LV Capacitor CLMD ........................................................................................................ 9/2 LV Capacitor LVCS.......................................................................................................... 9/3 LV Capacitor Bank APC ................................................................................................. 9/4 Dynacomp ....................................................................................................................... 9/6 Power Factor Controller RVC ........................................................................................ 9/8 Power Factor Controller RVT ........................................................................................ 9/9 LV Active Filters PQFI, PQFM, PQFK and PQFS .......................................................... 9/10 Third Harmonic Filter THF ............................................................................................. 9/14
o a
9/1
1SDC007200C0202
Network Quality
LV Capacitor CLMD
Technical Data
Terminals
CLMD 13 CLMD 33 From 220 to 1000 V. 50 and 60 Hz 50 Hz From 2.5 to 18 kvar depending From 17 to 26.8 kvar depending on the voltage and frequency. on the voltage. 3-phase as standard construction (single-phase on request). Permanently connected built-in Not included. discharge resistors are sized to ensure safe discharge of the capacitor to less than 50V in 1 minute after a switch off. three M6 terminals. three cable outputs.
CLMD 43, 53, 63 & 83 50 and 60 Hz From 11 to 130 kvar depending on the voltage and frequency. Permanently connected built-in discharge resistors are sized to ensure safe discharge of the capacitor to less than 50V in 1 minute after a switch off. with threaded rods M6, 8, 10 or 12 according to the power of the capacitor. a M8 terminal is included under the cover. By a knock out : CLMD43-53 : 37 mm. CLMD63-83 : 47 mm.
Execution Protection Maximum ambient temperature Minimum ambient temperature Minimum distance between units Minimum distance between units and wall Losses (discharge resistors included) Tolerance on capacitance Voltage test The acceptable overloads are those specied in IEC 831-1&2
Zinc electroplated mild steel. Beige RAL 7032. with two slots, diameter 6.5 mm with eight xation holes, (suitable xing for assembly in diameter 5.4 mm. module). Indoor (outdoor on request). IP 42 (IP 54 on request). Class D (+55C) according to IEC 831. Indoor type: -25C. Outdoor type: -40C. 20 mm. 20 mm. 20 mm. 20 mm. < 0.5 Watt/kvar for 380 V rated voltage and above.
50 mm. 50 mm.
0 % + 10 %. Between terminals: 2.15 Un for 10 seconds. Between terminals and earth: 3 kV for 10 seconds. Overvoltage tolerance: 10% max. at intervals. Overcurrent tolerance: 30% permanently. Maximum overload: stable operation at 135% of the nominal rating (generated by overvoltages and harmonics). Important: the installation of capacitors on networks disturbed by harmonics may require special precautions, especially when there is a risk of resonance.
LV Capacitor LVCS
Technical Data
Voltage range Power range Connection Discharge resistors Terminals Earth Color Weight (unpacked) Fixation Execution Protection Maximum ambient temperature Minimum ambient temperature Dielectric losses Total losses Tolerance on capacitance Voltage test Lightning impulse voltage test Acceptable overloads according to IEC 60831 1& 2
50 Hz: 230, 400, 415, 525 and 690 Vac. 60 Hz: 220, 240, 380, 440, 480 and 600 Vac. From 5 kvar to 25 kvar depending on the voltage and frequency. 3-phase. Built-in and sized for discharge of the capacitors to less than 50V in 1 min. Minimum time between disconnection and re-energization: 40 seconds. Contactor-type terminals with captive screws (Max. cable size: 35mm2 ) No earth connection needed. RAL 7012 (dark gray). +/- 2.5 kg / LVCS unit M6-through-hole bolts, M6-insertion-hole screws. Indoor. IP 20. Class D (+55C). -25C. < 0.2 Watt/kvar. < 0.5 Watt/kvar (discharge resistors included). 0 +10 %. Between terminals : 2.15 Un for 10 sec. Between terminals and container: 15 kV. Overvoltage tolerance : 10 % max. intermittently. Overcurrent tolerance : 30 % permanently. Important : The installation of capacitors on networks disturbed by harmonics may require special precautions, especially when there is a risk of resonance.
