Download as pdf or txt
Download as pdf or txt
You are on page 1of 96

Power Factor Correction

Reactive Energy Management


Low Voltage components
Catalogue 2011

Reactive Energy management

Your requirements.

Optimize energy consumption


By reducing electricity bills, By reducing power losses, By reducing CO2 emissions.

Increase power availability


Compensate for voltage sags detrimental to process operation, Avoid nuisance tripping and supply interruptions.

Improve your business performance


Optimize installation size, Reduce harmonic distortion to avoid the premature ageing of equipment and destruction of sensitive components.

Our solutions.
Reactive energy management
In electrical networks, reactive energy results in increased line currents for a given active energy transmitted to loads. The main consequences are: Need for oversizing of transmission and distribution networks by utilities, Increased voltage drops and sags along the distribution lines, Additional power losses. This results in increased electricity bills for industrial customers because of: Penalties applied by most utilities on reactive energy, Increased overall kVA demand, Increased energy consumption within the installations. Reactive energy management aims to optimize your electrical installation by reducing energy consumption, and to improve power availability. Total CO2 emissions are also reduced. Utility power bills are typically reduced by 5 % to 10 %.

+
Our energy con-sumption was reduced by

9%

after we installed 10 capacitor banks with detuned reactors. Electricity bill optimised by 8 % and payback in 2 years.

Testifies Michelin Automotive in France.


Energy consumption reduced by

5%

with LV capacitor bank and active filter installed. POMA OTIS Railways, Switzerland.

70 capacitor banks with detuned reactors installed, energy consumption reduced by 10 %, electrcity bill optimised by 18 %, payback in just

1 year.
Madrid Barrajas airport Spain.

Improve electrical networks and reduce energy costs


Power Factor Correction
Every electric machine needs active power (kW) and reactive power (kvar) to operate. The power rating of the installation in kVA is the combination of both: (kVA) = (kW) + (kvar). The Power Factor has been defined as the ratio of active power (kW) to apparent power (kVA). Power Factor = (kW) / (kVA). The objective of Reactive Energy management is improvement of Power Factor, or Power Factor Correction. This is typically achieved by producing reactive energy close to the consuming loads, through connection of capacitor banks to the network.

II

Ensure reliability and safety on installations

Quality and reliability


 Continuity of service thanks to the high performance and long life expectancy of capacitors. 100% testing in manufacturing plant. Design and engineering with the highest international standards.

Safety
Tested safety features integrated on each phase. Over-pressure system for safe disconnection at the end of life. All materials and components are free of PCB pollutants.

Thanks to the know-how developed over 50 years, Schneider Electric ranks as the global specialist in Energy management providing a unique and comprehensive portfolio. Schneider Electric helps you to make the most of your energy with innovative, reliable and safe solutions.

Efficiency and productivity


 Product development including innovation in ergonomics and ease of installation and connection.  Specially designed components to save time on installation and maintenance.  All components and solutions available through a network of distributors and partners in more than 100 countries.

III

Quality & Environment


Quality certified ISO 9001
A major strength
In each of its units, Schneider Electric has an operating organization whose main role is to verify quality and ensure compliance with standards. This procedure is: uniform for all departments; recognized by numerous customers and official organizations. But, above all, its strict application has made it possible to obtain the recognition of independent organizations. The quality system for design and manufacturing is certified in compliance with the requirements of the ISO 9001 Quality Assurance model.

Stringent, systematic controls


During its manufacture, each equipment item undergoes systematic routine tests to verify its quality and compliance: measurement of operating capacity and tolerances; measurement of losses; dielectric testing; checks on safety and locking systems; checks on low-voltage components; verification of compliance with drawings and diagrams. The results obtained are recorded and initialled by the Quality Control Department on the specific test certificate for each device.

Schneider Electric undertakes to reduce the energy bill and CO2 emissions of its customers by proposing products, solutions and services which fit in with all levels of the energy value chain. The Power Factor Correction and harmonic filtering offer form part of the energy efficiency approach.

IV

A new solution for building your electrical installations


A comprehensive offer
Power Factor Correction and harmonic filtering form part of a comprehensive offer of products perfectly coordinated to meet all medium- and low-voltage power distribution needs. All these products have been designed to operate together: electrical, mechanical and communications consistency. The electrical installation is accordingly both optimized and more efficient: improved continuity of service; reduced power losses; guarantee of scalability; efficient monitoring and management. You thus have all the trumps in hand in terms of expertise and creativity for optimized, reliable, expandable and compliant installations.

Tools for easier design and setup


With Schneider Electric, you have a complete range of tools that support you in the knowledge and setup of products, all this in compliance with the standards in force and standard engineering practice. These tools, technical notebooks and guides, design aid software, training courses, etc. are regularly updated.

Schneider Electric joins forces with your expertise and your creativity for optimized, reliable, expandable and compliant installations.

Because each electrical installation is a specific case, there is no universal solution. The variety of combinations available allows you to achieve genuine customization of technical solutions. You can express your creativity and highlight your expertise in the design, development and operation of an electrical installation.

Reactive Energy Management

General contents

Power Factor Correction guideline

Low Voltage capacitors

15

Detuned reactors

67

Power Factor controllers

71

Contactors

75

Appendix

79

Power Factor Correction guideline

Contents

Presentation

Why reactive energy management? Method for determining compensation Low Voltage capacitors with detuned reactors Rated voltage and current Capacitor selection guide Construction of references

4 6 10 11 12 13

Principle 13
Low Voltage capacitors 15 Detuned reactors 67 Power Factor controllers 71 Contactors 75 Appendix 79

Power Factor Correction guideline

Why reactive energy management?


Principle of reactive energy management
All AC electrical networks consume two types of power: active power (kW) and reactive power (kvar):  The active power P (in kW) is the real power transmitted to loads such as motors, lamps, heaters, computers, etc. The electrical active power is transformed into mechanical power, heat or light.  The reactive power Q (in kvar) is used only to power the magnetic circuits of machines, motors and transformers. The apparent power S (in kVA) is the vector combination of active and reactive power. The circulation of reactive power in the electrical network has major technical and economic consequences. For the same active power P, a higher reactive power means a higher apparent power, and thus a higher current must be supplied. The circulation of active power over time results in active energy (in kWh). The circulation of reactive power over time results in reactive energy (kvarh). In an electrical circuit, the reactive energy is supplied in addition to the active energy.

DE90087.eps

In this representation, the Power Factor (P/S) is equal to cosj.

Due to this higher supplied current, the circulation of reactive energy in distribution networks results in: >O  verload of transformers >H  igher temperature rise in power cables > Additional losses >L  arge voltage drops >H  igher energy consumption and cost >L  ess distributed active power.

DE90071_r.eps

Power generation

Active energy Reactive energy

Transmission network

Active energy

Motor
Reactive energy

Reactive energy supplied and billed by the energy provider. Active energy Active energy

Qc

Transmission For generation these reasons, there is a great advantage in generating reactive Motor network energy at the load level in order to prevent the unnecessary circulation Reactive energy of current in the network. This is what is known as power factor correction. This is obtained by the connection of capacitors, which produce reactive energy in opposition toCapacitors the energy absorbed by loads such as motors.

Power

DE90088.eps

The result is a reduced apparent power, and an improved power factor P/S as illustrated in the diagram opposite.
Motor Thegeneration power generation and transmission network networks are partially relieved, Reactive energy Reactive energy reducing power losses and making additional transmission capacity available. Power
Active energy

Transmission

Active energy

DE90071_r.eps

Power generation

Active energy

Transmission network

Active energy

Motor
Reactive energy

Capacitors
The reactive power is supplied by capacitors. No billing of reactive power by the energy supplier.

Why reactive energy management?

+
Benefits of reactive energy management
Optimized management of reactive energy brings economic and technical advantages.

Savings on the electricity bill


>  Eliminating penalties on reactive energy and decreasing kVA

demand.
>  Reducing power losses generated in the transformers and

conductors of the installation.

Example: Loss reduction in a 630 kVA transformer PW = 6,500 W with an initial Power Factor = 0.7. With power factor correction, we obtain a final Power Factor = 0.98. The losses become: 3,316 W, i.e. a reduction of 49 %.

Increasing available power


A high power factor optimizes an electrical installation by allowing better use of the components. The power available at the secondary of a MV/LV transformer can therefore be increased by fitting power factor correction equipment on the low voltage side. The table opposite shows the increased available power at the transformer output through improvement of the Power Factor from 0.7 to 1.

Power factor
0.7 0.8 0.85 0.90 0.95 1

Increased available power


0% +14% +21% +28% +36% +43%

Reducing installation size


Installing power factor correction equipment allows conductor cross-section to be reduced, since less current is absorbed by the compensated installation for the same active power. The opposite table shows the multiplying factor for the conductor cross-section with different power factor values.

Power factor

Cable crosssection multiplying factor


1 1.25 1.67 2.50

1 0.80 0.60 0.40

Reducing voltage drops in the installation


Installing capacitors allows voltage drops to be reduced upstream of the point where the power factor correction device is connected. This prevents overloading of the network and reduces harmonics, so that you will not have to overrate your installation.

Power Factor Correction guideline

Method for determining compensation

The selection of Power Factor Correction equipment can follow a 4-step process: Calculation of the required reactive energy. Selection of the compensation mode: - Central, for the complete installation - By sector - For individual loads, such as large motors. Selection of the compensation type: - Fixed, by connection of a fixed-value capacitor bank; - Automatic, by connection of a different number of steps, allowing adjustment of the reactive energy to the required value; - Dynamic, for compensation of highly fluctuating loads. Allowance for operating conditions and harmonics.

Step 1: Calculation of the required reactive power


DE90091.eps

The objective is to determine the required reactive power Qc (kvar) to be installed, in order to improve the power factor cos and reduce the apparent power S. For <, we obtain: cos>cos and tan<tan. This is illustrated in the diagram opposite. Qc can be determined from the formula Qc = P. (tan - tan), which is deduced from the diagram. Qc = power of the capacitor bank in kvar. P = active power of the load in kW. tan = tangent of phase shift angle before compensation. tan = tangent of phase shift angle after compensation. The parameters and tan can be obtained from billing data, or from direct measurement in the installation. The following table can be used for direct determination.
Before compensation Reactive power (kvar) to be installed per kW of load, in order to get the required cosj or tanj tan j 0.75 0.62 0.48 0.41 0.33 0.23 0.00 cos j 0.80 0.85 0.90 0.925 0.95 0.975 1.000
0.98 0.27 0.21 0.16 0.11 0.05 1.11 0.40 0.34 0.29 0.24 0.18 0.13 0.08 0.03 1.25 0.54 0.48 0.42 0.37 0.32 0.27 0.21 0.16 0.11 0.06 1.32 0.61 0.55 0.50 0.44 0.39 0.34 0.29 0.24 0.18 0.13 0.07 1.40 0.69 0.64 0.58 0.53 0.47 0.42 0.37 0.32 0.26 0.21 0.16 1.50 0.79 0.74 0.68 0.63 0.57 0.52 0.47 0.42 0.37 0.31 0.26 1.73 1.02 0.96 0.91 0.86 0.80 0.75 0.70 0.65 0.59 0.54 0.48

tan j 1.73 1.02 0.96 0.91 0.86 0.80 0.75 0.70 0.65 0.59 0.54 0.48

cosj 0.5 0.70 0.72 0.74 0.76 0.78 0.80 0.82 0.84 0.86 0.88 0.90

Example: consider a 1000 kW motor with cos j=0.8 (tanj=0.75). In order to obtain cos j=0.95, it is necessary to install a capacitor bank with a reactive power equal to k x P, i.e.: Qc = 0.42 x 1000 = 420 kvar.

Method for determining compensation


Step 2: Selection of the compensation mode
Supply Bus

Transformer

Circuit breaker

The location of low-voltage capacitors in an installation constitutes the mode of compensation, which may be central (one location for the entire installation), by sector (section-by-section), at load level, or some combination of the latter two. In principle, the ideal compensation is applied at a point of consumption and at the level required at any moment in time. In practice, technical and economic factors govern the choice.

CC

GC IC M M IC IC M

GC IC M

The location for connection of capacitor banks in the electrical network is determined by:  the overall objective (avoid penalties on reactive energy relieve transformer or cables, avoid voltage drops and sags) the operating mode (stable or fluctuating loads) the foreseeable influence of capacitors on the network characteristics the installation cost.

Central compensation
CC : Central Compensation GC : Group Compensation IC : Individual Compensation M : Motor Load

The capacitor bank is connected at the head of the installation to be compensated in order to provide reactive energy for the whole installation. This configuration is convenient for a stable and continuous load factor.

Group compensation (by sector)


The capacitor bank is connected at the head of the feeders supplying one particular sector to be compensated. This configuration is convenient for a large installation, with workshops having different load factors.

Compensation of individual loads


The capacitor bank is connected right at the inductive load terminals (especially large motors). This configuration is very appropriate when the load power is significant compared to the subscribed power. This is the ideal technical configuration, as the reactive energy is produced exactly where it is needed, and adjusted to the demand.

Power Factor Correction guideline

Method for determining compensation


Step 3: Selection of the compensation type
Different types of compensation should be adopted depending on the performance requirements and complexity of control: Fixed, by connection of a fixed-value capacitor bank  Automatic, by connection of a different number of steps, allowing adjustment of the reactive energy to the required value Dynamic, for compensation of highly fluctuating loads.

Fixed compensation
This arrangement uses one or more capacitor(s) to provide a constant level of compensation. Control may be: Manual: by circuit-breaker or load-break switch Semi-automatic: by contactor Direct connection to an appliance and switched with it. These capacitors are installed: At the terminals of inductive loads (mainly motors)  At busbars supplying numerous small motors and inductive appliances for which individual compensation would be too costly In cases where the load factor is reasonably constant.

Automatic compensation
This kind of compensation provides automatic control and adapts the quantity of reactive power to the variations of the installation in order to maintain the targeted cos j. The equipment is installed at points in an installation where the active-power and/or reactive-power variations are relatively large, for example: on the busbars of a main distribution switchboard on the terminals of a heavily-loaded feeder cable. Where the kvar rating of the capacitors is less than or equal to 15 % of the power supply transformer rating, a fixed value of compensation is appropriate. Above the 15 % level, it is advisable to install an automatically-controlled capacitor bank. Control is usually provided by an electronic device (Power Factor Controller) which monitors the actual power factor and orders the connection or disconnection of capacitors in order to obtain the targeted power factor. The reactive energy is thus controlled by steps. In addition, the Power Factor Controller provides information on the network characteristics (voltage amplitude and distortion, power factor, actual active and reactive power ) and equipment status. Alarm signals are transmitted in case of malfunction. Connection is usually provided by contactors. For compensation of highly fluctuating loads, fast and highly repetitive connection of capacitors is necessary, and static switches must be used.

Dynamic compensation
This kind of compensation is required when fluctuating loads are present, and voltage fluctuations have to be prevented. The principle of dynamic compensation is to associate a fixed capacitor bank and an electronic var compensator, providing either leading or lagging reactive currents. The result is continuously varying fast compensation, perfectly suitable for loads such as lifts, crushers, spot welding, etc.

Method for determining compensation

Step 4: Allowing for operating conditions and harmonics


Capacitors should be selected depending on the working conditions expected during their lifetime.

To know more about the influence of harmonics in electrical installations, see appendix page 80

Allowing for operating conditions


The operating conditions have a great influence on the life expectancy of capacitors. The following parameters should be taken into account: Ambient Temperature (C)  Expected over-current, related to voltage disturbances, including maximum sustained overvoltage Maximum number of switching operations/year Required life expectancy.

Allowing for harmonics


Depending on the magnitude of harmonics in the network, different configurations should be adopted. Standard capacitors: when no significant non-linear loads are present. Oversized capacitors: when a few non-linear loads are present. The rated current of capacitors must be increased in order to cope with the circulation of harmonic currents. Harmonic rated capacitors used with detuned reactors. Applicable when a significant number of non-linear loads are present. Reactors are necessary in order to limit the circulation of harmonic currents and avoid resonance. Tuned filters: when non-linear loads are predominant, requesting harmonic mitigation. A special design is generally necessary, based on on-site measurements and computer simulations of the network.

Capacitor selection
Different ranges with different levels of ruggedness are proposed: "SDuty": Standard duty capacitors for standard operating conditions, and when no significant non-linear loads are present. "HDuty": Heavy duty capacitors for difficult operating conditions, particularly voltage disturbances, or when a few non-linear loads are present. The rated current of capacitors must be increased in order to cope with the circulation of harmonic currents. "Energy": Specially designed capacitors, for harsh operating conditions, particularly high temperature.  Capacitors with detuned reactors: applicable when a significant number of non-linear loads are present.

Before

After
9

Power Factor Correction guideline

Low Voltage capacitors with detuned reactors


Reactors should be associated with capacitor banks for Power Factor Correction in systems with significant non-linear loads, generating harmonics. Capacitors and reactors are configured in a series resonant circuit, tuned so that the series resonant frequency is below the lowest harmonic frequency present in the system. For this reason, this configuration is usually called Detuned Capacitor Bank, and the reactors are referred to as Detuned Reactors. The use of detuned reactors thus prevents harmonic resonance problems, avoids the risk of overloading the capacitors and helps reduce voltage harmonic distortion in the network. The tuning frequency can be expressed by the relative impedance of the reactor (in %), or by the tuning order, or directly in Hz. The most common values of relative impedance are 5.7, 7 and 14 % (14 % is used with high level of 3rd harmonic voltages).
Relative impedance (%) 5.7 7 14 Tuning order 4.2 3.8 2.7 Tuning frequency @50Hz (Hz) 210 190 135 Tuning frequency @60Hz (Hz) 250 230 160

The selection of the tuning frequency of the reactor capacitor depends on several factors: Presence of zero-sequence harmonics (3, 9, ) Need for reduction of the harmonic distortion level Optimization of the capacitor and reactor components Frequency of ripple control system if any.  To prevent disturbances of the remote control installation, the tuning frequency should be selected at a lower value than the ripple control frequency.  In a detuned filter application, the voltage across the capacitors is higher than the systems rated voltage. In that case, capacitors should be designed to withstand higher voltages.  Depending on the selected tuning frequency, part of the harmonic currents is absorbed by the detuned capacitor bank. In that case, capacitors should be designed to withstand higher currents, combining fundamental and harmonic currents.

Effective reactive energy


In the pages relating to detuned capacitor banks (Harmonic HDuty and Harmonic Energy), the reactive energy (kvar) given in the tables is the resulting reactive energy provided by the combination of capacitors and reactors.

Capacitor rated voltage


Capacitors have been specially designed to operate in detuned bank configurations. Parameters such as the rated voltage, over-voltage and over-current capabilities have been improved, compared to standard configuration.

10

Rated voltage and current

According to IEC 60681-1 standard, the rated voltage (UN) of a capacitor is defined as the continuously admissible operating voltage. The rated current (IN) of a capacitor is the current flowing through the capacitor when the rated voltage (UN) is applied at its terminals, supposing a purely sinusoidal voltage and the exact value of reactive power (kvar) generated. Capacitor units shall be suitable for continuous operation at an r.m.s. current of (1.3 x IN). In order to accept system voltage fluctuations, capacitors are designed to sustain over-voltages of limited duration. For compliance to the standard, capacitors are for example requested to sustain over-voltages equal to 1.1 times UN, 8 h per 24 h. VarplusCan and VarplusBox capacitors have been designed and tested extensively to operate safely on industrial networks. The design margin allows operation on networks including voltage fluctuations and common disturbances. Capacitors can be selected with their rated voltage corresponding to the network voltage. For different levels of expected disturbances, different technologies are proposed, with larger design margin for capacitors adapted to the most stringent working conditions (HDuty & Energy).

