W Line

Semi-hermetic water-cooled condensing units

For more free Copeland literature please visit

www.HVACRinfo.com

Product Information
Horsepower:
Temperature Applications:
Refrigerants:
Installation Applications:

3/4 40
Low/Medium/High
R-134a, R-404A, R-22
A variety of applications including
walk-in boxes and industrial air dryers

Nomenclature Semi-Hermetic Condensing Units


Compressor Motor Types

Receiver Base
Flat Metal Base
Water
Condenser Base
Transport Unit

C
E, D
W
T

Temperature Application
Description
Code
High Temperature
H
Medium Temperature
M
Low Temperature
L
Extended Medium Temp.
F
Extra Low Temp.
E
High Temperature
B
R22/404A LT & R134a HT
G
R22 HT & R404A MT
J
R404A LT & R134a HT
K
Two Stage
U
Two Stage
T

Phase

Description

Code

Capacitor Run Capacitor Start

Induction Run Capacitor Start

Induction Run Split Phase

Capacitor Run Permanent


Split Capacitor

Three Phase

Wye (star) Delta

6 Lead Part Winding or Across


the Line except 575V

Product Variations
Numbers will be assigned as follows:
1. Number 100 is standard compressor used
in Copeland condensing units.
2. Number 200 indicates a STANDARD compressor parts B/M and model no.
3. Number 201 and larger will be assigned for
all other variations of a given model.
4. Number 800 indicates a standard replacement compressor and Component Parts B/M
and model no. 240 volt control.
5. Number 801 indicates a standard replacement compressor and component parts B/M
and model no. 120 volt control.

X X X X - X X X X - X X X - X X X
Refrigerant
R404A/507
J/4
R134a
T/2
R12
B/7
R22
3/M/L/C
Multiple
F
R22/407C
G
R22
9
R134a/404A/22
N
R134a/404A
P
R404A/22
8
Air Cooled Steel Base
Air Cooled Copevap Base
Water Cooled Steel Base
Custom Base
Discus

A
E
W
C
D

Comp. Motor
Rating
Nominal Code
(HP)
0050
1/2
0075
3/4
0100
1
0150
1-1/2
0200
2
0300
3
0400
4
0500
5
0600
6
7-1/2
0750
0900
9
1000
10
1500
15
2000
20
2200
22
2500
25
2700
27
3000
30
40
4000
5000
50
6000
60
7000
70
8000
80

Electrical Codes

Compressor Motor Protection


Type Protection

60 Hz.

Code

External Inherent ProtectionOne Protector, (Line Break)


Use with Contactor

Internal Inherent ProtectionOne Protector (Line Break)


Use with Contactor

Internal Thermal ProtectorsElectronic Sensors; and


Control Module External
Use with Contactor

115-1
230-1
208/230-3
460-3
575-3
208/230-1
-

50 Hz.
100-1
200/220-3
230-1
380/420-3
200-1
220-3
220/240-1

Code
A
B
C
D
E
G
M
V
W
Z

Note: When applicable, specific 50


Hz ratings (not necessarily identical
to typical shown above) will be shown
as alternate on 60 Hz rated models.

Note: Left position may


be a letter indicating a
revision change

Semi-hermetic water-cooled condensing units


Features

Benefits

Copeland Semi-hermetic Compressor

Reliability

Copeland Discus Compressor with


Unique Discus Valve Design

High Energy Efficiency

Modular Components

Replacement Serviceability

Positive Displacement Oil Pump

Oil Lubrication Under All Operating Conditions


Lower Service & Maintenance Cost

Low Re-expansion Volumes

Decreases Energy Costs


Greater Capacity

Lower Operating Speeds

Reduces Operating Component Stress


Low Sound
Lower Maintenance Costs

Wide Range of Available Models from 3 HP to 40 HP


For HCFC and HFC Refrigerants

Application Flexibility

Resources and Support

Application Engineering Bulletins

EmersonClimate.com

AE5-1174 Water Flow Requirement and Water Pressure


Drop for Copeland Water-Cooled Condensing
Units

Online Product Information and Technical Data


Application Engineering Bulletins

AE4-1135 Cooling Requirements for Copelametic and


Copeland Discus Compressors

Instruction Sheets
Marketing Brochures
Where to Buy

For more information, visit EmersonClimate.com and login to the Customer Portal to view Online Product Information

