Concrete Test
Concrete Test
ACME Consultants 1234 Main Street Some Place, USA 00000 Phone (000) 555-1234 Fax (000) 555-4321
1234.ABCD ACME Developments 4321 State St. Somewhere, CA
Mix Data
Material Type: Supplier: Mix Number: Cement Factor: Aggregate Size: Admixture: Specified Strength: Slump Requirement: Air Content Requirement: 1" x #4 --3000 3-5 4-6
psi at in. %
28
days
Sample Data
Sample Date: Laboratory Number: Set Number: Time Cast: Field Technician: Truck/Ticket Number: Testing Technician: Placement Location: 5/20/05 Notes: Light drizzle during sampling.
Page 1 of 1
Date Tested
5/27/05 6/3/05 6/17/05 6/17/05
Age
7 14 28 28
Dimensions (in)
6 6 6 6 X X X X 12 12 12 12
Area (in2)
28.27 28.27 28.27 28.27
Load (lbf)
62,420 102,150 125,650 126,850
Corr. Factor
1.00 1.00 1.00 1.00
Cure Type
L L L L
Fract. Type
A A A A
Defects not apparent unless otherwise noted. Sampled materials MEET the specified 28-day strength requirement as noted.
Cc:
Y. Me I. Be
Submitted by,
ACME Consultants
LOGO
CONCRETE COMPRESSION TEST REPORT
Report To: ACME Properties Attn: John Smythe 1234 Main Street Suite 111 Someplace, CA 94000 Concrete XYZ Concrete 4567 5.25 Project Number: Project: Location:
ACME Consultants 1234 Main Street Some Place, USA 00000 Phone (000) 555-1234 Fax (000) 555-4321
1234.ABCD ACME Developments 4321 State St. Somewhere, CA
Mix Data
Material Type: Supplier: Mix Number: Cement Factor: Aggregate Size: Admixture: Specified Strength: Slump Requirement: Air Content Requirement: 1" x #4 --3000 3-5 4-6
psi at in. %
28
days
Sample Data
Sample Date: Laboratory Number: Set Number: Time Cast: Field Technician: Truck/Ticket Number: Testing Technician: Placement Location: 5/20/05 Notes: Light drizzle during sampling.
Page 1 of 1
Date Tested
5/27/05 6/17/05 6/17/05
Age
7 28 28
Dimensions (in)
6 6 6 X X X 12 12 12
Area (in2)
28.27 28.27 28.27
Load (lbf)
73,960 109,640 110,220
Corr. Factor
1.00 1.00 1.00
Cure Type
L L L
Fract. Type
A A A
Defects not apparent unless otherwise noted. Sampled materials MEET the specified 28-day strength requirement as noted.
Cc:
Y. Me I. Be
Submitted by,
ACME Consultants
LOGO
CONCRETE COMPRESSION TEST REPORT
Report To: ACME Properties Attn: John Smythe 1234 Main Street Suite 111 Someplace, CA 94000 Concrete XYZ Concrete 4567 5.25 Project Number: Project: Location:
ACME Consultants 1234 Main Street Some Place, USA 00000 Phone (000) 555-1234 Fax (000) 555-4321
1234.ABCD ACME Developments 4321 State St. Somewhere, CA
Mix Data
Material Type: Supplier: Mix Number: Cement Factor: Aggregate Size: Admixture: Specified Strength: Slump Requirement: Air Content Requirement: 1" x #4 --3000 3-5 4-6
psi at in. %
28
days
Sample Data
Sample Date: Laboratory Number: Set Number: Time Cast: Field Technician: Truck/Ticket Number: Testing Technician: Placement Location: 5/20/05 Notes: Light drizzle during sampling.
Page 1 of 1
Date Tested
5/27/05 6/3/05 6/17/05 6/17/05
Age
7 14 28 28
Dimensions (in)
6 6 6 6 X X X X 12 12 12 12
Area (in2)
28.27 28.27 28.27 28.27
Load (lbf)
100,290 111,130 121,590 136,340
Corr. Factor
1.00 1.00 1.00 1.00
Cure Type
L L L L
Fract. Type
A A A A
Defects not apparent unless otherwise noted. Sampled materials MEET the specified 28-day strength requirement as noted.
Cc:
Y. Me I. Be
Submitted by,
ACME Consultants
LOGO
CONCRETE COMPRESSION TEST REPORT
Report To: ACME Properties Attn: John Smythe 1234 Main Street Suite 111 Someplace, CA 94000 Concrete XYZ Concrete 4567 5.25 Project Number: Project: Location:
ACME Consultants 1234 Main Street Some Place, USA 00000 Phone (000) 555-1234 Fax (000) 555-4321
1234.ABCD ACME Developments 4321 State St. Somewhere, CA
Mix Data
Material Type: Supplier: Mix Number: Cement Factor: Aggregate Size: Admixture: Specified Strength: Slump Requirement: Air Content Requirement: 1" x #4 --3000 3-5 4-6
psi at in. %
28
days
Sample Data
Sample Date: Laboratory Number: Set Number: Time Cast: Field Technician: Truck/Ticket Number: Testing Technician: Placement Location: 5/21/05
Page 1 of 1
Date Tested
5/28/05 6/4/05 6/18/05 6/18/05
Age
7 14 28 28
Dimensions (in)
6 6 6 6 X X X X 12 12 12 12
Area (in2)
28.27 28.27 28.27 28.27
Load (lbf)
62,420 102,150 125,650 126,850
Corr. Factor
1.00 1.00 1.00 1.00
Cure Type
L L L L
Fract. Type
A A A A
Defects not apparent unless otherwise noted. Sampled materials MEET the specified 28-day strength requirement as noted.
