Inspection Report

No. : R-4500101415-0-04 This is to certify that the components as described hereunder have been inspected. Client: Project Client's P.O./LOI No Items Supplier: Manufacturer: Place of Inspection: Date/Period of Inspection: : SAMSUNG ENGINEERING CO. LTD., : MA ADEN ALUMINUM PROJECT : 4500101415 : MES NETWORK : VECTOR INFO TECH PVT LTD. : VECTOR INFO TECH PVT LTD : BLK 3015A, UBI ROAD1, #07-08, SINGAPORE 408705 : 10 June 2013 (1 day) Inspection Item FAT

The following material was inspected: No 1 Item No 3350-M-NC-124 to 3350-M-NC-127 Name / Specification MES Network Cabinet QTY 4 Result A Remark

Applicable Specification / Drawings Document Name


Inspection and Test plan FAT Procedure for MES Network Bill of Material System Drawing General Arrangement & Outline Drawings Termination Drawing Wiring Diagram

Document No.
MD-451-0000-IN-01415-00015 MD-451-0000-IN-01415-00008 MD-451-0000-IN-01415-00005 MD-451-0000-IN-01415-00007 MD-451-0000-IN-01415-00010 MD-451-0000-IN-01415-00011 MD-451-0000-IN-01415-00012

Rev.
0 A 0 A A A A

Dated
17 Dec 12 29 Nov 12 06 Dec 12 29 Nov 12 29 Nov 12 29 Nov 12 29 Nov 12

Inspection Documents: acc. to Clients - Inspection notification By Mail GL Scope of Inspection QAP NO.: MD-451-0000-IN-01415-00015

Rev. 0

dated: 17 Dec 12

Page: 1 of 8

Inspection Report: - . R-4500101415-0-04

Scope of Inspection: - Witness the FAT inspection of MES Network Inspection Details: Based on the Notification of Inspection the below signed surveyor attended the inspection on 10th June 2013 at M/s. Vector Info Tech Pte Ltd, Blk 3015A, Ubi Road 1, #07-08, Singapore for the Witness of FAT for MES Network Cabinets. Description of Inspection: Dimensional Inspection was carried out for the MES Network Panel as per General Arrangement Drawing. Visual inspection was carried out for equipments, painting surface, cable entries, Breakers, cables termination, Lightings, Ventilation and equipment tag as per GA drawing and found Missing Equipment tag in All panels. Vendor to be fixed the missing tag before shipment. Equipment Quantity /Type / Model was verified as per the GA Drawing & BOM List. Cable termination and tagging was checked as per Wiring Diagram, modifications have to be Updated in Drawing as per as built. Witnessed -Performing System Power up sequence verified as per FAT procedure. Earthing test was not carried out as vendor hasnt provided Earthing for Front door, rear door, & Cabinet Roof. The same was noted in the punch list and advised vendor to clear before shipping System Functionality & Operation Test was carried out as per the FAT procedure. Redundancy test was carried out for Server Room Lan switch (CISCO 4500E) & Ele.Room Lan Switch ( Cisco-Catalyst 3750-X series) Network Ready for Use Test (NRFU) was carried out as per the FAT procedure for Hardware Test, Operation System Tests, Connectivity test & Logical Tests. All Observations were noted in Punch List. Vendor did not provide the Product Data Sheet (MD-451-0000-IN-01415-0006) at time of inspection.

Page: 2 of 7

Inspection Report: - . R-4500101415-0-04

Result of Inspection:

There were no reasons for objection, With objection, see Punch List attached with FAT Report.

Status of Items (acc. to P.O.):

complete Released for export packing

not complete ready for shipment not complete no

Purchase Order Status: Further Inspections: Associated Documents: -

complete yes (TBA)

FAT Test Report with Punch list

Place: Singapore Date: 10-June-2013

Note: This Inspection Report is not an authorization to dispatch the item(s). The item(s) can be dispatched only after the issue of a valid release note duly authorized by us. We are not responsible for any damages of the item(s) subsequent to the inspection due to handling during packing, loading/unloading, transit etc.

(K. Vinothan) Inspector to Germanischer Lloyd (Printed/signature/stamp)

Photos:

Cabinet Nameplate Verification

Page: 3 of 7

Inspection Report: - . R-4500101415-0-04

Cabinet Nameplate Verification

Dimensional Inspection

Dimensional Inspection

Page: 4 of 7

Inspection Report: - . R-4500101415-0-04

Cabinet Lighting Test

Network Ping Test

Network Ping Test Punch List Photos:

Doors are not grounded

Breaker Tag missing and Unused space left opened

Page: 5 of 7

Inspection Report: - . R-4500101415-0-04

No Eye Bolt and Side panels

Side panels and plinth plates not grounded

Page: 6 of 7