2011DS-4 _W (4/11)

Emerson Climate Technologies

Semi-hermetic water-cooled condensing units


Capacity Data

HIGH/MED TEMP
Model
W2WM-0075-CAV, TAC
WJWM-0075-CAV, TAC
W2WH-0075-TAC
WTWH-0075-CAV
W3WM-0100-CAV, TAC, TAD
WJWM-0100-TAC
W2WH-0100-CAV, TAC, TAD
WTWH-0100-CAV, TAC
WJWM-0152-TAC
W2WH-0151-CAV, TAC, TAD
WTWH-0151-CAV, TAC
W3WM-0201-CAV, TAC, TAD
WJWM-0202-TAC
WJWM-0203-TAC, TAD
W2WH-0201-CAB, TAC, TAD
WTWH-A201-CAV, TAC, TAD
WJWM-0300-TAC, TAD
W2WH-0300-CAB, TAC, TAD
WTDH-0301-TFC, TFD
W3DD-0504-TFD
WJDM-0502-TFC, TFD
WTDH-0601-TFD
W3DD-0752-TFC, TFD
WJDM-0751-TFC, TFD
WTDH-0751-TFD
W3DD-1003-TFC, TFD
WJDM-1001-TFC, TFD
W3DD-1502-TFC, TFD
W3DD-2002-TSD
W3DD-2502-TSC, TSD
W3DD-3002-TSC, TSD
W3DD-3502-TSD
W3DD-4001-TSD

Capacity (BTU/Hr) at 75 Inlet Water - Evaporator Temp (F)


BOM

Refrig.

H.P.

-5

+5

+10

+15

001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001

22
404A
22
134a
22
404A
22
134a
404A
22
134a
22
404A
404A
22
134a
404A
22
134a
22
404A
134a
22
404A
134a
22
404A
22
22
22
22
22
22

3/4
3/4
3/4
3/4
1
1
1
1
1-1/2
1-1/2
1-1/2
2
2
2
2
2
3
3
3
5
5
6
7-1/2
7-1/2
7-1/2
10
10
15
20
25
30
35
40

3680
3140

4260
3670
3450
3370
5730
5650
5050
4140
6470
6390
5960
8690
9750
11600
2960
8360
17000
14800
19600
23100
25800
24500
39400
46600
34600

4880
4270
3980
3910
6700
6410
5800
4890
7650
7270
7040
10200
11000
13300
5420
9880
19400
17100
22700
27000
29500
28300
46100
52500
40100

65600

73700

84800

96500

129000

147100

199200

225300

5550
4940
4570
4510
7750
7210
6640
5700
8640
8310
8210
11700
12300
15100
7890
11500
22000
19700
26100
31300
33600
32500
53100
58900
46100
75990
82600
102930
109400
142900
167200
209000
253700

6290
5660
5230
5160
8890
8090
7570
6580
9740
9510
9470
13400
13800
17100
10400
13300
24800
22400
29700
35800
38100
37100
60400
66000
52500
85930
92200
116170
123700
160200
189200
235300
284500

LOW TEMP

4890

5860

7260
8440
10000

14800

22500
33000
41300

58100

Capacity (BTU/Hr) at 75 Inlet Water - Evaporator Temp (F)

Model

BOM

Refrig.

H.P.

