CONCRETE COMPRESSION TEST REPORT


Report To: ACME Properties Attn: John Smythe 1234 Main Street Suite 111 Someplace, CA 94000 Concrete XYZ Concrete 4567 5.25 Project Number: Project: Location:

ACME Consultants 1234 Main Street Some Place, USA 00000 Phone (000) 555-1234 Fax (000) 555-4321
1234.ABCD ACME Developments 4321 State St. Somewhere, CA

Mix Data
Material Type: Supplier: Mix Number: Cement Factor: Aggregate Size: Admixture: Specified Strength: Slump Requirement: Air Content Requirement: 1" x #4 --3000 3-5 4-6

psi at in. %

28

days

Sample Data
Sample Date: Laboratory Number: Set Number: Time Cast: Field Technician: Truck/Ticket Number: Testing Technician: Placement Location: 5/20/05 Notes: Light drizzle during sampling.

Set Data (ASTM C31)


050520 1 of 3 10:00am A. Bore 0000 / 000-123456 I. Core Footings-Line 99/Row Z Slump (ASTM C143): Ambient Temperature: Sample Temperature (ASTM C1064): Air Content (ASTM C173/C231): Unit Weight-Fresh (ASTM C138): Unit Weight-Dry (ASTM C567): 3.25 65 61 6.0 150.0 --in. F F % pcf pcf

Page 1 of 1

Test Data (ASTM C39)


Sample Number
0001 0002 0003 0004
Cure Type: Fracture Type:

Date Tested
5/27/05 6/3/05 6/17/05 6/17/05

Age
7 14 28 28

Dimensions (in)
6 6 6 6 X X X X 12 12 12 12

Area (in2)
28.27 28.27 28.27 28.27

Load (lbf)
62,420 102,150 125,650 126,850

Corr. Factor
1.00 1.00 1.00 1.00

Cure Type
L L L L

Fract. Type
A A A A

Comp. Str. (psi)


2210 3610 4440 4490

L-Laboratory; F-Field A-Cone; B-Cone/Split; C-Cone/Shear; D-Shear; E-Columnar

Average 28-day Compressive Strength = 4470 psi

Defects not apparent unless otherwise noted. Sampled materials MEET the specified 28-day strength requirement as noted.

CONCRETE TEST CONCRETE TEST.GPJ CONCRETE TEST.GDT 9/11/05

Cc:

Y. Me I. Be

Submitted by,

ACME Consultants

Jon Smythe (6/28/05)

LOGO
CONCRETE COMPRESSION TEST REPORT
Report To: ACME Properties Attn: John Smythe 1234 Main Street Suite 111 Someplace, CA 94000 Concrete XYZ Concrete 4567 5.25 Project Number: Project: Location:

ACME Consultants 1234 Main Street Some Place, USA 00000 Phone (000) 555-1234 Fax (000) 555-4321
1234.ABCD ACME Developments 4321 State St. Somewhere, CA

Mix Data
Material Type: Supplier: Mix Number: Cement Factor: Aggregate Size: Admixture: Specified Strength: Slump Requirement: Air Content Requirement: 1" x #4 --3000 3-5 4-6

psi at in. %

28

days

Sample Data
Sample Date: Laboratory Number: Set Number: Time Cast: Field Technician: Truck/Ticket Number: Testing Technician: Placement Location: 5/20/05 Notes: Light drizzle during sampling.

Set Data (ASTM C31)


050520 Slump (ASTM C143): 2 of 3 Ambient Temperature: 1:28pm Sample Temperature (ASTM C1064): I. Core Air Content (ASTM C173/C231): 0001 / 98765432109 Unit Weight-Fresh (ASTM C138): Y. Me Unit Weight-Dry (ASTM C567): Rear Center of Slab, Post-Tensioned Slab On Grade 3.75 62 59 3.3 148.6 --in. F F % pcf pcf

Page 1 of 1

Test Data (ASTM C39)


Sample Number
0005 0007 0006
Cure Type: Fracture Type:

Date Tested
5/27/05 6/17/05 6/17/05

Age
7 28 28

Dimensions (in)
6 6 6 X X X 12 12 12

Area (in2)
28.27 28.27 28.27

Load (lbf)
73,960 109,640 110,220

Corr. Factor
1.00 1.00 1.00

Cure Type
L L L

Fract. Type
A A A

Comp. Str. (psi)


2620 3880 3900

L-Laboratory; F-Field A-Cone; B-Cone/Split; C-Cone/Shear; D-Shear; E-Columnar

Average 28-day Compressive Strength = 3890 psi

Defects not apparent unless otherwise noted. Sampled materials MEET the specified 28-day strength requirement as noted.