Contactor-type terminals
Built-in safety discharge resistor (<50V in 1 min) Dry type self-healing capacitor winding Thermo-setting resin
Insulating enclosure
Network Quality
APCR
APCM2 APCM1
APCL1
APCL2
APCL2
APCM2
APCR
APCL 230, 400V - 50Hz (standard range). 400V - 50Hz (reinforced range rated at 474V).
Power range
APCL1: from 20 to 75 kvar depending on the voltage. APCL2: from 50 to 125 kvar depending on the voltage.
APCM 230, 400V - 50Hz (standard range). 240, 480V - 60Hz (standard range). 400V - 50Hz (reinforced range rated at 474V). APCM1: from 75 to 200 kvar depending on the voltage and frequency. APCM2: from 112.5 to 400 kvar depending on the voltage and frequency.
APCR 400, 415, 525, 690V - 50Hz (de-tuned capacitor bank) 240, 380, 480, 600V - 60Hz (de-tuned capacitor bank)
Connection Conguration
Losses
Capacitors
Three phase. APCL1: master unit only. APCM1: master unit only. APCR: master and slave units. APCL2: master and slave units. APCM2: master and slave units. Slave units are not equipped with PF controller but are tted with an interconnection cable. From 0.7 inductive to 0.7 capacitive. From 0.01A to 3A for the RVC From 0.01A to 3A for the RVC controller. From 0.01A to 5A controller. for the RVT controller (optional) Automatic or manual setting of the controller with indication of : - the number of active outputs. - the inductive or capacitive power factor. - alarm conditions. - overtemperature. - demand for switching on/off a capacitor step. - voltage, current, THDV and THDI. Threshold setting for protections against overvoltage, undervoltage and THDV. Dielectric losses: less than 0.2 Watt/kvar. Capacitor total losses: less than 0.5 Watt/kvar (discharge resistors included). Automatic bank total losses at 400V 50Hz: less than 1.5 Watt/kvar (including accessories losses). less than 5.5 Watt/kvar (including accessories losses). Dry type self healing according to IEC 60831-1&2. Voltage test: 2.15 Un between terminals during 10 sec at rated frequency (above IEC 60831-1&2). Acceptable overloads: - overvoltage tolerance: 10% max. intermittently. - overcurrent tolerance: 30% permanently. Temperature range: -25C / class D according to IEC 60831-1&2.
9/4
1SDC007200C0202
APCR
APCM2 APCM1
APCL1
APCL2
APCL2
APCM2
APCR
Specications Capacitors
Reactors
Compliance Automatic capacitor bank tests CE Marking Protection Execution Color Ambient temperature Ventilation
Installation
APCL APCM APCR Dry type self healing according to IEC 60831-1&2. Voltage test: 2.15 Un between terminals during 10 sec at rated frequency (above IEC 60831-1&2). Acceptable overloads: - overvoltage tolerance: 10% max. intermittently. - overcurrent tolerance: 30% permanently. Temperature range: -25C / class D according to IEC 60831-1&2. Type : dry type resin embedded according to IEC 289, IEC 76 Maximal harmonic voltage distortion: U3/U1 = 0.5 % U5/U1 = 6.0 % U7/U1 = 5.0 % U11/U1 = 3.5 % U13/U1 = 3.0 % (not exceeding a THDU of 8 %). The automatic capacitor bank complies with EN 61921. Functional test. Insulation test. CE Marked. IP23D (closed door). Protected against direct and accidental contact (open door). Indoor. Beige RAL 7032. - 5C / + 40C according to EN 61921. Natural for the APCL1. Forced Forced. for the APCL2. (temperature(temperature-dependent speed control fans). dependent speed control fans). - Wall mounting (xation - Floor xation. brackets included). - Equipped with a plinth. - Bottom cable entry. - Lifting lugs provided. - Top or bottom cable entry. Slave units have to be connected to the master unit. Important notice: The installation of capacitors on networks disturbed by harmonics may require special precautions especially when there is a risk of resonance.
