DESIGN CHARACTERISTICS DIN 144x144 container, rapid coupling control unit on base with FASTON connectors and see-through cover. Protruding, built-in or back-of-board mounting possibility. All parameters are displayed on a 4-line alphanumeric display with 16 characters per line. To facilitate reading in bad light, press any key to light the display; the light goes off after about 60 seconds of being idle (no key pressed).
Use the UP and DOWN keys to move over a page and to go from one parameter to another
+ -
Use the < and > keys to go from one page to another
FANBUSFANBUS You may connect 15 different types of control units to the FANBUS with at most 8 of the same type of control units (so 15x8 = max of 120 control units). You may connect the EV90 to the slave with a simple low voltage, polarity free bifilar duplex cable (both wires may be inverted with each other without causing malfunction). All slaves must be connected in parallel to the BUS. ADDRESS OF CONTROL UNITS Each control unit is identified by two digits that determine its address. The first digit represents the model and cannot be modified. The second one may be set through jumpers on each slave's terminal board: EV91A first digit: 1 EV91C first digit: 2 EV92 first digit: 3 If only one control unit per type is present on the BUS, no intervention is needed. Since the second digit is automatically set =0, the control units will have the addresses 10, 20 and 30 respectively. If 3 EV91A control units are needed on the same BUS, you'll have to set address 1 on the second control unit, and address 2 on
So, the result will be: 1 - EV91A address 10 (no bridge = address 0) 2 - EV91A address 11 (set address 1) 3 - EV91A address 12 (set address 2) 1 - EV91C address 20 (no bridge = address 0) 1 - EV92 address 30 (no bridge = address 0) This way every control unit will have an address that identifies it unambiguously. N.B. the two digits of the address must go in front of all remote management commands for faultless communication with the desired device. 1 - EV91C indirizzo 20 (nessun ponte = indirizzo 0) ADDRESS OF CONTROL UNIT EV90 The master control unit EV90D should be considered in the same way as a slave with a fixed address : 00. So, if you have to change the current time, for instance, you must send the change command preceded by 00. HOW TO SET THE ADDRESSES The purpose of connector A on each device is to supply power and to set its address through jumpers. This is convenient when the device must be replaced because, instead of losing the address, it is memorised in the terminal board and so the new device will automatically assume the address of the old one. Below we have indicated the jumpers to make to have all combinations
AUTOMATIC RECOGNITION When a new device is added to the BUS it is automatically recognised. After about 60 seconds master EV90 is able to display and communicate with it.
GENERAL DIAGRAM
EXTERNAL PROBE
BOILER PROBE
2-STAGE BURNER
BOILER
SLAVE 1
SLAVE 2
SLAVE 3
SLAVE 4
PLANT MANAGEMENT In normal conditions control unit EV90 shows a list of connected slaves. The first one on the list is EV90 itself, followed by a description of the devices and their address. This description may be modified as desired for every slave and it may be useful to easily identify the devices. Use the up and down keys to position the cursor on the desired slave. Press the > key to communicate with the slave and display and modify its parameters.
MAIN MENU
Device Type EV90 00 GYM 10 SOUTH BUILDING 11 SANITARY 40 BOILERS 1-2 20 BOILERS 3-4 21 INPUTS 50 OUTPUTS 30 .
CALCULATED BOILER TEMPERATURE The boiler temperature the control unit calculates may be fixed or sliding. When it is fixed, the value set will not be changed, but when it is sliding, the value set is added to the highest temperature value required by connected slaves. This way it is possible to regulate the boiler with a temperature that continually varies depending on the requirements of the entire plant. N.B. when you are setting the desired boiler temperature value, bear in mind that with fixed point regulation it is the value the control unit uses, and with sliding regulation, it represents an increase with respect to the highest value decided by the various control units of the plant. LIMITS You may set the highest and lowest boiler temperature limits within which the calculated temperature may vary. The control unit will ensure that these values are not exceeded. DIFFERENTIAL 1 Differential of the first stage. It indicates the temperature difference with the one calculated by the control unit below which the first stage of the burner is turned on. DIFFERENTIAL 2 Differential of the second stage. It indicates the temperature difference with the one calculated by the control unit below which the second stage of the burner is turned on. To avoid useless or ill-timed interventions, this situation should persist for a certain length of time (may be set on the control unit).