-40

-35

-30

-25

-20

WJWL-0100-CAV, TAC, TAD

001

404A

2300

2800

3360

3980

4660

WJWL-0151-CAV, TAC, TAD

001

404A

3450

4200

5020

5920

6900

WJWL-A201-CAV, TAC, TAD

001

404A

4440

5460

6580

7810

9170

WJDL-0302-TFC, TFD

050

404A

9950

12100

14400

17000

19800

WJDL-0401-TFC, TFD

050

404A

12360

14900

17660

20700

24020

WJDL-0603-TFC, TFD

050

404A

18090

21350

24950

28920

33280

WJDL-0751-TFC, TFD

050

404A

21470

25470

29750

34390

39440

WJDL-0901-TFC, TFD

050

404A

26180

30920

36130

41850

48130

WJDL-1001-TFC, TFD

050

404A

10

29850

35220

41090

47500

54480

WJDL-1501-TSC, TSD

050

404A

15

41400

49300

57400

65800

74800

WJDL-2701-TSD

050

404A

27

59500

70700

83200

96900

121700

Performance data at 105 ambient subcooling 5 F


Return gas temperature 65 F; Condenser water inlet temperature 85 F; Water temperature difference 10 F

2011DS-4 _W (4/11)

Emerson Climate Technologies

Semi-hermetic water-cooled condensing units


Capacity Data

HIGH/MED TEMP
Model
W2WM-0075-CAV, TAC
WJWM-0075-CAV, TAC
W2WH-0075-TAC
WTWH-0075-CAV
W3WM-0100-CAV, TAC, TAD
WJWM-0100-TAC
W2WH-0100-CAV, TAC, TAD
WTWH-0100-CAV, TAC
WJWM-0152-TAC
W2WH-0151-CAV, TAC, TAD
WTWH-0151-CAV, TAC
W3WM-0201-CAV, TAC, TAD
WJWM-0202-TAC
WJWM-0203-TAC, TAD
W2WH-0201-CAB, TAC, TAD
WTWH-A201-CAV, TAC, TAD
WJWM-0300-TAC, TAD
W2WH-0300-CAB, TAC, TAD
WTDH-0301-TFC, TFD
W3DD-0504-TFD
WJDM-0502-TFC, TFD
WTDH-0601-TFD
W3DD-0752-TFC, TFD
WJDM-0751-TFC, TFD
WTDH-0751-TFD
W3DD-1003-TFC, TFD
WJDM-1001-TFC, TFD
W3DD-1502-TFC, TFD
W3DD-2002-TSD
W3DD-2502-TSC, TSD
W3DD-3002-TSC, TSD
W3DD-3502-TSD
W3DD-4001-TSD

Capacity (BTU/Hr) at 75 Inlet Water - Evaporator Temp (F)


BOM

Refrig.

H.P.

+20

+25

001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001
001

22
404A
22
134a
22
404A
22
134a
404A
22
134a
22
404A
404A
22
134a
404A
22
134a
22
404A
134a
22
404A
134a
22
404A
22
22
22
22
22
22

3/4
3/4
3/4
3/4
1
1
1
1
1-1/2
1-1/2
1-1/2
2
2
2
2
2
3
3
3
5
5
6
7-1/2
7-1/2
7-1/2
10
10
15
20
25
30
35
40

7110
6450
5960
5860
10100
9090
8590
7540
11000
10900
10900
15100
15400
19200
13000
15200
27800
25500
33700
40800
43100
42200
68200
73700
59600
96610
102800
130360
139400
178800
213200
263500
317900

8040
7280
6750
6620
11400
10260
9700
8580
12400
12300
12400
17000
17400
21600
15700
17300
31200
28800
38100
46100
48510
47700
76500
82100
67300
108090
114200
145600
156600
198900
239100
293900
353900

LOW TEMP

+30

+35

+40

+45

7610
7440

8550
8330

9570
9270

10700
10280

10900
9730

12200
11000

13600
12400

15000
13900

14000
14000

15700
15800

17600
17800

19600
20000

18600
19700

21600
22200

24800
25000

28200
28000

32400
42900
51900

36200
48100
58100

40400
53800
64900

44900
60100
72200

53700
85400

60400
95000

67600
105400

75400
116500

75800
120430

85000
133700

95200
147950

106300
163240

161970
175600
220700
266800
326800
392600

179560
196400
244500
296300
362500
434100

198450
219200
270400
327600
401400
478600

218750
244000
298700
360600
443900
526000

Capacity (BTU/Hr) at 75 Inlet Water - Evaporator Temp (F)

Model

BOM

Refrig.