9/5
1SDC007200C0202
Network Quality
Dynacomp
Introduction
Slow response time Electromechanically switched power factor correction systems are tted with discharge resistors. This allows reducing the voltage difference between the capacitors and the network and consequently the magnitude of the transients. Discharging the capacitors takes several seconds and tremendously limits the response time of such system, without suppressing the transients. Limited life Contactors have limited lifetimes and need to be replaced frequently. Such systems also require important maintenance efforts.
Fast response time The powerful control of the Dynacomp and its switching concept allows dynamic response times less than 80ms for power factor correction, less than 20ms for voltage drops compensation and instantaneous if an external signal is available.
Long life The transient free switching (with no electric arc, no moving parts) combined with the self healing capacitors used in the Dynacomp guarantees a very long life of the system without any limitation in the number of switching operations.
9/6
1SDC007200C0202
Dynacomp
Technical Data
Standard cubicle
From 220 to 690V - 50Hz or 60Hz, three or single-phase. Up to 500 kvar per step. The Dynacomp is a totally tailor-made product adapted to each particular need. Dry type self healing. Design according to IEC 831 1&2. Type RVT-D Micro-processor based system. Operating temperature: -20C to 70C. Current input: 5A or 1A (RMS) (class 1 CT). Network and Dynacomp measurements. Steel sheet. Color: RAL 7032. Protection: IP23. According to EN60439. According to IEC831 (-10C/+40C). Micro-processor based system for balanced three-phase networks or single-phase networks.
Applications
Motor start
Harbor crane
Welding machine
Network Quality
Measuring system Operating voltage Voltage tolerance Frequency range Measuring circuit terminals (L2, L3 and k, I) Current input Current input impedance Consumption of the controller Output contact rating
micro-processor based system for balanced three-phase networks or single-phase networks. 100V to 440V. +/- 10% on nominal voltages. 50 or 60 Hz +/- 5% (automatic adjustment to network frequency). CAT. III rated 1A or 5A (RMS). <0.1 Ohm. 8 VA max. -max. continuous current: 1.5 A; -max. peak current: 5 A; -max. voltage: 440 Vac; -terminal A is rated for a continuous current of 16 A. from 0.7 inductive to 0.7 capacitive. 0.01 to 3A. Automatic measurement of C/k RVC-3: programmable up to 3 outputs. RVC-6: programmable up to 6 outputs. RVC-8: programmable up to 8 outputs. RVC-10: programmable up to 10 outputs. RVC-12: programmable up to 12 outputs. programmable from 1s to 999s (independent of reactive load). User dened. the mode of switching for all the programmable switching sequences is integral, direct, circular or linear. all programmed parameters and modes are saved in a non-volatile memory. quick automatic disconnection in less than 20ms (50Hz) in case of power outage or voltage drop. 40 s. - normally open contact; - max. continuous current : 5A; - rated/max. breaking voltage: 250Vac/440Vac. -10 C to 60 C. - 30 C to 85 C. vertical panel mounting. 144x144x80 mm (HxWxD). 0.4 kg (unpacked). Spring clamp terminal block. IP40. maximum 95%, non-condensing. Overvoltage and undervoltage protection Auto-adaptation to the phase-rotation of the network and the CT-terminals. Not affected by the harmonics. Working with generative and regenerative loads. LCD contrast automatically compensated with temperature. CE Marked.
