Rated voltage Rated current Rated breaking current Installation 123-170 kV 3150 A 40 kA Outdoor/Indoor
Standard equipment
LTB Compact include all functions performed by a traditional circuit breaker bay. A standard LTB Compact consists of the following HV equipment: Circuit breaker LTB circuit breaker with BLK mechanism. Trolley Truck with type BCM-F motor operating mechanism or type BCH-F manual operating mechanism. Fixed contacts Gantry support for the xed contacts.
Optional equipment
In addition to the standard equipment, the LTB Compact can also be supplied with the following optional equipment: Current transformers: IMB (123-170 kV) conventional oil insulated current transformers. Voltage transformers: CPA/CPB (123-170 kV) conventional oil insulated capacitor voltage transformers. Brackets for mounting IMB, CPA/CPB on the circuit breaker frame can also be supplied. NVA Earthing switch. PEXLIM Polymeric insulated Surge arrester SWITCHGUARD condition monitoring unit including optional provisions for remote supervision. SWITCHSYNC relay for synchronizing circuit breaker close and/or open operations for switching of capacitor banks, reactors, transformers and long overhead lines. SWITCHCONTROL process bus interface for control of circuit breaker and disconnector functions. In addition to standard circuit breaker and disconnector control functions, SWITCHCONTROL can include the functions of both the SWITCHGUARD and the SWITCHSYNC.
Design
The base of the design is a truck mounted, standard ABB auto puffer circuit breaker. LTB Compact uses a three pole operated type LTB circuit breaker equipped with one (1) type BLK motor charged spring operating mechanism. The BLK mechanism is enclosed in a corrosion resistant housing rated IP 55 and is attached to the pole beam. LTB Compact includes a disconnector function which allows the circuit breaker to be maintained while it is either withdrawn or fully removed. Disconnector function is achieved by withdrawing the truck mounted circuit breaker from the xed contacts. Movement of the circuit breaker on the truck is provided via a standard ABB disconnector operating mechanism. Either the BCM-F motor operating mechanism or BCM-H manual operating mechanism can be used. Fixed contacts provided are part of the busbar system with no need for maintenance.
Benets
High availability...
Due to...
... no or few traditional disconnectors required. ... fast, easy replacement of the circuit breaker unit. ... optional condition monitoring.
... predictive maintenance via optional condition monitoring and self diagnostics. ... maintenance free xed contacts.
... no or few traditional disconnectors required. ... optional compact design including integrated instrument transformers.
... reduced maintenance work in the switchyard. ... pre-fabricated and pre-tested Switchgear Modules. ... reduced civil work and less switchyard material
Values complying with IEC 56 (50 Hz and 60 Hz) and ANSI C37 (60 Hz) 1) Other values on request 2) Tolerances according to IEC 233.
ABB Power Technology Products AB High Voltage Products SE-771 80 LUDVIKA, Sweden Tel +46 240 78 20 00 Fax +46 240 78 36 50 Internet:www.abb.com
3800 3800 4887 mm 4335 4335 5550 mm 3150 A 31.5/40 kA 1.5 79/100 kA 85/108 kA 3s 40 ms 20 ms 40 ms 300 ms 20 cycles O-0,3 sec-CO-3 min-CO CO-15 sec-CO
Prodouced by HVP/MD AO