CONCRETE TEST CONCRETE TEST.GPJ CONCRETE TEST.GDT 9/11/05

Cc:

Y. Me I. Be

Submitted by,

ACME Consultants

Jon Smythe (6/28/05)

LOGO
CONCRETE COMPRESSION TEST REPORT
Report To: ACME Properties Attn: John Smythe 1234 Main Street Suite 111 Someplace, CA 94000 Concrete XYZ Concrete 4567 5.25 Project Number: Project: Location:

ACME Consultants 1234 Main Street Some Place, USA 00000 Phone (000) 555-1234 Fax (000) 555-4321
1234.ABCD ACME Developments 4321 State St. Somewhere, CA

Mix Data
Material Type: Supplier: Mix Number: Cement Factor: Aggregate Size: Admixture: Specified Strength: Slump Requirement: Air Content Requirement: 1" x #4 --3000 3-5 4-6

psi at in. %

28

days

Sample Data
Sample Date: Laboratory Number: Set Number: Time Cast: Field Technician: Truck/Ticket Number: Testing Technician: Placement Location: 5/20/05 Notes: Light drizzle during sampling.

Set Data (ASTM C31)


050520 3 of 3 4:15pm Y. Me 99 / 123456 A. Bore Pour pads inside boiler room Slump (ASTM C143): Ambient Temperature: Sample Temperature (ASTM C1064): Air Content (ASTM C173/C231): Unit Weight-Fresh (ASTM C138): Unit Weight-Dry (ASTM C567): 4 65 68 ------in. F F % pcf pcf

Page 1 of 1

Test Data (ASTM C39)


Sample Number
0008 0009 0011 0010
Cure Type: Fracture Type:

Date Tested
5/27/05 6/3/05 6/17/05 6/17/05

Age
7 14 28 28

Dimensions (in)
6 6 6 6 X X X X 12 12 12 12

Area (in2)
28.27 28.27 28.27 28.27

Load (lbf)
100,290 111,130 121,590 136,340

Corr. Factor
1.00 1.00 1.00 1.00

Cure Type
L L L L

Fract. Type
A A A A

Comp. Str. (psi)


3550 3930 4300 4820

L-Laboratory; F-Field A-Cone; B-Cone/Split; C-Cone/Shear; D-Shear; E-Columnar

Average 28-day Compressive Strength = 4560 psi

Defects not apparent unless otherwise noted. Sampled materials MEET the specified 28-day strength requirement as noted.

CONCRETE TEST CONCRETE TEST.GPJ CONCRETE TEST.GDT 9/11/05

Cc:

Y. Me I. Be

Submitted by,

ACME Consultants

Jon Smythe (6/28/05)

LOGO
CONCRETE COMPRESSION TEST REPORT
Report To: ACME Properties Attn: John Smythe 1234 Main Street Suite 111 Someplace, CA 94000 Concrete XYZ Concrete 4567 5.25 Project Number: Project: Location:

ACME Consultants 1234 Main Street Some Place, USA 00000 Phone (000) 555-1234 Fax (000) 555-4321
1234.ABCD ACME Developments 4321 State St. Somewhere, CA

Mix Data
Material Type: Supplier: Mix Number: Cement Factor: Aggregate Size: Admixture: Specified Strength: Slump Requirement: Air Content Requirement: 1" x #4 --3000 3-5 4-6

psi at in. %

28

days

Sample Data
Sample Date: Laboratory Number: Set Number: Time Cast: Field Technician: Truck/Ticket Number: Testing Technician: Placement Location: 5/21/05

Set Data (ASTM C31)


050521 1 of 2 10:00am Y. Me 0000 / 000-123456 I. Core Footings-Line 99/Row Z Slump (ASTM C143): Ambient Temperature: Sample Temperature (ASTM C1064): Air Content (ASTM C173/C231): Unit Weight-Fresh (ASTM C138): Unit Weight-Dry (ASTM C567): 3.25 65 61 6.0 150.0 --in. F F % pcf pcf