H.P.

-15

-10

-5

WJWL-0100-CAV, TAC, TAD

001

404A

5420

6250

7170

8180

WJWL-0151-CAV, TAC, TAD

001

404A

7960

9130

10410

11800

WJWL-A201-CAV, TAC, TAD

001

404A

10700

12300

14100

16100

WJDL-0302-TFC, TFD

050

404A

22900

26300

30100

34200

WJDL-0401-TFC, TFD

050

404A

27660

31640

36000

40760

WJDL-0603-TFC, TFD

050

404A

38060

43300

49020

55260

WJDL-0751-TFC, TFD

050

404A

44980

51090

57810

65240

WJDL-0901-TFC, TFD

050

404A

55040

62620

70920

80010

WJDL-1001-TFC, TFD

050

404A

10

62050

70250

79120

88680

WJDL-1501-TSC, TSD

050

404A

15

84400

94800

106600

119600

WJDL-2701-TSD

050

404A

27

127800

145000

163400

183000

Performance data at 105 ambient subcooling 5 F


Return gas temperature 65 F; Condenser water inlet temperature 85 F; Water temperature difference 10 F

2011DS-4 _W (4/11)

Emerson Climate Technologies

Semi-hermetic water-cooled condensing units


Physical/Electrical Data

HIGH/MED TEMP
Model

Comp

W2WM-0075-CAV, TAC
WJWM-0075-CAV, TAC
W2WH-0075-TAC
WTWH-0075-CAV
W3WM-0100-CAV, TAC, TAD
WJWM-0100-TAC
W2WH-0100-CAV, TAC, TAD
WTWH-0100-CAV, TAC
WJWM-0152-TAC
W2WH-0151-CAV, TAC, TAD
WTWH-0151-CAV, TAC
W3WM-0201-CAV, TAC, TAD
WJWM-0202-TAC
WJWM-0203-TAC, TAD
W2WH-0201-CAB, TAC, TAD
WTWH-A201-CAV, TAC, TAD
WJWM-0300-TAC, TAD
W2WH-0300-CAB, TAC, TAD
WTDH-0301-TFC, TFD
W3DD-0504-TFD
WJDM-0502-TFC, TFD
WTDH-0601-TFD
W3DD-0752-TFC, TFD
WJDM-0751-TFC, TFD
WTDH-0751-TFD
W3DD-1003-TFC, TFD
WJDM-1001-TFC, TFD
W3DD-1502-TFC, TFD
W3DD-2002-TSD
W3DD-2502-TSC, TSD
W3DD-3002-TSC, TSD
W3DD-3502-TSD
W3DD-4001-TSD

KWE2-0075
KWNB-007E
KWN2-0075
KWMB-007E
KWM2-0100
KWRA-010E
KWR2-0100
KWJB-010E
KWGA-010E
KWGB-0150
KWLB-015E
KWKB-0200
KWKA-020E
ERCA-021E
ERA2-0200
EAVB-021E
ERFA-031E
ERF2-0310
2DF3F16KE
2DC3R53K0
2DC3R53KE
2DA3F23KE
2DA3R89KE
2DA3R89KE
3DB3F33KE
3DB3R12ME
3DB3R12ME
3DS3R17ME
4DA3R18M0
4DH3R22M0
4DJ3R28M0
6DH3A3500
6DJ3A4000

22
404A
22
134a
22
404A
22
134a
404A
22
134a
22
404A
404A
22
134a
404A
22
134a
22
404A
134a
22
404A
134a
22
404A
22
22
22
22
22
22

LOW TEMP
Model

Comp

Refrig.

