626
Test Methods
Tests shall be carried out as prescribed in the appropriate clauses of IS : 3025-1964* and IS : 3550-1965! as indicated against the characteristics in Table 1.
TABLE 1: CHEMICAL REQUIREMENTS OF FEED WATER AND BOILER WATER FOR LOW AND MEDIUM PRESSURE BOILERS (Regulation 624 and 626)
Sl.. No.
CHARACTERISTIC
REQUIREMENT FOR BOILER PRESSURE ---------------------------------------Up to 2.0 MN/m2 2.1 to 3.9 MN/m2 4.0 to 5.9 MN/m2
i)
Feed Water Total hardness a) b) c) d) (as CaCO2 ),mg/l, Max pH value Dissolved Oxygen, mg/1, Max Silica (as SiO2), mg/l, Max 10 8.5 to 9.5 0.1 -1 8.5 to 9.5 0.02 5 0.5 8.5 to 9.5 0.01 0.5
ii)
Boiler Water Total hardness(of filteredsample) (as CaCO3), mg/l, Total alkalinitya(as CaCO3), mg/l,Max Caustic alkalinity (as CaCO3), mg/lMax pH value Residual sodi um sulphite (asNa2SO3) mg/l Residual hydrazine (as N2H4),mg/l
j b
a)
700
500
300
c) d) e)
60 10.5 to 11.0 --
f)
0.05 to 0.3
g)
Ratio Na2SO4/Caustic alkalinity (as NaOH) or Ratio NaNO3/ total alkalinity (as NaOH)
g)
Ratio Na2SO4/Caustic alkalinity (as NaOH) or Ratio NaNO3/ total alkalinity (as NaOH) Phosphates (asPO4), mg/l (if added )
h)
20 to 40
15 to 30
5 to 20
i) k)
3500s
2500
1500 15
Note 1- Recovery Boilers - The boiler feed water used shall be completely de-mineralized and also the boiler feed water and
boiler water shall be conditioned in accordance with high pressure boilers working at 60 kg/cm2 and above (see IS : 43431967**)
Note 2 - When feed water heaters are of copper or copper alloy constructions, the pH of the feed water shall be maintained between 8.5 and 9.2 while when feed water heaters are of iron constructions, the pH of the feed may be maintained between 8. and 9.5. Note 3 - Silica in Boiler Water - Lower concentration of silica may be advisable for steam of turbines, which generally requires less than 0.02 mg/l silica in steam
Note 1- Recovery Boilers - The boiler feed water used shall be completely de-mineralized and also the boiler feed water and
boiler water shall be conditioned in accordance with high pressure boilers working at 60 kg/cm2 and above (see IS : 43431967**)
Note 2 - When feed water heaters are of copper or copper alloy constructions, the pH of the feed water shall be maintained between 8.5 and 9.2 while when feed water heaters are of iron constructions, the pH of the feed may be maintained between 8. and 9.5. Note 3 - Silica in Boiler Water - Lower concentration of silica may be advisable for steam of turbines, which generally requires less than 0.02 mg/l silica in steam
METHOD OF TEST (Ref. to Cl. No. of) ------------------------IS : 35501965* IS : 3025-_ 1964!
--25 16
16.1 8 ---
--
16.1
--
13
----
15 8 21
26
--
--
20.2 and 15
--
20.2 and 15
--
48 and 13
14
--
9 16
12 30
nd also the boiler feed water and cm2 and above (see IS : 4343-
nd also the boiler feed water and cm2 and above (see IS : 4343-