Switching time between steps Switching sequences Mode of switching Saving-function Power outage release Power outage reset delay time Alarm contact
Operating temperature Storage temperature Mounting position Dimensions Weight Connector Front plate protection Relative humidity Other features
Measuring system Supply voltage Consumption Connection type for measuring circuit and power supply Voltage tolerance Voltage measurement Frequency range Current input Current input impedance Output contact rating
Micro-processor-based system for balanced three-phase networks or single-phase networks. From 100Vac up to 440Vac. 15 VA max. Phase-phase or phase-neutral +/- 10% on indicated supply voltages. Up to 690Vac or higher with voltage transformer. Accuracy : 1% full scale. 50 or 60 Hz +/- 5% (automatic adjustment to network frequency). 5A or 1A (RMS) (class1 C.T.). <0.1 Ohm. -Max. continuous current: 1.5A (ac) 0.3A (110V dc). -Max. peak current: 8A. -Max. voltage: 440 Vac. -Terminal A-A are rated for a continuous current of 18A (9A/terminal). - Normally closed contact. - Max. continuous current: 1.5A. - Rated voltage: 250Vac (max. breaking voltage: 440Vac). - Normally open contact. - Max. continuous current: 1.5A. - Rated voltage: 250Vac (max. breaking voltage: 440Vac). From 0.7 inductive to 0.7 capacitive. - 0.01 to 5A. - automatic measurement of C/k. 1:1:1:1:1:.:1 - 1:2:2:2:2:..:2 - 1:2:4:4:4:..:4 - 1:2:4:8:8:.:8 1:1:2:2:2:.:2 - 1:1:2:4:4:..:4 - 1:1:2:4:8:..:8 - 1:2:3:3:3:.:3 1:2:3:6:6:.:6 - 1:1:2:3:3...:3 - 1:1:2:3:6...:6 and any other customer programmable sequence. 110 - 300 - 600 - 1200 - 2400 - 4800 - 6900 - 19200 - 38400 - 57600 (*) for RVT Modbus only Automatic, xed, disabled. 64 x 132 pixels with extra symbols. RVT 6: programmable up to 6 outputs. RVT 12: programmable up to 12 outputs. Programmable from 1s to 18h. All programmed parameters and modes are saved in a non-volatile memory. Automatic disconnection of all capacitors in case of a power outage longer than 20ms. -20 C to 70 C. -30 C to 85 C. Vertical panel mounting. Front plate : 144 x 144 mm (HxW). Overall : 144 x 211 x 67 mm (HxWxD). 1.0 kg (unpacked). Cage clamp type (2.5mm2 single core cable). IP 43 (IP54: on request). Maximum 95%, non-condensing. Automatic adaptation to the phase-rotation of the network and the CT-terminals. Insensitivity to harmonics. Working with passive and regenerative loads (four-quadrant operation). LCD contrast automatically compensated with temperature. CE Marked. UL Recognized (le n NKCR2.E163424). CSA certied for use in 120Vac system voltage.
Alarm contact rating (voltage free contact) Fan contact rating (voltage free contact) Power factor setting Starting current setting (C/k) Switching sequences
Modbus baud rate (*) Step conguration Full graphics display Number of outputs Switching time between steps Saving-function Power outage release Operating temperature Storage temperature Mounting position Dimensions Weight Connector Front plate protection Relative humidity Other features
Network Quality
The distortion is introduced by harmonics generated by the non-linear devices. These harmonics are a growing problem for both electricity suppliers and users. Harmonics can lead to serious problems: overheating of cables, motors and transformers damage to sensitive equipment tripping of circuit breakers blowing of fuses premature ageing of the installation capacitor overloading and failures high current in neutral conductors excitation of network resonance
-800
11
14
17
20
23
26
29
32
35
38
41
44
47
50
Harmonic order
generates Pulse Width Modulated (PWM) signals that drive IGBT power modules which through line reactors inject harmonic currents in the network with exactly the opposite phase to the components that are to be ltered. The PQF also offers communication facilities with the customers existing communication network. This feature which uses Modbus RTU, allows the PQF to be easily monitored and controlled from a remote location. The Modbus communication feature can be used by means of an RS-232 to RS485 converter (optional).