WJWL-0100-CAV, TAC, TAD


WJWL-0151-CAV, TAC, TAD
WJWL-A201-CAV, TAC, TAD
WJDL-0302-TFC, TFD
WJDL-0401-TFC, TFD
WJDL-0603-TFC, TFD
WJDL-0751-TFC, TFD
WJDL-0901-TFC, TFD
WJDL-1001-TFC, TFD
WJDL-1501-TSC, TSD
WJDL-2701-TSD

KWJB-010E
KWLB-015E
EAVB-021E
2DF3F16KE
2DL3F20KE
3DA3F-28KE
3DB3F33KE
3DF3F40KE
3DS3F-46KE
4DL3F-63KE
6DL3F-93KE

Refrig.

Overall Dimensions
(In)
L

404A
404A
404A
404A
404A
404A
404A
404A
404A
404A
404A

28.6
14.5
17.0
28.6
14.5
17.0
28.6
14.5
17.0
28.6
14.5
17.0
28.6
14.5
17.0
28.6
14.5
17.0
28.6
14.5
17.0
28.6
14.5
17.0
34.8
14.5
17.0
34.8
14.5
17.0
34.8
14.5
17.0
34.8
14.5
17.7
34.8
14.5
17.7
34.0
14.5
20.4
34.0
14.5
20.4
35.6
14.5
20.4
30.0
17.0
24.0
30.0
17.0
24.0
39.9
17.0
28.0
39.9
17.0
28.0
40.0
17.0
28.0
39.9
17.0
28.0
46.0
17.0
38.6
46.0
17.0
38.6
46.0
17.0
30.7
52.0
17.0
30.6
52.0
17.0
30.6
52.0
18.0
32.6
64.0
20.2
34.3
64.5
20.5
34.3
64.5
20.5
34.3
77.5
22.4
34.0
89.5
21.4
36.0
Overall Dimensions
(In)

Connecting
Lines
Suction

Liquid

Base Mounting
Centers
Length

Width

3/8 S
5/8 S
3/8 S
5/8 S
3/8 S
5/8 S
3/8 S
5/8 S
3/8 S
5/8 S
3/8 S
5/8 S
3/8 S
5/8 S
3/8 S
5/8 S
3/8 S
7/8 S
3/8 S
7/8 S
3/8 S
7/8 S
3/8 S
7/8 S
3/8 S
7/8 S
3/8 S
7/8 S
3/8 S
7/8 S
3/8 S
7/8 S
1/2 S
1-18 S
1/2 S
1-1/8 S
1/2 S
1-1/8 S
1/2 S
1-3/8 S
1/2 S
1-3/8 S
1/2 S
1-3/8 S
5/8 S
1-3/8 S
5/8 S
1-3/8 S
5/8 S
1-3/8 S
7/8 S
1-3/8 S
7/8 S
1-3/8 S
1-1/8 S 1-5/8 S
1-1/8 S 1-5/8 S
1-1/8 S 1-5/8 S
1-1/8 S 2-1/8 S
1-1/8 S 2-1/8 S
1-5/8 S 2-1/8 S
Connecting
Lines

14
13
14
12
14
13
14
13
14
13
14
12
14
13
14
13
18
13
18
13
18
13
18
13
18
13
18
13
18
13
18
13
18
16
18
16
25
16
25
16
25
16
25
16
25
16
25
16
25
16
38
16
38
16
38
16
38
16
38
16
38
17
38
18
38
18
Base Mounting
Centers