VarplusCan and VarplusBox capacitors when used along with Detuned Reactors have to be selected with a rated voltage higher than network service voltage (Us). In detuned filter applications, the voltage across the capacitor is higher than the network service voltage (Us). The recommended rated voltage of capacitors to be used in detuned filter applications with respect to different network service voltage (Us) and relative impedance is given in the table below. These values ensure a safe operation in the most stringent operating conditions. Less conservative values may be adopted, but a case by case analysis is necessary.
Capacitor Rated Voltage UN (V) Network Service Voltage US (V) 50 Hz 60 Hz 400 690 400 480 480 830 480 575 480 480

Relative Impedance (%)

5.7 7 14

600 690

11

Power Factor Correction guideline

Capacitor selection guide

Capacitors must be selected depending on the working conditions expected during their lifetime.
Solution SDuty Description Standard capacitor Recommended use for > Networks with non significant non-linear loads > Standard over-current > Standard operating temperature > Normal switching frequency > Standard life expectancy Heavy-duty > A few non-linear loads capacitor > Significant over-current > Standard operating temperature > Significant switching frequency > Long life expectancy Capacitor for > Significant number of nonspecial conditions linear loads (up to 25 %) > Severe over-current > Extreme temperature conditions > Very frequent switching > Extra long life expectancy Max. condition NLL y 10 % 1.5 IN 55 C (class D) 5,000/year Up to 100,000h* NLL y 20 % 1.8 IN 55 C (class D) 7,000/year Up to 130,000h* NLL y 25 % 2.5 IN 70 C 10,000/year Up to 160,000h*

HDuty

Energy

* The maximum life expectancy is given considering standard operating conditions: rated voltage (UN), rated current (IN), 35 C ambient temperature. WARNING: the life expectancy will be reduced if capacitors are used in maximum working conditions.

Since the harmonics are caused by non-linear loads, an indicator for the magnitude of harmonics is the ratio of the total power of non-linear loads to the power supply transformer rating. This ratio is denoted NLL, and is also known as Gh/Sn: NLL = Total power of non-linear loads (Gh) / Installed transformer rating (Sn). Example: Power supply transformer rating: Sn = 630 kVA Total power of non-linear loads: Gh = 150 kVA NLL = (150/630) x 100 = 24 % It is recommended to use Detuned Reactors with Harmonic Rated Capacitors (higher rated voltage than the network service voltage - see the Harmonic Application Tables) for NLL > 25 % and up to 50 %. See page 73 for Voltage selection of capacitors with Detuned Reactors. Note: there is a high risk in selecting the capacitors based only on NLL as the harmonics in grid may cause current amplification and capacitors along with other devices may fail. Refer to page 80 for further details.

12

Construction of references Principle


Capacitors
B L R C Construction C = CAN B = BOX H Range S = SDuty H = HDuty E = Energy 1 0 4 A Power at 50 Hz 10.4 kvar at 50 Hz A = 50 Hz 1 2 5 B 4 0 Voltage 24 - 240 V 40 - 400 V 44 - 440 V 48 - 480 V 52 - 525 V 57 - 575 V 60 - 600 V 69 - 690 V 83 - 830 V

Power at 60 Hz 12.5 kvar at 60 Hz B = 60 Hz "000B" means: labelled only for 50 Hz

Example: BLRBH172A206B48 = V  arplusBox Heavy Duty, 480 V, 17.2 kvar at 50 Hz and 20.6 kvar at 60 Hz

Detuned reactors
L V R Detuned Reactor 0 5 Relative impedance 05 = 5.7 % 07 = 7 % 14 = 14 % 1 2 5 Power 12.5 kvar A Freq. A = 50 Hz B = 60 Hz 6 9 Voltage 40 - 400 V 48 - 480 V 60 - 600 V 69 - 690 V

Example: LVR05125A69 = Detuned Reactor, 690 V, 5.7 %, 12.5 kvar, 50 Hz.

13

Low Voltage capacitors

Contents

Presentation Power Factor Correction guideline Low Voltage capacitors

3 15

Offer Overview VarplusCan SDuty VarplusCan HDuty VarplusCan Energy VarplusCan SDuty harmonic applications VarplusCan SDuty + Detuned Reactor + Contactor VarplusCan HDuty harmonic applications VarplusCan HDuty + Detuned Reactor + Contactor VarplusCan Energy harmonic applications VarplusCan Energy + Detuned Reactor + Contactor VarplusCan mechanicalcharacteristics VarplusBox capacitor VarplusBox SDuty VarplusBox HDuty VarplusBox Energy VarplusBox HDuty harmonicapplications VarplusBox HDuty + Detuned Reactor + Contactor VarplusBox Energy Harmonic applications VarplusBox Energy + Detuned Reactor + Contactor VarplusBox Mechanicalcharacteristics

16 20 24 29 32 33 35 36 38 39 40 42 44 47 52 56 57 59 60 61

VarplusCan 18

Detuned reactors 67 Power Factor controllers 71 Contactors 75 Appendix 79

15

Low Voltage Capacitors

Offer Overview

VarplusCan
group of 3caps_r.eps

Construction Voltage range Power range (three-phase) Peak inrush current Overvoltage Overcurrent Mean life expectancy Safety Dielectric

SDuty

Extruded aluminium can 230 V - 525 V 1 - 30 kvar Up to 200 x In 1.1 x Un 8 h every 24 h 1.5 x In Up to 100,000 h

HDuty
230 V - 830 V 1 - 50 kvar Up to 250 x In

Energy
380 V - 525 V 5 -15 kvar Up to 350 x In

1.8 x In Up to 130,000 h

2.5 x In Up to 160,000 h

Self-healing + pressure-sensitive disconnector + discharge device (50 V/1 min) Metallized Polypropylene film with Zn/Al alloy Metallized Polypropylene film with Zn/Al alloy with special profile metallization and wave cut Double metallized paper + Polypropylene film

Impregnation Ambient temperature Protection Mounting Terminals

Non-PCB, Biodegradable resin min. -25 C max 55 C IP20 , indoor Upright

Non-PCB, sticky Non-PCB, oil (dry) Biodegradable resin min. -25 C max 70 C

Upright, horizontal

Upright

bb Double fast-on + cable (y 10 kvar) bb CLAMPTITE - Three-phase terminal with electric shock protection (finger-proof) bb Stud type terminal (> 30 kvar)

16

Offer Overview

VarplusBoX
groupof3boxcaps_r.eps

Construction Voltage range Power range (three-phase) Peak inrush current Overvoltage Overcurrent Mean life expectancy Safety Dielectric

SDuty

Steel sheet enclosure 380 V - 480 V 7.5 - 100 kvar Up to 200 x In 1.1 x Un 8 h every 24 h 1.5 x In Up to 100,000 h

HDuty
230 V - 830 V 2.5 - 100 kvar Up to 250 x In

Energy
380 V - 525 V 7.5 - 100 kvar Up to 350 x In

1.8 x In Up to 130,000 h

2.5 x In Up to 160,000 h

Self-healing + pressure-sensitive disconnector + discharge device (50 V/1 min) Metallized polypropylene film with Zn/Al alloy Metallized Polypropylene film with Zn/Al alloy with special profile metallization and wave cut Double metallized paper + Polypropylene film

Impregnation Ambient temperature Protection Mounting Terminals

Non-PCB, Biodegradable resin min. -25 C max 55 C IP20, Indoor Upright

Non-PCB, sticky (dry) Non-PCB, oil Biodegradable resin min. -25 C max 70 C

Upright, Horizontal

Upright

Bushing terminals designed for large cable termination and direct busbar mounting for banking

17

Low Voltage Capacitors

VarplusCan

Aluminum can capacitors specially designed and engineered to deliver a long working life with low losses in standard, heavy-duty and severe operating conditions. Suitable for Fixed and Automatic PFC, real time compensation, detuned and tuned filters.
PE90131_r.eps

Main features

Easy installation & maintenance bb Optimized design for low weight, compactness and reliability to ensure easy installation. bb Unique termination system that allows maintained tightness. bb 1 point for mounting and earthing. bb Vertical and horizontal position. Safety bb Self-healing. bb Pressure-sensitive disconnector on all three phases. bb Discharge resistors fitted. bb Finger-proof CLAMPTITE terminals to reduce risk of accidental contact and to ensure firm termination (10 to 30 kvar). bb Special film resistivity and metallization profile for higher thermal efficiency, lower temperature rise and enhanced life expectancy. Compacity bb Optimized geometric design (small dimensions and low weight). bb Available on request in single phase.

For professionnals

bb High life expectancy up to 160,000 hours. bb Very high overload capabilities and good thermal and mechanical properties. bb Economic benefits due to its compact size. bb Easy maintenance. bb Unique finger proof termination to ensure tightness.

VarplusCan.

18

VarplusCan

group of 3caps_r.eps

Construction Voltage range Power range (three-phase) Peak inrush current Overvoltage Overcurrent Mean life expectancy Safety Dielectric

SDuty

Extruded aluminium can 230 V - 525 V 1 - 30 kvar Up to 200 x In 1.1 x Un 8 h every 24 h 1.5 x In Up to 100,000 h

HDuty
230 V - 830 V 1 - 50 kvar Up to 250 x In

Energy
380 V - 525 V 5 -15 kvar Up to 350 x In

1.8 x In Up to 130,000 h

2.5 x In Up to 160,000 h

Self-healing + pressure-sensitive disconnector + discharge device (50 V/1 min) Metallized Polypropylene film with Zn/Al alloy Non-PCB, Biodegradable resin min. -25 C max 55 C IP20 Indoor Upright Upright, horizontal Upright bb Double fast-on + cable (y 10 kvar) bb CLAMPTITE - Three-phase terminal with electric shock protection (finger-proof) bb Stud terminal (> 30 kvar) Metallized Polypropylene film with Zn/Al alloy with special profile metallization and wave cut Double metallized paper + Polypropylene film

Impregnation Ambient temperature Protection Mounting Terminals

Non-PCB, sticky Non-PCB, oil (dry) Biodegradable resin min. -25 C max 70 C

19

Low Voltage Capacitors

VarplusCan SDuty

A safe, reliable and high-performance solution for power factor correction in standard operating conditions.

Operating conditions

PE90131.eps

PE90130.eps

bb For networks with insignificant non-linear loads: (NLL y 10 %). bb Standard voltage disturbances. bb Standard operating temperature up to 55 C. bb Normal switching frequency up to 5000 /year. bb Maximum current (including harmonics) is 1.5 x IN.

Technology

Constructed internally with three single-phase capacitor elements assembled in an optimized design. Each capacitor element is manufactured with metallized polypropylene film as the dielectric having features such as heavy edge metallization and special profiles which enhance the self-healing properties. The active capacitor elements are encapsulated in a specially formulated biodegradable, non-PCB, PUR (soft) resin which ensures thermal stability and heat removal from inside the capacitor. The unique finger-proof CLAMPTITE termination is fully integrated with discharge resistors and allows suitable access to tightening and ensures cable termination without any loose connections. Once tightened, the design guarantees that the tightening torque is always maintained. For lower ratings, double fast-on terminals with wires are provided.

Benefits

VarplusCan SDuty

bb Safety: vv self-healing vv pressure-sensitive disconnector on all three phases vv discharge resistor. bb Life expectancy up to 100,000 hours. bb Economic benefits and easy installation due to its compact size an low weight. bb Easy maintenance thanks to its unique finger-proof termination to ensure tightening. bb Also available in small power ratings from 1 to 5 kvar.

20

VarplusCan SDuty

Technical specifications
Standards

General characteristics

IEC 60831-1/-2 230 to 525V 50 / 60Hz 1 to 30 kvar < 0.2W/kvar < 0.5W/kvar -5 %, +10 % 2.15 x UN (AC), 10s 3 kV (AC), 10s or 3.66 kV (AC), 2s 8 kV Fitted, standard discharge time 60s Discharge time 180s on request -25 / 55 C (Class D) 95 % 2,000 m above sea level 1.1xUN 8 h in every 24 h Up to 1.5xIN 200xIN Up to 5,000 switching operations per year Up to 100,000 hrs NLL y 10 % Indoor, upright Threaded M12 stud at the bottom CLAMPTITE - three-way terminal with electric shock protection (finger-proof) & double fast-on terminal in lower kvar Self-healing + Pressure-sensitive disconnector + Discharge device IP20 Extruded Aluminium Can Metallized polypropylene film with Zn/Al alloy Biodegradable, Non-PCB, PUR (soft) resin

Voltage range Frequency Power range Losses (dielectric) Losses (total) Capacitance tolerance Voltage test Between terminals Between terminal & container Impulse voltage Discharge resistor

Ambient temperature Humidity Altitude Overvoltage Overcurrent Peak inrush current

Working conditions

Switching operations (max.) Mean Life expectancy Harmonic content Mounting position Fastening Earthing Terminals

Installation characteristics

Safety

Safety features

Protection Casing

Construction

Dielectric Impregnation

21

Low Voltage Capacitors

VarplusCan SDuty

Rated Voltage 240/260 V


50 Hz
QN (kvar) 230 V 1.9 2.5 3.9 5.0 5.8 7.6 10 240 V 2.1 2.7 4.2 5.4 6.3 8.3 10.9 260 V 2.5 3.2 4.9 6.4 7.4 9.7 12.8 IN (A) at 260 V 5.5 7.1 10.9 14 16.4 21.6 28.4

60 Hz
QN (kvar) 230 V 2.3 3.0 4.6 6.0 6.9 9.2 12 240 V 2.5 3.3 5 6.5 7.5 10 13 260 V 3 3.8 6 7.7 8.8 11.7 15.3 IN (A) at 260 V 6.6 8.5 13.1 17.0 19.5 26.1 34.1

F (X3)

Case Code

Reference Number

38.7 50.1 77.3 100 116 152 200

HC HC HC LC NC NC SC

BLRCS021A025B24 BLRCS027A033B24 BLRCS042A050B24 BLRCS054A065B24 BLRCS063A075B24 BLRCS083A100B24 BLRCS109A130B24

Rated Voltage 380/400/415 V


50 Hz
QN (kvar) 380 V 0.7 0.9 1.5 1.8 2.3 2.7 3.0 3.6 3.8 4.5 5.6 6.8 7.5 9.4 11.3 13.5 15.1 18.1 18.8 22.6 400 V 0.8 1 1.7 2 2.5 3 3.3 4 4.2 5 6.3 7.5 8.3 10.4 12.5 15 16.7 20 20.8 25 415 V 0.9 1.1 1.8 2.2 2.7 3.2 3.6 4.3 4.5 5.4 6.8 8.1 8.9 11.2 13.5 16.1 18 21.5 22.4 26.9 IN (A) at 400 V 1.2 1.4 2.5 2.9 3.6 4.3 4.8 5.8 6.1 7.2 9.1 10.8 12 15 18 21.7 24.1 28.9 30 36.1

60 Hz
QN (kvar) 380 V 0.9 1.1 1.8 2.2 2.7 3.2 3.6 4.3 4.5 5.4 6.8 8.1 9 11.3 13.5 16.2 18.1 21.7 22.5 27.1 400 V 1 1.2 2 2.4 3 3.6 4 4.8 5 6 7.5 9 10 12.5 15 18 20 24 25 30 415 V 1.1 1.3 2.2 2.6 3.2 3.9 4.3 5.2 5.4 6.5 8.1 9.7 10.7 13.4 16.1 19.4 21.6 25.8 26.9 32.3 IN (A) at 400 V 1.4 1.7 2.9 3.5 4.3 5.2 5.7 6.9 7.3 8.7 10.8 13 14.4 18 21.7 26 28.9 34.6 36 43.3

F (X3)

Case Code

Reference Number

5.3 6.6 11.3 13.3 16.6 19.9 21.9 26.5 27.8 33.1 41.8 49.7 55.0 68.9 82.9 99.4 111 133 138 166

EC EC DC DC DC DC DC DC DC HC HC HC LC MC NC NC SC SC SC SC

BLRCS008A010B40 BLRCS010A012B40 BLRCS017A020B40 BLRCS020A024B40 BLRCS025A030B40 BLRCS030A036B40 BLRCS033A040B40 BLRCS040A048B40 BLRCS042A050B40 BLRCS050A060B40 BLRCS063A075B40 BLRCS075A090B40 BLRCS083A100B40 BLRCS104A125B40 BLRCS125A150B40 BLRCS150A180B40 BLRCS167A200B40 BLRCS200A240B40 BLRCS208A250B40 BLRCS250A300B40

22

VarplusCan SDuty

Rated Voltage 440 V


50 Hz
QN (kvar) 1 2 3 4 5 7.5 10 11.2 12.5 14.3 15 16.9 18.2 20 22.5 25 28.5 30.3

60 Hz

F (X3)
IN (A) 1.6 3.1 4.7 6.3 7.9 11.8 15.7 17.6 19.7 22.5 23.6 26.6 28.7 31.5 35.4 39.4 44.9 5.5 11 16.4 21.9 27.4 41.1 54.8 61.4 68.5 78.3 82.2 92.6 99.7 110 123 137 156 166

Case Code
EC FC DC DC HC HC LC NC NC NC NC SC SC SC SC SC SC SC

Reference Number

IN (A) 1.3 2.6 3.9 5.2 6.6 9.8 13.1 14.7 16.4 18.8 19.7 22.2 23.9 26.2 29.5 32.8 37.4 39.8

QN (kvar) 1.2 2.4 3.6 4.8 6 9 12 13.4 15 17.2 18 20.3 21.8 24 27 30 34.2 36.4

BLRCS010A012B44 BLRCS020A024B44 BLRCS030A036B44 BLRCS040A048B44 BLRCS050A060B44 BLRCS075A090B44 BLRCS100A120B44 BLRCS112A134B44 BLRCS125A150B44 BLRCS143A172B44 BLRCS150A180B44 BLRCS169A203B44 BLRCS182A218B44 BLRCS200A240B44 BLRCS225A270B44 BLRCS250A300B44 BLRCS285A342B44 BLRCS303A364B44

47.7

Rated Voltage 480 V


50 Hz
QN (kvar) 4.2 6.7 7.5 8.8 10.4 11.3 12.5 13.6 14.4 15.5 17 20.8 25.8 28.8 31.5 33.9

60 Hz

F (X3)
IN (A) 6.1 9.7 10.8 12.7 15 16.3 18 19.6 20.8 22.4 24.5 30 37.2 41.6 45.5 48.9 19.3 30.8 34.5 40.5 47.9 52 57.5 62.6 66.3 71.4 78.3 95.7 119 133 145 156

Case Code
DC HC HC LC MC MC NC NC NC NC NC SC SC VC VC XC

Reference Number

IN (A) 5.1 8.1 9.0 10.6 12.5 13.6 15 16.4 17.3 18.6 20.4 25.0 31.0 34.6 37.9 40.8

QN (kvar) 5 8 9.0 10.6 12.5 13.6 15 16.3 17.3 18.6 20.4 25 31 34.6 37.8 40.7

BLRCS042A050B48 BLRCS067A080B48 BLRCS075A090B48 BLRCS088A106B48 BLRCS104A125B48 BLRCS113A136B48 BLRCS125A150B48 BLRCS136A163B48 BLRCS144A173B48 BLRCS155A186B48 BLRCS170A204B48 BLRCS208A250B48 BLRCS258A310B48 BLRCS288A346B48 BLRCS315A378B48 BLRCS339A407B48

Rated Voltage 525 V


50 Hz
QN (kvar) 5 8 8.8 10.6 12.5 13.5 15.4 17.2 18.5 20 25 27.5

60 Hz

F (X3)
IN (A) 6.6 10.6 11.6 14.0 16.5 17.8 20.3 22.7 24.4 26.4 33 36.3 19.2 30.8 33.9 40.8 48.1 51.9 59.3 66.2 71.2 77 96.2 106

Case Code
HC HC LC MC NC NC NC NC SC SC SC SC

Reference Number

IN (A) 5.5 8.8 9.7 11.7 13.7 14.8 16.9 18.9 20.3 22 27.5 30.2

QN (kvar) 6 9.6 10.6 12.7 15 16.2 18.5 20.6 22.2 24 30 33

BLRCS050A060B52 BLRCS080A096B52 BLRCS088A106B52 BLRCS106A127B52 BLRCS125A150B52 BLRCS135A162B52 BLRCS154A185B52 BLRCS172A206B52 BLRCS185A222B52 BLRCS200A240B52 BLRCS250A300B52 BLRCS275A330B52

23

Low Voltage Capacitors

VarplusCan HDuty

A safe, reliable and high-performance solution for power factor correction in heavy-duty operating conditions.