=
Harmonics
PQF
Harmonics only
9/10
1SDC007200C0202
-800
11
14
17
20
23
26
29
32
35
38
41
44
47
50
Harmonic order
9/11
1SDC007200C0202
Network Quality
PQFS
Degree of ltering Harmonic attenuation factor (IH (source)/IH (load) Reactive Power Load balancing Communication Programming Response time Active Power
208VU240V: 30-45-60 A 380VU415V: 30-45-60 A 3 times the line rms current mentioned above. 3 CTs required (class 1.0 or better), 5 Amps secondary rating, lter burden: 5 VA. Up to 8 units (intermixing of units of both equal Up to 4 units of equal rating. and unequal rating is allowed in the same voltage group). Maximum one unit rating difference between the largest and the smallest unit rating in a lter system One unit per panel. Floor standing units Wall mount type, one unit per enclosure. +/- 10% in voltage. +/- 5% in frequency. 20 individual harmonics selectable from 2nd to 50th 15 individual 3-wire connection: 20 order. harmonics selectable individual harmonics from 2nd to 50th order. selectable from 2nd to 50th order. 4-wire connection: 15 individual harmonics selectable from 2nd to 50th order. Individually programmable per harmonic in absolute terms. Better than 97% (at rated load). Power factor programmable from 0.6 (inductive) to 0.6 (capacitive). Programmable load balancing. Using Modbus RTU. Through RS-232 Port with dedicated software (PQF-Link). Using PQF-Manager. Using optional PQF-Link software and PC (not provided). < 0.5 ms instantaneous. 40 ms (10-90% ltering). < 3% of the device power typically.
9/12
1SDC007200C0202
Color Installation
PQFI PQFM PQFK PQFS IP21 (IP20 open door). IP21 (IP20 open door). IP30. For higher protection IP00 plate execution. degree, please consult For higher protection degree, please consult us. us. 800 x 600 x 2150 mm. 600 x 600 x 2150 mm. 585 x 310 x 700 mm. Appr. 620 kg IP21: appr. 255 kg. IP21: appr. 250 kg. Appr. 120 kg. (450A/320A) or 525 kg IP00: appr. 125 kg. IP00: appr. 175 kg. (250A/180A) per unit. RAL 7035 (light gray). Other colors on request. Floor xation, lifting lugs Floor xation, lifting lugs provided, cable entry Wall mounting, cable provided, cable entry from top or bottom. entry from bottom. from bottom. Indoor installation in clean environment up to 1000 m altitude (higher altitudes with suitable derating.) -5C to +40C. (Up to 50C with suitable derating). Maximum 95% RH; non-condensing. PQF-Link software. PQF-Link software. Common cable entry cubicle. Cable connection box. IP41 protection degree execution (10% derating). Modbus kit (RS-485 Base frame (100 mm). based). Modbus kit (RS-485 based). Printer kit (RS-232 Printer kit (RS-232 based). based). Space heaters. Temperature probes. Temperature probes. MCB position status Main contactor position status lamps. lamps. Surge arresters If the nominal system voltage is higher than 600V (U>600V) the current rating of PQFI and PQFM units in this voltage range may be derated automatically depending on the operating temperature.
Network Quality
The Third Harmonic Causes Many Problems Problems are directly related to the harmonic content. The third harmonic found in the phase current appears neutral thus increasing the neutral current. See illustration above. In network: Overheating Increased power losses Poor quality of electricity Electromagnetic elds Malfunctions in earth fault control Failure in remote control systems
In plants: 9/14
1SDC007200C0202
Malfunction in electronics Damage to capacitors Power losses Increased magnetic elds Overload in neutral conductor Cable res Abnormal temperature changes and noise in transformers Nuisance tripping in circuit-breakers Shorter life time
THF patented
application
Transformer
Load
Transformer
Load
Example on how Third Harmonic Filter THF effects on third harmonic currents.
Benets of THF for lighting and mixed load Increased efciency in low voltage network Reduction in transmission losses Increased loadability of the existing network and switchboards Lower temperature of cables, switchboards and transformers Elimination of third harmonic current in neutral and phase conductor Increased efciency in lighting appliance and pc-load Less power or more lighting Less maintenance Longer lifetime of the lamps and capacitors Reduced Magnetic elds The reduction of third harmonic component of the current reduces the total magnetic eld Diagram indicating an example of the total magnetic eld spectrum typically in various locations
Without THF
With THF
Diagram indicating the level of magnetic eld with and without Third Harmonic Filter, Hospital building.
