Professional Documents
Culture Documents
Scure Premier
Scure Premier
The original member of the family, Premier is a full four-quadrant metering platform for use in deregulated markets where data storage, multi-utility and AMR facilities are important. A costeffective solution for CT/VT-operated applications, Premier combines AMR capability with the reliability of CALMU technology, providing an optimum metering solution.
Applications
? CT/VT-operated industrial and commercial billing
Features
? True four-quadrant measurement ? Time-of-use tariffs and maximum demands ? Logging of multi-parameter load survey, billing data and
purpose
? Three-phase LV or HV circuits ? Substation monitoring ? Multi-utility energy accounting
Benefits
? Compact and accurate ? Reliable and flexible in use ? Easy to install; wiring faults can be diagnosed from
communication
? Programmable pulse outputs ? Option for pulse inputs for logging external devices for
instantaneous parameters
? Easy to integrate into an AMR system
Premier
Technical specifications
Electrical Connection type Wiring configuration Voltage range Applicable to both LV and HV Current range Accuracy Mains frequency Burden Insulation class Impulse withstand Compliance Standards Mechanical Dimensions (W x H x D) Weight Enclosure Terminals Environmental Ingress protection Temperature Humidity Features Tariff Maximum demand Load survey Communication Pulse I/O (optional) Up to 8 rates Up to 2, configurable in 4 registers 120 parameter-days (up to 4 channels with 30 days each) with 30-minute integration period. Options for 15/60 minute integration periods PACT port, RS-232 port (25-pin D-sub) Up to 2 inputs and 4 outputs IP 51 -10 C to +55 C (operating) -25 C to +70 C (storage) 95% non-condensing 175 x 250 x 55 mm 1.5 kg (approx.) Engineering plastic Nickel-plated brass terminals, with two screws per conductor IEC62052-11, IEC 62053-21, IEC62053-22 LV CT-operated 3-phase 4-wire 240/230 V (L-N) HV CT/VT-operated 3-phase 3-wire, 3-phase 4-wire 110 V (L-L), 63.5 V (L-N)
5-6 A, 1-1.2 A Class 0.5s, 1.0 50 Hz 5% Voltage : < 1.0 W and < 1.5 VA per phase Current: < 0.1 VA per phase Protection class II 6 kV