Operating conditions

PE90131.eps

bb For networks with insignificant non-linear loads: (NLL < 20 %). bb Significant voltage disturbances. bb Standard operating temperature up to 55 C. bb Normal switching frequency up to 7000 /year. bb Maximum current (including harmonics) is 1.8 x IN.

PE90130.eps

Technology

Constructed internally with three single-phase capacitor elements. Each capacitor element is manufactured with metallized polypropylene film as the dielectric, having features such as heavy edge, slope metallization and wave-cut profile to ensure increased current handling capacity and reduced temperature rise. The active capacitor elements are coated with specially formulated sticky resin which ensures high overload capabilities and good thermal and mechanical properties The unique finger-proof CLAMPTITE termination is fully integrated with discharge resistors, allowing suitable access for tightening and ensuring cable termination without any loose connections. For lower ratings, double fast-on terminals with wires are provided.

Benefits

VarplusCan HDuty

bb Total safety: vv self-healing vv pressure-sensitive disconnector vv discharge resistor. bb Long life expectancy (up to 130,000 hours). bb Installation in any position. bb Optimized geometric design for improved thermal performance. bb Special resistivity and metallisation profile will enhance life and will give higher thermal efficiency with lower temperature rise. bb Unique finger-proof termination that ensures tightening for CLAMPITE terminals.

24

VarplusCan HDuty

Technical specifications
Standards

General characteristics

IEC 60831-1/-2 230 to 830 V 50 / 60Hz 1 to 50 kvar < 0.2W/kvar < 0.5W/kvar -5%, +10% 2.15 x UN (AC), 10s y 525 V: 3 kV (AC), 10 s or 3.66 kV (AC), 2 s > 525 V: 3.66 kV (AC), 10 s or 4.4 kV (AC), 2 s y 690 V: 8 kV > 690 V: 12 kV Fitted, standard discharge time 60s Discharge time 180s on request -25 / 55 C (Class D) 95 % 2,000 m above sea level 1.1xUN 8 h in every 24 h Up to 1.8xIN 250 x IN Up to 7,000 switching operations per year Up to 130,000 hrs NLL y 20 % Indoor, upright & horizontal Threaded M12 stud at the bottom CLAMPTITE - three-way terminal with electric shock protection (finger-proof) & double fast-on terminal in lower kvar Self-healing + Pressure-sensitive disconnector + Discharge device IP20 Extruded Aluminium Can Metallized polypropylene film with Zn/Al alloy. Special resistivity & profile, special edge (wave-cut) Non-PCB, PUR sticky resin (Dry)

Voltage range Frequency Power range Losses (dielectric) Losses (total) Capacitance tolerance Voltage test Between terminals Between terminal & container Impulse voltage Discharge resistor

Ambient temperature Humidity Altitude Overvoltage Overcurrent Peak inrush current

Working conditions

Switching operations (max.) Mean Life expectancy Harmonic content Mounting position Fastening Earthing Terminals

Installation characteristics

Safety

Safety features

Protection Casing

Construction

Dielectric Impregnation

25

Low Voltage Capacitors

VarplusCan HDuty

Rated Voltage 240/260 V


50 Hz
QN (kvar) 230 V 1.9 2.5 3.9 5 5.8 7.6 10 10.7 12 240 V 2.1 2.7 4.2 5.4 6.3 8.3 10.9 11.7 13.1 260 V 2.5 3.2 4.9 6.4 7.4 9.7 12.8 13.7 15.4 IN (A) at 260 V 5.5 7.1 10.9 14 16.4 21.6 28.4 30.4 34.1

60 Hz
QN (kvar) 230 V 2.3 3 4.6 6 6.9 9.2 12 12.9 14.4 240 V 2.5 3.3 5 6.5 7.5 10 13 14 15.7 260 V 3 3.8 6 7.7 8.8 11.7 15.3 16.4 18.4 IN (A) at 260 V 6.6 8.5 13.1 17.0 19.5 26.1 34.1 36.5 40.9

F (X3)

Case Code

Reference Number

38.7 50.1 77.3 100 116 152 200 215 241

HC HC HC LC RC RC TC TC TC

BLRCH021A025B24 BLRCH027A033B24 BLRCH042A050B24 BLRCH054A065B24 BLRCH063A075B24 BLRCH083A100B24 BLRCH109A130B24 BLRCH117A140B24 BLRCH131A157B24

Rated Voltage 380/400/415 V


50 Hz
QN (kvar) 380 V 4.5 5.7 6.8 7.5 9.4 11.3 13.5 15.1 18.1 18.8 22.6 27.1 30.1 36.1 37.6 45.1 400 V 5 6.3 7.5 8.3 10.4 12.5 15 16.7 20 20.8 25 30 33.3 40 41.7 50 415 V 5.4 6.8 8.1 8.9 11.2 13.5 16.1 18 21.5 22.4 26.9 32.3 35.8 43.1 44.9 53.8 IN (A) at 400 V 7.2 9.1 10.8 12 15 18 21.7 24.1 28.9 30 36.1 43.3 48.1 57.7 60.2 72.2

60 Hz
QN (kvar) 380 V 5.4 6.8 8.1 9 11.3 13.5 16.2 18.1 21.7 22.5 27.1 32.5 36.1 43.3 45.2 --400 V 6 7.5 9 10 12.5 15 18 20 24 25 30 36 40 48 50 --415 V 6.5 8.1 9.7 10.7 13.4 16.1 19.4 21.6 25.8 26.9 32.3 38.8 43 51.7 53.9 --IN (A) at 400 V 8.7 10.8 13 14.4 18 21.7 26 28.9 34.6 36 43.3 52 57.7 69.3 72.2 ---

F (X3)

Case Code

Reference Number

33.1 41.8 49.7 55.0 68.9 82.9 99.4 111 133 138 166 199 221 265 276 331

HC HC HC LC MC RC RC TC TC TC TC VC VC YC YC YC

BLRCH050A060B40 BLRCH063A075B40 BLRCH075A090B40 BLRCH083A100B40 BLRCH104A125B40 BLRCH125A150B40 BLRCH150A180B40 BLRCH167A200B40 BLRCH200A240B40 BLRCH208A250B40 BLRCH250A300B40 BLRCH300A360B40 BLRCH333A400B40 BLRCH400A480B40 BLRCH417A500B40 BLRCH500A000B40

Rated Voltage 440 V


50 Hz
QN (kvar) 5 7.5 10 11.2 12.5 14.3 15 16.9 18.2 20 22.5 23.8 25 28.5 30.3 40 50 57.1

60 Hz

F (X3)
IN (A) 7.9 11.8 15.7 17.6 19.7 22.5 23.6 26.6 28.7 31.5 35.4 37.5 39.4 44.9 --63 --27.4 41.1 54.8 61.4 68.5 78.3 82.2 92.6 99.7 110 123 130 137 156 166 219 274 313

Case Code
HC HC MC RC RC RC RC TC TC TC TC TC TC VC VC XC YC YC

Reference Number

IN (A) 6.6 9.8 13.1 14.7 16.4 18.8 19.7 22.2 23.9 26.2 29.5 31.2 32.8 37.4 39.8 52.5 65.6 74.9

QN (kvar) 6 9 12 13.4 15 17.2 18 20.3 21.8 24 27 28.6 30 34.2 --48 -----

BLRCH050A060B44 BLRCH075A090B44 BLRCH100A120B44 BLRCH112A134B44 BLRCH125A150B44 BLRCH143A172B44 BLRCH150A180B44 BLRCH169A203B44 BLRCH182A218B44 BLRCH200A240B44 BLRCH225A270B44 BLRCH238A286B44 BLRCH250A300B44 BLRCH285A342B44 BLRCH303A000B44 BLRCH400A480B44 BLRCH500A000B44 BLRCH571A000B44

---

26

VarplusCan HDuty

Rated Voltage 480 V


50 Hz
QN (kvar) 2.5 4.2 5 6.7 7.5 8.8 10.4 11.3 12.5 13.6 14.4 15.5 17 18 20.8 25.8 28.8 31.5 33.9

60 Hz

F (X3)
IN (A) 3.6 6.1 7.2 9.7 10.8 12.7 15 16.3 18 19.6 20.8 22.4 24.5 26 30 37.2 41.6 11.5 19.3 23 30.8 34.5 40.5 47.9 52 57.5 62.6 66.3 71.4 78.3 82.9 95.7 119 133 145 156

Case Code
DC DC HC HC HC LC MC MC RC RC RC RC RC TC TC TC VC VC XC

Reference Number

IN (A) 3 5.1 6 8.1 9 10.6 12.5 13.6 15 16.4 17.3 18.6 20.4 21.7 25 31 34.6 37.9 40.8

QN (kvar) 3 5 6 8 9 10.6 12.5 13.6 15 16.3 17.3 18.6 20.4 21.6 25 31 34.6 37.8 40.7

BLRCH025A030B48 BLRCH042A050B48 BLRCH050A060B48 BLRCH067A080B48 BLRCH075A090B48 BLRCH088A106B48 BLRCH104A125B48 BLRCH113A136B48 BLRCH125A150B48 BLRCH136A163B48 BLRCH144A173B48 BLRCH155A186B48 BLRCH170A204B48 BLRCH180A216B48 BLRCH208A250B48 BLRCH258A310B48 BLRCH288A346B48 BLRCH315A378B48 BLRCH339A407B48

45.5 48.9

Rated Voltage 525 V


50 Hz
QN (kvar) 5 8 8.8 10.6 12.5 13.5 15.4 17.2 18.5 20 25 30.9 34.4 37.7 40

60 Hz

F (X3)
IN (A) 6.6 10.6 11.6 14 16.5 17.8 20.3 22.7 24.4 26.4 33 40.8 45.4 49.8 52.8 19.2 30.8 33.9 40.8 48.1 51.9 59.3 66.2 71.2 77 96.2 119 132 145 154

Case Code
HC HC LC MC RC RC RC RC TC TC TC VC VC VC XC

Reference Number

IN (A) 5.5 8.8 9.7 11.7 13.7 14.8 16.9 18.9 20.3 22 27.5 34 37.8 41.5 44

QN (kvar) 6 9.6 10.6 12.7 15 16.2 18.5 20.6 22.2 24 30 37.1 41.3 45.2 48

BLRCH050A060B52 BLRCH080A096B52 BLRCH088A106B52 BLRCH106A127B52 BLRCH125A150B52 BLRCH135A162B52 BLRCH154A185B52 BLRCH172A206B52 BLRCH185A222B52 BLRCH200A240B52 BLRCH250A300B52 BLRCH309A371B52 BLRCH344A413B52 BLRCH377A452B52 BLRCH400A480B52

Rated Voltage 575 V


50 Hz
QN (kvar) 6 12 15 29.2

60 Hz

F (X3)
IN (A) 7.2 14.5 18.1 35.1 19.2 38.5 48.1 93.6

Case Code
MC TC VC YC

Reference Number

IN (A) 6 12 15.1 29.3

QN (kvar) 7.2 14.4 18 35

BLRCH060A072B57 BLRCH120A144B57 BLRCH150A180B57 BLRCH292A350B57

Available in Star Connection

27

Low Voltage Capacitors

VarplusCan HDuty

Rated Voltage 600 V


50 Hz
QN (kvar) 4.2 8.3 10.4 12.5 16.7 20.8 25 33.3 41.7

60 Hz

F (X3)
IN (A) 4.8 9.6 12 14.4 19.3 24 28.9 38.5 48.2 12.4 24.5 30.6 36.8 49.2 61.3 73.7 98.1 123

Case Code
HC RC TC TC VC VC XC YC YC

Reference Number

IN (A) 4 8 10 12 16.1 20 24.1 32 40.1

QN (kvar) 5 10 12.5 15 20 25 30 40 50

BLRCH042A050B60 BLRCH083A100B60 BLRCH104A125B60 BLRCH125A150B60 BLRCH167A200B60 BLRCH208A250B60 BLRCH250A300B60 BLRCH333A400B60 BLRCH417A500B60

Rated Voltage 690 V


50 Hz
QN (kvar) 5.5 10 11.1 12.5 13.8 15 20 25 27.6 30 40 52

60 Hz

F (X3)
IN (A) 5.5 10 11.1 12.6 13.8 15.1 20.1 25.1 27.7 30.1 40.2 52.2 12.3 22.3 24.7 27.8 30.6 33.4 44.6 55.7 61.4 66.8 89.1 116

Case Code
MC RC RC RC TC TC TC VC VC VC YC YC

Reference Number

IN (A) 4.6 8.4 9.3 10.5 11.5 12.6 16.7 20.9 23.1 25.1 33.5 43.5

QN (kvar) 6.6 12 13.3 15 16.5 18 24 30 33.1 36 48 62.4

BLRCH055A066B69 BLRCH100A120B69 BLRCH111A133B69 BLRCH125A150B69 BLRCH138A165B69 BLRCH150A180B69 BLRCH200A240B69 BLRCH250A300B69 BLRCH276A331B69 BLRCH300A360B69 BLRCH400A480B69 BLRCH520A624B69

Rated Voltage 830 V


50 Hz
QN (kvar) 17.1

60 Hz

F (X3)
IN (A) 14.3 26.3

Case Code
VC

Reference Number

IN (A) 11.9

QN (kvar) 20.5

BLRCH171A205B83

Available in Star Connection

28

VarplusCan Energy

A safe, reliable and high-performance solution for power factor correction for severe operating conditions.

PE90131.eps

bb For networks with significant non-linear loads: (NLL < 25 %). bb Severe voltage disturbances. bb Highest operating temperature (up to 70 C). bb High switching frequency up to 10,000 /year. bb Maximum current withstand 2.5 x IN.

Operating conditions

Technology

Constructed internally with three single-phase capacitor elements. This is the only technology which is capable of giving the longest life, highest overload limits and the highest operating ambient temperature due to use of the combination of polypropylene film and metallized paper. The presence of the paper ensures high-quality impregnation which is critical for increasing dielectric strength. Further, this quality of oil-impregnated dielectric system has far superior capabilities in terms of partial discharge behaviour and heat conduction.

Benefits

bb Safety: vv self-healing vv pressure-sensitive disconnector vv discharge resistor. bb Extra long life expectancy (up to 160,000 hours). bb Very high overload capabilities and good thermal and mechanical properties. bb Overcurrent withstand capabilities up to 2.5 x IN. bb Highest operating temperature (up to 70 C).

VarplusCan Energy

29

Low Voltage Capacitors

VarplusCan Energy

Technical specifications
Standards

General characteristics

IEC 60831-1/-2 380 to 525 V 50 / 60Hz 5 to 15 kvar < 0.2 W/kvar < 0.5 W/kvar -5%, +10% 2.15 x UN (AC), 10 s 3 kV (AC), 10 s or 3.66 kV (AC), 2 s 8 kV Fitted, standard discharge time 60s Discharge time 180s on request -25 / 70 C 95 % 2,000 m above sea level 1.1xUN 8 h in every 24 h Up to 2.5xIN 350xIN Up to 10,000 switching operations per year Up to 160,000 hrs NLL y 25 % Indoor, upright Threaded M12 stud at the bottom CLAMPTITE - three-way terminal with electric shock protection (finger-proof) & double fast-on terminal in lower kvar Self-healing + Pressure-sensitive disconnector + Discharge device IP20 Extruded Aluminium Can Double metallized paper + Polypropylene film Non-PCB, oil

Voltage range Frequency Power range Losses (dielectric) Losses (total) Capacitance tolerance Voltage test Between terminals Between terminal & container Impulse voltage Discharge resistor

Ambient temperature Humidity Altitude Overvoltage Overcurrent Peak inrush current

Working conditions

Switching operations (max.) Mean Life expectancy Harmonic content Mounting position Fastening Earthing Terminals

Installation characteristics

Safety

Safety features

Protection Casing

Construction

Dielectric Impregnation

30

VarplusCan Energy

Rated Voltage 380/400/415 V


50 Hz
QN (kvar) 380 V 4.5 5.7 6.8 7.5 9.4 11.3 13.5 400 V 5 6.3 7.5 8.3 10.4 12.5 15 415 V 5.4 6.8 8.1 8.9 11.2 13.5 16.1 IN (A) at 400 V 7.2 9.1 10.8 12 15 18 21.7

60 Hz
QN (kvar) 380 V 5.4 6.8 8.1 9 11.3 13.5 16.2 400 V 6 7.5 9 10 12.5 15 18 415 V 6.5 8.1 9.7 10.7 13.4 16.1 19.4 IN (A) at 400 V 8.7 10.8 13 14.4 18 21.7 26

F (X3)

Case Code

Reference Number

33.1 41.8 49.7 55 68.9 82.9 99.4

NC NC SC SC SC UC UC

BLRCE050A060B40 BLRCE063A075B40 BLRCE075A090B40 BLRCE083A100B40 BLRCE104A125B40 BLRCE125A150B40 BLRCE150A180B40

Rated Voltage 440 V


50 Hz
QN (kvar) 5 7.5 10 12.5 15

60 Hz

F (X3)
IN (A) 7.9 11.8 15.7 19.7 23.6 27.4 41.1 54.8 68.5 82.2

Case Code
NC NC SC SC UC

Reference Number

IN (A) 6.6 9.8 13.1 16.4 19.7

QN (kvar) 6 9 12 15 18

BLRCE050A060B44 BLRCE075A090B44 BLRCE100A120B44 BLRCE125A150B44 BLRCE150A180B44

Rated Voltage 480 V


50 Hz
QN (kvar) 4.2 6.7 7.5 8.8 10.4 11.3 12.5 13.6 14.4 15.5 17

60 Hz

F (X3)
IN (A) 6.1 9.7 10.8 12.7 15 16.3 18 19.6 20.8 22.4 24.5 19.3 30.8 34.5 40.5 47.9 52 57.5 62.6 66.3 71.4 78.3

Case Code
NC NC NC SC SC SC UC UC UC UC UC

Reference Number

IN (A) 5.1 8.1 9 10.6 12.5 13.6 15 16.4 17.3 18.6 20.4

QN (kvar) 5 8 9 10.6 12.5 13.6 15 16.3 17.3 18.6 20.4

BLRCE042A050B48 BLRCE067A080B48 BLRCE075A090B48 BLRCE088A106B48 BLRCE104A125B48 BLRCE113A136B48 BLRCE125A150B48 BLRCE136A163B48 BLRCE144A173B48 BLRCE155A186B48 BLRCE170A204B48

Rated Voltage 525 V


50 Hz
QN (kvar) 5 10 12.5 15.4

60 Hz

F (X3)
IN (A) 6.6 13.2 16.5 20.3 19.2 38.5 48.1 59.3

Case Code
NC SC UC UC

Reference Number

IN (A) 5.5 11 13.7 16.9

QN (kvar) 6 12 15 18.5

BLRCE050A060B52 BLRCE100A120B52 BLRCE125A150B52 BLRCE154A185B52

31

Low Voltage Capacitors

VarplusCan SDuty harmonic applications

This harmonic rated range of capacitors is dedicated to applications where a high number of non-linear loads are present (NLL up to 30 %). These capacitors are designed for use with detuned reactors, based on the Standard Duty technology.
PE90131.eps PE90154.eps

Operating conditions

bb For networks with a large number of non-linear loads (NLL < 50 %). bb Significant voltage disturbances. bb Significant switching frequency up to 5000 /year.

