Submittal Data Sheet

M30D-27HRDN1- M
Project Name
Location Engineer Submitted To Submitted By Location Approval Date Unit Designation Drawing Number Date

Reference

Approval

Construction

(Circle One)

Performance
Outdoor Unit Model Cooling Capacity (BTUH) Sensible Capacity (BTUH) SEER HSPF (BTUH/H/W) Heating Capacity (BTUH) M30D-27HRDN1-M 25,400 24,800 15.4 8.5 24,800

Specification
Maximum Zones Refrigerant Noise Level Cooling Outdoor (High) (Dba) Noise Level Heating Outdoor (High) (Dba) Connection (Tubing) Connection Pipe size Supply/Return Maximum Tube Length (Feet) Maximum Height Difference (Feet) 3 R-410a 60 61 Flare 1/4 , 3/8 150 32

Electrical
Voltage/Phase/Cycle Cable Indoor to outdoor Minimum Circuit Ampacity Recommended Fuse Size Current Rating Cooling Current Rating Heating Cooling Input Power (W) Heating Input Power (W) 30 12.2 16.0 2,806 3,680 230/1/60 14AWG/4 conductor Shielded

Physical
Net Weight (Indoor/Outdoor) (LBS) Height Condensing Unit (Inches) Depth Condensing Unit (Inches) Length Condensing Unit (Inches) 126 27 3/8 13 3/16 33 1/2