Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Series "NP" & "RG" AIRFLO Burners

Page 5505

Performance Selection Data

Operation in shaded area requires special considerations

Opti

mu

sig m De

n Ar

ea

Operation in shaded area requires special considerations

Op

m imu

De

A ign

rea

5/88

Page 5506

Series "NP" & "RG" AIRFLO Burners


(cont'd.)

Performance Selection Data

m pti

um

De

sig

r nA

ea

Airstream velocity across and through your burner's mixing plates must be kept uniform and within desired limits by use of a silhouette profile plate through which the burner fires. A 6" (minimum) profile plate should be installed surrounding the interior duct walls at the leading edge of your burners mixing plates. Optimum design ranges for the various burner types are shown in the above graphs. Velocities (SFPM) are measured with a velometer directly in the duct at the plane of the profile plate and leading edge of burner mixing plates. To determine profile opening areas, add burner displacement areas (Ft2/section) from Table 1 for your complete burner assembly to "Net Free Area" of your duct: "Net Free Area" of Duct (Ft ) = Fan Volume (SCFM) Velocity (SFPM) Net Free Area (Ft2) + Burner Displacement (Ft2) = Profile Area (Ft2) Various duct size/profile area relationships may give slightly different field site data than is shown in Table 2. Velocities should always be confirmed and established by use of a velometer on actual field site installation.
2

Table 1: Burner Displacement (ft2/section)


Section 6" Straight 12" Straight 18" Straight 24" Straight 12" Back Inlet 36" Back Inlet 12" x 6" Tee 6" x 6" Elbow NP 0.25 0.50 0.75 1.00 0.50 1.20 0.60 0.45 RG 0.33 0.66 0.99 1.32 0.66 1.50 0.75 0.60

Inlet Feed Limitations: NP-I NP-II 1-1/4" end 4' 4' inlet flange 1-1/2" back 5' 5' inlets*

NP-III RG-IV 2000 4' KBtu/hr 4500 5' KBtu/hr

*Note: For 36 back inlet sections, not more than 6" off any one leg

Pilot Capacities: Nominally rated at 25,000 Btu/hr with natural gas differential pressures of 4-6" w.c.

Table 1: Velocity Factors


Desired velocity across burner at profile plate opening (SFPM) Appoximate velocity pressure reading at profile plate ("wc) 1600 1800 2000 2200 2400 2600 2800 3000 3250 3500 3750 4000 4500 5000 0.16 0.20 0.25 0.30 0.36 0.42 0.49 0.57 0.64 .077 .088 1.00 1.26 1.55

Series "NP" AIRFLO Burners

Page 5507

Approximate Envelope Dimensions


(Nominal, in Inches)

Burner Sections
(All burners shown are available in NP-I, II or III versions. Use one of these numbers (I, II or III) in place of asterisk (*) in burner designation when ordering.)

NP- * -6 6" Straight or 6"P Pilot

NP- * -12 or NP- * -12B 12" Straight or 12B Back Inlet

NP- * -18 18" Straight

NP- * -24 24" Straight

NP- * -L 6" X 6" Elbow

NP- * -T 12" X 6" Tee

NP- * -36B 36B Back Inlet

Typical End View

4/95

Page 5508

Series "NP" AIRFLO Burners

Pilots, End Closures, and End Inlet Flange Sets


NOTE: All open ends of burner assembly must be closed off with one of these end closures or pilots. One-piece cast end closures should not be used if temperature rise exceeds 300F.

Plain End Closure Sets

End Inlet & Pilot Flange Sets

NP-EC (1 pc) End Closure Set

NP-EP (2 pc) End Plate Set

NPF- 1-1/4" -FR-SI (1 pc) Pilot Set w/SI

Pilot End Plate Sets

NPF- 1-1/4"- EP (2 pc) End Inlet Flange Set

NPF- 1-1/4"- FR-SI (2 pc) Pilot Set w/SI

NP-Pak Pilot Set w/SI

NP-Pak Pilot Set w/Adj. Orifice/SI

NP-Pak Pilot Set w/orifice/cock/ tube/SI

NP-EC-SI-3/4"UV (1 pc) Pilot Set w/ SI

NP-EC-SI-1/2"-FR (1 pc) End Closure Set w/SI

Common Dimensions (Nominal, in Inches)


Typical End View

Pilot Assembly Section


NP-6P Pilot Section w/Built-in Pilot includes end plate pilot w/SI onto its own special 6" Series NP AIRFLO Burner assembly

PIpe threads on this page conform to NPT (ANSI Standard B2.1)

Legend: 1 - 1/8" test connection 2 - 1/4" pilot gas connection 3 - 14mm spark ignitor connection 4 - 1/2" or 3/4" UV/FR connection bushed to 1/4" for FR 5 - Alternate 1/4" angled FR location 6 - 1/8" pilot gas connection 7 - 1-1/4" NPT gas inlet

Series "RG" AIRFLO Burners

Page 5509

Approximate Envelope Dimensions


(Nominal, in Inches)

Burner Sections
RG-IV-6 6" Straight or 6"P Pilot RG-IV-12 or RG-IV-12B 12" Straight or 12B Back Inlet RG-IV-18 18" Straight RG-IV-24 24" Straight

RG-IV-L 6" X 6" Elbow

RG-IV-T 12" X 6" Tee

RG-IV-36B 36B Back Inlet

Typical End View

5/88

Page 5510

Series "RG" AIRFLO Burners

Pilots, End Closures, and End Inlet Flange Sets


NOTE: All "open" ends of burner assembly must be closed off with one of these end closures or pilots. One piece cast end closures should not be used if temperature rise exceeds 300F.

Plain End Closure Sets

End Inlet & Pilot Flange Sets

RG-EP (2 pc) End Plate Set

RGF- 1-1/4" -FR-SI (1 pc) Pilot Set w/SI

RGF- 1-1/4"- EP (2 pc) End Inlet Flange Set

RGF- 1-1/4"- FR-SI (2 pc) Pilot Set w/SI

Pilot End Plate Sets

Pilot Assembly Section


RG-6P Pilot Section w/Built-in Pilot includes end plate pilot w/SI and a special 6" Series RG AIRFLO Burner assembly

RG-Pak Pilot Set w/ SI

RG-Pak Pilot Set w/Adj. Orifice/SI

RG-Pak Pilot Set w/orifice/cock/tube/SI

Common Dimensions (Nominal, in Inches)


Typical End View
Legend: 1 - 1/8" test connection 2 - 1/4" pilot gas connection 3 - 14mm spark ignitor connection 4 - 1/2" UV/FR conn. bushed to 1/4" for FR 5 - Alternate 1/4" angled FR location 6 - 1/8" pilot gas connection 7 - 1-1/4" NPT gas inlet

Pipe threads on this page conform to NPT (ANSI Standard B2.1)

"NP" & "RG" AIRFLO Burners

Page 5511

Accessories / Replacement Items


Dimensions, Nominal in Inches

14mm Spark Ignitor

Profile Plate Bracket Provides support for profile within closed burner loop.
1/4" dia.

Flame Rod (1/4" NPT)

Adjustable Orifice

Support Bracket Normally used in pairs as shown here. Mount to burner assembly at any joint. Division Plate Provides isolation of burner feed where desirable.

External Mounting Assembly


Frequently used to provide easy accessibility to spark ignitor and flame supervision components. External Mounting Plate Used with typical pilot Opening Required

Includes Mounting Plate with two (2) feed-through insulators for internal mounting of Spark Ignitor and Flame Rod.

5/88

Page 5512

"NP" & "RG" AIRFLO Burners

Notes