Rated voltage

In a detuned filter application, the voltage across the capacitors is higher than the network service voltage (US). Then, capacitors must be designed to withstand higher voltages. Depending on the selected tuning frequency, part of the harmonic currents are absorbed by the detuned capacitor bank. Then, capacitors must be designed to withstand higher currents, combining fundamental and harmonic currents. The rated voltage of VarplusCan SDuty capacitors is given in the table below, for different values of network service voltage and relative impedance.

+
Detuned reactor VarplusCan SDuty

Capacitor Rated Voltage UN (V)

Network Service Voltage US (V) 50 Hz 60 Hz 400 400 480 480

Relative Impedance (%)

5.7 7 14

In the following pages, the effective power (kvar) given in the tables is the reactive power provided by the combination of capacitors and reactors.

32

VarplusCan SDuty + Detuned Reactor + Contactor

PE90154_L28_r.eps

Network 400 V, 50 Hz Capacitor Voltage 480 V 5.7% / 7 % Filter


Effective QN Capacitor Ref. Power at (kvar) 480 V
6.5 12.5 25 50 100 8.8 17 33.9 67.9 136

5.7 % (210 Hz) R Ref

7% (190 Hz) R Ref.

Capacitor Duty Contactor Ref.

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1

BLRCS088A106B48 x 1 BLRCS170A204B48 x 1 BLRCS339A407B48 x 1 BLRCS339A407B48 x 2 BLRCS339A407B48 x 4

51573 x 1 52404 x 1 52405 x 1 52406 x 1 52407 x 1

51568 x 1 52352 x 1 52353 x 1 52354 x 1 51569 x 1

LC1-DFK11M7 x 1 LC1-DFK11M7 x 1

LC1-DMK11M7 x 1 LC1D32 x 1 LC1-DWK12M7 x 1 LC1D80 x 1 LC1D115 x 1

PE90131_L28_r.eps

Network 400 V, 50 Hz Capacitor Voltage 480 V 14 % Filter


Effective QN Capacitor Ref. Power at (kvar) 480 V
6.5 12.5 25 50 100 8.8 15.5 31.5 63 126

14 % (135 Hz) R Ref

Capacitor Duty Contactor Ref.


LC1-DFK11M7 x 1 LC1-DFK11M7 x 1 LC1-DLK11M7 x 1 -

Power Contactor Ref.


LC1D12 x1 LC1D12 x1 LC1D25 x1 LC1D115 x 1

BLRCS088A106B48 x 1 BLRCS155A186B48 x 1 BLRCS315A378B48 x 1 BLRCS315A378B48 x 2 BLRCS315A378B48 x 4

51563 x 1 51564 x 1 51565 x 1 51566 x 1 51567 x 1

LC1-DTK12M7 x 1 LC1D50 x1

PE90158_L20_r.eps

Network 400 V, 50 Hz Capacitor Voltage 525 V 5.7 % / 7 % Filter


Effective QN Capacitor Ref. Power at (kvar) 525 V
6.5 12.5 25 50 100 10.6 20 40 82.5 165

5.7 % (210 Hz) R Ref.

7% (190 Hz) R Ref.

Capacitor Duty Contactor Ref.

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1

BLRCS106A127B52 x 1 BLRCS200A240B52 x 1 BLRCS200A240B52 x 2 BLRCS275A330B52 x 3 BLRCS275A330B52 x 6

51573 x 1 52404 x 1 52405 x 1 52406 x 1 52407 x 1

51568 x 1 52352 x 1 52353 x 1 52354 x 1 51569 x 1

LC1-DFK11M7 x 1 LC1-DFK11M7 x 1

LC1-DMK11M7 x 1 LC1D32 x 1 LC1-DWK12M7 x 1 LC1D80 x 1 LC1D115 x 1

Contactor LC1DPK.

Network 400 V, 50 Hz Capacitor Voltage 525 V 14 % Filter


Effective QN Capacitor Ref. Power at (kvar) 525 V
6.5 12.5 25 50 100 10.6 18.5 37 75 150

14 % (135 Hz) R Ref.

Capacitor Duty Contactor Ref.


LC1-DFK11M7 x 1 LC1-DLK11M7 x 1 -

Power Contactor Ref.


LC1D12 x 1 LC1D25 x 1 LC1D115 x 1

BLRCS106A127B52 x 1 BLRCS185A222B52 x 1 BLRCS185A222B52 x 2 BLRCS250A300B52 x 3 BLRCS250A300B52 x 6

51563 x 1 51564 x 1 51565 x 1 51566 x 1 51567 x 1

LC1-DGK11M7 x 1 LC1D12 x 1 LC1-DTK12M7 x 1 LC1D50 x 1

33

Low Voltage Capacitors

VarplusCan SDuty + Detuned Reactor + Contactor

PE90154_L28_r.eps

Network 400 V, 60 Hz Capacitor Voltage 480 V 5.7% / 7 % Filter


Effective QN Capacitor Ref. Power at (kvar) 480 V
6.5 10 12.5 25 50 100 9 13.6 17.3 35 69 138

5.7 % (250 Hz) R Ref

7% (230 Hz) R Ref

Capacitor Duty Contactor Ref.

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D12 x 1

BLRCS075A090B48 x 1 BLRCS113A136B48 x 1 BLRCS144A173B48 x 1 BLRCS288A346B48 x 1 BLRCS288A346B48 x 2 BLRCS339A407B48 x 4

LVR05065B40 x 1 LVR05100B40 x 1 LVR05125B40 x 1 LVR05250B40 x 1 LVR05500B40 x 1 LVR05X00B40 x 1

LVR07065B40 x 1 LVR07100B40 x 1 LVR07125B40 x 1 LVR07250B40 x 1 LVR07500B40 x 1 LVR07X00B40 x 1

LC1-DFK11M7 x 1 LC1-DFK11M7 x 1 LC1-DFK11M7 x 1

LC1-DMK11M7 x 1 LC1D32 x 1 LC1-DWK12M7 x 1 LC1D80 x 1 LC1D115 x 1

PE90131_L28_r.eps

Network 400 V, 60 Hz Capacitor Voltage 480 V 14 % Filter


Effective QN Capacitor Ref. Power at (kvar) 480 V
6.5 10 12.5 25 50 100 8 12.5 16.3 31 62 124

14 % (135 Hz) R Ref.

Capacitor Duty Contactor Ref.


LC1-DFK11M7 x1 LC1-DFK11M7 x1 LC1-DFK11M7 x1 LC1-DLK11M7 x1 LC1-DTK12M7 x1 -

Power Contactor Ref.


LC1D12 x1 LC1D12 x1 LC1D12 x1 LC1D25 x1 LC1D50 x1 LC1D115 x 1

BLRCS067A080B48 x 1 BLRCS104A125B48 x 1 BLRCS136A163B48 x 1 BLRCS258A310B48 x 1 BLRCS258A310B48 x 2 BLRCS258A310B48 x 4

LVR14065B40 x 1 LVR14010B40 x 1 LVR14125B40 x 1 LVR14250B40 x 1 LVR14500B40 x 1 LVR14X00B40 x 1

PE90158_L20_r.eps

Network 400 V, 60 Hz Capacitor Voltage 525 V 5.7 % / 7 % Filter


Effective QN Capacitor Ref. Power at (kvar) 525 V
6.5 10 12.5 25 50 10.6 16.2 20.6 41 81 162

5.7 % (210 Hz) R Ref

7% (190 Hz) R Ref

Capacitor Duty Contactor Ref.

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D12 x 1

BLRCS088A106B52 x 1 BLRCS135A162B52 x 1 BLRCS172A206B52 x 1 BLRCS172A206B52 x 2

LVR05065B40 x 1 LVR05100B40 x 1 LVR05125B40 x 1 LVR05250B40 x 1

LVR07065B40 x 1 LVR07100B40 x 1 LVR07125B40 x 1 LVR07250B40 x 1 LVR07500B40 x 1 LVR07X00B40 x 1

LC1-DFK11M7 x 1 LC1-DFK11M7 x 1 LC1-DFK11M7 x 1

LC1-DMK11M7 x 1 LC1D32 x 1 LC1-DWK12M7 x 1 LC1D80 x 1 LC1D115 x 1

Contactor LC1DPK.

BLRCS200A240B52 x 2 + LVR05500B40 x 1 BLRCS275A330B52 x 1 BLRCS200A240B52 x 4 + LVR05X00B40 x 1 BLRCS275A330B52 x 2

100

Network 400 V, 60 Hz Capacitor Voltage 525 V 14 % Filter


Effective QN Capacitor Ref. Power at (kvar) 525 V
6.5 10 12.5 25 50 100 9.6 14.8 18.5 37 75 150

14 % (135 Hz) R Ref.

Capacitor Duty Contactor Ref.


LC1-DFK11M7 x 1 LC1-DFK11M7 x 1 LC1-DFK11M7 x 1 LC1-DLK11M7 x 1

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D12 x 1 LC1D25 x 1

BLRCS080A096B52 x 1 BLRCS125A150B52 x 1 BLRCS154A185B52 x 1 BLRCS154A185B52 x 2

LVR14065B40 x 1 LVR14010B40 x 1 LVR14125B40 x 1 LVR14250B40 x 1

BLRCS250A300B52 x 2 + LVR14500B40 x 1 BLRCS125A150B52 x 1 BLRCS250A300B52 x 4 + LVR14X00B40 x 1 BLRCS125A150B52 x 2

LC1-DTK12M7 x 1 LC1D50 x 1 LC1D115 x 1

34

VarplusCan HDuty harmonic applications


This harmonic rated range of capacitors is dedicated to applications where a high number of non-linear loads are present (NLL up to 30 %). These capacitors are designed for use with detuned reactors, based on the Standard Heavy technology.
PE90131.eps PE90154.eps

Operating conditions

bb For networks with a large number of non-linear loads (NLL < 50 %). bb Significant voltage disturbances. bb Significant switching frequency up to 7000 /year.

Rated voltage

In a detuned filter application, the voltage across the capacitors is higher than the network service voltage (US). Then, capacitors must be designed to withstand higher voltages. Depending on the selected tuning frequency, part of the harmonic currents are absorbed by the detuned capacitor bank. Then, capacitors must be designed to withstand higher currents, combining fundamental and harmonic currents. The rated voltage of VarplusCan HDuty capacitors is given in the table below, for different values of network service voltage and relative impedance.

+
Detuned reactor VarplusCan HDuty

Capacitor Rated Voltage UN (V)

Relative Impedance (%)

5.7 7 14

Network Service Voltage US (V) 50 Hz 60 Hz 400 690 400 480 480 830 480 575

600 690

In the following pages, the effective power (kvar) given in the tables is the reactive power provided by the combination of capacitors and reactors.

35

Low Voltage Capacitors

VarplusCan HDuty + Detuned Reactor + Contactor

PE90154_L28_r.eps

Network 400 V, 50 Hz Capacitor Voltage 480 V 5.7 % / 7 % Filter


Effective QN Capacitor Ref. Power at (kvar) 480 V
6.5 12.5 25 50 100 8.8 17 33.9 68 136

5.7 % (210 Hz) R Ref

7% (190 Hz) R Ref

Capacitor Duty Contactor Ref.

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D32 x 1 LC1D80 x 1 LC1D115 x 1

BLRCH088A106B48 x 1 BLRCH170A204B48 x 1 BLRCH339A407B48 x 1 BLRCH339A407B48 x 2 BLRCH339A407B48 x 4

51573 x1 52404 x1 52405 x1 52406 x1 52407 x1

51568 x1 52352 x 1 52353 x1 52354 x1 51569 x1

LC1-DFK11M71 LC1-DFK11M71 LC1-DMK11M71 LC1-DWK12M71 -

PE90131_L28_r.eps

Network 400 V, 50 Hz Capacitor Voltage 480 V 14 % Filter


Effective QN Capacitor Ref. Power at (kvar) 480 V
6.5 12.5 25 50 100 8.8 15.5 31.5 63 126

14 % (135 Hz) R Ref.

Capacitor Duty Contactor Ref.


LC1-DFK11M7 x1 LC1-DFK11M7 x1 LC1-DLK11M7 x1 LC1-DTK12M7 x1 -

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D25 x 1 LC1D50 x 1 LC1D115 x 1

BLRCH088A106B48 x 1 BLRCH155A186B48 x 1 BLRCH315A378B48 x 1 BLRCH315A378B48 x 2 BLRCH315A378B48 x 4

51563 x 1 51564 x 1 51565 x 1 51566 x 1 51567 x 1

PE90158_L20_r.eps

Network 400 V, 50 Hz Capacitor Voltage 525 V 5.7 % / 7 % Filter


Effective QN Capacitor Ref. Power at (kvar) 525 V
6.5 12.5 25 50 100 10.6 20 40.0 80.0 160.0

5.7 % (210 Hz) R Ref

7% (190 Hz) R Ref

Capacitor Duty Contactor Ref.

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D32 x 1 LC1D80 x 1 LC1D115 x 1

BLRCH106A127B52 x 1 BLRCH200A240B52 x 1 BLRCH400A480B52 x 1 BLRCH400A480B52 x 2 BLRCH400A480B52 x 4

51573 x 1 52404 x 1 52405 x 1 52406 x 1 52407 x 1

51568 x 1 52352 x 1 52353 x 1 52354 x 1 51569 x 1

LC1-DFK11M71 LC1-DFK11M71 LC1-DMK11M71 LC1-DWK12M71 -

Contactor LC1DPK.

Network 400 V, 50 Hz Capacitor Voltage 525 V 14 % Filter


Effective QN Capacitor Ref. Power at (kvar) 525 V
6.5 12.5 25 50 100 10.6 18.5 37.7 75 150

14 % (135 Hz) R Ref.

Capacitor Duty Contactor Ref.


LC1-DFK11M7 x 1 LC1-DFK11M7 x 1 LC1-DLK11M7 x 1 -

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D25 x 1 LC1D115 x 1

BLRCH106A127B52 x 1 BLRCH185A222B52 x 1 BLRCH377A452B52 x 1 BLRCH377A452B52 x 2 BLRCH377A452B52 x 4

51563 x 1 51564 x 1 51565 x 1 51566 x 1 51567 x 1

LC1-DTK12M7 x 1 LC1D50 x 1

Network 690 V, 50 Hz Capacitor Voltage 830 V 5.7 % / 7 % Filter


Effective QN Capacitor Ref. Power at (kvar) 830 V
12.5 25 50 100 17.1 34 68 136

5.7 % (210 Hz) R Ref

7% (190 Hz) R Ref

Capacitor Duty Contactor Ref.

Power Contactor Ref.


LC1D12 x 1 LC1D25 x 1

BLRCH171A205B83 x 1 BLRCH341A409B83 x 1 BLRCH341A409B83 x 2 BLRCH341A409B83 x 4

LVR05125A69 x 1 LVR05250A69 x 1 LVR05500A69 x 1 LVR05X00A69 x 1

LVR07125A69 x 1 LVR07250A69 x 1 LVR07500A69 x 1 LVR07X00A69 x 1

LC1-DFK11M7 x 1 LC1-DLK11M7 x 1

LC1-DTK12M7 x 1 LC1D50 x 1 LC1-DWK12M7 x 1 LC1D80 x 1

36

VarplusCan HDuty + Detuned Reactor + Contactor


Network 400 V, 60 Hz Capacitor Voltage 480 V 5.7 % / 7 % Filter
Effective QN Capacitor Ref. Power at (kvar) 480 V
6.5 10 12.5 25 50 100
PE90131_L28_r.eps

PE90154_L28_r.eps

5.7 % (250 Hz) R Ref

7% (230 Hz) R Ref

Capacitor Duty Contactor Ref.

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D12 x 1 LC1D32 x 1 LC1D80 x 1 LC1D115 x 1

9 13.6 17.3 34.6 68 136

BLRCH075A090B48 x 1 BLRCH113A136B48 x 1 BLRCH144A173B48 x 1 BLRCH288A346B48 x 1 BLRCH288A346B48 x 2 BLRCH288A346B48 x 4

LVR05065B40 x 1 LVR05100B40 x 1 LVR05125B40 x 1 LVR05250B40 x 1 LVR05500B40 x 1 LVR05X00B40 x 1

LVR07065B40 x 1 LVR07100B40 x 1 LVR07125B40 x 1 LVR07250B40 x 1 LVR07500B40 x 1 LVR07X00B40 x 1

LC1-DFK11M71 LC1-DFK11M71 LC1-DFK11M71 LC1-DMK11M71 LC1-DWK12M71 -

Network 400 V, 60 Hz Capacitor Voltage 480 V 14 % Filter


Effective QN Capacitor Ref. Power at (kvar) 480 V
6.5 10 12.5 25 50 100 8 12.5 16.3 31 62 124

14 % (160 Hz) R Ref.

Capacitor Duty Contactor Ref.


LC1-DFK11M7 x1 LC1-DFK11M7 x1 LC1-DFK11M7 x1 LC1-DLK11M7 x1 LC1-DTK12M7 x1 -

Power Contactor Ref.


LC1D12 x1 LC1D12 x1 LC1D12 x1 LC1D25 x1 LC1D50 x1 LC1D115 x 1

BLRCH067A080B48 x 1 BLRCH104A125B48 x 1 BLRCH136A163B48 x 1 BLRCH258A310B48 x 1 BLRCH258A310B48 x 2 BLRCH258A310B48 x 4

LVR14065B40 x 1 LVR14010B40 x 1 LVR14125B40 x 1 LVR14250B40 x 1 LVR14500B40 x 1 LVR14X00B40 x 1

Network 400 V, 60 Hz Capacitor Voltage 525 V 5.7 % / 7 % Filter


Effective QN Capacitor Ref. Power at (kvar) 525 V
6.5 10
PE90158_L20_r.eps

5.7 % (250 Hz) R Ref


LVR05065B40 x 1 LVR05100B40 x 1 LVR05125B40 x 1 LVR05250B40 x 1 LVR05500B40 x 1 LVR05X00B40 x 1

7% (230 Hz) R Ref


LVR07065B40 x 1 LVR07100B40 x 1 LVR07125B40 x 1 LVR07250B40 x 1 LVR07500B40 x 1 LVR07X00B40 x 1

Capacitor Duty Contactor Ref.


LC1-DFK11M71 LC1-DFK11M71 LC1-DFK11M71 LC1-DMK11M71 LC1-DWK12M71 -

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D12 x 1 LC1D32 x 1 LC1D80 x 1 LC1D115 x 1

10.6 16.2 20.6 41.3 83 165

BLRCH088A106B52 x 1 BLRCH135A162B52 x 1 BLRCH172A206B52 x 1 BLRCH344A413B52 x 1 BLRCH344A413B52 x 2 BLRCH344A413B52 x 4

12.5 25 50 100

Network 400 V, 60 Hz Capacitor Voltage 525 V 14 % Filter


Effective QN Capacitor Ref. Power at (kvar) 525 V
6.5 9.6 14.8 18.5 37.1 74 148

14 % (160 Hz) R Ref.