Condenser Water
Connections
In

Out

3/8 MPT
1/2 FPT
3/8 MPT
1/2 FPT
3/8 MPT
1/2 FPT
3/8 MPT 21/2 FPT
3/8 MPT
1/2 FPT
3/8 MPT
1/2 FPT
3/8 MPT
1/2 FPT
3/8 MPT 21/2 FPT
3/8 MPT
1/2 FPT
3/8 MPT
1/2 FPT
3/8 MPT 21/2 FPT
3/8 MPT
1/2 FPT
3/8 MPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1-1/4 FPT 1-1/4 FPT
1-1/4 FPT 1-1/4 FPT
1-1/4 FPT 1-1/4 FPT
1-1/4 FPT 1-1/4 FPT
1-1/4 FPT 1-1/4 FPT
1-1/4 FPT 1-14 FPT
1-1/4 FPT 1-1/4 FPT
1-1/4 FPT 1-1/4 FPT
1-1/4 FPT 1-1/4 FPT
1-1/4 FPT 1-1/4 FPT
1-1/4 FPT 1-1/4 FPT
1-1/2 FPT 1-1/2 FPT
2 FPT
2 FPT
2 FPT
2 FPT
2 FPT
2 FPT
2-1/2 FPT 2-1/2 FPT
2-1/2 FPT 2-1/2 FPT
Condenser Water
Connections

Suction

Liquid

Length

Width

In

Out

27
35
35
40
40
46
46
52
52
52
65

15
15
15
17
17
17
17
17
17
19
22

18
17
20
37
37
39
39
39
39
38
43

3/8 S
3/8 S
3/8 S
1/2 S
1/2 S
5/8 S
5/8 S
7/8 S
7/8 S
1-1/8 S
1-1/8 S

5/8 S
7/8 S
7/8 S
1-1/8 S
1-3/8 S
1-3/8 S
1-3/8 S
1-3/8 S
1-3/8 S
1-5/8 S
2-1/8 S

14
18
18
25
25
25
25
38
38
38
38

13
13
13
16
16
16
16
16
16
16
16

3/8 MPT
3/8 MPT
1/2 NPT
1-1/4 FPT
1-1/4 FPT
1-1/4 FPT
1-1/4 FPT
1-1/4 FPT
1-14 FPT
1-1/2 FPT
2 FPT

1/2 FPT
1/2 FPT
1/2 NPT
1-1/4 FPT
1-1/4 FPT
1-1/4 FPT
1-1/4 FPT
1-1/4 FPT
1-1/4 FPT
1-1/2 FPT
2 FPT

Performance data at 105 ambient subcooling 5 F


Return gas temperature 65 F; Condenser water inlet temperature 85 F; Water temperature difference 10 F

2011DS-4 _W (4/11)

Emerson Climate Technologies

Semi-hermetic water-cooled condensing units


Physical /Electrical Data

HIGH/MED TEMP
Model

Comp

W2WM-0075-CAV, TAC
WJWM-0075-CAV, TAC
W2WH-0075-TAC
WTWH-0075-CAV
W3WM-0100-CAV, TAC, TAD
WJWM-0100-TAC
W2WH-0100-CAV, TAC, TAD
WTWH-0100-CAV, TAC
WJWM-0152-TAC
W2WH-0151-CAV, TAC, TAD
WTWH-0151-CAV, TAC
W3WM-0201-CAV, TAC, TAD
WJWM-0202-TAC
WJWM-0203-TAC, TAD
W2WH-0201-CAB, TAC, TAD
WTWH-A201-CAV, TAC, TAD
WJWM-0300-TAC, TAD
W2WH-0300-CAB, TAC, TAD
WTDH-0301-TFC, TFD
W3DD-0504-TFD
WJDM-0502-TFC, TFD
WTDH-0601-TFD
W3DD-0752-TFC, TFD
WJDM-0751-TFC, TFD
WTDH-0751-TFD
W3DD-1003-TFC, TFD
WJDM-1001-TFC, TFD
W3DD-1502-TFC, TFD
W3DD-2002-TSD
W3DD-2502-TSC, TSD
W3DD-3002-TSC, TSD
W3DD-3502-TSD
W3DD-4001-TSD