9/15
1SDC007200C0202
Network Quality
N (PEN)
The size of the THF-lters is selected according to the supply transformer or back up fuses. The protection unit needs to be used, in case the dimensioning exceeds the thermal rating of the lter. The basis of dimensioning is that the lter withstands the 150Hz voltage and the fundamental neutral current generated by the phase unbalance. The THFstar lters are tested according to the highest possible short circuit current or back up fuse. Installation to the transformer star point, enclosed lters and system components,THFstar The new generation third harmonic lter THFstar is designed for small size and economical solutions to places, which are especially exposed by third harmonic currents. The lter can be installed outdoor in vicinity of transformer stations, as retrotting to existing transformer station or as additional eld of main switchboard. It is recommended to install the lter THFstar in PEN-conductor, whenever possible, equipped with appropriate protection unit THF1S_ . DIMENSIONING: According to the supply transformer PROTECTION: Protection unit THFS1_S, 50Hz and 150 Hz measurement according to the mounting instruction
L1 L2 L3
THF
N PE
S01545A
Rated current Transformer of the size transformer kVA A 8001) 900 630 630
System components IP 00 THFS400A1 + THF 1_S THFS630A1 + THF 1_S THFS1000A1 + THF 1_S THFS630A1x2
Internal connection to the lter 33% of phase conductor 33% of phase conductor 33% of phase conductor 33% of phase conductor
N (PEN)
Acc. to phase conductors Acc. to phase conductors Acc. to phase conductors Acc. to phase conductors
1250
1000
THFS1000S1
THFS1000U1
2500 3200
1600 2000
THFS1600S1 THFS1600S1x2
THFS1600U1 THFS1600U1x2
35
FILTE
R BY
NO
BASS
Transformer size [kVA] [A] 500 630 800 900 1450 2300
Dimensions L x S x K [mm] 1050 x 360 x 1200 654 x 654 x 2260 654 x 654 x 2260 840 x 654 x 2260
Input-Output Cabling /Busbar 2 x 150 mm2 Cu 2 x 150 mm2 Cu (max 4 cables) 4 x 150 mm2 Cu (max 6 cables) Busbar 2x10x120 6 x 150 mmm2 Cu
Type No. THFS 500US11) THFS 630S1 THFS 1000S1 THFS 1600S1
O OFF
S01552A
THFS_S1
THFS_U1
THF
Strmb
erg
Reset
OK
Test
R ByPass
Test
Aut
S01536A
THF 63NV
9/17
1SDC007200C0202
Network Quality
1000 1600
1)
Outdoor use IP 34. Includes base element, cabling from bottom Transformer size Dimensions Input-Output Type No. [kVA] [A] L x S x K [mm] Cabling /Busbar 630 1000 1600 900 1450 2300 1050 x 360 x 1200 1050 x 720 x 1200 1050 x 720 x 1200 2 x 150mm2 Cu (max 4 cables) 4 x 150mm2 Cu (max 6 cables) Busbar 2x10x120 6 x 150 mmm2 Cu THFS 630U1 THFS 1000U1 THFS 1600U1
[kg]
Third harmonic lters including guard unit and by-pass contactor Current transformer of the relay, cable diameter max. 27 mm, is included in the delivery. 25 6 250x180x400 IP 30 THF 25NV 1SCA022388R0700 63 16 400x230x600 IP 30 THF 63NV 1SCA022374R8260 125 35 400x230x1000 IP 30 THF 125NV 1SCA022374R8340 125 95 and 150 400x230x1400 IP 30 THF 125NLV 1SCA022378R6190 160 50 and 70 800x230x1000 IP 30 THF 160NV 1SCA022374R8420 Third harmonic lters without guard unit and by-pass contactor Can be used parallel with NV- and NLV- types. 63 16 400x230x600 IP 30 THF 63N 125 35 400x230x1000 IP 30 THF 125N 125 95 and 150 400x230x1400 IP 30 THF 125NL 160 50 and 70 800x230x1000 IP 30 THF 160N
19 43 76 83 110
43 76 83 110
NOTE: THF 125 NL include space for parallel connection of several lters.