Capacitor Duty Contactor Ref.


LC1-DFK11M7 x 1 LC1-DFK11M7 x 1 LC1-DFK11M7 x 1 LC1-DLK11M7 x 1 -

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D12 x 1 LC1D25 x 1 LC1D115 x 1

BLRCH080A096B52 x 1 BLRCH125A150B52 x 1 BLRCH154A185B52 x 1 BLRCH309A371B52 x 1 BLRCH309A371B52 x 2 BLRCH309A371B52 x 4

LVR14065B40 x 1 LVR14010B40 x 1 LVR14125B40 x 1 LVR14250B40 x 1 LVR14500B40 x 1 LVR14X00B40 x 1

Contactor LC1DPK.

10 12.5 25 50 100

LC1-DTK12M7 x 1 LC1D50 x 1

Network 480 V, 60 Hz Capacitor Voltage 575 V 5.7 % Filter


Effective QN Capacitor Ref. Power at (kvar) 575 V
12.5 25 50 100 18 35 70 140

5.7 % (250 Hz) R Ref.

Capacitor Duty Contactor Ref.


LC1-DFK11M7 x 1 LC1-DLK11M7 x 1 -

Power Contactor Ref.


LC1D12 x 1 LC1D25 x 1 LC1D115 x 1

BLRCH150A180B57 x 1 BLRCH292A350B57 x 1 BLRCH292A350B57 x 2 BLRCH292A350B57 x 4

LVR05125B48 x 1 LVR05250B48 x 1 LVR05500B48 x 1 LVR05X00B48 x 1

LC1-DTK12M7 x 1 LC1D50 x 1

Network 600 V, 60 Hz Capacitor Voltage 690 V 5.7 % Filter


Effective QN Capacitor Ref. Power at (kvar) 690 V
12.5 25 50 100 16.5 33.1 66 132

5.7 % (250 Hz) R Ref.

Capacitor Duty Contactor Ref.


LC1-DFK11M7 x 1 LC1-DLK11M7 x 1 -

Power Contactor Ref.


LC1D12 x 1 LC1D25 x 1 LC1D115 x 1

BLRCH138A165B69 x 1 BLRCH276A331B69 x 1 BLRCH276A331B69 x 2 BLRCH276A331B69 x 4

LVR05125B60 x 1 LVR05250B60 x 1 LVR05500B60 x 1 LVR05X00B60 x 1

LC1-DTK12M7 x 1 LC1D50 x 1

37

Low Voltage Capacitors

VarplusCan Energy harmonic applications

This harmonic rated range of capacitors is dedicated to applications where a high number of non-linear loads are present (NLL up to 30 %). These capacitors are designed for use with detuned reactors, based on the Energy technology.
PE90131.eps PE90154.eps

Operating conditions

bb For networks with a large number of non-linear loads (NLL < 50 %). bb Significant voltage disturbances. bb Severe temperature conditions up to 70 C. bb Very frequent switching operations up to 10,000/year.

Rated voltage

In a detuned filter application, the voltage across the capacitors is higher than the network service voltage (US). Then, capacitors must be designed to withstand higher voltages. Depending on the selected tuning frequency, part of the harmonic currents is absorbed by the detuned capacitor bank. Then, capacitors must be designed to withstand higher currents, combining fundamental and harmonic currents. The rated voltage of VarplusCan Energy capacitors is given in the table below, for different values of network service voltage and relative impedance.

+
Detuned reactor VarplusCan SDuty

Capacitor Rated Voltage UN (V)

Relative Impedance (%)

5.7 7 14

Network Service Voltage US (V) 50 Hz 60 Hz 400 400 480 480

In the following pages, the effective power (kvar) given in the tables is the reactive power provided by the combination of capacitors and reactors.

38

VarplusCan Energy + Detuned Reactor + Contactor

PE90154_L28_r.eps

Network 400 V, 50 Hz Capacitor Voltage 480 V 5.7 % / 7 % Filter


Effective QN Capacitor Ref. Power at (kvar) 480 V
6.5 12.5 25 50 100 8.8 17 34 68 136

5.7 % (210 Hz) R Ref

7% (190 Hz) R Ref

Capacitor Duty Contactor Ref.

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1

BLRCE088A106B48 x 1 BLRCE170A204B48 x 1 BLRCE170A204B48 x 2 BLRCE170A204B48 x 4 BLRCE170A204B48 x 8

51573 x 1 52404 x 1 52405 x 1 52406 x 1 52407 x 1

51568 x 1 52352 x 1 52353 x 1 52354 x 1 51569 x 1

LC1-DFK11M7 x 1 LC1-DFK11M7 x 1

LC1-DMK11M7 x 1 LC1D32 x 1 LC1-DWK12M7 x 1 LC1D80 x 1 LC1D115 x 1

PE90131_L28_r.eps

Network 400 V, 50 Hz Capacitor Voltage 480 V 14 % Filter


Effective QN Capacitor Ref. Power at (kvar) 480 V
6.5 12.5 25 50 100 8.8 15.5 31 62 124

14 % (135 Hz) R Ref.

Capacitor Duty Contactor Ref.


LC1-DFK11M7 x1 LC1-DFK11M7 x1 LC1-DLK11M7 x1 LC1-DTK12M7 x1 -

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D25 x 1 LC1D50 x 1 LC1D115 x 1

BLRCE088A106B48 x 1 BLRCE155A186B48 x 1 BLRCE155A186B48 x 2 BLRCE155A186B48 x 4 BLRCE155A186B48 x 8

51563 x 1 51564 x 1 51565 x 1 51566 x 1 51567 x 1

Network 400 V, 60 Hz Capacitor Voltage 480 V 5.7 % / 7 % Filter


Effective QN Capacitor Ref. Power at (kvar) 480 V
6.5 10 12.5 25 50
PE90158_L20_r.eps

5.7 % (250 Hz) R Ref

7% (230 Hz) R Ref

Capacitor Duty Contactor Ref.

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D12 x 1 LC1D32 x 1 LC1D115 x 1

8.9 13.6 17.3 35 69 138

BLRCE075A090B48 x 1 BLRCE113A136B48 x 1 BLRCE144A173B48 x 1 BLRCE144A173B48 x 2 BLRCE144A173B48 x 4 BLRCE144A173B48 x 8

LVR05065B40 x 1 LVR05100B40 x 1 LVR05125B40 x 1 LVR05250B40 x 1 LVR05500B40 x 1 LVR05X00B40 x 1

LVR07065B40 x 1 LVR07100B40 x 1 LVR07125B40 x 1 LVR07250B40 x 1 LVR07500B40 x 1 LVR07X00B40 x 1

LC1-DFK11M7 x 1 LC1-DFK11M7 x 1 LC1-DFK11M7 x 1 LC1-DLK11M7 x 1 -

LC1-DTK12M7 x 1 LC1D80 x 1

100

Network 400 V, 60 Hz Capacitor Voltage 480 V 14 % Filter


Effective QN Capacitor Ref. Power at (kvar) 480 V
6.5 10 12.5 25 50 100 8 12.5 16.3 33 65 130

14 % (160 Hz) R Ref.

Capacitor Duty Contactor Ref.


LC1-DFK11M7 x1 LC1-DFK11M7 x1 LC1-DFK11M7 x1 LC1-DMK11M7 x1 -

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D12 x 1 LC1D25 x 1 LC1D115 x 1

BLRCE067A080B48 x 1 BLRCE104A125B48 x 1 BLRCE136A163B48 x 1 BLRCE136A163B48 x 2 BLRCE136A163B48 x 4 BLRCE136A163B48 x 8

LVR14065B40 x 1 LVR14010B40 x 1 LVR14125B40 x 1 LVR14250B40 x 1 LVR14500B40 x 1 LVR14X00B40 x 1

Contactor LC1DPK.

LC1-DWK12M7 x1 LC1D50 x 1

39

Low Voltage Capacitors

VarplusCan mechanicalcharacteristics
Case Code: DC, HC & LC
Creepage distance Clearance Expansion (a)
min.16 mm min.16 mm max.10 mm

VPCDC,HC&LC_r.eps

Termination cable (300 mm length) FAST-ON Terminal 6.35 x 0.8 0.5 + a

19 2 2+t

Mounting details (for M10/M12 mounting stud)


Torque Toothed washer Hex nut Terminal assembly Ht. (t)
M10: 7 N.m M12: 10 N.m M10/M12 M10/M12 50 mm

TS

TH

h h

Toothed washer Hex nut


VarplusCan DC, EC, FC, HC & LC.

50 63 70

Size (d)

TS

M10 M12 M12

TH

10 mm 13 mm 16 mm

DC EC FC HC LC

Case code

Diameter d Height h (mm) (mm)


50 63 63 63 70 195 90 115 195 195

Height h + t (mm)
245 140 165 245 245

Weight (kg)
0.7 0.5 0.5 0.9 1.1

VPCMC,NC,RC&SC_r.eps

1+5 Finger proof CLAMPTITE terminal In-built resistor type (t)

Case Code: MC, NC, RC & SC


Creepage distance Clearance Expansion (a)
min.13 mm min.13 mm max.12 mm

3 3 + a (expansion) 3+t

Mounting details (for M12 mounting stud)


Torque Toothed washer Hex nut Terminal screw
Toothed washer Hex nut Tightening Torque = 2.5 Nm
T = 10 Nm J12.5 DIN 6797 BM12 DIN 439 M5 30 mm

16 + 1

M12 M

h h h

Terminal assembly Ht. (t)

MC NC RC SC

Case code

Diameter d Height h (mm) (mm)


75 75 90 90 203 278 212 278

Height h + t (mm)
233 308 242 308

Weight (kg)
1.2 1.2 1.6 2.3

15

15

VarplusCan MC, NC, RC & SC.

40

VPCTC,UC&VC_r.eps

1+5

F Finger proof C CLAMPTITE terminal In-built resistor type

Case Code: TC, UC & VC


Creepage distance Clearance Expansion (a)
min.13 mm min.13 mm max.12 mm

3 3 + a (expansion) 3+t

(t)

Mounting details (for M12 mounting stud)


Torque Toothed washer Hex nut Terminal screw Terminal assembly Ht. (t)
T = 10 Nm J12.5 DIN 6797 BM12 DIN 439 M5 30 mm

16 + 1

M12 M M12

h h h Toothed washer Hex nut

Tightening Torque = 2.5 Nm

TC

Case code

Diameter d Height h (mm) (mm)


116 116 136 212 278 212

Height h + t (mm)
242 308 242

Weight (kg)
2.5 3.5 3.2

15

15 5

UC VC

VarplusCan TC, UC & VC.


VPC XC, YC_r.eps

1+5 M10 2 STUD type terminal In-built resistor type

Case Code: XC & YC


Creepage distance Clearance Expansion (a)
3 + a (expansion)

min.13 mm 34 mm max.12 mm

Mounting details (for M12 mounting stud)


3+t

Torque Toothed washer Hex nut Terminal screw Terminal assembly Ht. (t)

T = 10 Nm J12.5 DIN 6797 BM12 DIN 439 M10 43 mm

16 + 1

M12 Toothed washer Hex nut

XC YC

Case code

Diameter d Height h (mm) (mm)


116 278 278 136

Height h + t (mm)
321 321

Weight (kg)
4.1 5.3

Tightening Torque = 12 N.m

47 1

VarplusCan XC & YC.

41

Low Voltage Capacitors

VarplusBox capacitor

VarplusBox capacitors deliver reliable performance in the most severe application conditions, in Fixed & Automatic PFC systems, in networks with frequently switched loads and harmonic disturbances.
PE90135_r.eps

Main features

Robustness bb Double metallic protection. bb Mechanically well suited for stand-alone installations. Safety bb Its unique safety feature electrically disconnects the capacitors safely at the end of their useful life. bb The disconnectors are installed on each phase, which makes the capacitors very safe, in addition to the protective steel enclosure. Flexibility bb These capacitors can be easily mounted inside panels or in a stand-alone configuration. bb Suitable for flexible bank configuration.

For professionnals

bb Metal box enclosure. bb High power ratings up to 100 kvar. bb Easy repair and maintenance. bb Up to 70 C temperature. bb High inrush current withstand up to 400 x IN. bb Stand-alone PFC equipment. bb Direct connection to a machine, in harsh environmental conditions.

VarplusBox.

42

VarplusBox capacitor

groupof3boxcaps_r.eps

Construction Voltage range Power range (three-phase) Peak inrush current Overvoltage Overcurrent Mean life expectancy Safety Dielectric

SDuty

Steel sheet enclosure 380 V - 480 V 2.5 - 100 kvar Up to 200 x IN 1.1 x UN 8 h every 24 h 1.5 x IN Up to 100,000 h

HDuty
230 V - 830 V

Energy
400 V - 525 V

Up to 250 x IN

Up to 350 x IN

1.8 x IN Up to 130,000 h

2.5 x IN Up to 160,000 h

Self-healing + pressure-sensitive disconnector + discharge device (50 V/1 min) Metallized polypropylene film with Zn/Al alloy Metallized Polypropylene film with Zn/Al alloy with special profile metallization and wave cut Double metallized paper + Polypropylene film

Impregnation Ambient temperature Protection Mounting Terminals

Non-PCB, Biodegradable resin min. -25 C max 55 C IP20 Indoor Upright

Non-PCB, sticky (dry) Non-PCB, oil Biodegradable resin min. -25 C max 70 C

Upright, Horizontal

Upright

Bushing terminals designed for large cable termination and direct busbar mounting for banking

43

Low Voltage Capacitors

VarplusBox SDuty

A safe, reliable and high-performance solution for power factor correction in standard operating conditions.

Operating conditions

bb For networks with insignificant non-linear loads (NLLy10 %). bb Standard voltage disturbances. bb Standard operating temperature up to 55 C. bb Normal switching frequency up to 5000 /year. bb Maximum current withstand 1.5xIN.

Constructed internally with three single-/three-phase capacitor elements. The design is specially adapted for mechanical stability. The enclosures of the units are designed to ensure that the capacitors operate reliably in hot and humid tropical conditions, without the need of any additional ventilation louvres (see technical specifications). Special attention is paid to equalization of temperatures within the capacitor enclosures since this gives better overall performance.

Technology

Benefits

VarplusBox SDuty

bb Mechanically well suited for stand-alone installations. bb Safety: vv self-healing vv pressure-sensitive disconnector on all three phases vv discharge resistor. bb These capacitors can be easily mounted inside panels or in a stand-alone configuration. bb Availability on power ratings up to 100 kvar. bb Suitable for flexible banking.

44

VarplusBox SDuty

Technical specifications
Standards

General characteristics

IEC 60831-1/-2 380 to 480V 50 / 60 Hz 7.5 to 100 kvar < 0.2W/kvar < 0.5W/kvar -5%, +10% 2.15 x UN (AC), 10 s 3 kV (AC), 10 s or 3.66 kV (AC), 2 s 8 kV Fitted, standard discharge time 60s Discharge time 180 s on request -25 / 55 C (Class D) 95 % 2,000 m above sea level 1.1xUN 8 h in every 24 h Up to 1.5xIN 200xIN Up to 5,000 switching operations per year Up to 100,000 hrs NLL y 10 % Indoor, upright Mounting cleats Bushing terminals designed for large cable termination and direct busbar mounting for banking Self-healing + Pressure-sensitive disconnector for each phase + Discharge device IP20 Sheet steel enclosure Metallized polypropylene film with Zn/Al alloy. Biodegradable, Non-PCB, PUR (soft) resin

Voltage range Frequency Power range Losses (dielectric) Losses (total) Capacitance tolerance Voltage test Between terminals Between terminal & container Impulse voltage Discharge resistor

Ambient temperature Humidity Altitude Overvoltage Overcurrent Peak inrush current

Working conditions

Switching operations (max.) Mean Life expectancy Harmonic content Mounting position Fastening Earthing Terminals

Installation characteristics

Safety

Safety features

Protection Casing

Construction

Dielectric Impregnation

45

Low Voltage Capacitors

VarplusBox SDuty

Rated Voltage 380/400/415 V


50 Hz
QN (kvar) 380 V 5.7 6.8 7.5 9.4 11.3 13.5 15.1 18.8 22.6 37.6 45.1 56.4 67.7 75.2 90.3 400 V 6.3 7.5 8.3 10.4 12.5 15 16.7 20.8 25 41.7 50 62.5 75 83.3 100 415 V 6.8 8.1 8.9 11.2 13.5 16.1 18.0 22.4 26.9 44.9 53.8 67.3 80.7 89.7 108 IN (A) at 400 V 9.1 10.8 12.0 15.0 18.0 21.7 24.1 30.0 36.1 60.2 72.2 90.2 108 120 144

60 Hz
QN (kvar) 380 V 6.8 8.1 9.0 11.3 13.5 16.2 18.1 22.6 27.1 45.1 ----67.7 81.2 90.3 108 400 V 7.5 9 10 12.5 15 18 20 25 30 50 --75 90 100 120 415 V 8.1 9.7 10.8 13.5 16.1 19.4 21.5 26.9 32.3 53.8 ----80.7 96.9 108 129 IN (A) at 400 V 10.8 13.0 14.4 18.0 21.7 26.0 28.9 36.1 43.3 72.2 ----108 130 144 173

F (X3)

Case Code

Reference Number

41.8 49.7 55.0 68.9 82.9 99.4 111 138 166 276 331 414 497 552 663

EB EB EB EB DB DB DB DB FB HB HB RB RB SB SB

BLRBS063A075B40 BLRBS075A090B40 BLRBS083A100B40 BLRBS104A125B40 BLRBS125A150B40 BLRBS150A180B40 BLRBS167A200B40 BLRBS208A250B40 BLRBS250A300B40 BLRBS417A500B40 BLRBS500A000B40 BLRBS625A750B40 BLRBS750A900B40 BLRBS833AX00B40 BLRBSX00AX20B40

Rated Voltage 440 V


50 Hz
QN (kvar) 7.5 10 12.5 15 20 25 50 75 100

60 Hz

F (X3)
IN (A) 11.8 15.7 19.7 23.6 31.5 39.4 --118 157 41.1 54.8 68.5 82.2 110 137 274 411 548

Case Code
EB EB EB DB DB DB HB RB SB

Reference Number

IN (A) 9.8 13.1 16.4 19.7 26.2 32.8 65.6 98.4 131

QN (kvar) 9 12 15 18 24 30 --90 120

BLRBS075A090B44 BLRBS100A120B44 BLRBS125A150B44 BLRBS150A180B44 BLRBS200A240B44 BLRBS250A300B44 BLRBS500A000B44 BLRBS750A900B44 BLRBSX00AX20B44

Rated Voltage 480 V


50 Hz
QN (kvar) 6.3 8.3 10.4 12.5 17 20.8 41.7 62.5 83.3

60 Hz

F (X3)
IN (A) 9.0 12.0 15.0 18.0 24.5 30.0 60.2 90.2 120 29.0 38.2 47.9 57.5 78.3 95.7 192 288 383

Case Code
EB EB EB DB DB DB HB RB SB

Reference Number

IN (A) 7.6 10 12.5 15 20.4 25 50.2 75.2 100

QN (kvar) 7.5 10 12.5 15 20.4 25 50 75 100

BLRBS063A075B48 BLRBS083A100B48 BLRBS104A125B48 BLRBS125A150B48 BLRBS170A204B48 BLRBS208A250B48 BLRBS417A500B48 BLRBS625A750B48 BLRBS833AX00B48

46

VarplusBox HDuty

A safe, reliable and high-performance solution for power factor correction in standard operating conditions.