KWE2-0075
KWNB-007E
KWN2-0075
KWMB-007E
KWM2-0100
KWRA-010E
KWR2-0100
KWJB-010E
KWGA-010E
KWGB-0150
KWLB-015E
KWKB-0200
KWKB-021E
ERCA-021E
ERA2-0200
EAVB-021E
ERFA-031E
ERF2-0310
2DF3F16KE
2DC3R53K0
2DC3R-53KE
2DA3F23KE
2DA3R89KE
2DA3R89KE
3DB3F33KE
3DB3R12ME
3DB3R12ME
3DS3R17ME
4DA3R18ME
4DH3R22ME
4DJ3R28ME
6DH3R35ME
6DJ3A40ME

22
404A
22
134a
22
404A
22
134a
404A
22
134a
22
404A
404A
22
134a
404A
22
134a
22
404A
134a
22
404A
134a
22
404A
22
22
22
22
22
22

LOW TEMP
Model

Comp

Refrig.

WJWL-0100-CAV, TAC, TAD


WJWL-0151-CAV, TAC, TAD
WJWL-A201-CAV, TAC, TAD
WJDL-0302-TFC, TFD
WJDL-0401-TFC, TFD
WJDL-0603-TFC, TFD
WJDL-0751-TFC, TFD
WJDL-0901-TFC, TFD
WJDL-1001-TFC, TFD
WJDL-1501-TSC, TSD
WJDL-2701-TSD

KWJB-010E
KWLB-015E
EAVB-021E
2DF3F16KE
2DL3F20KE
3DA3F28KE
3DB3F33KE
3DF3F40KE
3DS3F46KE
4DL3F63KE
6DL3F93KE

Minimum Circuit Ampacity Max Fuse Size

Refrig.

230-1-60
6.8
7.6
9
9.4

15
15
15
15

9.3
9

15
15

12
12
13.3

20
20
20

13
19
21.3

230-3-60
4.3
3.8
4.4
5.8
5.6
5.4
5.4
5.8
6
6.9
8.3
8.5
8.5
11
8.3
9.9
15.5
14.6
21

8.6
12.4
19

15

15

15

15

4
4
5
7
35
8
10
13
28
50
13
13
40
70
18
40
70
18
20
55
90
25
55
90
25
80
125
36
41
103
175
51
118
200
59
67
89
Minimum Circuit Ampacity Max Fuse Size
20
30

230-1-60
404A
404A
404A
404A
404A
404A
404A
404A
404A
404A
404A

15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
25
25
35

460-3-60

230-3-60

15
20
30

6
8
10
22
34
39
39
50
53
67

15
15
15
35
50
60
70
80
90
110

15
15
15
15
15
15
20
20
20
30
30
35
45
45
60
70
90
100
110
150

460-3-60
3
4
5
11
14
18
21
22
24
34
51

15
15
15
15
20
30
35
35
40
50
90

Pump
Down
Capacity
(lbs)
26
23
26
27
26
23
14
14
28
28
33
35
31
31
32
36
35
41
69
70
59
69
129
112
130
144
125
202
258
247
248
293
293
Pump
Down
Capacity
(lbs)
12
28
31
59
59
112
112
125
125
153
216

Ship
Weight
(lbs)
166
174
166
178
170
209
170
176
178
225
220
225
225
270
294
311
326
330
492
514
501
511
564
590
634
708
670
935
1160
1233
1160
1357
1522
Ship
Weight
(lbs)
177
218
314
501
513
651
655
500
743
865
1195

Performance data at 105 ambient subcooling 5 F


Return gas temperature 65 F; Condenser water inlet temperature 85 F; Water temperature difference 10 F

2011DS-4 _W (4/11)

Emerson Climate Technologies

2011DS-4_W (4/11) Emerson and Copeland are trademarks of Emerson Electric Co. or one of its affiliated companies. 2011 Emerson Climate Technologies, Inc. All rights reserved. Printed in the USA