Page 1 of 1

Test Data (ASTM C39)


Sample Number
0001 0002 0003 0004
Cure Type: Fracture Type:

Date Tested
5/28/05 6/4/05 6/18/05 6/18/05

Age
7 14 28 28

Dimensions (in)
6 6 6 6 X X X X 12 12 12 12

Area (in2)
28.27 28.27 28.27 28.27

Load (lbf)
62,420 102,150 125,650 126,850

Corr. Factor
1.00 1.00 1.00 1.00

Cure Type
L L L L

Fract. Type
A A A A

Comp. Str. (psi)


2210 3610 4440 4490

L-Laboratory; F-Field A-Cone; B-Cone/Split; C-Cone/Shear; D-Shear; E-Columnar

Average 28-day Compressive Strength = 4470 psi

Defects not apparent unless otherwise noted. Sampled materials MEET the specified 28-day strength requirement as noted.

CONCRETE TEST CONCRETE TEST.GPJ CONCRETE TEST.GDT 9/11/05

Cc:

Y. Me I. Be

Submitted by,

ACME Consultants

Jon Smythe (6/28/05)

LOGO
CONCRETE COMPRESSION TEST REPORT
Report To: ACME Properties Attn: John Smythe 1234 Main Street Suite 111 Someplace, CA 94000 Concrete XYZ Concrete 4567 5.25 Project Number: Project: Location:

ACME Consultants 1234 Main Street Some Place, USA 00000 Phone (000) 555-1234 Fax (000) 555-4321
1234.ABCD ACME Developments 4321 State St. Somewhere, CA

Mix Data
Material Type: Supplier: Mix Number: Cement Factor: Aggregate Size: Admixture: Specified Strength: Slump Requirement: Air Content Requirement: 1" x #4 --3000 3-5 4-6

psi at in. %

28

days

Sample Data
Sample Date: Laboratory Number: Set Number: Time Cast: Field Technician: Truck/Ticket Number: Testing Technician: Placement Location: 5/21/05

Set Data (ASTM C31)


050521 Slump (ASTM C143): 2 of 2 Ambient Temperature: 1:28pm Sample Temperature (ASTM C1064): J. Smith Air Content (ASTM C173/C231): 0001 / 98765432109 Unit Weight-Fresh (ASTM C138): A. Bore Unit Weight-Dry (ASTM C567): Rear Center of Slab, Post-Tensioned Slab On Grade 3.75 62 59 3.3 148.6 --in. F F % pcf pcf

Page 1 of 1

Test Data (ASTM C39)


Sample Number
0005 0007 0006
Cure Type: Fracture Type:

Date Tested
5/28/05 6/18/05 6/18/05

Age
7 28 28

Dimensions (in)
6 6 6 X X X 12 12 12

Area (in2)
28.27 28.27 28.27

Load (lbf)
73,960 109,640 110,220

Corr. Factor
1.00 1.00 1.00

Cure Type
L L L

Fract. Type
A A A

Comp. Str. (psi)


2620 3880 3900

L-Laboratory; F-Field A-Cone; B-Cone/Split; C-Cone/Shear; D-Shear; E-Columnar

Average 28-day Compressive Strength = 3890 psi

Defects not apparent unless otherwise noted. Sampled materials MEET the specified 28-day strength requirement as noted.

CONCRETE TEST CONCRETE TEST.GPJ CONCRETE TEST.GDT 9/11/05

Cc:

Y. Me I. Be

Submitted by,

ACME Consultants

Jon Smythe (6/28/05)

LOGO
Report To: ACME Properties Attn: John Smythe 1234 Main Street Suite 111 Someplace, CA 94000 Masonry Grout XYZ Concrete 8901 7.5 Project Number: Project: Location:

ACME Consultants 1234 Main Street Some Place, USA 00000 Phone (000) 555-1234 Fax (000) 555-4321

MASONRY GROUT COMPRESSION TEST REPORT


1234.ABCD ACME Developments 4321 State St. Somewhere, CA

Mix Data
Material Type: Supplier: Mix Number: Cement Factor: Aggregate Size: Admixture: Specified Strength: Slump Requirement: Air Content Requirement: 3/8" Max --2500 psi at 4-6 in. --- %

28

days

Sample Data
Sample Date: Laboratory Number: Set Number: Time Cast: Field Technician: Truck/Ticket Number: Testing Technician: Placement Location: 5/2/05 Notes: Light drizzle during sampling.