Operating conditions

PE90137

bb For networks with significant non-linear loads (NLLy 20 %). bb Standard voltage disturbances. bb Standard operating temperature up to 55 C. bb Significant number of switching operations up to 7,000/year. bb Long life expectancy up to 130,000 hours.

Technology

Constructed internally with three single-phase capacitor elements. The design is specially adapted for mechanical stability. The enclosures of the units are designed to ensure that the capacitors operate reliably in hot and humid tropical conditions, without the need of any additional ventilation louvres (see technical specifications). Special attention is paid to equalization of temperatures within the capacitor enclosures since this gives better overall performance. Special design for total modularity and easy assembly with VarplusBox HDuty "Compact".

VarplusBox HDuty "Compact"

Benefits
PE90135

bb High performance: vv heavy edge metallization/wave-cut edge to ensure high inrush current capabilities vv special resistivity and profile metallization for better self-healing & enhanced life. bb Safety: vv its unique safety feature electrically disconnects the capacitors safely at the end of their useful life vv the disconnectors are installed on each phase, which makes the capacitors very safe, in addition to its protective steel enclosure. bb Flexibility: vv special "Compact" case with small footprint to be easily mounted and assembled vv availability on power ratings up to 100 kvar with parallel connection.

VarplusBox

Accessory for VarplusBox HDuty Compact

One set of 3-phase copper bars and assembly of 2 and 3 capacitors: ref. 51459.

47

Low Voltage Capacitors

VarplusBox HDuty

Technical specifications
Standards

General characteristics

IEC 60831-1/-2 230 to 830 V 50 / 60 Hz 2.5 to 100 kvar (from 2.5 to 20kvar: unique footprint for easy assembly) < 0.2W/kvar < 0.5W/kvar -5%, +10% 2.15 x UN (AC), 10s y 525 V: 3 kV (AC), 10 s or 3.66 kV (AC), 2 s > 525 V: 3.66 kV (AC), 10 s or 4.4 kV (AC), 2 s y 690 V: 8 kV > 690 V: 12 kV Fitted, standard discharge time 60s Discharge time 180 s on request -25 / 55 C (Class D) 95 % 2,000 m above sea level 1.1xUN 8h in every 24 h Up to 1.8xIN 250xIN Up to 7,000 switching operations per year Up to 130,000 hrs NLL y 20 % Indoor, upright & horizontal Mounting cleats Bushing terminals designed for large cable termination and direct busbar mounting for banking Self-healing + Pressure-sensitive disconnector for each phase + Discharge device IP20 (IP54 for VarplusBox Compact) Sheet steel enclosure Metallized polypropylene film with Zn/Al alloy. special resistivity & profile. Special edge (wave-cut) Non-PCB, PUR sticky resin (Dry)

Voltage range Frequency Power range Losses (dielectric) Losses (total) Capacitance tolerance Voltage test Between terminals Between terminal & container Impulse voltage Discharge resistor

Ambient temperature Humidity Altitude Overvoltage Overcurrent Peak inrush current

Working conditions

Switching operations (max.) Mean Life expectancy Harmonic content Mounting position Fastening Earthing Terminals

Installation characteristics

Safety

Safety features

Protection Casing

Construction

Dielectric Impregnation

48

VarplusBox HDuty

Rated Voltage 240/260 V


50 Hz
QN (kvar) 230 V 2.5 5 6.5 7.6 10 240 V 2.7 5.4 7.1 8.3 10.9 260 V 3.2 6.4 8.3 9.7 12.8 IN (A) at 260 V 7.1 14.2 18.4 21.6 28.4

60 Hz
QN (kvar) 230 V 3 6 7.8 9.2 12 240 V 3.3 7 8 10 13.0 260 V 4 7.7 10 11.7 15.3 IN (A) at 260 V 8.5 17 22.1 26.1 33.9

F (X3)

Case Code

Reference Number

50.1 100 130 152 200

AB AB AB AB AB

BLRBH027A033B24 BLRBH054A065B24 BLRBH071A080B24 BLRBH083A100B24 BLRBH109A130B24

Rated Voltage 380/400/415 V


50 Hz
QN (kvar) 380 V 2.3 4.5 5.7 6.8 7.5 9.4 11.3 13.5 15.1 18.1 18.8 22.6 37.6 45.1 56.4 67.7 75.2 90.3 400 V 2.5 5 6.3 7.5 8.3 10.4 12.5 15 16.7 20 20.8 25 41.7 50 62.5 75 83.3 100 415 V 2.7 5.4 6.8 8.1 8.9 11.2 13.5 16.1 18.0 21.5 22.4 26.9 44.9 53.8 67.3 80.7 89.7 108 IN (A) at 400 V 3.6 7.2 9.1 10.8 12.0 15.0 18.0 21.7 24.1 28.9 30.0 36.1 60.2 72.2 90.2 108 120 144

60 Hz
QN (kvar) 380 V 2.7 5.4 6.8 8.1 9.0 11.3 13.5 16.2 18.1 21.7 22.6 27.1 45.1 --67.7 81.2 90.3 108 400 V 3 6 7.5 9 10 12.5 15 18 20 24 25 30 50 --75 90 100 120 415 V 3.2 6.5 8.1 9.7 10.8 13.5 16.1 19.4 21.5 25.8 26.9 32.3 53.8 --80.7 96.9 108 129 IN (A) at 400 V 4.3 8.7 10.8 13.0 14.4 18.0 21.7 26.0 28.9 34.6 36.1 43.3 72.2 --108 130 144 173

F (X3)

Case Code

Reference Number

16.6 33.1 41.8 49.7 55.0 68.9 82.9 99.4 111 133 138 166 276 331 414 497 552 663

AB AB AB AB AB AB AB AB AB AB GB GB IB IB KB KB LB LB

BLRBH025A030B40 BLRBH050A060B40 BLRBH063A075B40 BLRBH075A090B40 BLRBH083A100B40 BLRBH104A125B40 BLRBH125A150B40 BLRBH150A180B40 BLRBH167A200B40 BLRBH200A240B40 BLRBH208A250B40 BLRBH250A300B40 BLRBH417A500B40 BLRBH500A000B40 BLRBH625A750B40 BLRBH750A900B40 BLRBH833AX00B40 BLRBHX00AX20B40

Rated Voltage 440 V


50 Hz
QN (kvar) 5 7.5 10 12.5 15 20 25 50 57.1 75 100

60 Hz

F (X3)
IN (A) 7.9 11.8 15.7 19.7 23.6 31.5 39.4 --118 157 27.4 41.1 54.8 68.5 82.2 110 137 274 313 411 548

Case Code
AB AB AB AB AB AB GB IB IB KB LB

Reference Number

IN (A) 6.6 9.8 13.1 16.4 19.7 26.2 32.8 65.6 74.9 98.4 131

QN (kvar) 6 9 12 15 18 24 30 --90 120

BLRBH050A060B44 BLRBH075A090B44 BLRBH100A120B44 BLRBH125A150B44 BLRBH150A180B44 BLRBH200A240B44 BLRBH250A300B44 BLRBH500A000B44 BLRBH571A000B44 BLRBH750A900B44 BLRBHX00AX20B44

VarplusBox Compact

49

Low Voltage Capacitors

VarplusBox HDuty

Rated Voltage 480 V


50 Hz
QN (kvar) 4.2 6.7 7.5 8.3 8.8 10.4 11.3 12.5 13.6 14.4 15.5 17.2 19.2 20.8 21.6 22.7 25.8 28.8 31.5 33.9 41.7 51.6 56.6 61.9 62.5 83.3

60 Hz

F (X3)
IN (A) 6.1 9.7 10.8 12.0 12.7 15.0 16.3 18.0 19.6 20.8 22.4 24.8 27.7 30.0 37.2 19.3 30.8 34.5 38.2 40.5 47.9 52.0 57.5 62.6 66.3 71.4 79.2 88.4 95.7 99.4 104 119 133 145 156 192 238 261 285 288 383

Case Code
AB AB AB AB AB AB AB AB AB AB AB AB AB GB AB AB IB IB IB IB IB IB IB IB KB LB

Reference Number

IN (A) 5.1 8.1 9.0 10.0 10.6 12.5 13.6 15.0 16.4 17.3 18.6 20.7 23.1 25.0 26.0 27.3 31.0 34.6 37.9 40.8 50.2 62.1 68.1 74.5 75.2 100

QN (kvar) 5 8 9 10 10.6 12.5 13.6 15 16.3 17.3 18.6 20.6 23 25 31 34.6 37.8 40.7 50 61.9 67.9 75 100

BLRBH042A050B48 BLRBH067A080B48 BLRBH075A090B48 BLRBH083A100B48 BLRBH088A106B48 BLRBH104A125B48 BLRBH113A136B48 BLRBH125A150B48 BLRBH136A163B48 BLRBH144A173B48 BLRBH155A186B48 BLRBH172A206B48 BLRBH192A230B48 BLRBH208A250B48 BLRBH216A000B48 BLRBH227A000B48 BLRBH258A310B48 BLRBH288A346B48 BLRBH315A378B48 BLRBH339A407B48 BLRBH417A500B48 BLRBH516A619B48 BLRBH566A679B48 BLRBH619A000B48 BLRBH625A750B48 BLRBH833AX00B48

41.6 45.5 48.9 60.2 74.5 81.7 90.2 120

Rated Voltage 525 V


50 Hz
QN (kvar) 5 7.5 10 12.5 16.7 20 25 50 75 100

60 Hz

F (X3)
IN (A) 6.6 9.9 13.2 16.5 22.0 26.4 33.0 66.0 99.0 132 19.2 28.9 38.5 48.1 64.3 77.0 96.2 192 289 385

Case Code
AB AB AB AB AB AB GB IB KB LB

Reference Number

IN (A) 5.5 8.2 11.0 13.7 18.4 22.0 27.5 55.0 82.5 110

QN (kvar) 6 9 12 15 20 24 30 60 90 120

BLRBH050A060B52 BLRBH075A090B52 BLRBH100A120B52 BLRBH125A150B52 BLRBH167A200B52 BLRBH200A240B52 BLRBH250A300B52 BLRBH500A600B52 BLRBH750A900B52 BLRBHX00AX20B52

Rated Voltage 575 V


50 Hz
QN (kvar) 6 12 15 20 30

60 Hz

F (X3)
IN (A) 7.2 14.5 18.1 24.1 36.1 19.2 38.5 48.1 64.2 96.2

Case Code
AB AB AB GB GB

Reference Number

IN (A) 6.0 12.0 15.1 20.1 30.1

QN (kvar) 7.2 14.4 18 24 36

BLRBH060A072B57 BLRBH120A144B57 BLRBH150A180B57 BLRBH200A240B57 BLRBH300A360B57

VarplusBox Compact

50

VarplusBox HDuty

Rated Voltage 600 V


50 Hz
QN (kvar) 4.2 8.3 10.4 12.5 16.7 20.8 41.7 62.5 83.3

60 Hz

F (X3)
IN (A) 4.8 9.6 12.0 14.4 19.3 24.0 48.2 72.2 96.2 12.4 24.5 30.6 36.8 49.2 61.3 123 184 245

Case Code
AB AB AB AB GB GB JB KB LB

Reference Number

IN (A) 4.0 8.0 10.0 12.0 16.1 20.0 40.1 60.1 80.2

QN (kvar) 5 10 12 15 20 25 50 75 100

BLRBH042A050B60 BLRBH083A100B60 BLRBH104A125B60 BLRBH125A150B60 BLRBH167A200B60 BLRBH208A250B60 BLRBH417A500B60 BLRBH625A750B60 BLRBH833AX00B60

Rated Voltage 690 V


50 Hz
QN (kvar) 5.5 10 11.1 13.8 15 18.4 20 27.6 50 75 100

60 Hz

F (X3)
IN (A) 5.5 10.0 11.1 13.8 15.1 18.5 20.1 27.7 50.2 75.3 100 12.3 22.3 24.7 30.6 33.4 41.0 44.6 61.4 111 167 223

Case Code
AB AB AB AB AB GB GB GB JB KB LB

Reference Number

IN (A) 4.6 8.4 9.3 11.5 12.6 15.4 16.7 23.1 41.8 62.8 83.7

QN (kvar) 6.6 12 13.3 16.5 18 22.1 24 33.1 60 90 120

BLRBH055A066B69 BLRBH100A120B69 BLRBH111A133B69 BLRBH138A165B69 BLRBH150A180B69 BLRBH184A221B69 BLRBH200A240B69 BLRBH276A331B69 BLRBH500A600B69 BLRBH750A900B69 BLRBHX00AX20B69

Rated Voltage 830 V


50 Hz
QN (kvar) 17.1 34.1

60 Hz

F (X3)
IN (A) 14.3 28.5 26.3 52.5

Case Code
AB GB

Reference Number

IN (A) 11.9 23.7

QN (kvar) 20.5 40.9

BLRBH171A205B83 BLRBH341A409B83

VarplusBox Compact

51

VarplusBox Energy

A safe, reliable and high-performance solution for power factor correction in standard operating conditions.

bb For networks with significant non-linear loads: (NLL<25 %). bb Severe voltage disturbances. bb Highest operating temperature (up to 70 C). bb High switching frequency, up to 10,000/year bb Maximum current withstand 2.5 x In.

Operating conditions

PE90134

Technology

Constructed internally with three single-phase capacitor elements. The design is specially adapted for mechanical stability. The enclosures of the units are designed to ensure that the capacitors operate reliably in hot and humid tropical conditions, without the need of any additional ventilation louvres (see technical specifications). Energy capacitors are the only technology which is capable of giving the longest life, highest overload limits and the highest operating ambient temperature due to use of the combination of polypropylene film and metallized paper.

PE90135

Benefits
VarplusBox Energy

bb High performance: vv high life expectancy up to 160,000 hours vv very high overload capabilities and good thermal and mechanical properties vv highest operating temperature (up to 70 C). bb Safety: vv its unique safety feature electrically disconnects the capacitors safely at the end of their useful life; vv the disconnectors are installed on each phase, which makes the capacitors very safe, in addition to its protective steel enclosure.

52

Low Voltage Capacitors

VarplusBox Energy

Technical specifications
Standards

General characteristics

IEC 60831-1/-2 380 to 525 V 50 / 60 Hz 5 to 100 kvar < 0.2W/kvar < 0.5W/kvar -5 %, +10 % 2.15 x UN (AC), 10 s 3 kV (AC), 10 s or 3.66 kV (AC), 2 s 8 kV Fitted, standard discharge time 60 s Discharge time 180 s on request -25 / 70 C (Class D) 95 % 2,000 m above sea level 1.1xUN 8 h in every 24 h Up to 2.5xIN 350xIN Up to 10,000 switching operations per year Up to 160,000 hrs NLL y 25 % Indoor, upright & horizontal Mounting cleats Bushing terminals designed for large cable termination and direct busbar mounting for banking Self-healing + Pressure-sensitive disconnector for each phase + Discharge device IP20 Sheet steel enclosure Double metallized paper + polypropylene film Non-PCB, oil

Voltage range Frequency Power range Losses (dielectric) Losses (total) Capacitance tolerance Voltage test Between terminals Between terminal & container Impulse voltage Discharge resistor

Ambient temperature Humidity Altitude Overvoltage Overcurrent Peak inrush current

Working conditions

Switching operations (max.) Mean Life expectancy Harmonic content Mounting position Fastening Earthing Terminals

Installation characteristics

Safety

Safety features

Protection Casing

Construction

Dielectric Impregnation

53

VarplusBox Energy

Rated Voltage 380/400/415 V


50 Hz
QN (kvar) 380 V 5.7 6.8 7.5 9.4 11.3 13.5 15.1 18.8 22.6 37.6 45.1 56.4 67.7 75.2 90.3 400 V 6.3 7.5 8.3 10.4 12.5 15 16.7 20.8 25 41.7 50 62.5 75 83.3 100 415 V 6.8 8.1 8.9 11.2 13.5 16.1 18 22.4 26.9 44.9 53.8 67.3 80.7 89.7 108 IN (A) at 400 V 9.1 10.8 12 15 18 21.7 24 30 36 60 72 90 108 120 144

60 Hz
QN (kvar) 380 V 6.8 8.1 9.0 11.3 13.5 16.2 18.1 22.6 27.1 45.1 54.2 67.7 81.2 90.3 108 400 V 7.5 9 10 12.5 15 18 20 25 30 50 60 75 90 100 120 415 V 8.1 9.7 10.8 13.5 16.1 19.4 21.5 26.9 32.3 53.8 64.6 80.7 96.9 108 129 IN (A) at 400 V 10.8 13.0 14.4 18.0 21.7 26 29 36 43 72 87 108 130 144 173

F (X3)

Case Code

Reference Number

41.8 49.7 55.0 68.9 82.9 99.4 111 138 166 276 331 414 497 552 663

DB DB DB DB GB GB GB GB GB IB IB KB KB LB LB

BLRBE063A075B40 BLRBE075A090B40 BLRBE083A100B40 BLRBE104A125B40 BLRBE125A150B40 BLRBE150A180B40 BLRBE167A200B40 BLRBE208A250B40 BLRBE250A300B40 BLRBE417A500B40 BLRBE500A600B40 BLRBE625A750B40 BLRBE750A900B40 BLRBE833AX00B40 BLRBEX00AX20B40

Rated Voltage 440 V


50 Hz
QN (kvar) 7.5 10 12.5 15 20 25 50 75 100

60 Hz

F (X3)
IN (A) 11.8 15.7 19.7 23.6 31.5 39 79 118 157 41.1 54.8 68.5 82.2 110 137 274 411 548

Case Code
DB DB DB GB GB GB IB KB LB

Reference Number

IN (A) 9.8 13.1 16.4 19.7 26.2 33 66 98 131

QN (kvar) 9 12 15 18 24 30 60 90 120

BLRBE075A090B44 BLRBE100A120B44 BLRBE125A150B44 BLRBE150A180B44 BLRBE200A240B44 BLRBE250A300B44 BLRBE500A600B44 BLRBE750A900B44 BLRBEX00AX20B44

Rated Voltage 480 V


50 Hz
QN (kvar) 6.7 7.5 8.8 10.4 11.3 12.5 13.6 14.4 15.5 17 20.8 25.8 28.8 31.5 33.9 41.7 62.5 83.3

60 Hz

F (X3)
IN (A) 9.7 10.8 12.7 15 16.3 18 19.6 20.8 22.4 24.5 30 37 42 46 49 60 90 30.8 34.5 40.5 47.9 52.0 57.5 62.6 66.3 71.4 78.3 95.7 119 133 145 156 192 288 383

Case Code
DB DB DB DB DB FB FB FB GB GB GB IB IB IB IB IB KB LB

Reference Number

IN (A) 8.1 9.0 10.6 12.5 13.6 15 16.4 17.3 18.6 20.4 25 31 35 38 41 50 75 100

QN (kvar) 8 9 10.6 12.5 13.6 15 16.3 17.3 18.6 20.4 25 31 34.6 37.8 40.7 50 75 100

BLRBE067A080B48 BLRBE075A090B48 BLRBE088A106B48 BLRBE104A125B48 BLRBE113A136B48 BLRBE125A150B48 BLRBE136A163B48 BLRBE144A173B48 BLRBE155A186B48 BLRBE170A204B48 BLRBE208A250B48 BLRBE258A310B48 BLRBE288A346B48 BLRBE315A378B48 BLRBE339A407B48 BLRBE417A500B48 BLRBE625A750B48 BLRBE833AX00B48

120

54

VarplusBox Energy

Rated Voltage 525 V


50 Hz
QN (kvar) 7.5 10 12.5 15.4 20 25 50 75 100

60 Hz

F (X3)
IN (A) 9.9 13.2 16.5 20.3 26.4 33 66 99 132 28.9 38.5 48.1 59.3 77 96.2 192 289 385

Case Code
DB DB FB FB GB GB IB KB LB

Reference Number

IN (A) 8.2 11 13.7 16.9 22 27.5 55 82.5 110

QN (kvar) 9 12 15 18.5 24 30 60 90 120

BLRBE075A090B52 BLRBE100A120B52 BLRBE125A150B52 BLRBE154A185B52 BLRBE200A240B52 BLRBE250A300B52 BLRBE500A600B52 BLRBE750A900B52 BLRBEX00AX20B52

55

Low Voltage Capacitors

VarplusBox HDuty harmonicapplications


Operating conditions

This harmonic rated range of capacitors is dedicated to applications where a high number of non-linear loads are present (NLL up to 30 %). These capacitors are designed for use with detuned reactors, based on the Heavy Duty technology.
PE90154+PE90134_r.eps

bb For networks with a large number of non-linear loads (NLL< 50 %). bb Significant voltage disturbances. bb Very frequent switching operations, up to 7,000/year.