EXAMPLES OF PLANTS
Plant 1 -command of 2-stage boiler -two independent heating circuits
-remote management with GSM modem -the devices' addresses are in brackets
FANBUS
EV91A (10)
EV91A (11)
EXTERNAL PROBE
M BOILER PROBE
ANTENNA
2 - STAGE BURNER
BOILER
Plant 2 -command of two cascaded boilers -two heating circuits -boiler regulation for sanitary hot water -Remote management with GSM modem
FANBUS
EXTERNAL PROBE
EV91A (10)
EV91A (11)
ANTENNA
SC
B1
BOILER
B2
BOILER
1
V1 V2
SANITARY WATER
MODEM
EV90 (00)
EV91B (30)
INSTALLATION
INSTALLING THE CONTROL UNIT Fully loosen the tie rod to release the base of the control unit. Lever on the slots with a screwdriver to remove the base. After you have made the electric connections, press the FASTON connectors of the control unit into the couplings of the base until they are fully inserted. Tighten the tie rod.
DIMENSIONS OF CONTROL UNIT EV90 AND MOUNTING SYSTEMS BUILT-IN Fastening 93
screwlo
136
144
138
91 110
144
138
55 55 110
TEMPERATURE PROBE
BACK-OF-BOARD
EC81
EC82
EC83
138
138
EXTERNAL PROBE EC81 Install the external probe in a vertical position onto the north or north-west side of the building at least 2.5m from the ground. Apply the probe far from heat sources (windows, aerators, flues, etc.) to detect a meaningful temperature for the whole plant. N.B. It's always possible to install one of the external probes on control unit EV91A. The device will automatically use the value measured by its probe instead of the one transmitted by EV90 through the FANBUS. BOILER AND RETURN PROBE EC82-EC83 Contact probe EC82 must be applied onto the water pipe with a special clamp. Put some thermal compound between them to ensure good heat conductivity. For the same reason immersion probe EC83 must be inserted in the sheath filled with mineral oil or silicone grease.
+ 20 + 30 + 40 + 50 + 60 + 70 + 80 + 90 +100
CONNECTION TO THE FANBUS Connect the control units to the Master EV90 through the FANBUS. Bear in mind that the bus has low voltage and is not polarised, so the terminals may be inverted with each other without causing malfunction ADDRESS OF CONTROL UNITS The control units must be addressed to work properly and to be questioned by remote management. Make sure that they are properly configured.
WIRING DIAGRAM
17 18
POWER SUPPLY 230V STAGE 1 COMMAND RS232 TX RS 232 RX RS232 0V FANBUS AL MODEM
20 21 9 10 11 12 13 22 14 15 16
1 2 3 4 5 19 6
RETURN PROBE
STAGE 2 COMMAND
7 8
+ Use the UP and DOWN keys to move over a page and to go from one parameter to another Use the < and > keys to go from one page to another Use the + and keys to modify parameters
MAIN MENU It contains a list of available submenus. To enter a submenu, press the -> key
Device Type ......................................... EV90 00 GYM 10 SOUTH BUILDING 11 SANITARY 40 BOILERS 1+2 20 BOILERS 3+4 21 INPUTS 50 OUTPUTS 30 .
MENU EV90 . >Information >Boiler Regulation >Programming Schedules >Set Current Time >Remote Management >Temperature Limit ..................................
INFORMATION SUBMENU:
01/APR/2003 MONDAY 14.35 Outside T.: -02.5 Boiler T.: 58.5 Plant Description: EV90 Control Unit Value of boiler temperature
The user may modify the plant description. This may be useful to identify the plant commanded by the control unit
Desired temperature : fixed or sliding If fixed, the value set is the one used by the control unit (DBT). If sliding, it is higher (DBT) than the highest value required by the plant's control units.
Tcc represents the desired boiler temperature value. It takes account of the highest and lowest limits, the highest temperature of the plant, etc. Stage 1 Differential : 04.0 Stage 2 Differential: Setting of boiler differentials 0.8.5 Auxiliary Stage Command After Delay of : 02.00 Minutes The burner's second stage is turned off after this delay if the temperature falls below differential 2.
MON. on-off Copy Weekly programming of the boiler 07.0 09.30 Use the keys to go to the desired TUE. 22.30 on-off Copy 17.0 value and change it. 07.0 09.30 Position the cursor on the word Copy WED. on-off Copy 17.0 22.30 and press the + key to copy a program 07.0 ------09.30 ------THU. on-off Copy to the next day 17.0 22.30 07.0 ------09.30 ------FRI. on-off 17.0 22.30 Copy 07.0 ------09.30 ------SAT. on-off 17.0 22.30 Copy 07.0 ------09.30 ------17.0 SUN. 22.30 on-off Copy ------07.0 ------09.30 17.0 22.30 -------------
To set the starting and ending date of daylight saving time. The control unit automatically updates the time.
It indicates the address of slave device currently triggering alarm and the time lapse before the next alarm call.