Set Data (ASTM C1019, UBC 21-18)


050502 Slump (ASTM C143): 1 of 1 Ambient Temperature: 2:30pm Sample Temperature (ASTM C1064): Y. Me Air Content (ASTM C173/C231): 6023 / 215428031 Unit Weight-Fresh (ASTM C138): A. Bore Unit Weight-Dry (ASTM C567): CMU Walls: Line 28/Rows D-H, Courses 8-16 9 51 53 ------in. F F % pcf pcf

Page 1 of 1

Test Data (ASTM C1019, UBC 21-18)


Sample Number
0032 0034 0035 0033
Cure Type: Fracture Type:

Date Tested
5/9/05 5/30/05 5/30/05 5/30/05

Age
7 28 28 28 3.25 3.02 3.19 3.22

Dimensions (in)
X X X X 3.33 3.35 3.31 3.31 X X X X 6.6 5.8 6.4 6.5

Area (in2)
10.82 10.12 10.56 10.66

Load (lbf)
12,150 29,460 27,840 28,840

Corr. Factor
1.01 0.98 1.00 1.00

Cure Type
L L L L

Fract. Type
A A A A

Comp. Str. (psi)


1130 2850 2640 2710

L-Laboratory; F-Field A-Cone; B-Cone/Split; C-Cone/Shear; D-Shear; E-Columnar

Average 28-day Compressive Strength = 2730 psi

Defects not apparent unless otherwise noted. Sampled materials MEET the specified 28-day strength requirement as noted.

CONCRETE TEST CONCRETE TEST.GPJ CONCRETE TEST.GDT 9/11/05

Cc:

Y. Me I. Be

Submitted by,

ACME Consultants

Jon Smythe (6/28/05)

LOGO
Report To: ACME Properties Attn: John Smythe 1234 Main Street Suite 111 Someplace, CA 94000 Concrete Core N/A N/A --Project Number: Project: Location:

ACME Consultants 1234 Main Street Some Place, USA 00000 Phone (000) 555-1234 Fax (000) 555-4321

CONCRETE CORE COMPRESSION TEST REPORT


1234.ABCD ACME Developments 4321 State St. Somewhere, CA

Mix Data
Material Type: Supplier: Mix Number: Cement Factor: Aggregate Size: Admixture: Specified Strength: Slump Requirement: Air Content Requirement: " max. --N/A -----

psi at in. %

---

days

Sample Data
Sample Date: Laboratory Number: Set Number: Time Cast: Field Technician: Truck/Ticket Number: Testing Technician: Placement Location: 5/1/05 Notes: Light drizzle during sampling.

Set Data (ASTM C42)


050501 1 of 1 ------Y. Me Slab, West End Slump (ASTM C143): Ambient Temperature: Sample Temperature (ASTM C1064): Air Content (ASTM C173/C231): Unit Weight-Fresh (ASTM C138): Unit Weight-Dry (ASTM C567): N/A ----------in. F F % pcf pcf

Page 1 of 1

---

Test Data (ASTM C42)


Sample Number
0029 0030 0031
Cure Type: Fracture Type:

Date Tested
5/29/05 5/29/05 5/29/05

Age
28 28 28

Dimensions (in)
3 3 3 X X X 4.2 6.1 6.1

Area (in2)
7.07 7.07 7.07

Load (lbf)
39,140 42,130 40,940

Corr. Factor
0.95 1.00 1.00

Cure Type
L L L

Fract. Type
A A A

Comp. Str. (psi)


5260 5960 5790

L-Laboratory; F-Field A-Cone; B-Cone/Split; C-Cone/Shear; D-Shear; E-Columnar

Average 28-day Compressive Strength = 5670 psi

Defects not apparent unless otherwise noted. Sampled materials MEET the specified 28-day strength requirement as noted. Comments: Concrete cores taken in lieu of destroyed field samples.
CONCRETE TEST CONCRETE TEST.GPJ CONCRETE TEST.GDT 9/11/05

Cc:

Y. Me I. Be

Submitted by,

ACME Consultants

Jon Smythe (6/28/05)