Rated voltage

In a detuned filter application, the voltage across the capacitors is higher than the network service voltage (US). Then, capacitors must be designed to withstand higher voltages. Depending on the selected tuning frequency, part of the harmonic currents is absorbed by the detuned capacitor bank. Then, capacitors must be designed to withstand higher currents, combining fundamental and harmonic currents. The rated voltage of VarplusBox HDuty capacitors is given in the table below, for different values of network service voltage and relative impedance.

Detuned reactor VarplusBox HDuty

Capacitor Rated Voltage UN (V)

Network Service Voltage US (V) 50 Hz 400 690 830 60 Hz 400 480 480 575 600 690

Relative Impedance (%)

5.7 7 14

480

In the following pages, the effective power (kvar) given in the tables is the reactive power provided by the combination of capacitors and reactors.

56

VarplusBox HDuty + Detuned Reactor + Contactor

PE90154_L28_r.eps

Network 400 V, 50 Hz Capacitor Voltage 480 V 5.7 % / 7 % Detuned Reactor


Effective QN Capacitor Ref. Power at (kvar) 480 V
6.5 12.5 25 50 100 8.8 17 34 68 136

5.7 % (210 Hz) R Ref

7% (190 Hz) R Ref

Capacitor Duty Contactor Ref.

Power Contactor Ref.

BLRBH088A106B48 x 1 BLRBH172A206B48 x 1 BLRBH339A407B48 x 1 or BLRBH172A206B48 x 2 BLRBH339A407B48 x 2 or BLRBH227A000B48 x 3 BLRBH339A407B48 x 4 or BLRBH227A000B48 x 6

51573 x 1 52404 x 1 52405 x 1 52406 x 1 52407 x 1

51568 x 1 52352 x 1 52353 x 1 52354 x 1 51569 x 1

LC1-DFK11M7 x1 LC1-DFK11M7 x1 LC1-DMK11M7 x1

LC1D12 x 1 LC1D12 x 1 LC1D32 x 1

LC1-DWK12M7 x 1 LC1D80 x 1 LC1D115 x 1

PE90134_L28_r.eps

PE90154_L28_r.eps

Network 400 V, 50 Hz Capacitor Voltage 480 V 14 % Detuned Reactor


Effective QN Capacitor Ref. Power at (kvar) 480 V
6.5 12.5 25 50 100 8.8 15.5 31.5 63 126

14 % (135 Hz) R Ref.

Capacitor Duty Contactor Ref.

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D25 x 1 LC1D50 x 1 LC1D115 x 1

BLRBH083A100B48 x 1 BLRBH155A186B48 x 1 BLRBH315A378B48 x 1 or BLRBH155A186B48 x 2 BLRBH315A378B48 x 2 or BLRBH216A000B48 x 3 BLRBH315A378B48 x 4 or BLRBH216A000B48 x 6

51563 x 1 51564 x 1 51565 x 1 51566 x 1 51567 x 1

LC1-DFK11M7 x1 LC1-DFK11M7 x1 LC1-DLK11M7 x1 LC1-DTK12M7 x1 -

PE90137_L28_r.eps

PE90158_L20_r.eps

Network 690 V, 50 Hz Capacitor Voltage 830 V 5.7 % / 7 % Filter


Effective QN Power at (kvar) 830 V
12.5 25 17.1 34

Capacitor Ref.

5.7 % (210 Hz) R Ref

7% (190 Hz) R Ref


LVR07125A69 x1 LVR07250A69 x1 LVR07500A69 x1 LVR07X00A69 x1

Capacitor Duty Contactor Ref.


LC1-DFK11M7 x 1 LC1-DLK11M7 x 1

Power Contactor Ref.


LC1D12 x 1 LC1D25 x 1

BLRBH171A205B83 x 1 LVR05125A69 x 1 BLRBH341A409B83 x 1 LVR05250A69 x 1 or BLRBH171A205B83 x 2 50 68 BLRBH341A409B83 x 2 LVR05500A69 x 1 or BLRBH171A205B83 x 4 100 136 BLRBH341A409B83 x 4 LVR05X00A69 x 1 or BLRBH171A205B83 x 8 Note: reference Numbers in blue font are VarplusBox HDuty Compact.

LC1-DTK12M7 x 1 LC1D50 x 1 LC1-DWK12M7 x 1 LC1D80 x 1

57

Low Voltage Capacitors

VarplusBox HDuty + Detuned Reactor + Contactor

Network 400 V, 60 Hz Capacitor Voltage 480 V 5.7 % / 7 % Detuned Reactor


Effective Power (kvar)
6.5 10 12.5 25 50 100

QN at 480 V
9

Capacitor Ref.

5.7 % (250 Hz) R Ref

7% (230 Hz) R Ref

Capacitor Duty Contactor Ref.

Power Contactor Ref.


LC1D12 1 LC1D12 1 LC1D12 1 LC1D32 1 LC1D80 1 LC1D115 1

BLRBH075A090B48 1 BLRBH113A136B48 1 BLRBH144A173B48 1 BLRBH288A346B48 1 or BLRBH144A173B48 1 BLRBH566A679B48 1 or BLRBH192A230B48 3 BLRBH566A679B48 2 or BLRBH192A230B48 6

LVR05065B40 1 LVR05100B40 1 LVR05125B40 1 LVR05250B40 1 LVR05500B40 1 LVR05X00B40 1

LVR07065B40 1 LVR07100B40 1 LVR07125B40 1 LVR07250B40 1 LVR07500B40 1 LVR07X00B40 1

LC1-DFK11M7 1 LC1-DFK11M7 1 LC1-DFK11M7 1 LC1-DMK11M7 1 LC1-DWK12M7 1 -

13.6 17.3 34.6 67.9 135.8

Network 400 V, 60 Hz Capacitor Voltage 480 V 14 % Detuned Reactor


Effective Power (kvar)
6.5 10 12.5 25 50 100

QN at 480 V
8

Capacitor Ref.

14 % (160 Hz) R Ref.

Capacitor Duty Contactor Ref.


LC1-DFK11M7 1 LC1-DFK11M7 1 LC1-DFK11M7 1 LC1-DLK11M7 1 LC1-DTK12M7 1 -

Power Contactor Ref.


LC1D12 1 LC1D12 1 LC1D12 1 LC1D25 1 LC1D50 1 LC1D115 1

BLRBH067A080B48 1 BLRBH104A125B48 1 BLRBH136A163B48 1 BLRBH258A310B48 1 or BLRBH136A163B48 2 BLRBH516A619B48 1 or BLRBH172A206B48 3 BLRBH516A619B48 2 or BLRBH172A206B48 6

LVR14065B40 1 LVR14010B40 1 LVR14125B40 1 LVR14250B40 1 LVR14500B40 1 LVR14X00B40 1

12.5 16.3 31 61.9 123.8

Network 480 V, 60 Hz Capacitor Voltage 575 V 5.7 % Detuned Reactor


Effective Power (kvar)
12.5 25 50 100

QN at 575 V
18

Capacitor Ref.

5.7 % (250 Hz) R Ref.

Capacitor Duty Contactor Ref.


LC1-DFK11M7 1 LC1-DLK11M7 1 LC1-DTK12M7 1 -

Power Contactor Ref.


LC1D12 1 LC1D25 1 LC1D50 1 LC1D115 1

BLRBH150A180B57 1 BLRBH300A360B57 1 or BLRBH150A180B57 2 BLRBH300A360B57 2 or BLRBH150A180B57 4 BLRBH300A360B57 4 or BLRBH150A180B57 8

LVR05125B48 1 LVR05250B48 1 LVR05500B48 1 LVR05X00B48 1

36 72 144

Network 600 V, 60 Hz Capacitor Voltage 690 V 5.7 % Detuned Reactor


Effective Power (kvar)
12.5 25 50 100

QN at 690 V
16.5

Capacitor Ref.

5.7 % (250 Hz) R Ref.

Capacitor Duty Contactor Ref.


LC1-DFK11M7 1 LC1-DLK11M7 1 LC1-DTK12M7 1 -

Power Contactor Ref.


LC1D12 1 LC1D25 1 LC1D50 1 LC1D115 1

BLRBH138A165B69 1 BLRBH276A331B69 1 or BLRBH138A165B69 2 BLRBH276A331B69 2 or BLRBH138A165B69 4 BLRBH276A331B69 4 or BLRBH138A165B69 8

LVR05125B60 1 LVR05250B60 1 LVR05500B60 1 LVR05X00B60 1

33 66 132

Note: reference Numbers in blue font are VarplusBox HDuty Compact.

58

VarplusBox Energy Harmonic applications


This harmonic rated range of capacitors is dedicated to applications where a high number of non-linear loads are present (NLL up to 30 %). These capacitors are designed for use with detuned reactors, based on the Energy technology.
PE90154+PE90134_r.eps

Operating conditions

bb For networks with a large number of non-linear loads (NLL < 50 %). bb Significant voltage disturbances. bb Severe temperature conditions up to 70 C. bb Very frequent switching operations up to 10,000/year.

Rated voltage

In a detuned filter application, the voltage across the capacitors is higher than the network service voltage (US). Then, capacitors must be designed to withstand higher voltages. Depending on the selected tuning frequency, part of the harmonic currents is absorbed by the detuned capacitor bank. Then, capacitors must be designed to withstand higher currents, combining fundamental and harmonic currents. The rated voltage of VarplusBox Energy capacitors is given in the table below, for different values of network service voltage and relative impedance.

Detuned reactor VarplusBox Energy

Capacitor Rated Voltage UN (V)

Network Service Voltage US (V) 50 Hz 400 60 Hz 400 480

Relative Impedance (%)

5.7 7 14

480

In the following pages, the effective power (kvar) given in the tables is the reactive power provided by the combination of capacitors and reactors.

59

Low Voltage Capacitors

VarplusBox Energy + Detuned Reactor + Contactor

Network 400 V, 50 Hz Capacitor Voltage 480 V 5.7 % / 7 % Detuned Reactor


Effective Power (kvar)
6.5 12.5 25 50 100

QN at 480 V
8.8

Capacitor Ref.

5.7 % (210 Hz) R Ref

7% (190 Hz) R Ref

Capacitor Duty Contactor Ref.

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D32 x 1 LC1D80 x 1 LC1D115 x 1

BLRBE088A106B48 x 1 BLRBE170A204B48 x 1 BLRBE339A407B48 x 1 BLRBE339A407B48 x 2 BLRBE339A407B48 x 4

51573 x 1 52404 x 1 52405 x 1 52406 x 1 52407 x 1

51568 x 1 52352 x 1 52353 x 1 52354 x 1 51569 x 1

LC1-DFK11M71 LC1-DFK11M71 LC1-DMK11M71 LC1-DWK12M71

17 33.9 68 136

Network 400 V, 50 Hz Capacitor Voltage 480 V 14 % Detuned Reactor


Effective Power (kvar)
6.5 12.5 25 50 100

QN at 480 V
8.8

Capacitor Ref.

14 % (135 Hz) R Ref.

Capacitor Duty Contactor Ref.


LC1-DFK11M7 x1 LC1-DFK11M7 x1 LC1-DLK11M7 x1 LC1-DTK12M7 x1

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D25 x 1 LC1D50 x 1 LC1D115 x 1

BLRBE088A106B48 x1 BLRBE155A186B48 x1 BLRBE315A378B48 x1 BLRBE315A378B48 x2 BLRBE315A378B48 x4

51563 x 1 51564 x 1 51565 x 1 51566 x 1 51567 x 1

15.5 31 62 124

Network 400 V, 60 Hz Capacitor Voltage 480 V 5.7 % / 7 % Detuned Reactor


Effective Power (kvar)
6.5 10 12.5 25 50 100

QN at 480 V
8.9

Capacitor Ref.

5.7 % (250 Hz) R Ref

7% (230 Hz) R Ref

Capacitor Duty Contactor Ref.

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D12 x 1 LC1D32 x 1 LC1D80 x 1 LC1D115 x 1

BLRBE075A090B48 x 1 BLRBE113A136B48 x 1 BLRBE144A173B48 x 1 BLRBE288A346B48 x 1 BLRBE288A346B48 x 2 BLRBE288A346B48 x 4

LVR05065B40 x 1 LVR05100B40 x 1 LVR05125B40 x 1 LVR05250B40 x 1 LVR05500B40 x 1 LVR05X00B40 x 1

LVR07065B40 x 1 LVR07100B40 x 1 LVR07125B40 x 1 LVR07250B40 x 1 LVR07500B40 x 1 LVR07X00B40 x 1

LC1-DFK11M7 x 1 LC1-DFK11M7 x 1 LC1-DFK11M7 x 1 LC1-DMK11M7 x 1 LC1-DWK12M7 x 1

13.6 17.3 34.6 69 138

Network 400 V, 60 Hz Capacitor Voltage 480 V 14 % Detuned Reactor


Effective Power (kvar)
6.5 10 12.5 25 50 100

QN at 480 V
8

Capacitor Ref.

14 % (160 Hz) R Ref.

Capacitor Duty Contactor Ref.


LC1-DFK11M7 x 1 LC1-DFK11M7 x 1 LC1-DFK11M7 x 1 LC1-DLK11M7 x 1 LC1-DTK12M7 x 1

Power Contactor Ref.


LC1D12 x 1 LC1D12 x 1 LC1D12 x 1 LC1D25 x 1 LC1D50 x 1 LC1D115 x 1

BLRBE067A080B48 x 1 BLRBE104A125B48 x 1 BLRBE136A163B48 x 1 BLRBE258A310B48 x 1 BLRBE258A310B48 x 2 BLRBE258A310B48 x 4

LVR14065B40 x 1 LVR14010B40 x 1 LVR14125B40 x 1 LVR14250B40 x 1 LVR14500B40 x 1 LVR14X00B40 x 1

12.5 16.3 31 62 124

60

VarplusBox Mechanicalcharacteristics
Case Code: AB
Creepage distance Clearance Phase to phase Phase to earth Case code W1 (mm)
114
D
DB402729.eps

30 mm 25 mm (min.) 19 mm (min.)

Mounting details: mounting screw M6, 2 Nos.


W2 (mm)
97

W3 (mm)
76.5

H (mm)
229.5

D (mm)
225.5

Weight (kg)
3

AB

Terminal cover

Enclosure

W3 W2 W1

192

Case Code: DB, EB, FB, GB & HB


Creepage distance Clearance Phase to phase Phase to earth Case code W1 (mm)
263 263 309 309 309 30 mm 25 mm (min.) 19 mm (min.)

Mounting details: mounting screw M6, 2 Nos.


W2 (mm)
243 243 289 289 289

W3 (mm)
213 213 259 259 259

H (mm)
355 260 355 355 455

D (mm)
97 97 97 153 153

Weight (kg)
4.8 3.6 5.4 7.5 8.0

DB EB FB GB HB

D
DB402730.eps

Rubber grommet for cable entry

Enclosure

W3 W1

W2

61

Low Voltage Capacitors

VarplusBox Mechanicalcharacteristics
Case Code: IB
Creepage distance Clearance Phase to phase Phase to earth Case code W1 (mm)
309 30 mm 25 mm (min.) 19 mm (min.)

Mounting details: mounting screw M6, 2 Nos.


W2 (mm)
289

W3 (mm)
259

H (mm)
497
D

D (mm)
224

Weight (kg)
10.0

IB
DB402731.eps

Rubber grommet for cable entr y

Enclosure

W3 W1

W2

Case Code: LB & SB


Creepage distance Clearance Phase to phase Phase to earth Case code W1 (mm)
795 545 30 mm 25 mm (min.) 19 mm (min.)

Mounting details: mounting screw M6, 4 Nos.


LB

W2 (mm)
630 390

W3 (mm)
670 430

H (mm)
455 455

D (mm)
315 270

Weight (kg)
45 32.4

SB Al Busbar
DB402732.eps

Top cover To Capacitor units Capaci pacitor u W1 D

M 10x35 Bolt Bolt

250

H 125 Unit 1 Unit 2 Unit 3 Unit 4

W2 W3 Cable entry plate Earthing ng Bolt 7x14Slots 4 Nos

62

VarplusBox Mechanicalcharacteristics
Case Code: JB
Creepage distance Clearance Phase to phase Phase to earth
30 mm 25 mm (min.) 19 mm (min.)

Mounting details: mounting screw M6, 4 Nos.


Case code W1 (mm)
455
Al Busbar M 10x35 Bolt W1

W2 (mm)
290

W3 (mm)
330

H (mm)
455

D (mm)
315

Weight (kg)
22.5

JB
DB402733.eps

To cover Top Capaci pacitor units u Capacitor D

250

H 125 Unit 1 Unit 2

W2 W3 Cable entry plate ng Bolt Earthing

7x14 Slots 4 Nos

Case Code: KB & RB


Creepage distance Clearance Phase to phase Phase to earth
30 mm 25 mm (min.) 19 mm (min.)

Mounting details: mounting screw M6, 4 Nos.


KB

Case code

W1 (mm)
625 435

W2 (mm)
460 280

W3 (mm)
500 320

H (mm)
455 455

D (mm)
315 270

Weight (kg)
32 24.3

RB
DB402734.eps

Al Busbar M 10x35 Bolt W1

To cover Top Capaci pacitor units u Capacitor D

250

H 125 Unit 1 Unit 2 Unit 3

W2 W3 Cable entry plate ng Bolt Earthing

7x14 Slots 4 Nos

63

Low Voltage Capacitors

VarplusBox Mechanicalcharacteristics
Case Code: OB
Creepage distance Clearance Phase to phase Phase to earth
30 mm 25 mm (min.) 19 mm (min.)

Mounting details: mounting screw M6, 4 Nos.


Case code W1 (mm)
595

W2 (mm)
430

W3 (mm)
470

H (mm)
575

D (mm)
315

Weight (kg)
30

OB Al Busbar
DB402735.eps

To Top cover pacitor units u Capaci Capacitor W1 D

M 10x35 Bolt

250

H 125 Unit 1 Unit 2

W2 W3 Cable entry plate g Bolt Earthing

7x14 Slots 4 Nos

Case Code: QB
Creepage distance Clearance Phase to phase Phase to earth
30 mm 25 mm (min.) 19 mm (min.)

