Busbar Calculation: Design Rules
Busbar Calculation: Design Rules
Busbar calculation
Choose your cross-section S, linear mass m, modulus of inertia I/v, moment of inertia I for the bars defined below: Busbar dimensions (mm)
S cm2 m Cu daN/cm A5/L I
x' x
Arrangement*
x
100 x 10 10 0.089 0.027 0.83 1.66 83.33 16.66 21.66 14.45 166.66 33.33 82.5 33 250 50
80 x 10 8 0.071 0.022 0.66 1.33 42.66 10.66 17.33 11.55 85.33 21.33 66 26.4 128 32
80 x 6 4.8 0.043 0.013 0.144 0.48 25.6 6.4 3.74 4.16 51.2 12.8 14.25 9.5 76.8 19.2
80 x 5 4 0.036 0.011 0.083 0.33 21.33 5.33 2.16 2.88 42.66 10.66 8.25 6.6 64 16
80 x 3 2,4 0.021 0.006 0.018 0.12 12.8 3.2 0.47 1.04 25.6 6.4 1.78 2.38 38.4 9.6
50 x 10 5 0.044 0.014 0.416 0.83 10.41 4.16 10.83 7.22 20.83 8.33 41.25 16.5 31.25 12.5
50 x 8 4 0.036 0.011 0.213 0.53 8.33 3.33 5.54 4.62 16.66 6.66 21.12 10.56 25 10
50 x 6 3 0.027 0.008 0.09 0.3 6.25 2.5 2.34 2.6 12.5 5 8.91 5.94 18.75 7.5
50 x 5 2.5 0.022 0.007 0.05 0.2 5.2 2.08 1.35 1.8 10.41 4.16 5.16 4.13 15.62 6.25
cm4 cm3 cm4 cm3 cm4 cm3 cm4 cm3 cm4 cm3 cm4 cm3
I/v I
x' x
I/v I
x' x
I/v I
x' x
I/v I
x' x
I/v I
x'
I/v
f E
: :
resonant frequency in Hz modulus of elasticity: for copper = 1.3 106 daN/cm2 for aluminium A5/L = 0.67 106 daN/cm2 linear mass of the busbar (choose the value on the table above) length between 2 supports or busducts daN/cm
cm
moment of inertia of the busbar cross-section relative to the axis x'x, perpendicular to the vibrating plane cm4 (see formula previously explained or choose the value in the table above)
giving
f=
Hz
We must check that this frequency is outside of the values that must be avoided, in other words between 42 and 58 and 80 and 115 Hz.
Schneider Electric Merlin Gerin MV design guide
29
Design rules
Busbar calculation
Exercise data
c Consider a switchboard comprised of at least 5 MV cubicles. Each cubicle has 3 insulators(1 per phase). Busbars comprising 2 bars per phase, inter-connect the cubicles electrically. Busbar characteristics to check:
S d l n ( - n) profile
Top view
Cubicle 1 Cubicle 2 Cubicle 3 Cubicle 4 Cubicle 5
: : : : : : :
busbar cross-section (10 1) phase to phase distance distance between insulators on the same phase ambient temperature permissible temperature rise
(90-40=50)
10 18 70 40 50
cm2 cm cm
C C
flat busbars in copper 1/4 hard, with a permissible strain = 1 200 daN/cm2 edge-mounted
material
arrangement:
d d
c The busbars must be able to withstand a rated current Ir = 2,500 A on a permanent basis and a short-time withstand current Ith = 31,500 A rms. for a time of tk = 3 seconds. c Rated frequency fr = 50 Hz c Other characteristics:
1 cm 1 cm
v parts in contact with the busbars can withstand a maximum temperature of max = 100C v the supports used have a bending resistance of F' = 1 000 daN
10 cm 5 cm
12 cm
30
Schneider Electric
Design rules
Busbar calculation
I=K
20 [1+ ( - 20)]
with:
I n ( - n) S p
e
: : : : : :
permissible current expressed in amperes (A) ambient temperature permissible temperature rise* busbar cross-section busbar perimeter resistivity of the conductor at 20C copper: 1.83 cm 40 50 10 22
C C
cm2 cm
20
0.004
K
e
condition coefficient product of 6 coefficients (k1, k2, k3, k4, k5, k6), described below
e/a
0.05 0.06 0.08 0.10 number of bars per phase 2 1.63 1.73 1.76 1.80 3 2.40 2.45 2.50 2.55 0.12 k1 1.83 2.60 1.85 2.63 1.87 2.65 1.89 2.68 1.91 2.70 0.14 0.16 0.18 0.20
0.1 2 1.80
Schneider Electric
31