent Limit,Smart Ctrl 1 KVA-100 KVA 10-100% 10-100% 0.0 -300.0 KW 0.0 -300.0 KW 6-100H 0-5H Close, Open Close, Open 1 -60 Min 1-100 Min No,Yes Disable, Enable No,Yes Disable,Enable 0-20s 58.5-60.5V
PSU Summary
Issue 01 (2012-06-01)
96
B LCD Menu
Main Menu
Second-Lev el Menu
Third-Level Menu High PSU Cap % Low PSU Cap % Rect Redund Ena
Fourth-Le vel Menu Smart Mgmt En Float Charge Boost Charge Current Limit Over Current Rated Capacity Install Date
Default Value 20% 100% Disable Disable 53.5 V 56.4 V 0.15C10 0.25C10 100Ah 2010-01-01 Enable 0.05C10 30 Min 80% 10 Min 0.01C10 30 Min 16 H Enable 30 Day 9H
Range 0-120% 0-120% Disable,Enable Disable,Enable 48.0-58.3 V 48.0-58.3 V 0.05-0.25 0.05-0.50 10-10000 Ah YYYY-MM-DD Enable, Disable 0.01-0.30 2-1440 Min 50-100% 2-1440 Min 0.01-0.30 2-540 Min 5-48 H Enable, Disable 1-365 Days 1-24 H
Basic Para
FC BC
Auto BC Enabled To BC Current Curr BC Delay To BC Capacity Capa BC Delay BC to FC Curr BC to FC Delay Max BC Time Cyclic BC Ena Cyclic BC Intv Cyc BC
Issue 01 (2012-06-01)
97
B LCD Menu
Main Menu
Second-Lev el Menu
Third-Level Menu
Default Value
Range
Battery Test
Test End Volt Test End Capa Test End Temp Test End Time Mains Fail Test Batt Test Type Short Test Ena Short Test Intv ShortT Duration
46.0 V 20.0% 5degC 480Min Disable No Test Enable 30 Day 5 Min 80 mV/degC 25degC 20.00 H 10.00H 4.00 H 2.42 H 1.63 H 1.16H 0.87 H 0.61 H
43.0-53.0 V 0.0-100.0% -5-15 degC 1-6000 Min Disable,Enable No Test,Cyclic Test, Plan Test Enable,Disable 1-360 Days 1-240 Min 0-500 mV/degC 5-45 degC 0.20-50.00 H 0.20-50.00 H 0.20-50.00 H 0.20-50.00 H 0.20-50.00 H 0.20-50.00 H 0.20-50.00 H 0.20-50.00 H
Temp Comp
Charge Disch
0.05C10 DisTime 0.1C10 Dis Time 0.2C10 Dis Time 0.3C10 Dis Time 0.4C10 Dis Time 0.5C10 Dis Time 0.6C10 Dis Time 0.7C10 Dis Time
Issue 01 (2012-06-01)
98
B LCD Menu
Main Menu
Second-Lev el Menu
Third-Level Menu
Fourth-Le vel Menu 0.8C10 Dis Time 0.9C10 Dis Time 1.0C10 Dis Time Capacity Coeff
Range 0.20-50.00 H 0.20-50.00 H 0.20-50.00 H 60-1005% Lower DC Volt,BLVD,Do Nothing 42.0-53.0 V 25-80 degC 25-80 degC -20-20 degC -20-20 degC Enable, Disable By Voltage,By Capacity,By Time 35.0-47.8 V 37.0-53.0 V Disable ,Enable Normal Close ,Normal Open 0~31 9600,19200
Other
Batt Temp VHigh Over Temp Volt Batt High Temp Bat V-High Temp Batt Low Temp Batt V-Low Temp
50.5V 45degC 53degC 5degC 10degC Enable By Voltage 43.2 V 51.5 V Disable Normal Close
LVD Setting
BLVD Enabled BLVD Mode BLVD Voltage BLVD Recon Volt LLVD1 Enabled
ECC500
MUC01A_DI_1
Comm Para
Network Mode IP Address Subnet Mask Gateway Host Comm Addr Comm Baudrate
Issue 01 (2012-06-01)
99
B LCD Menu
Main Menu
Second-Lev el Menu
Third-Level Menu DHCP Phone Number (1-3) Account(1-3) Password NetEco Main IP NetEco Bak IP NetEco Port
Default Value Disable 58.251.159.33 58.251.159.33 31220 ENGLISH GMT +08:00 Yes Yes Yes Yes NA 5 Auto Yes No No No Open Yes Float Charge Stop Yes Yes
Range Disable,Enable English , Chinese Auto ,Manual Yes, No No, Yes Open, Close Float Charge, Boost Charge Stop, Start -
System Para
LUI Language Set Date Set Time Set Time Zone Save As Def Cfg Restore Def Cfg Restore Manu Cfg Logout Set Site Name Set Batt Type LCD Contrast
Control
Site Summary
Auto/Man Ctrl Network Detect Clear PeakPower Clr ATS Alarm Clr D.G.Fault E04A_D(01-08) Smoke 1 Reset
Batt Summ
BC/FC Ctrl Battery Test Reset Batt Cap Clear Batt Alm
Issue 01 (2012-06-01)
100
B LCD Menu
Main Menu
Second-Lev el Menu
Default Value Stop Connect 121% 53.2V On Yes Yes Yes 1 100 Ah -
Range Stop, Start Connect, Disconnect 1~121% 42.0~58.0 V On,Off 0-50 10 Ah-10000Ah -
PSU Summary
Current Limit DC Votage Ctrl On/Off Control Reset Clear Rect Lost Clr Phase Fail
PSU Clr Alm Hist Quick Settings Qty of Battery Rated Capacity Set Date Set Time IP Address Subnet mask Gateway
Issue 01 (2012-06-01)
101
C
A AC PDU ASIC ATS D DC PDU
Alternating Current Power Distribution Unit Application-Specific Integrated Circuit Automatic Transfer Switch
Issue 01 (2012-06-01)
102
Issue 01 (2012-06-01)
103