THFS_
400 x 500 x 350 400 x 500 x 500 400 x 500 x 700 400 x 500 x 500x2 350 x145 x 415
800 x 350x 350 800 x 350x 500 800 x 350x 700 800 x 350x 500x2
THFS 400A1 THFS 630A1 THFS 1000A1 THFS 630A1x2 THF 63NB
230V~
50/60Hz
H D
S01601A
Protection unit
Back up fuse
Terminals [mm2] / Cu
Protection degree
Type
Order Code
Weight [kg]
10A
2.5
IP00
4.6 4.6 15
230V~
50/60H
230V~
50/60H
z
2 B
18 1 A
17
S01602A
SM 1152
4 2 6
30
8
SM 1152
4 2 6
30
8 10
1 A
2 B
0 10
THF1BSMNS
2.5
IP44
THF1BS
KORE06F1 250/1THF KORE06F1 250/1THF KORE06F1 300/1THF KORE06F1 400/1THF KORE06F1 500/1THF KORE06F1 750/1THF KORE06F1 1000/1 KORE06F1 1250/1 KORE06F1 1500/1
230V~ 50/60Hz
SM 115230
2 4 6 8 2 4 6 8
A1 A2
0 10 0 10
230V~ 50/60Hz
18 17
SM 115230
1 A 2 B 1 A 2 B
S00978A
18
ByPass OK
50/60H
Error z 50/60H
150/18
A1 A2 A1 A2
0Hz
17 1 A 2 B 18 17
Test
R
Reset
S00977A
Test
Auto
Str mbe rg
THF1S
9/18
1SDC007200C0202
FILTER
I
SS BYBA
NO
Check THFstar lters Installation and commissioning: The installation of THFstar is in theory easy but in practice certain points have to be checked : Ensure by measurement that there is no parallel current path to the lter Check up also the possible inuence of parallel transformers or generators Ensure that the lter is installed in the right location. The neutral conductor from the star point of the transformer is the recommended place. Check up that the current measurement is right. The CT shall always measure the sum of all neutral and earth currents of the network. Check up the relay setting of the protection unit. Read mounting instruction 34THF1S Check that there is no largely dimmer loads. Network Quality 9/19
1SDC007200C0202
O OFF
-S
Transformer
L1 L2 L3 N PE
N L1 L2 L3 X
THFS
TN-S-system, where the original cabling to the transformer star point need to be displaced to fundamentally same position in the N-conductor of the main switchboard. THFstar installation.
S01541B
Earthing electrode
Water meter
Main switchboard
Distribution switchboard
-S
Transformer
L1 L2 L3 PEN
-S
L1 L2 L3 N PE
THF
TN-C-S system Alternative installation examples when using THFstar with protection unit(_S) or THF with guard unit(_V).
N
L1 L2 L3
S01543B
THFS
N
L1 L2 L3 PE
1) THFS/ THF
-V
-V
Distribution swtichboard
Earthing electrode
Water meter
Distribution switchboard
-S
L1L2 L3 N PE
-S
L1 L2 L3 N PE
THF
TN-S system Alternative installation example when using THFstar with protection unit(_S) or THF with guard unit(_V).
N
L1 L2 L3
S01542B
THFS
N
L1 L2 L3 PE
1) THFS/ THF
-V
-V
Distribution swtichboard
Earthing electrode
Water meter
1)
9/20
1SDC007200C0202
S01549A
N PE
THFS
In this installation model, the current transformer need to measure both N- and PE-current, unless additional guard unit is used.
Notes
9/21
1SDC007200C0202
Network Quality