Cc:
Y. Me I. Be
Submitted by,
ACME Consultants
LOGO
CONCRETE COMPRESSION TEST REPORT
Report To: ACME Properties Attn: John Smythe 1234 Main Street Suite 111 Someplace, CA 94000 Concrete XYZ Concrete 4567 5.25 Project Number: Project: Location:
ACME Consultants 1234 Main Street Some Place, USA 00000 Phone (000) 555-1234 Fax (000) 555-4321
1234.ABCD ACME Developments 4321 State St. Somewhere, CA
Mix Data
Material Type: Supplier: Mix Number: Cement Factor: Aggregate Size: Admixture: Specified Strength: Slump Requirement: Air Content Requirement: 1" x #4 --3000 3-5 4-6
psi at in. %
28
days
Sample Data
Sample Date: Laboratory Number: Set Number: Time Cast: Field Technician: Truck/Ticket Number: Testing Technician: Placement Location: 5/21/05
Page 1 of 1
Date Tested
5/28/05 6/18/05 6/18/05
Age
7 28 28
Dimensions (in)
6 6 6 X X X 12 12 12
Area (in2)
28.27 28.27 28.27
Load (lbf)
73,960 109,640 110,220
Corr. Factor
1.00 1.00 1.00
Cure Type
L L L
Fract. Type
A A A
Defects not apparent unless otherwise noted. Sampled materials MEET the specified 28-day strength requirement as noted.
Cc:
Y. Me I. Be
Submitted by,
ACME Consultants
LOGO
Report To: ACME Properties Attn: John Smythe 1234 Main Street Suite 111 Someplace, CA 94000 Masonry Grout XYZ Concrete 8901 7.5 Project Number: Project: Location:
ACME Consultants 1234 Main Street Some Place, USA 00000 Phone (000) 555-1234 Fax (000) 555-4321
Mix Data
Material Type: Supplier: Mix Number: Cement Factor: Aggregate Size: Admixture: Specified Strength: Slump Requirement: Air Content Requirement: 3/8" Max --2500 psi at 4-6 in. --- %
28
days
Sample Data
Sample Date: Laboratory Number: Set Number: Time Cast: Field Technician: Truck/Ticket Number: Testing Technician: Placement Location: 5/2/05 Notes: Light drizzle during sampling.
Page 1 of 1
Date Tested
5/9/05 5/30/05 5/30/05 5/30/05
Age
7 28 28 28 3.25 3.02 3.19 3.22
Dimensions (in)
X X X X 3.33 3.35 3.31 3.31 X X X X 6.6 5.8 6.4 6.5
Area (in2)
10.82 10.12 10.56 10.66
Load (lbf)
12,150 29,460 27,840 28,840
Corr. Factor
1.01 0.98 1.00 1.00
Cure Type
L L L L
Fract. Type
A A A A
Defects not apparent unless otherwise noted. Sampled materials MEET the specified 28-day strength requirement as noted.
Cc:
Y. Me I. Be
Submitted by,
ACME Consultants
LOGO
Report To: ACME Properties Attn: John Smythe 1234 Main Street Suite 111 Someplace, CA 94000 Concrete Core N/A N/A --Project Number: Project: Location:
ACME Consultants 1234 Main Street Some Place, USA 00000 Phone (000) 555-1234 Fax (000) 555-4321
Mix Data
Material Type: Supplier: Mix Number: Cement Factor: Aggregate Size: Admixture: Specified Strength: Slump Requirement: Air Content Requirement: " max. --N/A -----
psi at in. %
---
days
Sample Data
Sample Date: Laboratory Number: Set Number: Time Cast: Field Technician: Truck/Ticket Number: Testing Technician: Placement Location: 5/1/05 Notes: Light drizzle during sampling.
Page 1 of 1
---
Date Tested
5/29/05 5/29/05 5/29/05
Age
28 28 28
Dimensions (in)
3 3 3 X X X 4.2 6.1 6.1
Area (in2)
7.07 7.07 7.07
Load (lbf)
39,140 42,130 40,940
Corr. Factor
0.95 1.00 1.00
Cure Type
L L L
Fract. Type
A A A
Defects not apparent unless otherwise noted. Sampled materials MEET the specified 28-day strength requirement as noted. Comments: Concrete cores taken in lieu of destroyed field samples.
CONCRETE TEST CONCRETE TEST.GPJ CONCRETE TEST.GDT 9/11/05
Cc:
Y. Me I. Be
Submitted by,
ACME Consultants