Mounting details: mounting screw M6, 4 Nos.


QB
DB402736.eps

Case code

W1 (mm)
1080

W2 (mm)
920

W3 (mm)
960

H (mm)
575

D (mm)
315

Weight (kg)
60

Al Busbar M 10x35 Bolt W1

Top To cover Capacitor units Capaci D

250

H 125 Unit 1 Unit 2 Unit 3 Unit 4

W2 W3 Cable entry plate Earthing g Bolt

7x14 Slots 4 Nos

64

65

66

Detuned reactors

Contents

Presentation Power Factor Correction guideline Low Voltage capacitors

3 15

Detuned reactors

68

Power Factor controllers 71 Contactors 75 Appendix 79

67

Detuned reactors

Detuned reactors

The detuned reactors (DR) are designed to protect the capacitors by preventing amplification of the harmonics present on the network.

Operating conditions

bb Use: indoor. bb Storage temperature: -40 C, +60 C. bb Relative humidity in operation: 20-80 % . bb Salt spray withstand: 250 hours (for 400 V - 50 Hz range). bb Operating temperature: vv altitude: 1000 m: Min = 0 C, Max = 55 C, highest average over 1 year = 40 C, 24 hours = 50 C. vv altitude: 2000 m: Min = 0 C, Max = 50C, highest average over 1 year = 35 C, 24 hours = 45C.

PE90154.eps

Installation guidelines

bb Forced ventilation required. bb Vertical detuned reactor winding for better heat dissipation. As the detuned reactor is provided with thermal protection, the normally closed dry contact must be used to disconnect the step in the event of overheating.

Technical specifications General characteristics


Description Degree of protection Insulation class Rated voltage

Three-phase, dry, magnetic circuit, impregnated IP00 H 400 to 690V - 50Hz 400 to 600V - 60Hz Other voltages on request -5, +5% 1.1 kV 4 kV, 1 min Restored on terminal block 250 V AC, 2 A

Inductance tolerance per phase Insulation level Dielectric test 50/60Hz between windings and windings/earth Thermal protection

Lets define the service current (IS) as the current absorbed by the capacitor and detuned reactor assembly, when a purely sinusoidal voltage is applied, equal to the network service voltage (V). IS = Q (kvar)/(3xUS) In order to operate safely in real conditions, a detuned reactor must be designed to accept a maximum permanent current (IMP) taking account of harmonic currents and voltage fluctuations. The following table gives the typical percentage of harmonic currents considered for the different tuning orders. (%) Tuning order 2.7 3.8 4.2 Harmonic currents i5 i7 i3 5 15 5 3 40 12 2 63 17 i11 2 5 5

A 1.1 factor is applied in order to allow long-term operation at a supply voltage up to (1.1xUS). The resulting maximum permanent current (IMP) is given in the following table: Tuning order
2.7 3.8 4.2

IMP (times IS)


1.12 1.2 1.3

68

Detuned reactors

Network voltage 400 V


50 Hz Relative Impedance (%)
5.7

kvar
6.5 12.5 25 50 100 6.5 12.5 25 50 100 6.5 12.5 25 50 100

14

4.7 2.4 1.2 0.59 0.3 6 3 1.5 0.75 0.37 12.6 6.6 3.1 1.6 0.8

Inductance (mH)

IMP (A)
12 24 47 95 190 11 22 43 86 172 10 20 40 80 160

200 245 240 260 380 200 245 240 260 380 200 245 240 260 380

W (mm)

110 205 205 205 205 110 205 205 205 205 110 205 205 205 205

W1 (mm)

140 140 140 160 220 140 140 140 160 220 140 140 140 160 220

D (mm) D1 (mm)
87 110 110 120 120 87 110 110 120 120 87 110 110 120 120

230 230 230 270 330 230 230 230 270 330 230 230 230 270 330

H (mm) Weight Reference Number (kg)


8.6 12 18.5 25 42 8.5 10 18 27 42 9 13 22 32 57 51573 52404 52405 52406 52407 51568 52352 52353 52354 51569 51563 51564 51565 51566 51567

Network voltage 690 V


50 Hz Relative Impedance (%)
5.7

kvar
12.5 25 50 100 12.5 25 50 100

9.1 4.6 2.3 1.1 9.1 4.6 2.3 1.1

Inductance (mH)

IMP (A)
13.3 27 53 106 12 24 47 94

Reference Number
LVR05125A69 LVR05250A69 LVR05500A69 LVR05X00A69 LVR07125A69 LVR07250A69 LVR07500A69 LVR07X00A69

Network voltage 400 V


60 Hz Relative Impedance (%) kvar
6.5 10 12.5 25 50 100 6.5 10 12.5 25 50 100 6.5 10 12.5 25 50 100

5.7

14

Network voltage 480 V


H

4 2.6 2 1 0.51 0.26 5.3 3.2 2.6 1.3 0.64 0.32 11.2 6.9 5.5 2.8 1.4 0.69

Inductance (mH)

IMP (A)
11.5 18.4 23 46 92 184 10.3 16.4 20.5 41 82 164 9.7 15.4 19.3 39 77 154 19.2 38 77 154 15.3 31 61 123

Reference Number
LVR05065B40 LVR05100B40 LVR05125B40 LVR05250B40 LVR05500B40 LVR05X00B40 LVR07065B40 LVR07100B40 LVR07125B40 LVR07250B40 LVR07500B40 LVR07X00B40 LVR14065B40 LVR14100B40 LVR14125B40 LVR14250B40 LVR14500B40 LVR14X00B40 LVR05125B48 LVR05250B48 LVR05500B48 LVR05X00B48 LVR05125B60 LVR05250B60 LVR05500B60 LVR05X00B60

5.7

Network voltage 600 V


W1 W D1 D

12.5 25 50 100 12.5 25 50 100

2.9 1.5 0.74 0.37 4.6 2.3 1.15 0.58

5.7

For dimensions and more details, please consult us.

69

70

Power Factor controllers

Contents

Presentation Power Factor Correction guideline Low Voltage capacitors Detuned reactors

3 15 67

Varlogic series
RT6, NR6/NR12, NRC12

72
72

Contactors 75 Appendix 79

71

Power Factor controllers

Varlogic series

RT6, NR6/NR12, NRC12

The Varlogic controllers permanently monitor the reactive power of the installation and control the connection and disconnection of capacitor steps in order to obtain the targeted power factor.
PE90155.eps

Performance

bb Permanent monitoring of the network and equipment. bb Information provided about equipment status. bb Alarm signals transmitted in case of anomaly (for NR6, NR12, NRC12). bb Communication by Modbus protocol (for NRC12). bb New control algorithm designed to reduce the number of switching operations and quickly attain the targeted power factor.

Simplicity

bb Simplified programming and possibility of intelligent self set-up. bb Ergonomic layout of control buttons. bb Quick and simple mounting and wiring. bb A special menu allows controller self-configuration.

User-friendliness

Varlogic RT6/8*/12* *: on request

The large display allows: bb Direct viewing of installation electrical information and capacitor stage condition. bb Direct reading of set-up configuration. bb Intuitive browsing in the various menus (indication, commissioning, configuration). bb Alarm indication.

PE90161.eps

Monitoring and protection

Alarms bb Should an anomaly occur on the network or the capacitor bank, alarms are indicated on the screen and alarm contact closure is initiated. bb The alarm message is maintained on the screen once the fault clears until it is manually removed. Protection bb If necessary, the capacitor steps are automatically disconnected to protect the equipment.

Varlogic NR6/12

Range Type
NR6 NR12 NRC12 RT6 RT8 RT12

Number of step output contacts Part number


6 52448 52449 52450 51207 On request On request 52451 52452 12 12 6 8 12

PE90156.eps

Communication RS485 Modbus set for NRC12 Temperature external probe for NRC12 type in addition to internal probe allows measurement at the hottest point inside the capacitor bank

Accessories

Varlogic NRC12

72

Technical specifications General characteristics


Output relays
AC DC 5 A / 120 V 0.3 A / 110 V IP41 IP20 0 to 5 A 2 A / 250 V 0.6 A / 60 V 1 A / 400 V 2 A / 24 V

Protection Index
Front panel Rear Measuring current Number of steps

Specific features

RT6
6 185 to 265 320 to 460

NR-6/12
6 / 12 88 to 130 185 to 265 320 to 460

NRC12
12 88 to 130 185 to 265 320 to 460

Supply voltage (V AC) 50/60Hz

Display
4 digit 7 segment LEDs 65 x 21 mm backlit screen 55 x 28 mm backlit screen Dimensions Flush panel mounting 35 mm DIN rail mounting (EN 50022) Operating temperature Alarm contact Internal temperature probe Separate fan relay contact Alarm history b Last 5 alarms b b b b b b b b 2 % 10 to 1800 s b b b b Modbus 5 % 10 to 120 s b b 2 % 10 to 180 s b 0 C 55 C 143 x 143 x 67 b 155 x 158 x 70 b b 0 C 60 C b b b 155 x 158 x 80 b b 0 C 60 C b b b Last 5 alarms b b

Type of connection
Phase-to-neutral Phase-to-phase

Current input
CT 10000/5 A CT 25/5 A 6000/5 A CT 25/1 A 6000/5 A

Target cosj setting


0.85 ind. 1 0.85 ind. 0.9 cap. Possibility of a dual cosj target Accuracy Response delay time

Reconnection delay time


10 to 1800 s 10 to 600 s 10 to 900 s 4-quadrant operation for generator application Communication protocol

73

74

Contactors

Contents

Presentation Power Factor Correction guideline Low Voltage capacitors Detuned reactors Power Factor controllers

3 15 67 71

Contactors 76
Appendix 79

75

Contactors

Contactors

Special contactors LC1 DK are designed for switching 3-phase, single- or multiple-step capacitor banks. They comply with standards IEC 60070 and 60831, NFC 54-100, VDE 0560, UL and CSA.

There is no need to use choke inductors for either single or multiple-step capacitor banks. Short-circuit protection must be provided by gI type fuses rated at 1.72 In.

Operating conditions

Specifications

These contactors are fitted with a block of early make poles and damping resistors, limiting the value of the current on closing to 60 IS max. This current limiting increases the life of all the installations components, especially the fuses and capacitors.

PE90157.eps

Technical specifications Network voltage (V) 50-60Hz


220 - 240 400 - 440
kvar 6.7 8.5 10 15 20 25 40 12.5 16.7 20 25 33.3 40 60 18 24 30 36 48 58 92

660 - 690

Part number
LC1 DFK---LC1 DGK---LC1 DLK---LC1 DMK---LC1 DPK---LC1 DTK---LC1 DWK----

Contactor LC1DFK

Standard control circuit voltages (@ 50/60 Hz) are: 24, 42, 48, 110, 115, 220, 230, 240, 380, 400, 415, 440 V. Other voltages are available on request. The power values given in the selection table are for the following operating conditions: Prospective peak current at switch-on Maximum operating rate
LC1 DK LC1 DFK, DGK, DLK, DMK, DPK LC1 DTK, DWK 200 In 240 operating cycles/hour 100 operating cycles/hour 400 V 690 V 300,000 operating cycles 200,000 operating cycles

PE90158.eps

Electrical durability atnominal load

All contactor ratings

Contactor LC1DPK

76

Contactors

LC1, DFK, DGK


LC1 DFK DGK
DE90169.eps

C 117 122

Type of fixing LC1 D12 LC1 D18

130

74

45

LC1 DPK DTK


DE90170.eps

LC1, DPK, DTK

Type of fixing LC1 D40 LC1 D50

180

150

127

75

LC1 DLK DMK


DE90171.eps

LC1, DLK, DMK


C 117 122

Type of fixing LC1 D40 LC1 D50

140

84

56

LC1 DWK
DE90172.eps

LC1, DWK

Type of fixing LC1 D80

200

127

157

85

77

78

Appendix

Contents

Presentation Power Factor Correction guideline 3 Low Voltage capacitors 15 Detuned reactors 67 Power Factor controllers 71 Contactors 75

Influence of harmonics in electrical installations Safety features

80 81

Glossary 82 Relevant documents 84

79

Appendix

Influence of harmonics in electrical installations


Definition of harmonics

Since the harmonics are caused by nonlinear loads, an indicator for the magnitude of harmonics is the ratio of the total power of nonlinear loads to the power supply transformer rating.

This ratio is denoted NLL, and is also known as Gh/Sn: NLL=Total power of non-linear loads (Gh)/ Installed transformer rating (Sn) Example: > Power supply transformer rating:Sn=630 kVA > Total power of non-linear loads:Gh=150 kVA > NLL = (150/630) x 100 = 24 %.

The presence of harmonics in electrical systems means that current and voltage are distorted and deviate from sinusoidal waveforms. Harmonic currents are currents circulating in the networks and whose frequency is an integer multiple of the supply frequency. Harmonic currents are caused by non-linear loads connected to the distribution system. A load is said to be non-linear when the current it draws does not have the same waveform as the supply voltage. The flow of harmonic currents through system impedances in turn creates voltage harmonics, which distort the supply voltage. The most common non-linear loads generating harmonic currents use power electronics, such as variable speed drives, rectifiers, inverters, etc. Loads such as saturable reactors, welding equipment, and arc furnaces also generate harmonics. Other loads such as inductors, resistors and capacitors are linear loads and do not generate harmonics.

Effects of harmonics

Capacitors are particularly sensitive to harmonic currents since their impedance decreases proportionally to the order of the existing harmonics. This can result in capacitor overload, constantly shortening its operating life. In some extreme situations, resonance can occur, resulting in an amplification of harmonic currents and a very high voltage distortion. To ensure good and proper operation of the electrical installation, the harmonic level must be taken into account in selecting power factor correction equipment. A significant parameter is the cumulated power of the non-linear loads generating harmonic currents.

The percentage of non-linear loads NLL is a first indicator for the magnitude of harmonics. The proposed selection of capacitors depending on the value of NLL is given in the diagram below. NLL(%)
SDuty HDuty Energy HDuty Energy (with detuned reactor) Supply transformer Measure THDi, THDu

Taking account of harmonics

10

20

25

50

A more detailed estimation of the magnitude of harmonics can be made with measurements. Significant indicators are current harmonic distortion THDi and voltage harmonic distortion THDu, measured at the transformer secondary, with no capacitors connected. According to the measured distortion, different technologies of capacitors shall be selected: THDi(%) 5 8 10 20

DE90182

Linear loads

Non-linear loads

SDuty HDuty Energy HDuty Energy (with detuned reactor)

THDu(%)
SDuty HDuty Energy HDuty Energy (with detuned reactor)

The capacitor technology has to be selected according to the most restrictive measurement. Example, a measurement is giving the following results : - THDi = 15 % Harmonic solution. - THDu = 3.5 % HDuty / Energy solution. Harmonic solution has to be selected.

80

Safety features

(a) (b)
DE90175

Self-healing is a process by which the capacitor restores itself in the event of a fault in the dielectric which can happen during high overloads, voltage transients etc. When insulation breaks down, a short duration arc is formed (figure 1). The intense heat generated by this arc causes the metallization in the vicinity of the arc to vaporise (figure 2).

Figure 1 - (a) Metal layer - (b) Polypropylene film.

DE90174

Figure 2

Simultaneously it re-insulates the electrodes and maintains the operation and integrity of the capacitor (figure 3).

DE90173

Figure 3

DB403284

Pressure Sensitive Disconnector (also called tear-off fuse): this is provided in each phase of the capacitor and enables safe disconnection and electrical isolation at the end of the life of the capacitor. Malfunction will cause rising pressure inside the can. Pressure can only lead to vertical expansion by bending lid outwards. Connecting wires break at intended spots. Capacitor is disconnected irreversibly.

DB403285

T+12+2 Cross-section view of a three-phase capacitor after Pressure Sensitive Device operated: bended lid and disconnected wires.

81

Appendix

Glossary

Active current (Ia):

In the vector representation, component of the current vector which is co-linear with the voltage vector. Real power transmitted to loads such as motors, lamps, heaters, computers, and transformed into mechanical power, heat or light. In a circuit where the applied r.m.s. voltage is Vrms and the circulating r.m.s. current is Irms, the apparent power S (kVA) is the product: Vrms x Irms. The apparent power is the basis for electrical equipment rating. Reactor associated to a capacitor for Power Factor Correction in systems with significant non-linear loads, generating harmonics. Capacitor and reactor are configured in a series resonant circuit, tuned so that the series resonant frequency is below the lowest harmonic frequency present in the system.

Active power:

Apparent power:

Detuned reactor:

Displacement Power Factor: For sinusoidal voltage and current with a phase angle j, the Power Factor is equal to cosj, called Displacement Power Factor (DPF)

Harmonic distortion:

Indicator of the current or voltage distortion, compared to a sinusoidal waveform. The presence of harmonics in electrical systems means that current and voltage are distorted and deviate from sinusoidal waveforms. Harmonic currents and voltages are signals circulating in the networks and which frequency is an integer multiple of the supply frequency. "Shunt power capacitors of the self-healing type for a.c. systems having a rated voltage up to and including 1 000 V Part 1: General Performance, testing and rating Safety requirements Guide for installation and operation". High-intensity current circulating in one piece of equipment after connection to the supply network. Maximum apparent power to be delivered by the Utility, which determines the rating of the supply network and the tariff of subscription. Plastic dielectric material used for the construction of low-voltage capacitors. The power factor is the ratio of the active power P (kW) to the apparent power S (kVA) for a given circuit. = P (kW) / S (kVA). Improvement of the Power Factor, by compensation of reactive energy or harmonic mitigation (reduction of the apparent power S, for a given active power P).

Harmonics:

IEC 60831-1:

In-rush current:

kVA demand:

Polypropylene:

Power Factor:

Power Factor Correction:

82

Rated current:

Current absorbed by one piece of equipment when supplied at the rated voltage. Operating voltage for which a piece of equipment has been designed, and which can be applied continuously. Component of the current vector which is in quadrature with the voltage vector. Product of the reactive current times the voltage. Value of the supply network voltage, declared by the Utility Amplitude of the steady-state current absorbed by one piece of equipment, when supplied by the Service Voltage.

Rated voltage:

Reactive current (Ir):

Reactive power: Service voltage:

Service current:

Usual formulas:

Apparent power: S = Vrms x lrms (kVA). Active power:  P = Vrms x la = Vrms x lrms x cosj (kW). Reactive power:  Q = Vrms x lr = Vrms x lrms x sinj (kvar). Temporary reduction of the supply voltage magnitude, between 90 and 1 % of the service voltage, with a duration between period and 1 minute.

Voltage sag:

83

Appendix

Relevant documents

Relevant documents published by Schneider Electric

bb Electrical Installation Guide. bb Expert Guide n4: "Harmonic detection & filtering". bb Expert Guide n6: "Power Factor Correction and Harmonic Filtering Guide" bb Technical Guide 152: "Harmonic disturbances in networks, and their treatment". bb White paper: controlling the impact of Power Factor and Harmonics on Energy Efficiency.

Relevant websites

bb http://www.schneider-electric.com bb https://www.solution-toolbox.schneider-electric.com/segment-solutions bb http://engineering.electrical-equipment.org/ bb http://www.electrical-installation.org

84

85

86

Schneider Electric Industries SAS


35, rue Joseph Monier CS 30323 92506 Rueil Malmaison Cedex France RCS Nanterre 954 503 439 Capital social 896 313 776 www.schneider-electric.com PFCED310003EN

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Design: Schneider Electric Photos: Schneider Electric Edition: Altavia Connexion - made in France

05-2011

ART.837809 2011 - Schneider Electric - All rights reserved.

You might also like