To set modem type: GSM (for SMS management) or PSTN analog (for analog modem or GSM modem in data mode) To set the telephone numbers to send alarms to. Unused digits must be cancelled . N.B. an alarm is immediately sent to operator No. 1. and after 15 minutes to Nos. 1 and 2, and after another 15 minutes to Nos. 1, 2 and 3.
REMOTE MANAGEMENT
SMS CONNECTION
ANTENNA
VIA D CAL ELLOSI DAIA O IN BLO6 CCO
1 4 7 8 0 5 9 2 6 3
DATA CONNECTION
+ SOFTWARE
SMS GMS MODEM ANALOG OR GSM DATA MODEM ANALOG OR GSM DATA MODEM RS232 SERIAL CABLE
DEDICATED
By connecting the EV90 controller to a GSM modem, the significant parameters of the control unit can be set or read (see SMS remote controls). To connect the controller to an analog or GSM modem follow the instructions relative to the wiring diagram to connect the modem or use the TC EV85 cable. N.B. The maximum length between controller and modem is 15 metres. If management takes place via a GSM modem a mobile phone can be used. If an analog or GSM modem in data mode is used, it is necessary to use a Personal Computer with dedicated control software available only in Italian provided by Fantini Cosmi or downloaded over the Internet. CONNECTING THE MODEM Follow the diagram below to connect the EV90 to the modem. It's necessary to connect pins 7-8 and 4-6 to each other for faultless communication.
20 21 9 10 11 12 13 22 EV90
TX RX 0V
5 4 3 2 1
9 8 7 6
MODEM CONNECTOR
MALE CONNECTOR DB9
PREPARING THE MODEM Both the GSM and the analogue modem supplied by Fantini-Cosmi will work properly. Another modem may be used provided that the communication speed is 2400bit/sec. To do this, use the command AT+IPR =2400 and save the new configuration with the command: AT&W. If a GSM modem is used, use and memorise the command AT+CMGF=1 to set the SMS message format to text mode. USING A SIM CARD The GSM modem works with any SIM card. Before using one, however, we recommend that you test it in a mobile phone to see if it's working. Particularly: -check that no PIN code has been set. If so, try to exclude it -Check the remaining credit -Send an SMS message and check if it arrives After these checks, install the SIM card in the modem connector OPERATION When a GSM or analogue modem is connected to the EV90, you may remotely read and change some of its data and data of all devices connected to the FANBUS. To properly communicate with the desired device, every command must be preceded by two digits representing the device's address. So, to address commands to unit EV90, you must first enter 00. All possible commands for each slave are described on the instruction sheets for each device. REMOTE MANAGEMENT SMS COMMANDS These commands may be used through a mobile phone by sending an SMS message containing the message to the unit's GSM modem. It answers with a reply SMS message to the phone number that requested the information. To facilitate message reading, the information is enclosed in a < and > sign. And every reply message is preceded by a description of control unit EV90, at times followed by a description of the slave control unit to easily identify the sender.
10
-???
It is used to know which SMS commands may be sent. -Reply: list of possible commands
-STATUS=?
-Reply: information about state of control unit such as temperatures read and set, current time and date
-TIME=12.33
It sets the current time -Reply: information about state of control unit such as temperatures read and set, current time and date
-BOILERT=82.5 It sets the desired boiler temperature without changing the fixed or sliding temperature selection -Reply: information about the state of the control unit -BOILERT=82.5F It sets the desired FIXED boiler temperature -Reply: information about the state of the control unit -BOILERT=82.5S It sets the desired SLIDING boiler temperature -Reply: information about the state of the control unit -PROGx=? -It programs the day x, where x represents the day of the week 1 = Monday, 2 = Tuesday, etc. -Reply: all 6 programming schedules for that day -PROGx=07.00-09.30 17.30-22.00 --.----.-It sets a program schedule for the day there are 3 on and 3 off periods by specifying hours and minutes. Unscheduled periods should be filled in with dashes. Leave a dash or a space between two periods. -Reply: all 6 programming schedules for that day -PAUT It sets the automatic programming schedules -Reply: information about the state of the control unit -PON It sets the always on program -Reply: information about the state of the control unit -POFF It sets the always off program RESET It deletes any alarms Reply: ALARMS DELETED TECHNICAL CHARACTERISTICS Power supply 230V 50Hz Power consumption 5 VA (4W) Contact rating 5A-230Vac (Ohmic charge) voltage free contacts Ambient temperature: 0 50C Weekly programming clock, 5-year battery life, automatic management of daylight saving time (DST) Compliant with norm EN60730-1 Measuring probes: - EC81 external probe - EC82 contact probe - EC83 immersion probe
11
EV91B
EV92
12